Produal HLS 44-SER User Manual

USER GUIDE
HLS 44-SER
V1.1.0 (22.04.2014)
1 (6)
Produal Oy Keltakalliontie 18, 48770 Kotka FINLAND Tel: +358 10 219 9100 / Fax: +358 5 230 9210 info@produal.fi www.produal.com
Commissioning tool HLS 44-SER
HLS 44-SER is a tool for commissioning HLS 44 and HLS 44-V controllers. By using this tool the commissioning is fast and you may rely on that the settings are as planned.
It is useful to plan and program the settings to the tool with care in advance. After that, you can load the settings to the controllers in office or on the installation site during commissioning.
This user guide is for the commissioning tool software version 1.1.0 or newer. The tool software version shows on the tool display when the power is switched on.
PROFILES
HLS 44-SER commissioning tool contains fixed factory settings (PRSET 1) for HLS 44 and HLS 44-V, memory slots for 5 user defined solutions (SET 1...5) and 4 pre-programmed application profiles (SET 6...9). All parameters of SET 1...9 can be changed for a best possible room control solution. For more information see the instructions of HLS44 and HLS 44-V.
Pre-programmed applications (SET 6…9) are the following:
SET 6 Heating by radiator and cooling by beam SET 7 Heating and cooling by a fan coil unit SET 8 Heating by radiator and cooling by VAV and beam (VAV control based on CO
2
concentration)
SET 9 Heating by radiator and cooling by beam (dampers and lights ON/OFF by PIR detection; HLS 44-V)
GETTING STARTED
1. Remove the controller cover.
2. Connect the commissioning tool cable to the controller programming terminal.
A. Commissioning tool cable NOTE: Connecting the tool to the programming terminal will disconnect the controller from the Modbus communication.
3. Connect the supply voltage either to the commissioning tool or the controller. IMPORTANT: Do not connect the supply voltage to both devices.
4. Check that the software version numbers are compatible. The software versions are shown on the displays when you switch on the power. See the compatible software versions from the
following table.
HLS 44-SER software version
Compatible HLS 44 and HLS 44-V software versions
1.0.0 1.0.0 -> 1.0.2
1.1.0 1.1.0 -> 1.1.2
1.1.3
1.1.3
1.1.4
1.1.4 -> 1.1.7
1.1.8
1.1.4 -> 1.1.9
USER GUIDE
HLS 44-SER
2 (6)
Produal Oy Keltakalliontie 18, 48770 Kotka FINLAND Tel: +358 10 219 9100 / Fax: +358 5 230 9210 info@produal.fi www.produal.com
LOADING PARAMETERS TO THE CONTROLLER
1. Press the and buttons to select the profile (SET 1…9 or PRSET 1) which you want to load to the controller.
2. Press the
button to enter the Modbus address setting view.
3. Press the
and buttons to select the Modbus address for the controller.
The Modbus address number steps automatically forward number by number, when multiple controllers are programmed.
4. Press the
button to load the parameters to the controller.
SETTING THE PARAMETERS IN THE COMMISSIONING TOOL
1. Press the and buttons to select the profile (SET 1…9) in which you want to store the parameters. NOTE: The selected profile will be overwritten with the new parameters. You cannot recover the overwritten profiles.
2. Press the
button.
3. Make the wanted adjustments in the menu. See the detailed parameter setting instructions from the HLS 44 or HLS 44-V user guide.
4. Load the parameters to the controller.
LOADING PARAMETERS FROM THE CONTROLLER TO THE COMMISSIONING TOOL
1. Press the and buttons to select the profile (SET 1…9) in which you want to load the parameters. NOTE: The selected profile will be overwritten with the new parameters. You cannot recover the overwritten profiles.
2. Press the
button until you reach the parameter loading menu.
3. Press the
button.
Verification message appears on the display.
4. Press
button to change the verification message to “Yes” status.
5. Press the
button to load the parameters from the controller to the commissioning tool memory.
8
ID=
1
SET
1
SET
----
COMM
1
SET
1
SET
Yes
Sure?
No
Sure?
----
LOAD
Loading...