The IPStecker, Worktime, Workstar, WtKomm, Proxernet, are official brand names of Procontrol
Electronics Ltd.
Trademarks in the document are the property of the respective owners. Procontrol Electronics Ltd.
reserves all copyright of the document: it may not be copied for third party, modified and published
without prior written permission of the author.
Procontrol Electronics Ltd. reserves the right to alter the document and the software without notice.
Procontrol Electronics Ltd. assumes no liability for the accuracy for the product, the software and
documentation and also for its adequacy and usability for specific applications.
The software and its documentation is provided „as is”, without warranty of any kind, including but
not limited to the warranties of accuracy or fitness for a particular purpose. In no event shall the
authors be liable for any claim, damages or other liability out of or in connection with the product.
Page 3
Index
Index ......................................................................................................... 3
3. Command line remote control through user developed program (SDK) ........... 26
Contact to the manufacturer................................................................ 30
Page 4
IPStecker
IPStecker
Welcome
Thank you for choosing a Procontrol product.
Procontrol Electronics Ltd has grown to an important national company of
developing and manufacturing software, hardware, electronic devices, access control,
time-attendance systems, queue control, client caller and access protection systems
since 1981.
Thousands of satisfied customers have experienced the security ensured by our long
time period planning, reliable work and the world trademarks standing behind us.
Our qualified staff does its best to satisfy your requirements in the electrical
development.
Procontrol 4
Page 5
Safety Precautions
Please read this guide before installing and
using the device. Please use the device
properly and as described in the following
manual.
The guarantee is insured only if the device is
used with the implements approved or
specified by the manufacturer, and it is
cleaned and maintained as described in this
guide.
The authors are NOT liable for any claim,
damages or other liability out of:
- using not the proper way
- incorrect installation
- connecting to inappropriate electronic
network
- incorrect maintenance
- not approved modifications,
interventions
- using non-original elements
- using with implements not approved
or specified by the manufacturer
Only the technical service authorized by the
manufacturer is allowed to do interventions in
the device.
Maximum number of connectable devices
using switching power supply is 2/socket!
Do not try to modify or dismount any part of
the device
Do not store and operate the device out of the
given ranges
Only use the device the proper way as
described in guide.
Do not store the device close to a heat source
or direct flame, because the device may
explode
Never allow water or any other foreign matter
to get into the unit. The unit contains sensitive
electronic parts, so water and foreign matter
not only can cause malfunction, they also
create the risk of overheating due to short
circuiting and insulation failure, fire and
smoke, combustion, and electric shock. Should
water or foreign matter ever get into the unit,
IPStecker
immediately turn off the unit and contact a
qualified service person.
Only use the product for it’s intended purpose!
Security
Keep the device in operation only from
electric sources defined in this user manual.
Do not open the device, there are no user
serviceable parts inside!
Attention! Connect the product exclusively
to a grounded power outlet with relay
contact protection network.
To avoid fire and risk of electronic shock:
Beware that your children do not throw or
push objects through the slots of the device.
Do not mount accessories or attachments on
the device that are not designed for this
device. If you do not use the device for longer
time or in case of lightning, you shall unplug
the power cord.
Risks at Installation
Do not store anything on the power cord. Do
not place the device, where the power cord can
be damaged. Do not use the device under wet
circumstances or in humid premises.
Cleaning
Switch off the device before cleaning. Use
slightly wet mop. Excessive humidity may
cause electric shock.
General rights and responsibility
Manufacturing rights of this device are
reserved by Procontrol Electronics Ltd.
Modifying or copying of this device or parts is
prohibited!
Procontrol Ltd. reserves the right to modify
this documentation without prior notice
Procontrol Ltd. is not liable for using of this
device and the consequences of the
application.
Procontrol 5
Page 6
IPStecker
Introduction
The IP Stecker is an intelligent socket strip with IP address and individually,
remotely controllable power outlets for switching up to four devices on and off
through the Internet and Ethernet using a notebook, pocket PC.
Types:
IPStecker 3 IPStecker 4
IPStecker 4
Plans for Product Enhancement
• We currently provide the two models above - series R9C, both provided with
Ethernet and USB port. The USB (12C) connector is prepared for future
enhancements.
As advanced option you will be able to connect external thermometer sensors
(TS-05 or THS-05) through the USB (I2C) port, for applications e.g.
emergency stop at a certain temperature, i.e. the user sets a threshold value,
when exceeded, the device stops operating. This „Smart Metering” will be
available, when the manufacturing of next series has been launched, which is
at present in the process of development.
A built in current and voltage meter function is planned, this „Smart
Metering” will be available similarly, when the manufacturing of next series
has been launched, which is at present in the process of development.
In case of any requested modification and enhancement please do not hesitate to
contact us, any individual request is highly appreciated. Please contact our colleagues
for details and prices!
Procontrol 6
Page 7
Type
IPStecker 3
IPStecker 4
Picture
Revision
0802-03-R9C
0802-03-R9C
Part number
141108
141106
Number of remotable switched sockets
3 sockets
4 sockets
Ethernet interface
10/100BaseT
10/100BaseT
Remote abilities
o Web /internet browser
o Telnet
o Command prompt remote control, Perl script,
PHP script
o PCSW protokoll
o Web /internet browser
o Telnet
o Command prompt remote control, Perl script,
PHP script
o PCSW protokoll
Compatibility
Can be used in all operation system, with all
browsers: Microsoft Internet Explorer, Opera,
Mozilla Firefox, Netscape, etc.
Windows 98SE / 2000 / XP / XP SP1-SP2, Server
2003 / Vista / Linux / Me / Mac OS etc.
Can be used in all operation system, with all
browsers: Microsoft Internet Explorer, Opera,
Mozilla Firefox, Netscape,
Windows 98SE / 2000 / XP / XP SP1-SP2, Server
2003 / Vista / Linux / Me / Mac OS
Language
english, hungarian
english, hungarian
Mounting
19 "rack mountable with included metal fixing
brackets
19 "rack mountable with included metal fixing
brackets
Connectors
RJ45, USB B
RJ45, USB B
Socket standard
F (Hungary)
F (Hungary)
Power supply
AC 230V, 50Hz
AC 230V, 50Hz
Power consumption
max: 3 VA
max: 3 VA
Capacity
max: 230V, Σ16A total, max: 230V 8A / socket at
continuous load. Maximum number of devices
using switching power supply is 2/socket.
max: 230V, Σ16A total, max: 230V 8A / socket at
continuous load. Maximum number of devices
using switching power supply is 2/socket.
Needed cable type
CAT5, CAT6
CAT5, CAT6
Support / feedback on hardware
- double-pole main switch
- 1 hidden reset button
- 3+2 pcs status LED
- Ethernet status leds for , a LINK signal and
10/100Mbit mode
- Built-in clock, and memory protection batteries
- 1 hidden reset button
- 3+2 pcs status LED
- Ethernet status leds for , a LINK signal and
10/100Mbit mode
- Built-in clock, and memory protection batteries
Casing
Indoor durable case, compact, distinguished
Indoor durable case, compact, distinguished
Dimensions
Without fixing brackets: 430x60x45mm
With fixing brackets: 480x60x45mm
Without fixing brackets: 430x60x45mm
With fixing brackets: 480x60x45mm
Weight
Net 1000g, gross 1130g
Net 1000g, gross 1140g
Operating temperature
-25 - +50 °C
-25 - +50 °C
Storage temperature
-40 - +60 °C
-40 - +60 °C
Properties, types
IPStecker
Procontrol 7
Page 8
IPStecker
Operating relative humidity
max. 80%
max. 80%
Storage relative humidity
max. 90%
max. 90%
Standards
Ethernet IEE802
Ethernet IEE802
USB (I2C) - prepared for later
developments
x
x
Smart Metering: current and voltage
measurement functions
under development
under development
* A Special communication protocol developed by Procontrol, which allows the implementation and communication of IPStecker with other Procontrol
manufactured products and systems.
Attention!Maximum number of devices using switching power supply is 2/socket.
Procontrol 8
Page 9
IPStecker
For English users
If the web interface of the IPStecker is in Hungarian, you can change it to English in
Rendszer section, by changing the dropbox value Magyar to English, and clicking
Mentés button.
Procontrol 9
Page 10
What kind of Ethernet network we have?
What kind of Ethernet network we have?
(Estimation of Ethernet network topology)
Connect the device to a free end point (or directly to your PC) of an established
Ethernet network as following.
Ethernet on PC network is not everywhere accessible, therefore we suggest two
solutions for testing your device:
1. In Case of Established Computer Network
Connect a free end point of the PC network with a straight patch cable (StraightTrough) to the device. We recommend this solution, if possible. Test the device with
a patch cable (Straight-Trough, attached to the customer package) on an Ethernet
socket of a network-connected PC. Connect the Ethernet cable to the SWITCH or
HUB of your PC network (Ethernet).
Procontrol 10
Page 11
What kind of Ethernet network we have?
o
Procontrol 11
Page 12
What kind of Ethernet network we have?
2. Directly Wired Connection between Terminal and PC
If a network SWITCH is not available, but you want to connect it directly to the
Ethernet socket of your PC, you need a special Cross-Over wire. Connect the device
to your PC’s built in connector through the Cross-Over patch cable.
Procontrol 12
Page 13
Ethernet data connection establishment
Ethernet data connection establishment
Product setup
Connect the socket strip to a 230V mains socket outlet. Use a grounded outlet only.
Connect the Ethernet network cable, then turn on the power switch of the device (I O
labeled rocker switch). After about 10 seconds the device is available on the
computer network with default connection settings.
IP address: 192.168.0.250
Subnet mask: 255.255.255.0
Web port: 80
You can now connect the remotely switched 230V powered devices as you wish.
The product is supplied with the relays switched on, so after switching on the first
time, all four sockets will be powered with 1-2-3-4 seconds delay.
Procontrol 13
Page 14
IPStecker remote control function
IPStecker remote control function
The remote control modes of the IPStecker were developed according to different
customer needs and requests. Controlling the power supply of the connected devices
is available through the following channels:
Web browser port 80 / internet browser (IPStecker Online)
Most of the user's choice, the simplest plausible method for remote
control via an Internet Browser with graphic interface. Most parameters of
the unit are accessible through this default interface. The following
browsers were tested:
a. Internet Explorer 5,6,7,8
b. Mozilla
c. Opera
Telnet port 23 / command line
a. Microsoft Telnet
b. Debian linux – telnet
PCSW protocol, port 1001
Secret internal protocol of Procontrol Ltd., used to edit system parameters
and for firmware upgrades. Only for system administration purposes.
Through web port 80 instead of web browser, even scheduled, or command
line remote control, Perl script, PHP script. ( sample script is available on the
product’s website)
Power supply control of the connected devices is even possible scheduled
through web port 80 (instead of web browser), or controlled by program
code. Tested under the following environment:
a. Microsoft Windows 2000, Windows XP, Windows Vista, Windows
2003 Server, Windows 2008 Server, Windows 7
Procontrol 14
Page 15
IPStecker remote control function
Testing the IPStecker Ethernet connection
Ping test: enter following command into the command line: PING
192.168.0.250
If you receive a reply, you can try with your browser according to description
below. If you do not receive any reply, check as follows:
FIREWALL DIFFICULTIES: A well operating firewall may prevent the
program from running correctly.
Procontrol 15
Page 16
IPStecker remote control function
1. Web browser / IP Stecker Online
Power of the IPStecker’s sockets can be individually switched on and off through a
web browser. Access to the control page can be password protected.
FIREWALL DIFFICULTIES: A well operating firewall may prevent the program
from running correctly.
Enter the default IP address into the browser: 192.168.0.250
If the user interface is not displayed, please check:
Whether you established all connections properly? Whether at least one of the IPStecker’s status LEDs is lit?Whether your PC’s IP address is in the same network: 192.168.0.xxx?
After displaying the user interface you can enter a new IP address into the IP field of
connection preferences.
To log in, enter the correct password. (default is admin)
To set interface language see section 10 below.
Procontrol 16
Page 17
IPStecker remote control function
Sections of the web interface:
1. Plugs – Remote access of powers sockets.
The first section of the IPStecker’s user interface displays the current status of power socket strip. A powered plug is marked green (ON), an unpowered plug
is marked red (OFF).
With a single click on the buttons in the On/Off column, power can be switched
ON or OFF in each plug (R1, R2, R3).
Restarting of each plug is also possible, they remain unpowered till the time delay
set in section Delays. After the time period expires, the plug automatically
switches on, and the web page is being refreshed. Each plug can be renamed by
the user for easier identification in the User section of the web interface. The
names given there are displayed in the User name column.
ATTENTION! ALWAYS USE THE SAVE BUTTON AFTER SETTINGS
MODIFICATION AND DATA ENTRY!
Procontrol 17
Page 18
IPStecker remote control function
2. Events – User operations log
The device logs each user operation and stores the last 128 event
3. User – User settings
(Operation of the IPStecker is not affected by the settings in this section)
Each plug can be renamed (according to the connected devices e.g.) by the user
for easier identification in this section. The names given here are displayed in the
User name column of the first section. A maximum 10 character long name can
be given to each plug with contents of the English alphabet.
Procontrol 18
Page 19
IPStecker remote control function
4. Connection – Connection settings
Parameters of the connection with the IPStecker can be changed here: IP address,
default gateway, subnet mask, TCP/IP port.
Procontrol 19
Page 20
IPStecker remote control function
5. Security – Security settings
A password can be set here to access the IPStecker’s web interface. The password
can be changed any time inside the control page. If you set and save a password here,
the device asks for it the next time you want to log in. The default password is
“admin”. (Recommended to change it after the first login)
The Current state column gives information if a password is required to enter the web
interface. If you do not wish to use a password, just leave the New settings field
empty and click the Save setting button. The next login can be done without using a
password. To restore password controlled access, it is only needed to type in a new
password and click the Save setting button.
6. Date time – Date and time settings
The actual date and time can be set in this section. Certain types of IPStecker can
automatically synchronize date and time data from an NTP server.
Procontrol 20
Page 21
IPStecker remote control function
7. Delays – Plug power on delay settings
A power on time delay can be set to each plug, measured in milliseconds. Using this
option a heavy startup load is avoidable in case of devices with high power
consumption starting simultaneously.
Procontrol 21
Page 22
IPStecker remote control function
8. Save state – Saving the states of plugs
In this section the states of each plug can be set after a device restart or switching off.
In the New settings column “Unchanged” leaves the plug in the current state, the “On” or “Off” changes the mode currently set. Currently stored state is displayed in
the Current state column. During a power failure, or a blackout the IP Stecker’s nonvolatile memory "remembers" the latest switching states and settings and reestablishes them when the power supply is restored. So the IP Stecker operates
unchanged until you give a new command. This function can be turned off.
9. Ping settings – Automatic plug restart (automatic restart of crashed
systems e.g., RESET)
With this function any number of operation checking signal can be sent out at any
time to devices connected to the network. A device crash or a network failure is
easily detectable with this method, and the malfunctioning device connected to the
specific plug can be restarted.
The pinger pings a given IP address at specified time intervals, and if there is no
answer after 5 times, the appropriate plug will be switched off and after 5 seconds on
again.
Procontrol 22
Page 23
IPStecker remote control function
10. System – Language settings and device restart/logout
Language of the web interface can be set to Hungarian or English.
Clicking the Restart device button, the IPStecker restarts, and by clicking the Logout
button we can leave the web interface.
Procontrol 23
Page 24
IPStecker remote control function
ATTENTION! ALWAYS USE THE SAVE BUTTON AFTER SETTINGS
MODIFICATION AND DATA ENTRY!!
Procontrol 24
Page 25
IPStecker remote control function
2. Telnet
Some functions of the IPStecker is available via Telnet. If a password was set to
access the device, it will be also required to establish a Telnet connection. To access
the IPStecker this way, create a command prompt: type in Start menu / Run window
“cmd”; in case of Windows 98: command; and enter OK. Into the appearing textbox
type in “telnet (IP address of the device)”
E.g. telnet 192.168.0.250
After the welcome screen of the IPStecker appears, you can type in any command.
For the list of available commands type “,” or “help”.
Accessing the plugs, modifying connection settings and changing password are also
available via Telnet. The password set this way is the same to reach the web
interface.
Procontrol 25
Page 26
IPStecker remote control function
3. Command line remote control through user developed
program (SDK)
Remote control of the IPstecker through command prompt is also possible by
downloading a utility software (Perlscript), which is available free of charge from
www.activeperl.com.
Perl script usage:
1. Install Perl interpreter to the computer. (interpreter / motor / engine)
2. Start the command line script: stecker.pl [IP address][settings]
The script can be accessed from a webpage or from a unique program.
E.g. stecker.pl 192.168.2.25 +1 -2 +3 (this sample command switches
on plug 1 and 3, and switches off plug 2.)
E.g. stecker.pl +1 Pass=admin
4. Command line control through USB connection
IPStecker is accessible not exclusively through Ethernet but it is connectible to your
PC also through USB A-B wire and enables you to switch the sockets on a command
line interface.
When you attach the device to your computer the first time, a dialogue box appear
which guides you through the steps of driver setup. Once you click on „Not now”
option you are enabled to give the path of the driver.
(The window below appears in the default language of Setup Wizard on your PC.)
Procontrol 26
Page 27
IPStecker remote control function
Select the option of alternative setup path (advanced) and click „Continue”.
Select the option „No search. I select the setup driver”:
Int he next window click on „My disc” and browse „usbser.info” file:
Procontrol 27
Page 28
IPStecker remote control function
Click „Continue” and Windows executes the driver setup. The device is now
available in your system as a serial port device.
Command line interface:
You can control the device by a simple line command user interface. Attach it with a
USB wire, from your user kit, to your PC and start „Terminal” software, from your
user kit.
COM Port: select the COM Portot, which you connected with your device
Baudrate: 115200
Data bits: 8
Parity: none
Stop bits: 1
Handshaking: none
Tick „+CR” option beside „Send” button
Procontrol 28
Page 29
IPStecker remote control function
Procontrol 29
Page 30
Contact to the manufacturer
Contact to the manufacturer
If any remark, question or request occurs to you contact us as follows:
PROCONTROL ELECTRONICS LTD.
www.procontrol.hu
email: service@procontrol.hu
Hardware manufacturing/service:
6725 Szeged, Cserepes sor 9/b.
Hungary
Tel: +36-62-444-007
Fax: +36-62-444-181
Please turn to us with your requests concerning the program in written form possibly,
as obvious and detailed as possible.
Procontrol 30
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.