WARNING: If the information in this manual is
not followed exactly, a fire or explosion may re-
sult causing property damage, personal injury, or
loss of life.
WARNING: This is an unvented gas-fired
heater. It uses air (oxygen) from the room in
which it is installed. Provisions for adequate
combustion and ventilation air must be provided.
Refer to Air For Combustion and Ventilation
section on page 4 of this manual.
If you cannot reach your gas supplier, call
the fire department.
Installation and service must be performed by a
qualified installer, service agency or gas
supplier.
WARNING: Improper installation, adjustment,
alteration, service or maintenance can cause injury or property damage. Refer to this manual for
correct installation and operational procedures. For
assistance or additional information consult a
qualified installer, service agency, or gas supplier.
This appliance may be installed in an aftermarket*
permanently located, manufactured
(mobile) home, where not prohibited by local
codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This
appliance is not convertible for use with other
gases.
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM
HEATERS
Water vaporis a by-product of gas combustion.An unvented
room heater productes approximately one (1) ounce (30ml)
of water for every 1,000 BTU’s (.3KW’s) of gas input per hour.
Refer to page 6.
Installer:Please leave these instructions with the
consumer
CINTINENT AL APPLIANCE INC
5 Musick4600 Highlands Parkway S.E.
Irvine SUITE# D/E
CA 92618 Smyrna, GA 30080
TOLL-FREE NUMBER: 1-877-886-5989
Consumer: Please retain these instructions for future
use.
*Aftermarket: Completion of sale, not for purpose of resale,
from the manufacturer.
SAFETY INFORMATION WARNINGS
IMPORTANT: Read this
owner’s manual carefully and
completely before trying to
assemble, operate, or service
this heater. Improper use of
this heater can cause serious
injury or death from burns,
fire, explosion, electrical
shock, and carbon monoxide
poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning:
Early signs of carbon monoxide
poisoning resemble the flu with
headaches, dizziness, or nausea.
If you have these signs, the heater
may not be working properly. Get
fresh air immediately! Have heater
serviced. Some people are more affected by carbon monoxide than
others. These include pregnant
women, people with heart or lung
disease or anemia, those under the
influence of alcohol, and those
at high altitudes.
Propane/LP Gas: Propane/LP gas
is odorless. An odor-making agent
is added to Propane/LP gas. The
odor helps you detect a Propane/LP
gas leak. However, the odor added
to Propane/LP gas can fade. Propane/
LP gas may be present even though
no odor exists.
Make certain you read and under-
stand all warnings. Keep this manual
for reference. It is your guide to
safe and proper operation of this
heater.
WARNING: Any change to
this fireplace or its controls can
be dangerous.
WARNING: Do not allow fans to
blow directly into the heater. Avoid any
drafts that alter burner flame patterns.
Ceiling fans can create drafts that alter burner flame patterns. Altered
burner patterns can cause sooting.
WARNING: Do not use acces-
sories not approved for use with
this heater.
Due to high temperatures, the
appliance should be located out of
traffic and away from furniture
and draperies.
Do not place clothing or other
flammable material on or near the
appliance. Never place any objects
in the fireplace.
Heater becomes very hot when
running fireplace. Keep children and
adults away from hot surfaces to
avoid burns or clothing ignition.
Fireplace will remain hot for a time
after shutdown. Allow surfaces to
cool before touching.
Carefully supervise young children
when they are in the room with
fireplace.
You must operate this heater with
the heater screen in place. Make
sure heater screen is in place
before running heater.
Keep the appliance area clear and
free from combustible materials,
gasoline, and other flammable
vapors and liquids.
1. This appliance is only for use
with the type of gas indicated
on the rating plate. This
appliance is not convertible for
use with other gases.
2. Do not place Propane/LP
supply tank(s) indoors.
3. If you smell gas
Shut off gas supply.
Do not try to light any appliance.
Do not touch any electrical switch;
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbor’s phone. Follow
the gas supplier’s instructions.
If you cannot reach your gas
supplier, call the fire department.
4. This heater shall not be installed
in a bedroom or bathroom.
5. Do not use this heater as a
wood-burning heater. Use only
the logs provided with the heater.
6. Do not add extra logs or ornaments
such as pine cones, vermiculite, or
rock wool. Using these added items
can cause sooting. Do not add lava
rock around base. Rock and debris
could fall into the control area of
heater. After servicing, always
replace screen before operating
heater.
7. You must operate this heater with
the heater screen in place. Make
sure heater screen is in place
before running heater.
8. This heater is designed to be
smokeless. If logs ever appear to
smoke, turn off heater and call a
qualified service person.
Note: During initial operation, slight
smoking could occur due to log
curing and heater burning
manufacturing residues.
9. To prevent the creation of soot,
follow the instructions in the
Cleaning and Maintenance Section,
pages 11.
10.Before using furniture polish, wax,
carpet cleaner, or similar products,
turn heater off. If heated, the
vapors from these products may
create a white powder residue
within burner box or on adjacent
walls or furniture.
11.This heater needs fresh air
ventilation to run properly. This
heater has an Oxygen Depletion
Sensing (ODS) safety shutoff
system. The ODS shuts down the
heater if not enough fresh air is
available. See the Air for Combustionand Ventilation Section, pages 4
through 5. If heater keeps shutting off,
see Troubleshooting, pages 12 .
12. Do not run heater
Where flammable liquids or vapors
are used or stored.
Under dusty conditions.
13.Do not use this heater to cook
food or burn paper or other objects.
14. Do not use heater if any part has
been under water. lmmediately call
a qualified service technician to
inspect the room heater and to
replace any part of the control
system, and any gas control which
has been under water.
2
SAFETY
INFORMATION
Continued
15. Turn off and unplug heater and
let cool before servicing. Only a
qualified service person should
service and repair heater.
16. Operating heater above elevations of 4,500 feet could cause pilot
outage.
17. Do not operate heater if any log
is broken. Do not operate heater
if a log is chipped (dime-sized or
larger).
18. To prevent performance
problems, do not use fuel tank of less
than 100 lbs. capacity.
LOCAL CODES
lnstall and use heater with care.
Follow all local codes. In the
absence of local codes, use the
latest edition of The National Fuel
Gas Code. ANSZ223.1, also known
as NFPA54*.
*Available from:
American National Standards
lnstitute, lnc.
1430 Broadway
New York. NY10018
National Fire Protection
Association, lnc.
Batterymarch Park
Quincy. MA 02269
This heater is designed for ventfree operation. State and local
codes in some areas prohibit the
use of vent-free heaters.
UNPACKING
1. Remove top inner pack.
2. Tilt carton so that fireplace is
upright.
3. Remove protective side packaging.
4. Slide fireplace out of carton.
5. Remove protective plastic wrap.
6. Remove screen by lifting and then
pulling forward.
7. Remove log set by cutting plastic
ties.
8. Carefully unwrap logs.
9. Check for any shipping damage. If
fireplace or logs are damaged,
promptly inform dealer where you
bought the fireplace from.
PRODUCT FEATURES
SAFETY PILOT
This heater has a pilot with an
Oxygen Depletion Sensing (ODS)
safety shutoff system. The ODS/
pilot is a required feature for ventfree room heaters. The ODS/pilot
shuts off the heater if there is not
enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo ignitor.
This system requires no matches,
batteries, or other sources to light
heater.
PRODUCT IDENTIFICATION
Decorative Frame
Heater Cabinet
Grill
Logs
Heater Controls
(Inside Door)
Figure1-Compact Vent-Free Fireplace
3
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a confined
space or unusually tight construction unless provisions are provided
for adequate combustion and ventilation air. Read the following instructions to insure proper fresh
air for this and other fuel-burning
appliances in your home.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from
National Fuel Gas Code, NFP A 54/ANSZ 223.1.Section 5.3, Air for
Combustion and Ventilation.
All spaces in homes fall into one
of the three following ventilation
classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
The information on pages 4 through
5 will help you classify your space
and provide adequate ventilation.
Confined and Unconfined Space
The National Fuel Gas Code, ANS
Z223.1 defines a confined space as
a space whose volume is less
than 50 cubic feet per 1,000 Btu per
hour (4.8 m3 per kw) of the aggregate input rating of all appliances
installed in that space and an
unconfining space as a space
whose volume is not less than 50
cubic feet per 1,000 Btu per hour
(4.8 m3 per kw) of the aggregate
input rating of all appliances installed in that space. Rooms communicating directly with the space
in which the appliances are
installed*, through openings not
furnished with doors, are considered a part of the unconfined
space.
This heater shall not be installed
in a confined space or unusually
tight construction unless provisions
are provided for adequate combustion and ventilation air.
* Adjoining rooms are communicating only if there are doorless
passageways or ventilation grills
between them.
Unusually Tight Construction
The air that leaks around doors
and windows may provide enough
fresh air for combustion and
ventilation. However, in buildings of
unusually tight construction, you
must provide additional fresh air.
Unusually tight construction is
defined as construction where:
a) walls and ceilings exposed to
the outside atmosphere have a
continuous water vapor retarder with
a rating of one perm ( 6×10
-11
kg per
pa-sec-m2) or less with openings
gasketed or sealed and
b) weather stripping has been
added on windows that open and
doors and
c) caulking or sealants are applied to areas such as joints around
window and door frames, between
sole plates and floors, between
wall-ceiling joints, between wall
panels, at penetrations for plumbing,
electrical, and gas lines, and at other
openings.
If your home meets all of the
three criteria above, you must provide additional fresh air. See Ven-tilation Air From Outdoors, page 5.
If your home does not meet all of the
three criteria above, proceed to
Determining Fresh-Air Flow For
Heater Location, below.
AIR FOR COMBUSTION AND VENTILATION
DETERMINING FRESH AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways
or ventilation grills between the rooms.
1. Determine the volume of the space (length
Length
Example: Space size 20ft. (length)
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these
rooms to the total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
(volume of space)÷50 cu. ft.=(Maximum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space)÷50 cu.ft.=51.2 or 51,200(maximum Btu/Hr the space can support)
Width×Height= cu.ft. (volume of space)
×
16ft. ( width)×8ft. (ceiling height)=2560 cu. ft. (volume of space)
×
width×height).
×
4
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater Btu/Hr
Gas water heater*
Gas furnace
Vented gas heater
Gas heater logs
Other gas appliances* +
Total =
*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and
vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
Btu/Hr (maximum the space can support)Btu/Hr (actual amount of Btu/Hr used)
Example : 51,200 Btu/Hr(maximum the space can support)
56,000 Btu/Hr(actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the
maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined
space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air FromInside Building (below).
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors (below) .
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an
unconfined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be operated is smaller than that defined as
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Example:
Gas water heater 30,000 Btu/Hr
Vent-free heater
Total = 56,000 Btu/Hr
+ 26,000 Btu/Hr
an unconfined space or if the building is of unusually tight construction, provide adequate
combustion and ventilation air by one of the methods described in the National Fuel Gas Code,
ANS Z223.1, Section 5.3 or applicable local codes.
Ventilation Air From lnside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining
unconfined space, you must provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting
the two spaces (see options 1 and 2, Figure 2).
You can also remove door into adjoining room
(see option 3, Figure 2). Follow the National Fuel
Gas Code. NFP A 24/ANS Z223.1. Section 5.3, Air
for Combustion and Ventilation for required size of
ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or
ducts. You must provide two permanent openings:
one within 12" of the ceiling and one within 12" of
the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces
include attics and crawl spaces. Follow the National
Fuel Gas Code, NFPA 54/ANS Z223.1, Section 5.3.
Air for Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT:Do not provide openings for inlet
or outlet air into attic if attic has a thermostatcontrolled power vent. Heated air entering the
attic will activate the power vent.
Figure 2 -Ventilation Air from Inside Building
Figure 3 -Ventilation Air from Outdoors
WARNING: Rework worksheet, adding the space of the adjoining unconfined space. The
combined spaces must have enough fresh air to supply all appliances in both spaces.
5
NOTICE: This heater is intended for use as supplemental
heat. Use this heater along with your
primary heating system. Do not
install this heater as your primary
heat source. If you have a central
heating system, you may run
system's circulating blower while
using heater. This will help circulate
the heat throughout the house . In
the event of a power outage, you
can use this heater as your primary
heat source.
WARNING: A qualified service
person must install heater. Follow
all local codes.
WARNING: Never install the
heater:
in a bedroom or bathroom
in a recreational vehicle
where curtains, furniture, clothing,
or other flammable objects are
less than 36 inches from the
front, top, or sides of the heater
in high traffic areas
in windy or drafty areas
CAUTION: This heater creates
warm air currents. These currents
move heat to wall surfaces next to
heater. Installing heater next to vinyl
or cloth wall coverings or operating
heater where impurities (such as
tobacco smoke, aromatic candles,
cleaning fluids, oil or kerosene lamps,
etc.) in the air exist,may discolor walls.
WARNING: Maintain the
minimum clearances. If you can,
provide greater clearances from
floor, ceiling, and adjoining side and
back walls.
INSTALLATION
6” Minimum
6” min
Figure 4 -Minimum Clearance to Wall
IMPORTANT: Vent-free heaters add
moisture to the air. Although this is
beneficial, installing heater in rooms
without enough ventilation air may
cause mildew. See Air for Combustionand Ventilation, pages 4 through 5.
CHECK GAS TYPE
Use only the type of gas indicated on
the plate. If your gas supply can not
meet that requirement, do not install
heater. Call dealer where you bought
heater from for proper heater type.
CLEARANCES TO COMBUSTIBLES
(Vent-Free Operation Only)
Carefully follow the instructions below.
This fireplace is a freestanding unit
designed to set directly on the floor.
6” min
IMPORTANT: You must maintain
minimum wall and ceiling clearances
during installation. The minimum
clearances are shown in Figure 4.
Measure from outermost point of fireplace top.
Minimum Wall and Ceiling
Clearances
(see Figure 4)
A. Clearances from outermost point
of fireplace top to any combustible side
wall should not be less than 12 inches.
B. Clearances from the fireplace top
to the ceiling should not be less than 48
inches.
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS
Water vaporis a by-product of gas combustion.An unvented room
heater productes approximately one (1) ounce (30ml) of wter for
every 1,000 BTU’s (.3KW’s) of gas input per hour.
Unvented room heaters are remommended as supplemental heat
(a room) rather than a primary heat source (an entire house) .In
most supplemental heat application, the water vapor does not create
a problem. In most applications, the water vapor enhances
humidity atmosphere experience during cold weather.
the low
6
The following steps will help insure that water vapor does not
become a problem.
1. Be sure the heater is sized properly for the application,
including ample combusion air and circulation air.
2. If high humidity is experienced, a dehumidifier may be used
to help lower the water vapor content of the air.
3. Do not use an unvented room heater as the primary heat
source.
INSTALLATION
Continued
CONNECTING TO GAS SUPPLY
WARNING: A qualified service
person must connect heater to gas
supply. Follow all local codes.
CAUTION: Never connect heater
directly to the gas supply. This heater
requires an external regulator (not
supplied). lnstall the external regulator
between the heater and gas supply.
INSTALLATION ITEMS NEEDED
Before installing heater, make sure you
have the items listed below.
piping (check local codes)
sealant (resistant to natural or propane/
LP gas)
equipment shutoff valve*
test gauge connection*
sediment trap
see joint
pipe wrench
flexible gas hose (check local codes)
* A CSA design-certified equipment shutoff
valve with 1/8
alternative to test gauge connection.
Purchase the optional CSA design-certified equipment shutoff valve and flex
hose from your dealer. See Accessories,
page 14.
WARNING: Never connect heater
to private (non-utility) gas wells. This gas
is commonly known as wellhead gas.
" NPT tap is an acceptable
The installer must supply an external
regulator. The external regulator will reduce incoming gas pressure. You must
reduce incoming gas pressure to between
11 to 14
coming gas pressure, heater regulator damage could occur. lnstall external regulator
with the vent pointing down as shown in
Figure 6. Pointing the vent down protects
it from freezing rain or sleet.
CAUTION: Only use a new black
iron or steel pipe. Internally-tinned copper tubing may be used in certain areas.
Check your local codes. Use pipe of 1/
2
gas volume to heater. If pipe is too
small, undue loss of pressure will occur.
Installation must include an equipment
shutoff valve, union, and plugged 1/8
tap. Locate NPT tap within reach for test
gauge hook up. NPT tap must be upstream from heater (see Figure 7).
inches. If you do not reduce in-
" diameter or greater to allow proper
" NPT
IMPORTANT: Install equipment shutoff
valve in an accessible location. The equipment shutoff valve is for turning on or
shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male
threads.This will prevent excess sealant from going into pipe. Excess sealant
in pipe could result in clogged heater
valves.
CAUTION: Use pipe joint sealant
that is resistant to liquid petroleum(LP)
gas.
We recommend that you install a sediment trap in supply line as shown in
Figure 7. Locate sediment trap where it is
within reach for cleaning. Install in piping
system between fuel supply and heater.
Locate sediment trap where trapped matter is not likely to freeze. A sediment trap
traps moisture and contaminants. This
keeps them from going into heater
controls. If sediment trap is not installed or is installed incorrectly, heater
may not run properly.
CAUTION: Avoid damage to
regulator. Hold gas regulator with wrench
when connecting into gas piping and/or
fittings.
NG MODELS:
5” to 10.5” W.C.
Gas supplier provides external regulator for natural gas.
Front View
Side View
Front
of
heater
unit
Gas Regulator
Inlet Connection
Figure 5-Gas Regulator Location and
Gas Line Access Into Heater Cabinet
Figure 6- External Regulator
With Vent Pointing Down
’’
Figure 7 -Gas Connection
* Purchase the optional CSA design-certified equipment shutoff valve and flex hose from
your dealer. See Accessories, page 14.
** 11” W.C. pressure is the minimum inlet pressure for purpose of input adjustment.
7