This is an unvented gas-red heater. It uses air (oxygen)
from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided.
Refer to Air for Combustion and Ventilation section on
page 6 of this manual.
WARNING: Improper installation, adjustment, al-
teration, service or maintenance can cause injury or
property damage. Refer to this manual for correct installation and operational procedures. For assistance
or additional information consult a qualied installer,
service agency or the gas supplier.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where
not prohibited by local codes.
This appliance is only for use with propane or natural
gas. Field conversion by any other means including the
use of a kit is not permitted.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.
IMPORTANT: Read this owner’s manual carefully and
completely before trying to assemble, operate, or service this heater. Improper use of this heater can cause
serious injury or death from burns, re, explosion, electrical shock and carbon monoxide poisoning. Failure to
follow these instructions will void the warranty.
Only a qualied installer, service
agent, or local gas supplier may
install and service this product.
WARNING: Keep the appli-
ance area clear and free from
combustible materials, gasoline,
and other ammable vapors and
liquids.
WARNING: This appliance
is equipped for use with natural
gas OR propane gas. Field conversion is not permitted.
This appliance is only for use
with the type of gas indicated on
the rating plate. This appliance
is not convertible for use with
other gases.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the u,
with headaches, dizziness or nausea. If you
have these signs, the heater may not be working properly. Get fresh air at once! Have heater
serviced. Some people are more affected by
carbon monoxide than others. These include
pregnant women, people with heart or lung
disease or anemia, those under the inuence
of alcohol and those at high altitudes.
Natural And Propane/LP Gas: Natural and
Propane/LP gas are odorless. An odor-making
agent is added to the gas. The odor helps you
detect a gas leak. However, the odor added to
the gas can fade. Gas may be present even
though no odor exists.
WARNING: Do not use a
blower insert, heat exchanger
insert or any accessory not approved for use with this log set.
WARNING: Do not allow fans
to blow directly into the heater.
Avoid any drafts that alter burner
ame pattern including ceiling
fans. Altered burner patterns
can cause sooting.
www.usaprocom.com
3200068-01A
SAFETY
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not place
clothing or other flammable
material on or near the appliance. Never place any objects
in the heater.
WARNING: Due to high temperatures, the appliance should
be located out of trafc and away
from furniture and draperies.
WARNING: Heater becomes
very hot when running. Keep
children and adults away from
hot surfaces to avoid burns or
clothing ignition. Heater will remain hot for a time after shutoff.
Allow surfaces to cool before
touching.
WARNING: Carefully supervise young children when they
are in the room with the heater.
WARNING: Make sure a replace screen is in place before
running heater.
1. Do not place Propane/LP supply tank(s)
inside any structure. Propane/LP supply
tank(s) must be placed outdoors.
2. This heater should not be installed in a
bedroom or bathroom unless installed as
a vented appliance.
3. This heater needs fresh air ventilation to
run properly. This heater has an Oxygen
Depletion Sensing (ODS) safety shutoff
system. The ODS shuts down the heater
if not enough fresh air is available. See Air for Combustion and Ventilation, page 6.
If heater keeps shutting off, see Trouble-shooting, page 25.
4. Do not add extra logs or ornaments such
as pine cones, vermiculite, or rock wool.
Using these added items can cause soot-
www.usaprocom.com
ing. Do not add lava rock around base.
Rock and debris could fall into the control
area of heater. After servicing, always
replace screen before operating heater.
5. If replace has glass doors, never operate
this heater with glass doors closed. If you
operate heater with doors closed, heat will
build-up inside replace and cause glass
to burst. If replace opening has vents
at the bottom, you must open the vents
before operating log set. Always operate
heater with glass doors fully open.
6. This log heater is designed to be smokeless. If logs ever appear to be smoking,
turn off heater and call a qualied service
technician. NOTE: During initial operating,
slight smoking could occur due to log curing and heater burning off manufacturing
residues.
7. To prevent the creation of soot, follow the
instructions under Care and Maintenance
page 24.
8. Do not run heater:
• Where ammable liquids or vapors are
used or stored.
• Under dusty conditions.
9. Before using furniture polish, wax, carpet
cleaner, or similar products, turn heater
off. If heated, the vapors from these products may create a white powder residue
within burner box or on adjacent walls or
furniture.
10. Do not use heater if any part has been
under water. Immediately call a qualied
service technician to inspect the room
heater and to replace any part of the
control system and any gas control which
has been under water.
11. Turn off and let cool before servicing. Only
a qualied service person should service
and repair heater.
12. Operating heater above elevations of
4,500 feet could cause pilot outage.
13. Do not use this heater if any log is broken.
Do not operate heater if a log is chipped
(dime-size or larger).
14. To prevent performance problems, do
not use propane/LP fuel tank of less than
100 lbs. capacity.
15. Solid fuels should not be burned in
replace in which a vent-free log set is
installed. Do not use this heater to cook
food or burn paper or other objects.
200068-01A4
PRODUCT FEATURES
This heater is clean burning. It requires no outside venting. There is no heat loss out of a
vent or up a chimney. Heat is generated by realistic, dancing yellow ames. This heater is
designed for vent-free operation with ue damper closed. It has been tested and approved to
ANSI Z21.11.2 standard for unvented heaters. State and local codes in some areas prohibit
the use of vent-free heaters.
SAFETY PILOT
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot shuts off the heater if there is not
enough fresh air.
PIEZO IGNITION SYSTEM
This heater is equipped with a piezo ignitor.
This system requires no matches, batteries,
or other sources to light heater.
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
25 West 43rd Street
New York, NY 10036
National Fire Protection Association, Inc.
1 Batterymarch Park
Quincy, MA 02269-9101
UNPACKING
CAUTION: Do not remove the
metal data plates from the burner
pan. The data plates contain
important product information.
1. Remove logs and burner base assembly
from carton. NOTE: Do not pick up burner
base assembly by burners as this could
damage heater. Always handle base assembly by grate.
2. Remove all protective packaging applied
to logs and base for shipment.
3. Check all items for any shipping damage.
If damaged, promptly inform dealer where
you purchased the heater.
State of Massachusetts: The installation
must be made by a licensed plumber or
gas tter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
In the State of Massachusetts the gas
cock must be a T-handle type. The State
of Massachusetts requires that a exible
appliance connector cannot exceed three
feet in length.
Ignitor
Figure 1 - Product Identication
(Logs May Vary by Model, HLA Base
Control Knob
Shown)
www.usaprocom.com
5200068-01A
QUALIFIED INSTALLING AGENCY
Only a qualied agency should install and
replace gas piping, gas utilization equipment
or accessories, and repair and equipment servicing. The term “qualied agency” means any
individual, rm, corporation, or company that
either in person or through a representative
is engaged in and is responsible for:
a) Installing, testing, or replacing gas piping
or
b) Connecting, installing, testing, repairing,
or servicing equipment; that is experienced
WATER VAPOR: A BY-PRODUCT OF
UNVENTED ROOM HEATERS
Water vapor is a by-product of gas combustion. An unvented room heater produces approximately one (1) ounce (30 mL) of water
for every 1,000 BTUs (0.3 KWs) of gas input
per hour. Unvented room heaters are recommended as supplemental heat (a room) rather
than a primary heat source (an entire house).
In most supplemental heat applications, the
water vapor does not create a problem. In
most applications, the water vapor enhances
the low humidity atmosphere experienced
during cold weather.
AIR FOR COMBUSTION AND VENTILATION
in such work; that is familiar with all precautions required; and that has complied with
all the requirement of the authority having
jurisdiction.
In areas that prohibit the use of vent-free
heaters, the log set has been tested and
approved to the ANSI Z21.60 standard for
Vented Decorative Logs. When used as a
vented log set refer to additional instructions
on page 11.
The following steps will help ensure that water
vapor does not become a problem.
1. Be sure the heater is sized properly for the
application, including ample combustion
air and circulation air.
2. If high humidity is experienced, a dehumidier may be used to help lower the
water vapor content of the air.
3. Do not use an unvented room heater as
the primary heat source.
WARNING: This heater shall
not be installed in a conned
space or unusually tight construction unless provisions are
provided for adequate combustion and ventilation air. Read the
following instructions to insure
proper fresh air for this and
other fuel-burning appliances
in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors
to keep the cold air out and the warm air in.
During heating months, home owners want
their homes as airtight as possible.
www.usaprocom.com
While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the
house to operate. You must provide adequate
fresh air for these appliances. This will insure
proper venting of vented fuel-burning appliances.
WARNING: This heater
shall not be installed in a room
or space unless the required
volume of indoor combustion
air is provided by the method
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA
54, the International Fuel Gas
Code, or applicable local codes.
200068-01A6
AIR FOR COMBUSTION AND VENTILATION
Ventilation
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combustion and ventilation air shall be
provided by one of the methods
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA
54, the International Fuel Gas
Code, or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconned space. When ventilating to an
adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door
into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings
for inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air
entering the attic will activate the power vent. If
an attic opening is unacceptable. Recongure
the conned space, by adding ventilation to
adjoining unconned space or removing doors
as indicated in Figure 2, Option 1 and 2. The
combined spaces must have enough fresh air
to supply all appliances in both spaces. Otherwise a lower input model must be installed
that meets the room size requirements.
Ventilated
Attic
To Attic
Outlet
Air
Outlet
Air
12"
Grills Into
Adjoining
Room,
Option 1
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
12"
Option 2
Figure 2 - Ventilation Air from Inside
Building
www.usaprocom.com
To
Crawl
Inlet
Air
Inlet Air
Ventilated
Crawl Space
Space
Figure 3 - Ventilation Air from Outdoors
7200068-01A
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualied service person must install heater.
Follow all local codes.
WARNING: Before installing
in a solid fuel burning replace,
the chimney ue and rebox
must be cleaned of soot, creosote, ashes and loose paint by
a qualified chimney cleaner.
Creosote will ignite if highly
heated. A dirty chimney ue may
create and distribute soot within
the house. Inspect chimney ue
and rebox for damage. If damaged, repair ue before operating heater.
WARNING: Seal any fresh
air vents or ash clean-out doors
located on oor or wall of replace. If not, drafting may cause
pilot outage or sooting. Use a
heat-resistant sealant. Do not
seal chimney ue damper.
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, cloth-
ing, or other ammable objects
are less than 36" from the front,
42" from top, or 16" from sides
of the heater.
• in high trafc areas
• in windy or drafty areas
CAUTION: This heater cre-
ates warm air currents. These
currents move heat to wall surfaces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as tobacco smoke, aromatic candles,
cleaning uids, oil or kerosene
lamps, etc.) in the air exist, may
discolor walls or cause odors.
NOTICE: State or local codes
may only allow operation of this
appliance in a vented conguration. Check your state or local
codes.
WARNING: This appliance is
designed for installation in only
a solid-fuel burning masonry or
UL 127 factory-built replace or
in a listed ventless rebox enclosure. Exception: DO NOT install
this appliance in a factory-built
replace that includes instructions stating it has not been
tested or should not be used
with unvented gas logs.
www.usaprocom.com
200068-01A8
INSTALLATION
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing
heater in rooms without enough ventilation air
may cause mildew to form too much moisture.
See Air for Combustion and Ventilation, pages
6 and 7.
Before beginning assembly or operation of
the product, make sure all parts are present. Compare parts with package contents
list. If any part is missing or damaged, do
not attempt to assemble, install or operate
the product. Contact customer service for
replacement parts.
Before installing heater, make sure you have
the items listed below:
• Hardware package (provided with heater)
• Electric drill with 3/16" drill bit
• Phillips screwdriver
CHECK GAS TYPE
Be sure your gas supply is right for your heater. Otherwise, call dealer where you bought
the heater for proper type heater.
CLEARANCES TO
COMBUSTIBLES
WARNING: Maintain the mini-
mum clearances. If possible, provide greater clearances from oor,
ceiling, and adjoining wall. Measure
from outermost point of heater.
Minimum Fireplace Clearance To
Combustible Materials
Side Wall 16", Ceiling 42", Front 36"
LOG SIZING REQUIREMENTS
Minimum Firebox Size
18" Log Set: Height 20", Depth 14",
Front Width 29", Rear Width 23"
24" Log Set: Height 20.5", Depth 14",
Front Width 34", Rear Width 25.5"
30" Log Set: Height 20.5", Depth 14",
Front Width 39", Rear Width 31.5"
Minimum Clearances For Side
Combustible Material, Side Wall
and Ceiling
A. Clearance from the side of the replace
cabinet to any combustible material and
wall should follow diagram in Figure 4.
B. Clearance from the top of the replace
opening to the ceiling must not be less
than 42".
www.usaprocom.com
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel, proceed to If Using
Mantel, page 10. If not using a mantel, follow
the information below.
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material behind it. Noncombustible material must extend
at least 12" up (for all models). See Figure 5
for minimum clearances.
Requirements for Safe Installation
(A) 12" or more: Noncombustible material okay.
(A) Between 8" and 12":
24" & 30" Models, install replace hood
accessory. 18" Models, noncombustible
material okay.
(A) Less than 8": Noncombustible
material must be extended to at least 8".
See Between 8" and 12", above. If you
cannot extend material, you must operate
heater with ue damper open.
Noncombustible
Material Distance
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
9200068-01A
INSTALLATION
Mantel Shelf
Minimum
Noncombustible
Material
Mantel Shelf
NOTICE: This heater may be
used as a vented product. If so,
you must always operate log set
with chimney ue damper open.
If running log set with damper
open, noncombustible material
above replace opening is not
needed. Go to Installing Damper
Clamp Accessory for Vented
Operation, page 11.
If Using Mantel
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
10"
8"
6"
1
2
/2"
Minimum
Noncombustible
Material
(A)
8" 14" 16" 20"
8"
12" 18" 20" 22" 24" 24" Log Set
Minimum
Noncombustible
Material Height
Distances to
Underside of
Mantel
Figure 6 - Minimum Mantel Clearances
Without Using Hood
12"
10"
8"
6"
2½"
8"
12" 15" 18" 20"
Hood
Min.
Distances to
Underside of
Mantel
Figure 7 - Minimum Mantel Clearances
When Using Hood
Underside of
Mantel Shelf
All minimum
distances are
in inches
18" Log Set
30" Log Set
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Top of
Fireplace
Opening
www.usaprocom.com
you must have noncombustible material behind it. Noncombustible material must extend
at least 8" up. If noncombustible material is
less than 12", you must install the replace
hood accessory. Even if noncombustible
material is more than 12", you may need the
hood accessory to deect heat away from
your mantel shelf. See Figures 5, 6 and 7, for
minimum clearances.
MANTEL CLEARANCES
In addition to meeting noncombustible material clearances, you must also meet required
clearances between replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel
Clearance
If you meet minimum clearance between
mantel shelf and top of replace opening, a
hood is not required (see Figure 6).
Determining Minimum Mantel
Clearance When Using a Hood
If minimum clearances in Figure 6 are not met,
you must have a hood. When using a hood
there are still certain minimum mantel clearances required. Follow minimum clearances
shown in Figure 7, when using hood.
NOTICE: Surface temperatures
of adjacent walls and mantels
become hot during operation.
Walls and mantels above the
firebox may become hot to
the touch. If installed properly,
these temperatures meet the
requirement of the national
product standard. Follow all
minimum clearances shown in
this manual.
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• operate the logs only with the
ue damper open
• raise the mantel to an accept-
able height
• move the mantel
200068-01A10
INSTALLATION
Combustible
FLOOR CLEARANCES
A. If installing appliance on the oor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 8).
Combustible
14"
Min.
Material
Noncombustible Material
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED
OPERATION
When used as a vented heater, appliance
must be installed only in a solid-fuel burning
replace with a working ue constructed of
noncombustible material. You may use this
heater as a vented product. There are three
reasons for operating your heater as a vented
model:
1. The replace does not meet the clearance
requirements for vent-free operation.
2. State or local codes do not permit ventfree operation.
3. You prefer vented operation.
If reasons number 1 or 2 above apply, you
must permanently open chimney ue damper.
You must install the damper clamp accessory
(not provided). This will insure vented operation (see Figure 10). The damper clamp will
keep damper open. Installation instructions
are included with clamp accessory.
See chart below for the minimum permanent
ue opening you must provide. Attach damper
clamp so the minimum permanent opening will
be maintained at all times.
B. If combustible materials are less than 14"
to the replace, you must install appliance
at least 5" above the combustible ooring
(see Figure 9).