Procom ML060HBA, ML100HBA, ML100TBA Owner's Operation And Installation Manual

Page 1
BLUE FLAME VENT-FREE
PROPANE/LP GAS
SPACE HEATER
OWNER’S OPERATION AND INSTALLATION MANUAL
Table of Contents
ML060HBA ML100HBA ML100TBA
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.
Important Safety Information.................................2
Product Features.....................................................3
Proper Ventilation & Fresh Air...............................4
Installation................................................................6
Operating Your Heater...........................................10
Cleaning & Maintenance.......................................13
Trouble Shooting...................................................14
Specifications..........................................................17
Parts List.................................................................19
TOLL FREE NUMBER: 1-877-886-5989
WARNING: This is an unvented gas-fired
heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air For Combus­tion and Ventilation section on page 4 of this manual.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
Do not store, or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
l Do not try to light any appliance. l Do not touch any electrical switch; do not
use any phone in your building. l Immediately call your gas supplier from a neighbors phone. Follow the gas suppliers instructions. l If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or gas supplier.
WARNING: Improper installation,
adjustment, alteration, service or mainte­nance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or gas supplier.
This appliance may be installed in an aftermar­ket* permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS Water vapor is a by-product of gas combustion. An unvented room heater produces approximately one (1) ounce (30ml) of water for every 1,000 BTUs (.3KWs) of gas input per hour. Refer to page 3.
Installer: Please leave these instructions with the consumer.
Consumer: Please retain these instructions for future use.
CONTINENTAL APPLIANCE INC/U.S. OFFICE
5 Musick 4600 Highlands Parkway S.E.
Irvine Suite # D/E
CA 92618 Smyrna, GA 30080
Nanjing PRO-COM Electric Appliance Co.,Ltd.
#6 Chuangye Road,High New Tech.Zone,
Great Bridge Road North,Nanjing,210061,
China.
PR-ML062-16-0803
Page 2
2
IMPORTANT SAFETY INFORMATION
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors.
3. If you smell gas
l Shut off gas supply. l Do not try to light any appliance. l Do not touch any electrical switch;
do not use any phone in your building. l Immediately call your gas sup plier from a neighbors phone. Follow the gas suppliers instructions. l If you cannot reach your gas supplier, call the fire department.
4. This heater needs fresh, outside air ventilation to run properly. This heater has an Oxygen Depletion Sensor (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Fresh Air For Combustion And Ventilation, pages 4 through 6.
5. Keep all air openings in the front and bottom of heater clear and free of debris. This will insure enough air for proper combustion.
6. If heater shuts off, do not relight until you provide fresh, outside air. If heater keeps shutting off, have it serviced.
7. Do not operate heater l where flammable liquids or va pors are used or stored l under dusty conditions
9. Do not use heater if any part has been under water.
Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.
10. Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.
11. Operating heater above elevations of 4,500 feet could cause pilot outage.
12. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.
13. Do not install in a bathroom except model ML060HBA.
Carbon Monoxide Poisoning:
Early signs of carbon monoxide poisoning resemble the flu with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, persons with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Propane/LP: Propane/LP gas is odorless. An odor-making agent is added to Propane/LP gas. The odor helps you detect a Propane/LP gas leak. However, the odor added to Propane/LP gas can fade. Propane/LP gas may be present even though no odor exists.
Make certain you read and under­stand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
DANGER: Carbon monoxide
poisoning may lead to death
heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
8. Turn heater off before using furniture polish, wax, carpet cleaner, or similar products. If
copy of 527 CMR 30 upon sale of the unit.
Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
IMPORTANT: Read this
owners manual carefully and completely before trying to assemble, operate, or service this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Due to high temperatures, heater should be kept out of traffic and away from furniture and draperies.
Surface of heater becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will remain hot for a time after shut down. Allow surface to cool before touching.
Carefully supervise young children when they are in the same room with heater.
Make sure grill guard is in place before running heater.
WARNING: Do not use any
accessory not approved for use with this heater.
WARNING: Any change to
this heater or its controls can be dangerous.
State of Massachusetts: The
installation must be made by a li­censed plumber or gas fitter in the Commonwealth of Massachusetts. Sellers of unvented propane or natu­ral gas-fired supplemental room heat­ers shall provide to each purchaser a
In the state of Massachusetts, unvented propane or nature gas-fired space heat­ers shall be prohibited in bedrooms and
bathrooms.
Modeles ML060HBA, ML100HBA, ML100TBA are equipped for propane gas. Field conversion is not permitted.
WARNING
Page 3
3
PRODUCT FEATURES
SAFETY DEVICE
A standard requirement for all vent-free room heaters. This heater has a pilot with an Oxygen Depletion Sensor(ODS) safety shutoff system. The ODS/pilot shuts off the heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater is equipped with a piezo ignitor. This system requires no matches, batteries, or other sources to light heater.
THERMOSTATIC CONTROL ON THERMOSTAT MODEL
These heaters have a control valve with a thermostat sensing bulb. This results in the greatest heater comfort and may result in lower gas bills.
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of National Fuel Gas Code ANSZ223.1, also known as NFPA 54*. *Available from: American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park Quincy, MA 02269
UNPACKING
1. Remove heater from carton.
2. Remove all protective packaging applied to
heater for shipment.
3. Check heater for any shipping damage. If heater is damaged, promptly inform dealer where you bought heater.
Figure1-Vent-Free Propane/LP Gas Heater
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS
Water vapor is a by-product of gas combustion. An unvented room heater produces approximately one (1) ounce (30ml) of water for every 1,000 BTUs (.3KWs) of gas input per hour. Unvented room heaters are recommended as supple­mental heat (a room) rather than a primary heat source (an entire house). In most supplemental heat applications, the water vapor does not create a problem. In most applications, the water vapor en­hances the low humidity atmosphere experienced during cold weather.
The following steps will help insure that water vapor does not become a problem.
1. Be sure the heater is sized properly for the application, including ample combustion air and circulation air.
2. If high humidity is experienced, a dehumidifier may be used to help lower the water vapor con­tent of the air.
3. Do not use an unvented room heater as the pri­mary heat source.
Page 4
4
FRESH AIR FOR COMBUSTION AND
VENTILATION
PROVIDING ADEQUATE VENTILATION
The following are excerpts from
National Fuel Gas Code. NFPA 54/ANS Z223.1, Section 5.3. Air for
Combustion and Ventilation. All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 4 through 6 will help you classify your space and provide adequate ventilation.
WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Confined and Unconfined Space
The National Fuel Gas Code ANS Z223.1 defines a confined
space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space. This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.
*
Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the outside atmosphere have a con­tinuous water vapor retarder with a rating of one perm (6×10
-11
kg per pa-sec-m2) or less with openings gasketed or sealed and b. weather stripping has been added on openable windows and doors and c. caulking or sealants are applied to areas such as joints around win­dow and door frames, between sole plates and floors, between wall­ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings. If your home meets all of
the three criteria above, you must provide additional fresh air. See
Ventilation Air From Outdoors, page 5 and 6.
If your home does not meet all of the three criteria above, see
Determining Fresh-Air Flow for Heater Location, page 4, 5.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if you Have a Confined or Unconfined Space*
Use this worksheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length×width×height). Length×Width×Height= cu.ft. (volume of space) Example: Space size 20ft. (length)×16ft( width)×8ft. (ceiling height)=2560cu. ft. (volume of space) If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support. (volume of space)÷50 cu. ft.=(Maximum Btu/Hr the space can support) Example: 2560 cu. ft. (volume of space)÷50 cu.ft.=51.2 or 51,200(maximum Btu/Hr the space can support)
Page 5
5
WARNING: Rework worksheet, add­ing the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.
AIR FOR COMBUSTION AND VENTILATION
Continued VENTILATION AIR
Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National
Fuel Gas Code NFPA 54/ANS Z223.1. Section 5.3, Air for Combustion and Ventilation for required size of
ventilation grills or ducts
Example: Gas water heater 44,000 Btu/Hr Vent free heater + 10,000 Btu/Hr Total = 54,000 Btu/Hr
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
3. Add the Btu/Hr of all fuel burning appliances in the space. Vent-free heater Btu/Hr Gas water heater* Btu/Hr Gas furnace Btu/Hr Vented gas heater Btu/Hr Gas Fireplace logs Btu/Hr Other gas appliances* + Btu/Hr Total = Btu/Hr
*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
Btu/Hr (maximum the space can support) Btu/Hr (actual amount of Btu/Hr used) Example : 51,200 Btu/Hr(maximum the space can support)
54,000 Btu/Hr(actual amount of Btu/Hr used) The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows: A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 5. B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6 . C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
Figure 2 -Ventilation Air from Inside Building
Page 6
6
VENTILATION AIR
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or duels: You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas
Code NFPA 54/ANS Z223.1, Section 5.3. Air for Combustion and Ventilation for
required size of ventilation grills or ducts. IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run systems circulating blower while using heater. This will help circulate the heat through­out the house. In the event of a power outage, you can use this heater as your primary heat source.
CHECK GAS TYPE
Use only propane/LP gas. If your gas supply is not propane/LP, do not install heater. Call dealer where you bought heater for proper type heater.
*A CSA/AGA design-certified equip­ment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA/AGA design certi­fied equipment shutoff valve from your dealer. See Accessories, page
17.
LOCATING HEATER
This heater is designed to be mounted on a wall. For convenience and efficiency, install heater
l where there is an easy access for
operation, inspection, and service
l in coldest part of room
INSTALLATION
CAUTION: If you install the
heater in a home garage
l heater pilot and burner must
be at least 18 inches above
floor.
l locate heater where moving
vehicle will not hit it.
CAUTION: This heater creates warm air currents. These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as tobacco smoke, aromatic candles, clean­ing fluids, oil or kerosene lamps, etc.) in the air exist may discolor walls.
Figure 3 -Ventilation Air from Outdoors
INSTALLATION NEEDS
Before installing heater, make sure you have the items listed below.
l piping (check local codes) l sealant (resistant to Propane/LP
gas)
l equipment shutoff valve*
l ground joint union
l test gauge connection*
l sediment trap
l tee joint
l pipe wrench
WARNING: A qualified service person must install heater. Follow all local codes.
WARNING: Never install
the heater l in a bathroom (Models
ML100HBA and ML100TBA, only ML060HBA is allowed in bathroom. Check local codes.)
l in a recreational vehicle. l where curtains, furniture,
clothing, or other flammable ob­jects are less than 36 inches from the front, top, or sides of the heater.
l as a fireplace insert. l in high traffic areas. l in windy or drafty areas.
When the heater is installed in
Bathrooms,do not use flammable
products such as aerosol hair spray,
foot spary or any product that contains
flammable vapors and keep towels
away from heater.(only ML060HBA is allowed in a bathroom.)
Page 7
7
INSTALLATION
Figure 8 - Mounting Bracket Clearances
Figure 7 - Removing Lower Front Panel Of Heater
Figure 4 -Mounting Clearances As Viewed From Front Of Heater
WARNING: Maintain the minimum clearances shown in Figure 4. If you can, provide greater clearances from floor, ceiling, and joining wall.
FASTENING HEATER TO WALL Mounting Bracket
The mounting bracket is located on back panel of heater (see Figure 6). It has been taped there for shipping. Remove mounting bracket from back panel.
Removing Lower Front Panel Of Heater
1. Remove two screws near bottom corners of lower front panel.
2. Pull bottom of lower front panel forward, then down (see Figure 7).
Methods For Attaching Mounting Bracket To Wall
Only use last hole on each end of mounting bracket to attach bracket to wall. Attach mounting bracket to wall only in one of two ways:
1. Attaching to wall stud
2. Attaching to wall anchor
Attaching to Wall Anchor: This method allows you to attach mounting bracket to hollow walls (wall areas between studs) or to solid walls (concrete or masonry).
Decide which method better suits your needs. Either method will provide a secure hold for the mounting bracket.
Marking Screw Locations
1. Tape mounting bracket to wall where heater will be located. Make sure mounting bracket is level.
2. Mark screw locations on wall. (see Figure 8) Note: Only mark last hole on each end of mounting bracket. Insert mounting screws through these holes only.
3. Remove tape and mounting bracket from wall.
Attaching to Wall Stud: This method provides the strongest hold. Insert mounting screws through mounting bracket and into wall studs.
Figure 5 -Moving Thermostat Sensing Bulb
Figure 6 -Mounting Bracket Location
WARNING: Maintain minimum clearances shown in Figure 8. If you can, provide greater clearances from floor and joining wall.
INSTALLING THERMOSTAT SENSING BULB For T-Stat Model Only
1. Pull out the sensing bulb from the two clips located in the shippng position according to the direction as shown by the arrow. There is no need to take out the two bulb clips.
2. Take out the bulb clip from the hardware package and insert it into the square hole and then insert the sensing bulb into the bulb clip (see Figure 5).
Page 8
8
INSTALLATION
Figure 11 - Mounting Heater Onto Mounting Bracket
Figure 9 - Folding Anchor
Figure 10 - Popping Open Anchor Wing For Thin Walls
Attaching Mounting Bracket To Wall
Note: Wall anchors, mounting screws, and spacers are in hardware package. The hardware package is provided with heater.
Attaching to Wall Stud Method
For attaching mounting bracket to wall studs
1. Drill holes at marked locations using 9/64" drill bit.
2. Place mounting bracket onto wall. Line up last hole on each end of bracket with holes drilled in wall.
3. Insert mounting screws through bracket and into wall studs.
4. Tighten screws until mounting bracket is firmly fastened to wall studs.
Attaching to Wall Anchor Method
For attaching mounting bracket to hollow walls (wall areas between studs) or solid walls (concrete or masonry)
1. Drill holes at marked locations using 5/16" drill bit. For solid walls (concrete or masonry), drill at least 1" deep.
2. Fold wall anchor as shown in Figure 9 below.
3. Insert wall anchor (wings first) into hole. Tap anchor flush to wall.
4. For thin walls (1/2" or less), insert red key into wall anchor. Push red key to "pop" open anchor wings (See Figure 10).
IMPORTANT: Do not hammer key! For thick walls (over 1/2" thick) or solid walls, do not pop open wings.
5. Place mounting bracket onto wall. Line up last hole on each end of bracket with wall anchors.
6. Insert mounting screws through bracket and into wall anchors.
7. Tighten screws until mounting bracket is firmly fastened to wall.
Placing Heater On Mounting
Bracket
1. Locate two horizontal slots on back panel of heater (see Figure 11).
2. Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on mounting bracket.
Installing Bottom Mounting Screw
1. Locate bottom mounting hole. This hole is near bottom on back panel of heater(see Figure 12).
2. Mark screw location on wall.
3. Remove heater from mounting bracket.
4. If installing bottom mounting screw into hollow or solid wall, install wall anchors. Follow steps
1 through 4 under Attaching To
Wall Anchor Method. If installing bottom mounting screw into wall stud, drill holes at marked locations using 9/64" drill bit.
5. Replace heater onto mounting bracket.
6. Place spacers between bottom mounting holes and wall anchor or drilled hole.
7. Hold spacer in place with one hand. With other hand, insert mounting screw through bottom mounting hole and spacer. Place tip of screw in opening of wall anchor or drilled hole.
8. Tighten screw until heater is firmly secured to wall. Do not over tighten. l Note: Do not replace lower front panel at this time. Replace lower front panel after making gas connections and checking for leaks (see page 10).
Figure 12 - Installing Bottom Mounting screw
Page 9
9
INSTALLATION
CONNECTING TO GAS SUPPLY
WARNING: A qualified
service person must connect heater to gas supply. Follow all local codes.
WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pressure regulator.
CAUTION: Never connect heater directly to the propane/LP supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and propane/LP supply.
*A CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA/AGA design-certified equipment shutoff valve from your dealer. See Accessories, page 17.
Figure 14 -Gas Connection
The installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 13. Pointing the vent down protects it from freezing rain or sleet.
Figure 13 - External Regulator with Vent Pointing Down
excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
IMPORTANT: Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of large enough diameter to allow proper gas volume to heater. If pipe is too small, undue loss of pressure will occur.
Typical Inlet Pipe Diameters
All models up to 20,000 BTUs use 3/8’’ or greater pipe; All models 25,000 BTUs and higher, use 1/2 or greater pipe. Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 14).
Install sediment trap in supply line as shown in Figure 14. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly. IMPORTANT: Hold pressure regulator with wrench when connecting it to gas piping and/or fittings.
CAUTION: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
WARING:Do not over tighten gas
connections.
Apply pipe joint sealant lightly to male threads. This will prevent
Page 10
10
Figure 15 -Equipment Shutoff Valve
INSTALLATION
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections for leaks after installing or servicing. Correct all leaks at once.
WARNING: Never use an
open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.
Pressure Testing Gas Supply Piping System Test Pressures In Excess Of 1/2 PSIG (3.5 K Pa)
1. Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve
was connected.
3. Pressurize supply piping system by either using compressed air or opening
propane/LP supply tank valve.
4. Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show
a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment
shutoff valve to gas supply. Check
reconnected fittings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 K Pa)
1. Close equipment shutoff valve
(see Figure 15).
2. Pressurize supply piping system
by either using compressed air or opening propane/LP supply tank valve.
3. Check all joints from gas meter to
equipment shutoff valve (see Figure 16). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Pressure Testing Heater Gas Connections
1. Open equipment shutoff valve (see Figure 15).
2. Open propane/LP supply tank valve.
3. Make sure control knob of heater is in the OFF position.
4. Check all joints from equipment shutoff valve to control valve (see Figure 16 ). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operating Heater, pages 10 and 11 for non-thermostat models or page 12 for thermostat model). Check the rest of the internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to Appliance, page 11 for non-thermostat models or page 12 for thermostat model).
8. Replace lower front panel.
OPERATING YOUR HEATER
NON-THERMOSTAT MODEL
nFOR YOUR SAFETYn
READ BEFORE LIGHTING
WARNING: If you do not
follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A When lighting the pilot, follow these instructions exactly. B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor .
WHAT TO DO IF YOU SMELL GAS
l Do not try to light any appliance. l Do not touch any electric switch;
do not use any phone in your building. l Immediately call your gas supplier from a neighbors phone. Follow the gas suppliers instructions. l If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, dont try to repair it, call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Figure 16 -Checking Gas Joints
Page 11
11
Figure 18 - Pilot
Manual Control Models
nLIGHTINGn
INSTRUCTIONS
1. STOP! Read the safety
information on the side of heater.
2. Check that gas supply to
heater is on.
3. Push in gas control knob
slightly and turn clockwise to the OFF position.
4. Wait five (5) minutes to clear
out any air. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information on the side of the heater. If you do not smell gas, go to the next step.
5. Push in gas control knob
slightly and turn counterclockwise to "PILOT/IGN" and depress for five(5) seconds NOTE: The first time that the heater is operated after connecting the gas supply , the control knob should be depressed for about thirty (30) seconds. This will allow air to bleed from the gas system.
6. With control knob pressed in,
push down and release the ignitor button. This will light pilot. If needed, keep pressing ignitor button until pilot lights.
7. Keep control knob depressed
for ten (10) seconds after lighting pilot. If pilot goes out, repeat steps 5,6 and 7.
8. To select the desired heating
level, partially press down the control knob slightly and rotate counterclockwise . Release the downward pressure on the knob while continuing to turn until the knob locks at the desired set­ ting position. Do not operate between locked positions.
l Set control knob to desired heating position. NOTE: Both HIGH and LOW are locked positions. You must press in control knob before turning it from these positions.
nTO TURN OFFn
GAS TO APPLIANCE
Shutting Off Heater
1. Turn control knob clockwise to the OFF position.
2. Turn off all electric power to the appliance if service is to be performed.
SHUTTING OFF BURNER ONLY (PILOT STAYS LIT)
Turn control knob clockwise
to the PILOT/IGN position.
nMANUAL LIGHTINGn
PROCEDURE
1. Remove lower front panel (see Figure 7 page 7).
2. Follow steps 1 through 5 under Lighting Instructions.
3. With control knob pressed in, strike match. Hold match to pilot until pilot lights.
4. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Follow step 8 under Lighting Instructions.
5. Replace lower front panel.
OPERATING YOUR HEATER
CAUTION: Do not try to
adjust heating levels by using the equipment shutoff valve.
Figure 17-2 - Control Knob in The OFF Position (ML100HBA&ML100TBA)
Figure 17 -1- Control Knob In The OFF Position (ML060HBA)
Page 12
12
OPERATING YOUR HEATER
THERMOSTAT MODEL
nFOR YOUR SAFETYn
READ BEFORE LIGHTING
A. When lighting the pilot, follow these instructions exactly. B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
l Do not try to light any appliance. l Do not touch any electric
switch, do not use any phone in your building. l Immediately call your gas
supplier from a neighbors
phone. Follow the gas suppliers instructions. l If you cannot reach your gas
supplier, call the fire department. C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, dont try to repair it , call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
nLIGHTINGn
INSTRUCTIONS
4. Wait five(5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow B in the safety information on the side of heater. If you dont smell
gas, go to the next step.
5. Turn control knob counterclock­wise to the PILOT position. Press in control knob for five(5) seconds. (see Figure19).
Note: You may be running
this heater for the first time after hooking up to gas supply. If so, the control knob may need to be pressed in for 30 seconds. This will allow air to
bleed from the gas system. l If control knob does not
pop up when released, contact a qualified service person or
gas supplier for repairs.
6. With control knob pressed in, push down and release ignitor button. This will light pilot. The pilot is attached to the front of burner. The pilot can be seen through the glass panel. If
needed, keep pressing ignitor button until pilot lights. Note: If pilot does not stay lit, refer to Troubleshooting, pages 14 through
16. Also contact a qualified service
person or gas supplier for repairs. Until repairs are made, light pilot with match.To light pilot with match, see Manual Lighting Procedure.
7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release
control knob. l If control knob does not
pop up when released, contact a qualified service person or gas
supplier for repairs.
nTO TURN OFF GASn
TO APPLIANCE
Shutting Off Heater
1. Turn control knob clockwise to the OFF position.
2. Turn off all electric power to the appliance if service is to be performed.
Shutting Off Burner Only (pilot stays lit )
Turn control knob clockwise to the PILOT position.
Figure 19 - Control Knob in The OFF Position
Figure 20 - Pilot
Note: If pilot goes out,repeat steps 3
through 7.This heater has a safety interlock system. Wait one(1) minute before lighting pilot again.
8. Turn control knob counter­clockwise to desired heating
level. The main burner should
light. Set control knob to any
heat level between HI and LO.
WARNING: If you do not follow
these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
1. STOP! Read the safety information on the side of heater.
2. Make sure equipment shutoff
valve is fully open.
3. Turn control knob clockwise
to the OFF position.
CAUTION: Do not try to adjust heating levels by using the equipment shutoff valve.
nTHERMOSTAT CONTROL OPERATIONn
The thermostatic control used on this model differs from standard thermostats.Standard thermostats simply turn on and off the burner. The thermostat used on this heater senses the room temperature. At times the room may exceed the set temperature. If so, the burner will shut off. The burner will cycle back on when room temperature drops below the set temperature. The control knob can be set to any comfort level between HI and LO.
Note: The thermostat sensing bulb mea-
sures the temperature of air near the heater cabinet.This may not always agree with room temperature(depending on housing construction, installation location, room size, open air temperature,etc.) Frequent use of your heater will let you determine your own comfort levels.
Page 13
13
Figure 21 - Correct Pilot Flame Pattern
Figure 22 - Incorrect Pilot Flame Pattern
Figure 24 - Incorrect Burner Flame Pattern
Figure 23 - Correct Burner Flame Pattern
l turn heater off (see To Turn Off
Gas to Appliance, pages 10 & 11 for non-thermostat models and page 12 for thermostat model ).
l see Troubleshooting, pages 14
through 16.
ODS/PILOT AND BURNER
l Use a vacuum cleaner, pres-
surized air, or a small, soft
bristled brush to clean.
CLEANING BURNER PILOT AIR INLET HOLE
We recommend that you clean the unit every 2,500 hours of operation or every three months. We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recommend using compressed air no greater than 30 PSl.Your local computer store, hardware store, or home center may carry compressed air in a can. You can use a vacuum cleaner in the blow position. If using compressed air in a can, please follow the directions on the can. If you dont follow directions on the can, you could damage the pilot assembly.
1. Shut off the unit, including the pilot. Allow the unit to cool for
at least thirty minutes.
2. Inspect burner and pilot for dust
and dirt.
3. Blow air through the ports/slots
and holes in the burner. Also clean the pilot assembly. A yellow tip on the pilot flame indi­cates dust and dirt in the pilot assembly. There is a small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot assembly (see Figure 25). With the unit off , lightly blow air through the air inlet hole. You may blow through a drinking straw if compressed air is not available.
Figure 25 - Pilot Inlet Air Hole
CABINET
Air Passageways
l Use a vacuum cleaner or pressurized air to clean.
Exterior
l Use a soft cloth dampened with a mild soap and water mixture. Wipe the cabinet to remove dust.
nINSPECTING BURNERn
Check pilot flame pattern and burner flame pattern often.
PILOT FLAME PATTERN
Figure 21 shows a correct pilot flame pattern. Figure 22 shows an incorrect pilot flame pattern. The incorrect pilot flame is not touching thermocouple. This will cause the thermocouple to cool. When the thermocouple cools, the heater will shut down. If pilot flame pattern is incorrect, as shown in Figure 22. l turn heater off (see To Turn Off
Gas to Appliance on page 11
for non-thermostat models or page 12 for thermostat models) l see Troubleshooting pages 14 through 16
n CLEANING AND n MAINTENANCE
BURNER FLAME PATTERN
Figure 23 shows a correct burner flame pattern. Figure 24 shows an incorrect burner flame pattern. If pilot flame pattern is incorrect, as shown in Figure 24.
WARNING: Turn off heater
and let cool before servicing.
CAUTION: You must keep con­trol areas, burner, and circulating air passageways of heater clean. Inspect these areas of heater be­fore each use. Have heater in­spected yearly by a qualified ser­vice person. Heater may need more frequent cleaning due to excessive lint from carpeting, bedding material, pet hair, etc.
OPERATING HEATER
Continued
1. Remove lower front panel (see Figure 7 page 7).
2. Follow steps through 5 under
Lighting Instructions on page12.
3. With control knob pressed in,
strike match. Hold match to pilot until pilot lights.
4. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Follow step 8 under Lighting Instuctions on page 12.
5. Replace lower front panel.
nMANUAL LIGHTINGn
PROCEDURE
WARNING: If yellow tipping
occurs, your heater could produce increased levels of carbon monoxide. If burner flame pattern shows yellow tipping, follow instructions at bottom of this page.
Notice: Do not mistake orange flames with yellow tipping. Dirt or other fine particles enter the heater and burn causing brief patches of orange flame.
Page 14
14
TROUBLESHOOTING
Note : All troubleshooting items are listed in order of operation.
WARNING: Only a qualified service person should service and repair heater.
CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/pilot unit.
OBSERVED PROBLEM
When ignitor button is pressed in, there is no spark at ODS/pilot.
When ignitor button is pressed in, there is a spark at ODS/pilot but no ignition.
ODS/pilot lights but flame goes out when control knob is released.
POSSIBLE CAUSE
1. Ignitor electrode is positioned wrong.
2. Ignitor electrode is broken.
3. Ignitor electrode is not connected to ignitor cable.
4. Ignitor cable is pinched or wet.
5. Broken ignitor cable.
6. Bad piezo ignitor.
1.Gas supply is turned off or equipment shutoff valve is closed.
2. Control knob not fully pressed in while pressing ignitor button.
3. Air in gas lines when installed.
4. ODS/pilot is clogged.
5. Gas regulator setting is not correct.
6. Control knob not in PILOT position.
7. Depleted gas supply .
1. Control knob is not fully pressed in.
2. Control knob is not pressed in long enough.
3. Equipment shutoff valve is not fully open.
4. Thermocouple connection is loose at control valve.
5. Thermocouple damaged.
6. Control valve damaged.
REMEDY
1. Replace ignitor.
2. Replace ignitor.
3. Reconnect ignitor cable.
4. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry.
5. Replace ignitor cable.
6. Replace piezo ignitor.
1. Turn on gas supply of open equipment shutoff valve.
2. Fully press in control knob while pressing ignitor button.
3. Continue holding down control knob. Repeat igniting operation
until air is removed.
4. Clean ODS/pilot (see Cleaning
and Maintenance, Page 13) or
replace ODS/pilot assembly
5. Replace gas regulator.
6. Turn control knob to pilot position
7. Contact local propane/LP gas campany.
1. Press in control knob fully.
2. After ODS/pilot lights, keep control
knob pressed in 30 seconds.
3. Fully open equipment shutoff valve
4. Hand tighten until snug, then
tighten 1/4 turn more.
5. Replace thermocouple.
6. Contact Dealer or PRO-COM
Page 15
15
TROUBLESHOOTING
Continued
OBSERVED PROBLEM
Burner(s)does not light after ODS/pilot is lit.
Delayed ignition of burner(s).
Burner backfiring during combustion.
Yellow flame during burner combustion.
Slight smoke or odor during initial operation.
Heater produces a whistling noise when burner is lit.
Heater produces a clicking/ticking noise just after burner is lit or shut off.
White powder residue forming within burner box or on adjacent walls or furniture.
POSSIBLE CAUSE
1. Burner orifice is clogged.
2. Burner orifice diameter is too small.
3. Inlet gas pressure is too low.
1. Manifold pressure is too low.
2. Burner orifice is clogged.
1. Burner orifice is clogged or damaged.
2. Burner is damaged.
3. Gas regulator is defective.
1. Not enough air.
2. Gas regulator is defective.
3. Inlet gas pressure is too low.
1. Residues from manufacturing processes.
1. Turning control knob to HI position when burner is cold.
2. Air in gas line.
3. Air passageways on heater are blocked.
4. Dirty or partially clogged burner orifice.
1. Metal is expanding while heating or contracting while cooling.
1. When heated, the vapors from furniture polish, wax, carpet cleaners, etc. turn into white powder residue.
REMEDY
1. Clean burner orifice (see Cleaning and Maintenance Page 13) or replace burner orifice.
2. Replace burner orifice.
3. Contact local propane/LP gas company.
1. Contact local propane/LP gas company.
2. Clean burner (see Cleaning and Maintenance Page 13) or replace burner orifice.
1. Clean burner orifice (see Cleaning and Maintenance Page 13) or replace.
2. Contact Dealer or PRO-COM
3. Replace gas regulator.
1. Check burner for dirt and debris. If found, clean burner (see Cleaning and Maintenance Page 13).
2. Replace gas regulator.
3. Contact local propane/LP gas company.
1. Problem will stop after a few hours of operation.
1. Turn control knob to LO position and let warm up for a minute.
2. Operate burner until air is removed from line. Have gas line checked by local propane/LP gas company.
3. Observe minimum installation clearances (Figure 4, p7).
4. Clean burner (see Cleaning and maintenance Page 13) or replace burner orifice.
1. This is common with most heaters. if noise is excessive, contact qualified service person.
1. Turn heater off when using furniture polish, wax, carpet cleaner, or similar products.
Page 16
16
TROUBLESHOOTING
Continued
WARNING: If you smell gas
l Shut off gas supply.
l Do not try to light any appliance.
l Do not touch any electrical switch; do not use any phone in your building.
l Immediately call your gas supplier from a neighbors phone. Follow the gas
suppliers instructions.
l If you cannot reach your gas supplier, call the fire department.
IMPORTANT: Operating heater where impurities in air exist may create odors. Clean-
ing supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or
textiles, etc., create fumes. These fumes may mix with combustion air and create odors.
REMEDY
1. Ventilate room. Stop using odor causing products while heater is running.
2. Locate and correct all leaks(see Checking Gas Connections, Page 10).
3. Refill supply tank.
1. Open window and/or door for ventilation.
2. Contact local propane/LP gas company.
3. Clean ODS/pilot (see Cleaning Page 13).
1. Locate and correct all leaks (see Checking Gas Connections, Page 10).
2. Contact Dealer or PRO-COM
1. Take apart gas tubing and remove foreign matter.
2. Locate and correct all leaks (see Checking Gas Connections, Page 10).
1. Refer to Air for Combustion and Ventilation requirements Page 4.
POSSIBLE CAUSE
1. Heater is burning vapors from paint, hair spray, glues, etc. (See IMPORTANT statement above).
2. Gas leak. See Warning Statement at the top of page.
3. Low fuel supply.
1. Not enough fresh air is available.
2. Low line pressure.
3. ODS/pilot is partially clogged.
1. Gas leak. See Warning Statement at top of page.
2. Control valve is defective.
1. Foreign matter between control valve and burner.
2. Gas leak. See Warning Statement at top of page.
1. Not enough combustion/ventilation air.
OBSERVED PROBLEM
Heater produces unwanted odors.
Heater shuts off in use (ODS operates).
Gas odor exists even when con­trol knob is in OFF position.
Gas odor during combustion.
Moisture/condensation noticed on windows.
Page 17
17
SPECIFICATIONS
Btu(available) Gas Type Ignition Pressure Regulator setting Inlet Gas Pressure *(inches of water) Maximum Minimum Dimensions, Inches (HxWxD) Heater Carton Weight (pounds) Heater Shipping
ML100HBA
5,500/10,000
Propane/LP Only
Piezo
8" W.C.
14" 11"
19-1/8×14-1/8×6-3/8
22×16-3/4×8-1/8
13 16
Note: Dimensions listed are outer most points on the heater (includes control knobs and grill). * For purposes of input adjustment.
EQUIPMENT SHUTOFF VALVE
For all models. Equipment shutoff valve with 1/8" NPT tap.
TECHNICAL SERVICE
You may have further questions about installation, operation, or troubleshooting. If so, contact PRO-COM through the phone num­ber 1-877-886-5989. The information is listed on the front of manual.
SERVICE HINTS When Gas Pressure Is Too Low
l Pilot will not stay lit l Burner will have delayed ignition l Heater will not produce specified
heat
When Gas Quality Is Bad
l Pilot will not stay lit l Burner will produce flames and
soot
l Heater will backfire when lit l Propane/LP gas supply may be
low You may feel your gas pressure is too low or the gas quality is poor. If so, contact your local propane/LP gas supplier.
REPLACEMENT PARTS
Note: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.
PARTS UNDER WARRANTY
Contact authorized dealer from whom you purchased this product. If they are unable to supply original replacement part(s), call the num­ber on the front of this manual. When contacting your dealer or PRO-COM, have ready:
l your name l your address l model and serial numbers of
your heater
l how heater was malfunctioning l type of gas used (propane/LP or
natural gas)
l purchase date l warranty card
Usually, we will ask you to return the defective part to the factory.
PARTS NOT UNDER WARRANTY
Contact authorized dealers of this product. If they cant supply original replacement part(s), contact PRO­COM through the phone number 1­877-886-5989.
ML100TBA
10,000
Propane/LP Only
Piezo
8" W.C.
14" 11"
19-1/8×14-1/8×6-3/8
22×16-3/4×8-1/8
14 17
FLOOR MOUNTING STAND
Models ML060HBA,ML100HBA, ML100TBA
For locating heater on the floor away from a wall. Complete installation instructions provided with floor mounting stand.
ACCESSORIES
Purchase these heater accesso­ries from your local dealer. If they can not supply these accessories, contact PRO-COM for information. You can also write to the ad­dress listed on the front of this manual.
ML060HBA
6,000
Propane/LP Only
Piezo
8" W.C.
14" 11"
19-1/8×14-1/8×6-3/8
22×16-3/4×8-1/8
12 15
Page 18
18
ILLUSTRATED
PARTS BREAKDOWN
ML060HBA
Page 19
19
PARTS LIST
ML060HBA
This list contains replaceable parts for your heater. When ordering replacement parts, follow the instructions listed under Replacement Parts on page17 of this manual.
KEY NO.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
23-1 23-2
24 25 26 27 28 29
PART NO.
MB10008 MB09003 MB11005 ML086-03 ML087-03 ML088-03 ML069-02 NV2020-12 ML073-01 ML029-01 MB16002 NRV81FI-8 ML079-01 ML119-01 MB40033 MB40045 MB40043
NBB06-000M1
ML101-02 ML091-11 ML103-02 ML129-02 ND1103x600x9 ND0803-6 ND0807 ML105-01 6170-5Z MB29003 ML084-03 ML060-02 ML083-03
MB28001 ML070-12 ML071-01
DESCRIPTION
Cabinet Assembly Lower Front Panel Assembly Reflector Unit Glass Upper Glass Retainer Lower Glass Retainer Self Tapping Screw Control Valve Ignitor Line Control Valve Fixed Nut Control Knob Assembly Pressure Regulator Self Locking Screw Pressure Tap Main Inlet Tube Assembly ODS Line Assembly Gas Outlet Tube Assembly Burner Burner Connector Injector Left Burner Support Bracket Regulator Mounting Bracket ODS/Pilot Assembly Thermocouple Ignitor Electrode ODS Deflector Nut Grill Guard Middle Panel Mounting Bracket Ignitor Assembly
Assembly Hardware CSA/AGA Label Gas Instruction Decal
QTY.
1 1 1 1 1 1
12
1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1
1 1 1
Page 20
20
ILLUSTRATED
PARTS BREAKDOWN
ML100HBA
Page 21
21
PARTS LIST
ML100HBA
This list contains replaceable parts for your heater. When ordering replace­ment parts, follow the instructions listed under Replacement Parts on page17 of this manual.
KEY NO.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22
22-1 22-2
23 24 25 26 27 28
PART NO.
MB10008 MB09003 MB11005 ML086-03 ML087-03 ML088-03 ML069-02 NV2020-1209 ML073-01 ML029-01 MB16002 NRV81FI-8 ML079-01 MB40034 MB40056 MB40054
NBB10-000M1
ML101-01 ML091-10 ML103-02 ML129-02 ND1308x600x9 ND0803-6 ND0807 ML105-03 6170-5Z MB29003 ML084-03 ML060-02 ML083-03
MB28001 ML070-14 ML071-02
DESCRIPTION
Cabinet Assembly Lower Front Panel Assembly Reflector Unit Glass Upper Glass Retainer Lower Glass Retainer Self Tapping Screw Control Valve Ignitor Line Control Valve Fixed Nut Control Knob Assembly Pressure Regulator Self Locking Screw Main Inlet Tube Assembly ODS Line Assembly Gas Outlet Tube Assembly Burner Burner Connector Injector Left Burner Support Bracket Regulator Mounting Bracket ODS/pilot Assembly Thermocouple Ignitor Electrode ODS Deflector Nut Grill Guard Middle Panel Mounting Bracket Ignitor Assembly
Assembly Hardware CSA/AGA Label Gas Instruction Decal
QTY.
1 1 1 1 1 1
12
1 2 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1
1 1 1
Page 22
22
ILLUSTRATED
PARTS BREAKDOWN
ML100TBA
Page 23
23
PARTS LIST
ML100TBA
This list contains replaceable parts for your heater. When ordering replace­ment parts, follow the instructions listed under Replacement Parts on page17 of this manual.
KEY NO.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
26 26-1 26-2
27
28
PART NO.
MB10007 MB09003 MB11005 ML086-03 ML087-03 ML088-03 ML069-02 SIT544-090 ML111-02 6170-5Z 845-4.8x60Z MB29003 ML079-01 ML084-03 NRV81FI-8 ML073-01 ML060-02 MB40048 MB40049 MB40050 NBB10-000M1 ML101-01 ML091-10 ML103-02 ML129-02 ND1308x800x9 ND0803-8 ND0807 ML105-03 ML083-03
MB28001 ML160-20 ML071-02 ML065-01
DESCRIPTION
Cabinet Assembly Lower Front Panel Assembly Reflector Unit Glass Upper Glass Retainer Lower Glass Retainer Self Tapping Screw SIT Thermostat Valve Assembly Thermostat Valve Base/Bracket Nut Screws Grill Self Locking Screw Middle Panel Pressure Regulator Ignitor Line Mounting Bracket Main Inlet Tube Assembly ODS Line Assembly Burner Inlet Tube Assembly Burner Burner Connector Injector Left Burner Support Bracket Regulator Mounting Bracket ODS/Pilot Assembly Thermocouple Ignitor Electrode ODS Upper Deflector Ignitor Assembly
Assembly Hardware CSA/AGA Label Gas Instruction Decal Thermostat Sensing Bulb Clip
QTY
1 1 1 1 1 1
12
1 1 2 2 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1
Loading...