Procom ECON-F Installation Manual

Page 1
OPERATING INSTRUCTIONS
ECON-F(GC)/F(4C)
Page 2
Operating Instructions
Page - 1
INDEX
1. Introduction
3. Digital Output
4. Digital Input
5. Indication
6. Front Panel Switch
7. Setting Procedure
8. Technical Specification
9. Analog Channel Data
10. Wiring Diagram
11. Dimensional Drawing
Page 3
1.0 Introduction
lECON- F(GC)/F(4C) is an Engine Control / Protection Unit for engines
used for NON DG applications.
lThe controller can measure signals from either MPU or charging
alternator to calculate RPM.
lECON provide choice of Varity of sensor selection from predefined
selection chart
lIn critical operation it is possible to disable or debar tripping of engine via
an external digital input.
l128x64 pixel graphical display enhance convenience in configuration of
controller.
2.0 Protection, Supervision Salient Features Protection
Low Lube Oil Pressure(LLOP)l High Water Temp. (HWT)l Fuel Level l [In ECON-F(4C)only] Emergency off l Oil Temperature .l Charging Alternator Fail/V-Belt failurel
Display and Measurement
Battery Voltagel Engine Run Hourl RPMl Oil Pressure in KG/cm2l Water Temp in degree centigradel Oil Temp in degree centigradel Fuel Level in % l [In ECON-F(4C)only] Service Hourl
3.0 Digital Output
Seven digital output (Six negative and one positive) are available, four output contacts programmable . Start/Crank (Battery Negative)l Charging Alternator (Battery positive)l Solenoid (Battery Negative)l Annunciation 1 (Battery Negative)l Annunciation 2 (Battery Negative)l Annunciation 3 (Battery Negative)l Annunciation 4 (Battery Negative)l Hooter (Battery Negative)l
Page - 2
Operating Instructions
Page 4
Page - 3
4.0 Digital Input
ECON can measure / detect three Analog, seven digital and one pulse input. These inputs are as mentioned below.
1. Fuel Sensor : Resistive sensor can be connected to fuel sensor
terminal(1). Pre Programmed sensor value (Listed in TABLE 5.1) can be assigned to fuel input [In ECON-F(4C)only]
2. LLOP Sensor : Resistive sensor can be connected to LUBE OI PRESSURE terminal(2). Pre Programmed sensor value (Listed in
TABLE 5.1) can be assigned to LOP input
3. HWT Sensor : Resistive sensor can be connected to Water
Temperature terminal(3). Pre Programmed sensor value (Listed in TABLE 5.1) can be assigned to WT input
4. Oil Temp sensor : resistive sensor can be connected to Oil Temp
sensor terminal (4). Pre Programmed sensor value (Listed in TABLE
5.1) can be assigned to Oil Temp input
5. LLOP Switch : Oil pressure switch can be connected to LOP switch
terminal (8) . The input is activated on connection of DC negative at terminal no. 8. on activation stop command is issued to the engine and the fault is indicated on front LED.
6. HWT Switch : Water Temperature switch can be connected to HWT
switch terminal (9) . The input is activated on connection of DC negative at terminal no. 9. on activation stop command is issued to the engine and the fault is indicated on front LED
7. Oil Temp Switch : Oil Temp level switch can be connected to Oil Temp
level switch terminal (10) . The input is activated on connection of DC negative at terminal no. 10. on activation stop command is issued to the engine and the fault is indicated on front LED
8. Emergency Off : The input is activated on connection of DC negative
at
terminal no. 11. on activation stop command is issued to the engine and
the fault is indicated on front LED
9. Protection Debar : The input is activated on connection of DC negative
at terminal no. 12. on activation ECON disable trip function on all the faults.
10. Remote Start : ECON issues start command to engine on receipt of
DC negative at remote start terminal
11. Remote Stop : ECON issues stop command to engine on receipt of DC
negative at remote stop terminal
5.0 Indication
Listed below are the two LED indication available on front of ECON-F/P Warning : Blinks in case of sensor open or on low fuel warning
Operating Instructions
Page 5
Page - 4
6.0 Front Panel Switch
ECON – F/4C has four switch provided on its front panel. Switch can h more than one functions assigned to them. The table below describes the operation of these
7.0 Setting Procedure / Menu
ECON is user/site configurable. User can view all parameters, fault history, events no. of start/stop and can also edit, system parameter (password protected), engine / generator parameter, annunciation setting,RS485 parameter clock and password. Following is the sequential procedure to edit. view all the menu and submenus Press “R” & “Enter“ switch simultaneously. The LCD shall display, “System Parameter”
1. System Parameter
lSystem parameter are password protected. lTo enter “system parameter” press “Enter”. lECON will request for password, LCD will display “ Enter Password” lSystem parameter can be edited by entering correct password or else
can be viewed by entering “0” as password.
2. Engine / Generator Parameter
lTo go to next menu after system parameter, press “Increment”. lThe LCD shall display “Generator Parameter”. lGenerator parameter can modified / viewed by pressing “Enter”.
(for setting details pls refer table 5.1)
Switch
Symbol
Switch
Function
Description
Increment
/Start
Programming Mode: It is used to increment the value of the parameters under
programming. & it is used to issue the crank/ start command to DG
Decrement
/Stop
Programming mode: It is used to decrement the value of the parameter under programming &. It is used to issue the stop command to DG
Next
Normal operation mode: In this mode, it is
used to change the parameters being displayed on LCD.
Programming Mode: Next key is used to
select the next parameter to be programmed.
Reset
Either to reset the fault / Or press enter and
reset together to select programming mode.
Operating Instructions
Page 6
3. Annunciation Setting
l To go to next menu after generator parameter, press “Increment”. l The LCD shall display “annunciation setting”. l Annunciation settings can modified / viewed by pressing “Enter”.
(for setting details pls refer table 5.1) 4 RS-485 Parameter In ECON F (4C) only
l To go to next menu after Annunciation Setting, press “Increment”. l The LCD shall display “ ”.RS-485 parameter l can modified / viewed by pressing “Enter”.RS-485 parameter
(for setting details pls refer table 5.1)
5. Display History
l To go to next menu after annunciation press “Increment”. l The LCD shall display “Display History”. l Trip record / history can be viewed by pressing “Enter”. l ECON keep a record of last 32 tripping with date and time stamp. l Tripping records are updated on first in first out basis
6. Display Event
l To go to next menu after history press “Increment”. l The LCD shall display “Display Event”. l Display Event can be viewed by pressing “Enter”. l ECON keep a record of last 32 event with date and time stamp. l Event record is updated on first in first out basis.
7. Display Start Stop
l To go to next menu after event press “Increment”. l The LCD shall display “Display Start / Stop”. l Start Stop can viewed by pressing “Enter”. l ECON keep a record of last 100 start and stop event with date and time
stamp.
l Start/ stop record is updated on first in first out basis.
8. Reset Service Alarm
l To go to next menu after Start-Stop press “Increment”. l The LCD shall display “Reset Service Alarm”. l Service due hour can be reset by pressing start button after entering in
to this menu.
9. Adjust Clock
l To go to next menu after Service Alarm press “Increment”. l The LCD shall display “Adjust Clock”. l Time can be modified / viewed by pressing “Enter”.
Page - 5
Operating Instructions
Page 7
Page - 6
10. Reset Password
l To go to next menu after annunciation press “Increment”. l The LCD shall display “Reset Password”. l Password can be modified by pressing “Enter” l ECON will request for the present password, after feeding correct
password change password will be requested and the password will be replaced by new password on pressing start button..
Parameter Mode
Parameter
Options/Limits
Description
Default Setting
A. System Parameter System parameters are the parameters which are programmed once during initial installation and does not require frequent changes. As these are critical parameter and hence are password protected. It is possible to view system parameter without knowing the password but editing is possible only after entering correct password
All system parameters are listed below along with their default value and minimum / maximum variation range. Values can be increased or decreased by pressing up/start and down/stop button respectively . Next parameter can be selected by pressing next button
Solenoid Type
1: Pull to Start 2: Pull to Stop
Pull To Start
In this mode fuel solenoid contact changes from Open to Close at the time of cranking and remains close till the genset is running. For stopping the generator this contact opens.
Pull To Stop
In this mode fuel solenoid contact remains open at the time of cranking and till the genset is running. For stopping the generator this contact closes for a user programmed time.
Pull to Stop
Operating Instructions
Page 8
LLOP
Sensor
1: Type A 2: Type B 3: M&M 4: MNEPL 5: VE 6: TMTL 7: HUAFANG 8: TATA 9: GC(VDO) 10:
GC(Murphy 11: MVD 12: Disabled
Select the installed sensors. If no sensor is installed select “Disabled”
Type A
Oil Temp Sensor
1: Type A 2: Type B 3: M&M 4: MNEPL 5: VE 6: TMTL 7: HUAFANG 8: TATA 9: GC(VDO) 10:GC(Murph y
Select the installed sensors. If no sensor is installed select “Disabled”
Type A
Fuel
Sensor
1: Type A, 2: Sam-0, 3: Sam-1, 4: Disabled*
Select the installed sensors. If no sensor is installed select “Disabled”
Type A
HWT Sensor
1: Type A 2: Type B 3: M&M 4: MNEPL 5: VE 6: TMTL 7: HUAFANG 8: TATA 9: GC(VDO) 10:GC(Murph y
Select the installed sensors. If no sensor is installed select “Disabled”
Type A
Page - 7
Operating Instructions
Page 9
Sensor Open
1: Warning 2:Fault 3: Disabled
The action to be taken if the sensor is found to be open.
Warning
Pulses/Re volution
1-300
No of pulses, from Magnetic Pickup unit or W point of charging alternator, in one revolution of the engine. This shall be used to calculate the
RPM.
132
Page - 8
Operating Instructions
Start Stop Config
1: Separate keys 2: Only Start key
This parameter decides as to how the remote start and stop shall be done. Option 1: Separate keys is selected than a single pulse on remote start shall the engine and another pulse on remote stop shall stop the engine. The duration of these pulses shall be more than 200msec. Option 2: In this option the engine shall be stated and kept working till Remote start is pulled low. As soon as the pin is released the engine shall stop. To attempt a new start cycle, after the engine fails to start, the remote start pin must be released for some time and again pulled low. * Option 2 should not be selected if the start and stop functions are to be executed from front keys.
Separate keys
B. Engine/Generator Parameter
All the Engine programmable parameters are listed below along with their default value and minimum / maximum variation range. Values can be increased or decreased by pressing up/start and down/stop button respectively . Next parameter can be selected by pressing next button.
Page 10
Maximum
RPM
600-4000
Maximum allowed RPM of Engine. Engine running at speed above this is treated as over speeding and a fault is registered and engine stopped.
1600
Minimum
RPM
600-4000
Minimum allowed RPM of Engine.running at speed below this is treated as over speeding and a fault is registered and engine Stopped.
1400
RPM Delay
1-999 Sec
Duration for which engine is allowed to operated outside the set RPM limits. If it continues to operate beyond the limits for more than the set time a fault condition is registered and engine stopped.
5
Pick Up
RPM
80-1000
The engine stalling RPM. This parameter defines the RPM above which the engine will not stall and hence can be treated as running. This is used to detect the engine running condition after crank.
1000
Service Due Hour
10-999Hrs
Service due warning is generated after the engine has logged these many hours.
250
Oil temp Trip Level
40-250oC
The maximum OIL temperature up to which the engine is allowed to operate.
o
95 C
Oil temp trip delay
1-999Sec
Monitoring time for the Oil temp level to avoid false tripping of the engine.
10
U
U
U
Page - 9
Operating Instructions
Page 11
Fuel Warn
Level #
25 %
Monitoring value of fuel level below which fuel level warning is generated.
Disable*
11-80 %
Fuel Warn
Delay #
10 Sec
Monitoring time of fuel level after which fuel level warning is generated.
1-999Sec
Fuel Trip
Level #
15 %
Monitoring value of fuel level below which fuel level trip is generated.
10-80 %
Fuel Trip
Delay #
10 Sec
Monitoring time of fuel level after which fuel level trip is generated.
1-999 Sec
LLOP Trip Level
0.4-
2
8.5Kg/cm
The minimum lubricant oil pressure
on which the engine is allowed to
operate. A drop of pressure below the
set limit shall trigger a fault condition
thereby stopping the engine
2
1.0Kg/cm
Page - 10
Operating Instructions
LLOP Trip Delay
1-999 Sec
Duration for which the low lubricant oil pressure can be tolerated.
5
HWT trip level
o
40-250 C
The maximum coolant temperature up to which the engine is allowed to operate.
o
95 C
Page 12
Page - 11
HWT Trip delay
1-999 Sec
The duration for which the engine is allowed to operate at temperature higher than the above set maximum temperature
5
ChgAlt­Vbelt
1-999Sec Disabled
While the engine is running and the Charging alternator pin is not pulled low for this duration it is assumed that either the charging alternator or V-Belt has failed thereby generating a fault ondition and stopping the engine.
Disabled Crank On
Time
1-10 Sec
The maximum duration for which the engine can be cranked continuously. In case engine fails to start another attempt to start shall be attempted after some time.
5
Hooter On Time
1-999 Sec
Duration for which the hooter shall be . This setting is only available if the hooter is assigned to an DO.
15
Solenoid On Time
1-60 Sec
The duration for which the Pull solenoid can be continuously energized while trying to stop the engine.
22
Operating Instructions
Auto Scroll
1: Enabled 2: Disabled
Can be used to stop/start the automatic scrolling of the display parameters.
Enabled
C. Annunciation Setting It is possible to freely assign digital outputs to different fault. There are four (ANN1 , ANN2, ANN3 and ANN4) field programmable output. It is also possible to assign same digital output to more than one fault( e.g.
ANN1 can be assigned to fuel fault and HWT fault both, in this case ANN1 will activate on both the faults.
Page 13
Ann oil temp fault
1: No Annunciation 2:On DO Ann1 3:On DO Ann2 4:On DO Ann3 5:On DO Ann4
If desired, the oil temp fault can be announced at one of the annunciation Digital Output.
No Annun­ciation
Ann Fuel Fault
1: No Annunciation 2:On DO Ann1 3:On DO Ann2 4:On DO Ann3 5:On DO Ann4
If desired, the Low Fuel fault can be announced at one of the annunciation Digital Output.
No Annun­ciation
Ann
HWT Fault
1: No Annunciation 2:On DO Ann1 3:On DO Ann2 4:On DO Ann3 5:On DO Ann4
If desired, the High water temperature fault can be announced at one of the annunciation Digital Output.
No Annun­ciation
Ann
LLOP Fault
1: No Annunciation 2:On DO Ann1 3:On DO Ann2 4:On DO Ann3 5:On DO Ann4
If desired, the LLOP fault can be announced at one of the annunciation Digital Output.
No Annun­ciation
Ann
RPM Fault
1: No Annunciation 2:On DO Ann1 3:On DO Ann2 4:On DO Ann3 5:On DO Ann4
If desired, the Over/Under speed fault can be announced at one of the annunciation Digital Output.
No Annun­ciation
Announce Unit
OK
1: No Annunciation 2:On DO Ann1 3:On DO Ann2 4:On DO Ann3 5:On DO Ann4
If desired, the healthiness of the controller can be announced at one of the annunciation Digital Output
No Annun­ciation
D. RS-485 Parameter #
Device Id
Modbus device ID
1
1-247
Baud Rate
RS 485 Communication Baudrate
9600
1200
2400
4800
9600
19200
Page - 12
Operating Instructions
Page 14
Parity
RS 485 Communication Parity Bits
None
Even
Odd
None
Stop Bit
RS 485 Communication Stop Bits
1
1
2
E Reset Service Alarm
Press INC to Reset Press DEC to esc
F Adjust Clock
Automatic real time based DG Start & Stop (Manual Controller Configuration) RTC Time and Date can be easily entered
00.00
00.00
DD/MM/YY
YY
G Reset Password
Three digit password protection for system settings Password can be change easily.
8.0 Technical Specification
AC voltage withstand 330 VAC, Continuously, (Phase to
neutral) Frequency Range 40-70 Hz Measurement Accuracy Voltage & Current ± 2% Frequency ± 0. 05 Hz. Surge 1.2/50Usec 2.5KV Auxiliary Voltage 8-35V/DC OR 50-300 V AC/DC Contact Rating 230 VAC, 5A Humidity 95 %
Page - 13
Operating Instructions
9.0 Analog Channel Data
Page 15
Continues on Next Page
Temp.
Resistance in ohms
In °C
Type A
Type B
M&M
MNEPL
VE
Huafang
TATA
GC
(VDO)
GC
(Murphy)
TMTL
Water
0
3282
1525
3282
3282
2363
2900
3192.6
3417
10613
3512
5
2765
1319
2765
2765
1873
2199
2461.1
2609
7764
2707
10
2247
1112
2247
2247
1383
1684
1914.6
2011
5743
2106
15
1730
906
1730
1730
1111
1301
1502.7
1564
4292
1653
20
1212
700
1212
1212
839
1015
1189.2
1227
3240
1308
25
1036
570
1036
1036
683
798
948.4
970
2469
1043
30
860
440
860
860
527
632
762.1
773
1898
838
35
684
365
684
684
434
505
616.7
621
1472
678
40
508
287
508
508
340
406
502.5
520
1050
552
45
426
260
426
426
283
327
412
438
885
453
50
343
232
343
343
226
247
340
356
720
374
55
291
205
291
291
190
214
282.1
288
560
310
60
238
178
238
238
154
187
235.5
220
410
259
65
203
151
203
203
131
154
197.6
183
360
217
70
167
123
167
167
107
120
166.6
145
300
183
75
144
96
144
144
92
101
141.2
128
240
155
80
120
69
120
1207685
120.2
110
193
132
85
104
62
104
1046674
102.8
95
160
113
90885488885562
88.380145
97
95774677774855
76.271120
83
1006638666641476661
100
72
105583558583641
57.45290
63
110503150503036
43.84580
55
115452745452731
38.54070
48
120392339392327
33.93455
42
12534193434212430304537
130301530301821
26.62738
33
135271127271618
23.72333
29
14025025251415
21.12129
26
14523023231212
18.91825
23
150210212110101622
20
Operating Instructions
Page - 14
Page 16
S.No
.
Temperature in °C
Resistance in ohms
TMTL AIR3C
TMTL AIR1C
1
80
300
300285
279.3
273.1
3
90
258.5
246.2
4
95
237.8
223.8
5
100
217
208.5
6
105
201.3
193.1
7
110
185.5
177.7
8
115
169.8
162.3
9
120
154
146.9
10
125
138.3
131.5
11
130
122.5
116.2
12
135
106.8
100.8
13
140
91
85.4
14
145
76.3
7015150
61.5
57.3
16
155
46.8
44.7
17
160323218165
30.3
30.3
19
170
28.5
28.7
20
175
26.8
27
21
180
25
23.6
22
185
22.3
20.2
23
190
19.5
16.8
24
195
16.8
13.4
25
2001410
26
205
13
27
210
1228215
1129220
10
Operating Instructions
Page - 15
Page 17
Operating Instructions
Page - 16
S.No.
Fuel in %
Resistance in ohms
Type A
Sam_0
Sam_1
Electronics
Linear
1001410
10
1025518
18.5
19.5
18.5
310102227
29
27
41717
29.5
35.5.
38.5
35.5
520343744
48
44625
51
55.5
52.5
57.5
52.5
730687461
67
618358592
69.5
76.5
69.5
940102
110
78
86
781045
110.5
124.5
86.5
95.5
86.5
1150119
139
95
105
95
1255127.5
149
103.5
114.5
103.5
1360136
159
112
124
1121465
144.5
165
120.5
133.5
120.5
1570153
171
129
143
1291675
157.7
172.5
137.5
152.5
137.5
1780162.3
174
146
162
1461885
167
176
154.5
171.5
149.5
1990171.7
178
163
181
1532095
176.3
181
171.5
190.5
166.5
21
100
180
184
180
200
180
Page 18
9.3 Low Lube Oil Pressure Sensors Data
Operating Instructions
Page - 17
Pressure
Resistance In Ohms
2
In Kg/cm
Type A
Type B
M&M
MNEPL
Volvo
TMTL
Huafang
TATA
GC
(VDO)
GC
(Murphy)
0
101010101510101010
240
0.5
16.5
20
16.5
20.5
19.52120
20.520214
1
23.5
30
23.5312432303130
189
1.5
30.2
40
30.2
41.5
28.54340
41.541166
2
375037523354505252
147
2.5
49.5
58.7
49.5
70
40.5
62.7
58.7
6161129
3
62
67.56288
48
71.5
67.5
7070115
3.5
74.5
76.2
74.5
106
54.5
80.2
76.2
7979102
4
878587
124
6189858888
91
4.5
96
93.596142
63.5
97.7
93.5
979781
5
105
102
105
160
66
106.5
102
106
106
71
5.5
114
110.5
114
178
72.5
115.2
110.5
115
115616
123
119
123
196
79
124
119
124
124
51
6.5
133.5
127.2
133.5
214
82
132.7
127.2
132
132417
143
135.5
143
232
85
141.5
135.5
140
139
31
7.5
152.5
143.7
152.5
250
87.5
150.2
143.7
148
146248
162
152
162
268
90
159
152
156
152
20
8.5
171.5
159
171.5
286
95
167.7
159
164
159
16
Page 19
Page - 18
10.0 Wiring Diagram
Operating Instructions
Page 20
11.0 Dimensional Detail
Loading...