Procom ECON-A-4C, ECON-A-A, ECON-A-S, ECON-A-M Operating Instructions Manual

OPERATING INSTRUCTIONS
ECON-A-4C/A/S/M
INDEX
1.0 Introduction
2.0 Salient features, Protection & Supervision
3.0 Display/ Front Panel
5.0 LED Annunciations Description
6.0 Lamp Test
7.0 Digital Input
8.0 Analog Input
9.0 Digital Output
10.0 Modes of Operation
10.1 AMF Mode (ECON-A & ECON -A-4C)
10.1.1 Auto Mode
10.1.2 Semi Auto Mode
10.1.3 Manual Mode
10.2 Auto Stop Mode ( ECON-A & ECON - A-4C or ECON-S)
10.3 Manual Controller ( All models)
11.0 Setting Procedure
12.0 Parameter Mode
12.1 System Parameter
12.2 Generator Parameter
12.3 AMF Parameter
12.4 Protection Parameter
12.5 RS 485 parameters
12.6 Reset Service Alarm
12.7 Adjust Clock
12.8 Reset Password
13.0 Model Selection Chart
14.0 Load Management
15.0 Event Recording
16.0 Faults
16.1 Internal Faults
16.2 External Faults
16.3 Fault Reset
17.0 Communication
18.0 MODBUS Specifications.
19.0 Terminal description
20.0 Specifications
21.0 Dimension
Operating Instructions
Page - 1
1.0 Introduction Microprocessor based controller for DG Set which can be configured as both
automatic or manual controller.
ECON comes in various models to cater for varieties of requirements:
ECON-A-4C
ECON-A
ECON-S
ECON-M
• ECON-A-4C: It is a AMF controller with 4 channel of analog measurement and can be site configured as ECON-A or ECON-S or ECON-M.
• ECON-A: It is a AMF controller with 3 Analog channels and is site configurable to ECON-S or ECON-M
• ECON-S: It is a manual controller with Shunt trip contact for MCCB. This is to
avoid shutting down the engine on load in manual operation. After the shunt trip is initiated the generator stops after re-cooling time. ECON-M is sub set of this model
• ECON-M: This is a pure manual controller for manual operation only.
All these models can be ordered with optional features such as RS485
communication,3 Extra digital inputs of Canopy fan current protection. This manual has to be read along with the controller selected and all the features may not be available in all the models.
• Display: 128*64 pixel graphial backlit LCD for ease of readout and symbolic
representation.
• Cyclic Timer based Engine Operation. Maximum engine on time as well as
rest time are programmable
• Fan Current monitoring for canopy fan (Optional)
• Menu driven MM1 for easy in field configuration without PC or any
customized equipment.
• Load Management . Load Dependent start/stop of 2nd DG in case of two DG
application.
• Periodic Automatic Start of engine if not used for a predefined time to charge
the battery as well as maintenance.
• ECON reminds user for timely service by indicating service due alarm.
• True RMS measurement of all measured parameters with 1% accuracy of
measured value.
• Plug in connectors for error free replacement.
• Programmable DG on delay, DG continuous on time, DG Rest Time, warm-up
time along with 33 other times.
• Automatic real time based DG Start and Stop(Manual Control Configuration.).
• Dimensions 167 х 129 х 41.8 mm.
Operating Instructions
Page - 2
2.0 Salient Features, Protection and Supervision
• Mains Measurements
◦ 1 Phase/ 3 Phase Voltage ◦ 1 Phase/ 3 Phase Current ◦ Frequency ◦ PF, KW, KVA,
• Generator Measurements
◦ 1 Phase / 3 Phase Voltage ◦ 1 Phase / 3 Phase Current ◦ Frequency ◦ PF, KW, KVA, KWH . ◦ Battery Voltage ◦ Water Temperature ◦ Oil Pressure ◦ Fuel Level ◦ RPM ◦ Run Hour ◦ Service Due Hour
• Protection / Supervision Mains
◦ Under/Over Voltage ◦ Under/Over Frequency ◦ Phase Sequence ◦ Voltage Unbalance ◦ Overload
• Protection / Supervision DG
◦ Under/Over Voltage ◦ Under/Over Frequency ◦ Current Unbalance ◦ Over Speed ◦ RWL ◦ LLOP ◦ HWT ◦ LFL ◦ Charging Alternator/V-belt ◦ Emergency off ◦ Service Due ◦ Fail To Start ◦ Fail To Stop
Digital Input : 10 digital [3 fixed, 4 programmable, 3 programmable (optional)]
Output: 9 digital
Operating Instructions
Page - 3
AMF Operation: 9 outputs (five fixed and three programmable) and one for
charging Alternator
Fault Data Recording: Last 64 fault with date and time stamping
Event Recording: Last 64 event with date and time stamping
Start Stop Recording: Last 100 records with date and time stamping
Password Protection: Three digit password protection for system settings.
• Real Time Clock (RTC)
Communication: RS232, USB, Fully Isolated RS485(Optional)
• Provision for switching ON or OFF the measurement for individual sensors.
• Option of warning or tripping when open sensor is detected
• Programmable crank cut off method based on either voltage built up, or oil
pressure build up & voltage built up
3.0 Display / Front Panel
128x64 pixels Graphical LCD Display for ease of readout. Parameters are
displayed in English along with symbolic representation. Normally the display auto scrolls and displays a parameter for 10 seconds, but any time the Next key ( ) can be pressed to select the next parameter window.
4.0 Switches Description
ECON has 7 switches provided on its front panel. The table below describes
the operation of these.
Start
Switch
MCB
Switch
Reset
Switch
Mode
Indication
LEDs
Next
Switch
GCB
Switch
Stop
Switch
Mode
selection
switch
Mains & DG
Contactor
Indicator
Operating Instructions
Page - 4
Switch
Symbol
Switch
Function
Description
Next
Normal operation mode: In this mode, it is
used to change the parameters being displayed on LCD.
Programming Mode: Next key is used to
select the next parameter to be programmed.
Increment
/Start
This key has dual function Programming Mode: It is used to increment the value of the parameters under
programming.
Manual mode: it is used to issue the crank/
start command to DG
Decrement
/Stop
This key has dual function Programming mode: It is used to decrement
the value of the parameter under programming.
Manual mode: It is used to issue the stop
command to DG
Reset
Reset key resets the Hooter and Fault signals. The first press shall reset the hooter and next
shall reset the faults. A long press of 1 Sec shall reset both.
Programming
/History
Fault Mode
Entry
If both the keys are pressed simultaneously
the unit will enter in Programming Mode History Fault/Service Hours
MCB
In Manual Mode this toggles the mains
contactor, On/Off
GCB
In Manual Mode this toggles the generator
contactor, On/Off
MODE
Toggle between Auto, Manual & Test Mode
5.0 LED Annunciations Description: ECON has nine annunciations on its front panel. These either announce the faults or indicate status of the system.
Nomenclature
Symbol
Description
Auto
Led lights up when ECON is in Auto mode
Manual Mode
Led lights up when ECON is in manual mode
Operating Instructions
Page - 5
Nomenclature
Symbol
Description
Semi Auto
Led lights up when ECON is in Semi Auto
Mains Voltage
This symbol lights up continuously if Main is
healthy else starts blinking.
MCB
LED turns on in case the mains breaker is
switched on or else turned off
GCB
LED turns on in case the DG breaker is switched
on or else turned off
DG Voltage
This indication glows continuously when the
generator is running.
Warning
This LED blinks in case of a warning.
Fault
This LED blinks in case of a fault
6.0 Lamp Test: If the ECON is switched on while the reset switch is pressed, all the LEDs
start blinking till reset switch is kept pressed.. This state shall persist till the switch is kept pressed and on release of the switch ECON shall start functioning normally
7.0 Digital Input: ECON has 10 digital input as below
Fixed Inputs ◦ Remote Start, ◦ Remote Stop / Semi Auto ◦ Emergency
Programmable 4 inputs each can be programmed as one of the
following inputs.
◦ RWL Switch ◦ LLOP Switch ◦ Fuel Switch ◦ HWT Switch ◦ Oil Level Switch ◦ Canopy Temperature Switch ◦ Oil Temperature Switch
Optional programmable 3 inputs each can be programmed as one of the
following inputs.
◦ Earth Fault ◦ Oil Level Switch ◦ Canopy Temperature Switch ◦ Oil Temperature Switch
Operating Instructions
Page - 6
Operating Instructions
Page - 7
• 8.0 Analog Input: ECON has 4 Analog Input
◦ Low Lube Oil Pressure Sensor ◦ High Water Temperature Sensor ◦ Low Fuel Level Sensor ◦ OIL Temperature (ECON-A-4C only )
• 9.0 Digital Output: ECON has 9 digital outputs :
Programmable output
Three digital outputs can independently be configured for the any functions
from the list below. ◦ Unit Healthy ◦ Load Warning ◦ Fuel Pump ◦ Heater/Choke ◦ Pull Solenoid ◦ None
• Fixed output: The remaining 6 digital outputs are fixed: ◦ Charging Alt( Battery Voltage) ◦ Crank ◦ Solenoid ◦ Hooter ◦ Mains Contactor ◦ Generator Contactor
• 10.0 Modes of Operation
10.1 AMF Mode (ECON-A & ECON -A-4C)
• 10.1.1 Auto Mode
ECON monitors the Mains supply, if Mains supply varies beyond set limit of
under/over voltage or under/over frequency or voltage unbalance for more
than their individual programmed supervision time, ECON releases the MCB
contactor (to protect the contactor from failure because of low input voltage)
and attempts to starts the generator after the following conditions are meet:
1. If engine start delay is enabled than the engine will wait for the programmed
delay before cranking the engine
2. In case the mains voltage returns to normal before cranking the engine the
engine shall not be cranked. Heater/Fuel Pump contact are switched on depending upon their settings.
Heater/choke/glow plug is first switched followed by fuel pump. Next ECON
cranks the engine. Crank command is withdrawn once the engine start which
is detected, either by LLOP pressure or by build-up of generator voltage, as
per the setting by the user. Max duration of crank command is user settable. In case of non-start of the engine ECON re-cranks it till it starts or user
programmed crank attempts are exhausted. If generator fails to start after the
maximum programmed crank attempts, Fail to Start LED starts blinking,
indicating start failure and the hooter is switched on. After successful start of the generator, it is allowed to warm up for a user
programmed time before the load is transferred to generator. While the generator is running ECON monitors it for external fault (Digital
Inputs: Emergency, V-Belt, RWL,, LLOP Switch etc) and internal faults
(Measured Values faults: LLOP, HWT, Fuel, Over Load, voltage and frequency).
On persistence of any fault for more than the programmed supervision
delay,for that fault, generator is stopped, corresponding fault is announced & hooter is switched on. On restoration of healthy mains supply, continuously, for the programme duration the load is transferred to the mains and generator is stopped after expiry of re-cooling time. In case mains again become unhealthy during the re-cooling period the load is switched to generator.
After successful stopping of the generator either normally or on fault the Fuel
Pump Contact is removed. In case of fail to stop, the Fuel Pump Contact is not removed to avoid air locking.
Cyclic Operation: ECON can be programmed to automatically shut down
the engine, for a predefined duration, after a predefined duration of operation, even if the mains is unhealthy. In case the mains continue to be unhealthy this cyclic operation will continue till the mains is restored.
• 10.1.2 Semi Auto Mode
Semi Auto Mode is sub set of Auto mode. This mode can be selected by
pulling the pin 28(Semi/Auto) low and selecting auto mode from the front panel. The Auto LED will blink indicating that the unit is in Semi-Auto Mode. In this mode the unit does not automatically starts the engine after the mains has failed and mains supervision timer has expired but waits for an external start signal pin 29(Remote Start/Stop). Once the start signal is given the unit now functions like auto mode with 3 crank attempts. The unit can be stopped by pulling low Pin 29(Remote Stop). Both Remote start and remote stop are one touch and hence should not be continuously activated. These pins shall only function during semi auto mode.
• 10.1.3 Manual Mode
ECON-A, in this mode is under the manual control of the operator for starting
and stopping of the generator. Engine has to be started manually by manually pressing “Start” switch. The “Start” switch shall not operate if GCB contact is closed, to provide protection to generator. Once the generator is started the load can be switched to generator by pressing “GCB” switch or to mains by pressing MCB switch. At any given time, either of GCB or MCB can be operational. Attempt to switch on GCB while MCB is on will be ignored and vice versa. Both MCB and GCB key have dual function of either switching ON or OFF the respective contactor. A press shall toggle the state. Continuously pressing these keys shall keep toggling the status. To stop the generator, switch off the GCB contactor and press “STOP” key. Any attempt to stop the generator, while the GCB contact is engaged, shall be ignored.
While the generator is running ECON-A protects the generator by monitoring
all internal and external faults.
Operating Instructions
Page - 8
• 10.2 MCCB Shunt trip or Auto Stop Mode (ECON-A , ECON -A-4C or
ECON-S)
This mode is a mix of Manual and Auto mode. In this mode the engine is
manually started but its shut down on the restoration of the mains. To make
sure that the engine is not shut down on load and also to recool the engine
before shutting it down it has provision to activate the shunt trip coil of MMCB before shutting it down it has provision to activate the shunt trip coil of MMCB and isolate the generator from load and engine is stopped after running it for the predefined recooling time.
Engine can be started or stopped either the front keys or remotely by use of
Remote start/stop keys. ECON will monitor the engine and alternator for any fault and take corrective action
• 10.3 Manual Controller ( All models)
This mode is a pure manual operation mode. The engine has to be manually
started and stopped. The responsibility of disengaging the load from generator and allowing the engine to cool before stopping has to be performed by the operator. The engine and Alternators are protected while the engine is running.
*RTC Based operation :
In ECON-M/ECON-S and other models when used as manual controller the
RTC based start stop can be activated. If activated the engine can be made to automatically start at a given time of the day and stop at a predefined time.
11.0 Setting Procedure: How to Enter in Parameter Mode Press Next & Reset switches simultaneously. The LCD shall display, “System
Parameter”
To enter System Parameter setting mode, press Next Switch, the LCD
shall display, “Enter Password” and default password is 123 then press
Next Switch. For any change in value, press Start switch and Stop switch. For next parameter, press Next Switch.
To go to next menu press Start Switch the LCD shall display “Generator
Parameter” To enter Generator Parameter setting mode press Next Switch.
For any change in value, press Start switch and Stop switch. For next parameter, press Next Switch.
To go to next menu press Start Switch the LCD shall display “AMF
Parameter” To enter AMF Parameter setting mode press Next Switch. For any change in value, press Start switch and Stop switch. For next parameter, press Next Switch.
Operating Instructions
Page - 9
Operating Instructions
Page - 10
To go to next menu press Start Switch the LCD shall display “Protection
Parameter” To enter Protection Parameter setting mode press Next Switch.
For any change in value, press Start switch and Stop switch. For next parameter, press Next Switch.
To go to next menu press Start Switch the LCD shall display “Comm Rs485 Parameter”To enter Comm RS-485 Parameter setting mode press Next Switch. For any change in value, press Start switch and Stop switch. For next parameter, press Next Switch.
To go to next menu press Start Switch the LCD shall display “Display History” To View Display History mode press Next Switch.
To go to next menu press Start Switch the LCD shall display “Display Event” To View Display Event mode press Next Switch.
To go to next menu press Start Switch the LCD shall display “Display
Start/Stop” To View Display Start/Stop mode press Next Switch.
To go to next menu press Start Switch the LCD shall display
“Reset Service Alarm”
To enter Reset Service Alarm mode press Next Switch. The LCD shall display
“Press START to Reset
Press STOP to ESC”
The unit shall ask for confirmation to reset the service hours pressing desired
Switch.
To go to next menu press Start Key the LCD shall display “Adjust Clock” To
enter Adjust Clock setting mode press Next Key. For setting up of the time, press Start switch and Stop switch.
Press Next Key the LCD shall display DD/MM/YYYY. For setting up of the
date, press Start switch and Stop switch
To go to next menu press Start Key the LCD shall display “Reset Password” To enter Reset Password setting mode Press “Enter Password” then Press “Change Password” the LCD
shall display “
Press START to Change
Press STOP to ESC”
12.0 Parameter Mode: The following tables give the detailed descriptions. Please note that 20sec of
inactivity will take the unit back in normal mode and all the changes done shall be cancelled.
12.1 System Parameter
Parameter
Name on
LCD & Icon
Explanation of Parameter
Factory
Setting
Setting Range
Enter
Password
Systems setting are password protected. Password is a three digit number
123
0-999
System
Config
ECON provides complete flexibility in system designing; it is possible to select auto and manual operation for any combination of mains and DG phases. E.g. mains 3 phase and DG single phase or vice versa, or three phase mains and DG, or single phase mains and DG.
M:3P/G:1P
AMF M:3P/G:1P AMF M:3P/G:3P AMF M:1P/G:1P
MANUAL1P
MANUAL 3P AUTO STOP 1P AUTO STOP 3P
Solenoid
Type
Pull To Start
In this mode fuel solenoid contact changes from Open to Close at the time of cranking and remains close till the genset is running. For stopping the generator this contact opens.
Pull To Stop
In this mode fuel solenoid contact remains open at the time of cranking and till the genset is running. For stopping the generator this contact closes for a user programmed time.
Pull to
Stop
Pull to Stop Pull to Start
LLOP
Sensor
Type
Select the installed sensor for LLOP
Type A
Type A Type B, M&M, MNEPL, VE, TMTL, HUAFANG, TATA, GC(VDO), GC (MURPHY), Disabled *
A/M
Operating Instructions
Page - 11
Fuel Sensor
Select the installed sensor for Fuel
Type A
Type A, Sam-0, Sam-1, Electronics, Linear, 0-5V(0-100%), Disabled*
HWT
Sensor
Select the installed sensor for HWT
Type A
Type A, Type B,M&M,
MNEPL,VE, TMTL AIR 1C, TMTL AIR 3C, TMTL WATER HUAFANG, TATA, GC(VDO), GC(MURPHY),
Disabled *
Oil Temp.
Sensor
Select the installed sensor for Oil Temp.
Type A
Type A, Type B,M&M,
MNEPL,VE, TMTL AIR 1C, TMTL AIR 3C, TMTL WATER HUAFANG, TATA, GC(VDO), GC(MURPHY),
Disabled *
Sensor
Open
User can select the action to be taken in case of sensor open, it can be configured as a fault, or as warning or no action to be taken i.e. disable.
Disabled
Disabled * Fault Warning
CT Ratio
Current Transformer ratio
1
1-9999
Gen. RPM
Engine RPM Type
1500RPM
1500RPM 3000RPM
OPEN
CT R
Operating Instructions
Page - 12
KW
Contact ON
Pin 32,31,30
These are three programmable output which can be configured for any one function from the list
None
None Unit Healthy Load Warning Fuel Pump Heater / Choke Pull Solenoid
Over
Load KW
The Power(KW) above which the over load fault monitoring will start. The timer for it is as described in 13. This fault is only enabled while the generator is running. On expiry of the timer the generator is stopped
40
1-9999
Over
Current
The current above which the over current fault monitoring will start. The timer for it is as described in 13. This fault is only enabled while the generator is running. On expiry of the timer the generator is stopped
50
1-9999
Over Load
Delay
This is the timer for the over load condition either due to over KW or over current. On expiry of this timer the engine shall be stopped
5 Sec
1-999 Sec
Digital Input
1
This can be configured for one out the listed below Parameters. RWL Oil Level Oil Temperature Canopy Temperature
RWL
RWL Oil Level Oil Temperature Canopy Temperature
Digital Input
2
This can be configured for one out the listed below Parameters. LLOP Oil Level Oil Temperature Canopy Temperature
LLOP
LLOP Oil Level Oil Temperature Canopy Temperature
Digital Input
3
This can be configured for one out the listed below Parameters. FUEL Oil Level, Oil Temperature Canopy Temperature
FUEL
FUEL Oil Level Oil Temperature, Canopy Temperature
CT R
Operating Instructions
Page - 13
Digital Input
4
This can be configured for one out the listed below Parameters. HET Oil Level Oil Temperature Canopy Temperature
HWT
HWT Oil Level Oil Temperature, Canopy Temperature
Digital Input
5#
This can be configured for one out the listed below Parameters. Canopy door open Oil Level Oil Temperature Canopy Temperature
Oil Temp.
Oil Level Oil Temp., Canopy Temp.
Digital Input
6#
This can be configured for one out the listed below Parameters. Fire Oil Level Oil Temperature Canopy Temperature
Oil Level
Oil Level Oil Temperature Canopy Temperature
Digital Input
7#
This can be configured for one out the listed below Parameters. Fuel Warning Oil Level Oil Temperature Canopy Temperature
Earth
Fault
Earth Fault Oil Temperature Oil Level
Digital input
1 polarity
Normally open: Open contact is healthy. Normally close: Close contact is healthy.
Normally
open
Normally
closed
Normally open
Digital input
2 polarity
Normally open: Open contact is healthy. Normally close: Close contact is healthy.
Normally
open
Normally
closed
Normally open
Digital input
3 polarity
Normally open: Open contact is healthy. Normally close: Close contact is healthy.
Normally
open
Normally
closed
Normally open
Operating Instructions
Page - 14
Operating Instructions
Page - 15
Fan High
Current
Maximum limit for fan current
2.0
0-3.5
Fan Low
Current
Minimum limit for fan current
0.2
0-3.5
Fan Current
Delay
This is the timer for fan current trip.
5
1-100
>
>
Digital input
4 polarity
Normally open: Open contact is healthy. Normally close: Close contact is healthy.
Normally
open
Normally
closed
Normally open
Digital input
5 polarity #
Normally open: Open contact is healthy. Normally close: Close contact is healthy.
Normally
open
Normally
closed
Normally open
Digital input
6 polarity #
Normally open: Open contact is healthy. Normally close: Close contact is healthy.
Normally
open
Normally
closed
Normally open
Digital input
7 polarity #
Normally open: Open contact is healthy. Normally close: Close contact is healthy.
Normally
open
Normally
closed
Normally open
Operating Instructions
Page - 16
12.2 Generator Parameter
Generator
O/V
Max. Permissible Generator voltage, above this the Generator voltage is treated unhealthy & the Generator is stopped on voltage fault.
270V
50-300V
Generator
U/V
Min. permissible Generator voltage, below this the Generator voltage is treated unhealthy & the Generator is stopped on voltage fault.
180V
50-300V
Gen Voltage
Delay
Duration for which generator Over/Under voltage condition can be tolerated before stopping the Generator.
10 Sec
1-999 Sec
VOLT
Generator
O/F
Max. Permissible Generator freque­ncy, above this the Generator freque­ncy is treated unhealthy & the Gene­rator is stopped on frequency fault.
65Hz
25-70Hz Disable*
Generator
U/F
Min. permissible Generator frequency, below this the Generator frequency is treated unhealthy & the Generator is stopped frequency fault.
45Hz
Disable* 25-70Hz
Gen Freq
Delay
Duration for which Generator Over /Under frequency condition can be tolerated before stopping the Generator. This setting is not available if (4)&(5) are disabled
5 Sec
1-999 Sec.
Current
Unbalance
IN
The maximum permissible current unbalance in %. The unbalance starts only after the system is loaded to 25% of its capacity
Disable
5-100%
Disable
Current
Unbalance
Delay
Duration for which the current unbalance can be tolerated before triggering the fault
10 Sec
1-999Sec
Pickup
Voltage
This parameter specifies the generator voltage at which it is presumed to have started and crank has to be terminated
100V
80-150V
Hz
Hz
Hz
A
A
U
U
U
Operating Instructions
Page - 17
Service Due
Hr
Time, in hours, for next service due warning.
250Hrs
10-999 Hrs
Crank Cut
Method
Auto disconnects the crank command on detection of either voltage buildup/ voltage or oil pressure build up
Voltage
Only
Voltage only Voltage or
LLOP
Pick Up
KVA
warning
If the current level crosses this limit the contact is energized after the programmed supervision time
8
1-9999
KVA
Reset KVA
warning
If the current level falls below this limit the contact is de-energized after the programmed supervision time.
8
1-9999
KVA
Warning
Delay
The supervision time for the above 2 parameters.
5
1-999Sec
Choke Pre
time
Keep the choke for this time before the engine has started.
Disable
Disable* 1-999 Sec
Choke Post
time
Keep the choke for this time after the engine has started.
Disable
Disable* 1-999 Sec
Pump Pre
Time
Activate the Pump by this time before cranking
2
1-999Sec
Engine Off
Time
In manual mode, some time its required to switch off/on the engine at a predetermined time. This setting set the time for automatic switch off of the engine
Disable
00:01 to23.59 Disable *
KVA
KVA
E û
Operating Instructions
Page - 18
Engine On
Time
In manual mode, some time its required to switch off/on the engine at a predetermined time. This setting set the time for automatic switch ON of the engine
Disable
00:01 to23.59 Disable*
Eü
Mains O/V
Max. Permissible Mains voltage, above this the Mains voltage is treated unhealthy & Generator is started
270V
50-300V
Mains U/V
Min. permissible voltage, below this the voltage is treated unhealthy & Generator is started
180V
80-300V
12.3 AMF Parameter
Mains
Voltage
Delay
Duration for which Mains Over/Under voltage condition can be tolerated before starting the Generator.
10
1-999 Sec
Mains O/F
Max. Permissible Mains frequency, above this frequency the Mains is treated unhealthy & Generator is started.
65Hz
40-70Hz Disable*
Mains U/F
Min. permissible Mains frequency, below this frequency the Mains is treated unhealthy & Generator is started.
45Hz
Disable* 40-70Hz
Mains Freq
Delay
Time for which the Mains frequency has to be unhealthy (under or over frequency as defined above in 4 & 5) before starting the Generator.
5 Sec
1-999 Sec.
Voltage
Unbalance
Max. allowed voltage unbalance in volt
Disable
10-100 Volt Disable*
Voltage
Unbalance
Time
Duration for which unbalance can be allowed before starting the Generator. This parameter is not available if above is set to disabled.
10
1-999Sec
VOLT
Hz
Hz
Hz
V
V
Operating Instructions
Page - 19
Phase
Sequence
Delay
This setting determines if the engine shall be started and load switch to generator in case of reverse phase sequence of mains.
Disable
Disable 1-999 Sec
Mains
Restoration
Time
The time for which Mains should be continuously healthy before stopping the Generator and load transferred to Mains.
10 Sec
1-999 Sec
Warm Up
Time
The load is transferred to generator after expiry of this time
0Sec
0-999 Sec
Gen Start
Delay
The starting of generator is delayed by this time after the mains unhealthy timers have expired and the mains contact has been released. This is required in certain applications where immediate generator starting is not required but the mains contactors are to be protected. This timer is automatically reset, if during this duration the mains become healthy for “Mains Restoration Delay”
Disable
Disable* 1-999 Mins
Gen. 0n
Time
Max. duration for which the generator is allowed to work continuously
Disable
Disable* 1-999 Mins
Gen Rest
Time
If the generator has run continuously as per above parameter, the genera­tor is given rest irrespective of the mains condition. In case of mains unhealthy during this time the mains contact is deactivated but the generator is not started. This is unavailable if above is Disabled This timer is automatically reset, if during this duration the mains become healthy for “Mains Restoration Delay”
Disable
Disable * 1-999 mins
Operating Instructions
Page - 20
Mains Over
Load
Econ-A can protect contactors from mains over load. If this setting is enabled than the mains contactor shall drop after the mains current crosses the set limit for a programmed duration
Disable
Disable* 2-9999Amps
Mains O/L
Delay
The monitoring duration for the above parameter before the fault is triggered.
5 Sec
1-999 Sec
Contactor
Protection
In case of the unit placed under manual mode of tripped due to a fault condition and the mains voltage falls below the safe limit of the contactor, the contactor burns after chattering. This can be avoided by enabling this protection. If enabled the mains contactor shall drop if the mains voltage becomes unhealthy and the contactor will again engage after the mains voltage turns healthy
Disable
Disable / Enable
Mains Fail
Some application require the generator to start on failure of one or more phases Other wants all the 3 phases to become unhealthy before starting the generator ECON-A can handle both situations
Any
Phase
Fail
Any Phase Fail/ All Phase Fail
GCB to
MCB Delay
User programmable delay when the load is transferred from Generator to Mains.
2 Sec
1-10 Sec
Recool
Time
The time for which generator is allowed to run on no load before switching off
30 Sec
0-999Sec
1/3
Operating Instructions
Page - 21
Service
Delay hour
In AMF mode,if this parameter is enabled, the engine will automatically start after this periodic time lapse from the last start. This is meant for periodic function
Disabled
2-999 Hrs
Service Run
min.
The genset will work for this duration in service run mode. It will stop automatically after expiry of this time. During this time if the mains become unhealthy the generator contactor shall be engaged and the engine shall be stopped after the mains is healthy
Disabled
1-999 Min Disabled
s
s
Contact
Type
This setting is for units which have external change over. The sections are change over(external) or contactors (built in and controlled by ECON)
Contactor
Change over Contactor
12.4 Protection Parameter
Fuel Warn
Level
Monitoring value of fuel level below which fuel level warning is generated.
25 %
Disable* 11-80 %
Fuel Warn
Delay
Monitoring time of fuel level after which fuel level warning is generated.
10 Sec
1-999Sec
Fuel Trip
Level
Monitoring value of fuel level below which fuel level trip is generated.
15 %
10-80 %
Fuel Trip
Delay
Monitoring time of fuel level after which fuel level trip is generated.
10 Sec
1-999 Sec
Operating Instructions
Page - 22
LLOP Trip
Level
Monitoring value of lube oil pressure below which LLOP trip is generated.
1.0
2
Kg/cm
0.4-8.5
2
Kg/cm
LLOP Trip
Delay
Monitoring time of lube oil pressure after which LLOP trip is generated.
10 Sec
0-999 Sec
HWT Trip
Level
Monitoring value of water temperature below which HWT trip is generated.
90
40-250 Disabled*
HWT Trip
Delay
Monitoring time of water temperature after which HWT trip is generated.
5 Sec
1-999 Sec
Oil Temp.
Trip Level
Monitoring value of Oil temperature below which Oil Temp. trip is generated.
90
40-250 Disabled*
Oil Temp.
Trip Delay
Monitoring time of Oil temperature after which Oil Temp. trip is generated.
5 Sec
1-999 Sec
D1-D7
Input Delay
Delay for 7 programmable digital inputs . Digital input are explained above.
5 sec
1-999 Sec
Chg Alt-
V Belt Delay
Duration for which the V-Belt signal should be continuously deactive to be recognized as a fault and action initiated. This fault is only enabled while the generator is running.
Disable
Disable* 2-999 Sec
Hooter ON
Time
Duration for which the hooter shall be ON, if not externally reset, while announcing a fault.
30Sec
1-999 Sec
Operating Instructions
Page - 23
Crank ON
Time
Maximum crank time
5 Sec
1-999 Sec
Crank Gap
Time
The delay between two successive cranks
5 Sec
1-999 Sec
Crank
Attempts
The maximum number of cranks that shall be issued to start the Engine
3
1-10
Solenoid
ON time
The time for which stop solenoid will be kept active while stopping the engine
22 Sec
1-999Sec
Disp Auto
Scroll
Setting ON will enable Auto Scroll of display. OFF: No scroll and next
parameter can be viewed by pressing next switch
ON
ON/OFF
Battery UV
Warning
Min. permissible battery voltage, below this the voltage is treated unhealthy & warning is generated.
Disabled
Disabled* 9-35V
Battery OV
Warning
Max. permissible battery voltage, above this the voltage is treated unhealthy & warning is generated.
Disabled
9-35V Disabled*
N
12.5 Comm RS485 Parameter #
Device Id
Modbus device ID
1
1-247
Baud Rate
RS 485 Communication Baudrate
9600
1200 2400 4800 9600 19200
Parity
RS 485 Communication Parity Bits
None
Even Odd None
Page - 24
Operating Instructions
Stop Bit
RS 485 Communication Stop Bits
1
1 2
12.6 Reset Service Alarm
Press INC to Reset Press DEC to esc
12.7 Adjust Clock
Automatic real time based DG Start & Stop (Manual Controller Configuration) RTC Time and Date can be easily entered
00.00
00.00
DD/MM/YYYY
12.8 Reset Password
Three digit password protection for system settings Password can be change easily.
* This parameter can be disabled while programming # These Parameters are model dependent Note: To save the parameter, switch of and switch on the controller.
13.0 Model Selection Chart
Model
AMF
Mode
Manual
Mode
Auto Stop
Mode
D5-D7
Input
Oil Temp.
Sensor
ECON-A-4C
√√√√√
ECON-A
√√√XX
ECON-S
X√√XX
ECON-M
X√XXX
Operating Instructions
Page - 25
14.0 Load Management ECON-A has programmable contact Load management function. The load
management contact will switch on when the current on the generator has crossed a programmed limit and will reset when the current has fallen below the reset programmed limit. This function can be used to cut-off unnecessary loads or start a second generator when the load goes above a limit.
15.0 Event Recording: ECON keeps a log of last 64 events. Setting change and warning are considered as event. Events are stamped along with date and time
16.0 Faults ECON keeps a log of last 64 Faults. These Faults are stamped along with date and time There are two categories of faults
• Internal Faults
• External faults
16.1 Internal Faults Internal faults are the faults, which do not need any external signals and are detected by the system itself. They are:
• Generator Fails to Start. • Generator Voltage Unhealthy
• Generator Frequency Unhealthy. • Generator over Speed.
• Generator Fails to Stop. • Over Load
16.2 External Faults Those faults which cannot be sensed by the unit itself (these faults are not reflected by the generator voltage) and are to be provided externally. They are:
• LLOP • HWT • Oil Level
• RWL • Fuel • Oil Temp.
• Emergency • V-Belt • Earth Fault
• 16.3 Fault Reset
Internal Faults & LLOP fault: All internal faults and LLOP fault can be reset by pressing (R) switch after the generator is stopped. External Fault except LLOP & V-Belt faults: These faults cannot be reset till the engine is running and/or fault conditions persist. Once the faults are rectified, the fault can be reset by pressing Reset switch (R). In case the engine fails to stop “STOP KEY” can be pressed for manual attempt to stop engine
17.0 Communication
• Rs232 • USB
• Modbus on Isolated Rs485 (optional)
Operating Instructions
Page - 26
Terminal No.
Description
1
Fan Current S1
2
Fan Current S2
3
NC
4
CT Common
5
CT B
6
CT Y
7
CT R
8
Sensor Oil Temp.
9
Sensor LLOP
10
Sensor HWT
11
Sensor Fuel
12
V-DG-N
13
V-DG-B
14
V-DG-Y
15
V-DG-R
16
V-Mains-N
17
V-Mains-B
18
V-Mains-Y
19
V-Mains-R
20
NC
21
NC
22
NC
23
D Input 4
24
D Input 3
25
D Input 2
26
D Input 1
27
Emergency
28
SemiAuto
29
R Start/Stop
30
Programmable Output 3
• 18.0 Terminal Numbers
Operating Instructions
Page - 27
31
Programmable Output 2
32
Programmable Output 1
33
Hooter
34
Solenoid
35
Crank
36
GCB
37
MCB
38
Chg. Alt. Contact
39
Battery(+ve)(8-35 V DC)
40
Battery(-ve)
41
Sensor(-ve)
42
D Input 5
43
D Input 6
44
D Input 7
45
D(+): RS485
46
D(-):RS485
Operating Instructions
Page - 28
Connect the wires as per the labelling done in back sticker:
19.0 Technical Specifications AC voltage withstand 330 VAC (Phase to neutral) Measurement Accuracy Voltages & Current 1% of Reading Power & Energies 2% of Reading Surge 1.2/50Usec 2.5KV Battery Voltage 9-35 V DC DC Interruption time 0.4 Sec Cut out Dimensions 155mm X 117mm Depth 41.8 mm Digital Input Level Battery Voltage (Negative)
Digital Output Battery Voltage (Negative)
20.0 Dimensions
Loading...