PROCESS HEATING COMPANY UNITIZED HEATER KIT Installation, Operation & Maintenance Manual

Page 1
INSTALLATION,
OPERATION
AND
MAINTENANCE
MANUAL
UNITIZED HEATER
PROCESS HEATING COMPANY, INC.
POST OFFICE BOX 84585
SEATTLE, WASHINGTON 98124-5885
KIT
Page 2
WARNINGS
1) READ AND UNDERSTAND ALL TAGS AND INSTALLATION AND OPERATING INSTRUCTIONS BEORE COMMENCING.
2) CHECK THAT THE ELECTRICAL SERVICE WILL HANDLE THE LOAD. UNIT MUST BE ADEQUATELY GROUNDED.
3) ALL WIRING SHOULD CONFORM TO REQUIREMENTS OF NATIONAL AND LOCAL ELECTRICAL CODES AND STANDARDS.
4) ONLY LICENSED ELECTRICIAN SHOULD CONNECT POWER TO PANEL AND SYSTEM.
5) NEVER EXPOSE HEATER TUBES TO AIR WITH POWER ON.
6) CARE SHOULD BE USED WHEN WORKING AROUND TUBES WHEN CLEANING OR INSTALLING. WALLS ARE LESS THEN ¼” THICK.
7) IF THERE ARE ANY QUESTIONS CONCERNING THE RATINGS OR INSTRUCTIONS PLEASE CONTACT YOUR LOCAL DISTRIBUTOR OR THE FACTORY. PHONE (206) 682-3414 FAX (206) 682-1582
2
Page 3
ADDITIONAL IMPORTANT INFORMATION
1) THESE INSTRUCTIONS CANNOT POSSIBLY COVER EVERY SITUATION CONCERNING THE OPERATION, INSPECTION, ADJUSTMENT AND TEST OF THE EQUIPMENT FURNISHED. PROCESS HEATING COMPANY (PHCo), IN THE FURNISHING OF THIS EQUIPMENT AND THESE INSTRUCTIONS, MUST PRESUME THAT THE OPERATING AND MAINTENANCE PERSONEL USING THIS EQUIPMENT HAVE SUFFICIENT TECHNICAL KNOWLEDGE AND EXPERIENCE TO APPLY SOUND SAFETY AND OPERATIONAL PRACTICES WHICH MAY NOT BE MENTIONED.
2) IN APPLICATIONS WHERE PHCo FURNISHED EQUIPMENT THAT IS TO BE INTEGRATED WITH A PROCESS OR OTHER EQUIPMENT, THESE INSTRUCTIONS SHOULD BE THOROUGHLY REVIEWED TO DETERMINE THE PROPER INTEGRATION OF THE EQUIPMENT INTO THE OVERALL PLANT OR SYSTEM OPERATIONAL PROCEDURES.
3) PHCo DOES NOT SUPPLY, RECOMMEND OR APPROVE THE VARIOUS SYSTEMS IN WHICH ITS PRODUCTS ARE OR MAY BE USED. UNLESS DESIGNED, MANUFACTURED AND USED PROPERLY, VARIOUS SYSTEMS MAY BE INHERENTLY UNSAFE OR DANGEROUS. THE USER SHOULD CHECK AND COMPLY WITH ALL FEDERAL, STATE AND LOCAL REGULATIONS AND OTHER REGULATIONS AND RECOMMENDATIONS SUCH AS: NFPA, UL, API, OSHA, ETC.
3
Page 4
PREPERATION
1) REMOVE JACKETING AND INSULATION FROM SECTION OF TANK HEATER IS TO BE INSTALLED THROUGH.
2) MARK LOCATION OF OPENING ON TANK. HEATER SHOULD BE KEPT AS LOW AS POSSIBLE IN TANK.
CAUTION
BEFORE BURNING OR WELDING ON TANK, CLEAN THOROUGHLY AND KEEP WELL VENTILATED.
INSTALLATION
1) BURN OPENING IN TANK SLIGHTLY LARGER THAN HEATER TERMINAL BOX (SNUG FIT). REMOVE SLAG AND GRIND OPENING SMOOTH.
2) REMOVE BLOCKING FROM SUPPORT PLATE(S) AND SLIDE HEATER THROUGH OPENING IN TANK. STOP AT MARKED “WELD LINE” ON HEATER TERMINAL BOX.
3) HEATER TUBE SUPPORT PLATE(S) SHOULD BE ATTACHED TO TANK BOTTOM. LEVEL HEATER TUBES AND WELD SUPPORT(S) TO TANK. DO NOT
4) WELD HEATER TERMINAL BOX TO TANK. TERMINAL BOX IS ¼” THICK STEEL. WELD MUST BE LIQUID TIGHT.
5) TANK DISCHARGE SHOULD BE KEPT 2” TO 3” ABOVE HEATER TUBES. NEVER EXPOSE HEATER TUBES TO AIR WITH POWER ON.
6) HAVE LICENSED ELECTRICIAN CONNECT PROPER VOLTAGE AND PHASE TO THE LINE SIDE OF THE MAIN DISCONNECT SWITCH USING SUITABLE WIRE GAUGE FOR HEATER LOAD. UNIT MUST BE PROPERLY GROUNDED.
7) CHECK ALL CONNECTIONS TO INSURE THEY ARE ALL TIGHT SINCE VIBRATION IN TRAVEL CAN LOOSEN WIRE CONNECTIONS.
WELD HEATER TUBES TO SUPPORT PLATE(S).
4
Page 5
OPERATION
1) TURN ON THE MAIN DISCONNECT SWITCH.
2) PUSH THE RED HIGH LIMIT RESET PUSHBUTTON TO PULL IN THE CONTACTOR AND PROVIDE LOAD POWER.
3) THE INDICATING TEMPERATURE CONTROL (IN ENCLOSURE DOOR) SHOULD BE SET TO DESIRED PROCESS TEMPERATURE BY PRESSING UP/DOWN ARROWS AND THEN PRESSING ENTER (HALF CIRCLE) KEY (FACTORY SET TO 125°F).
4) THE HIGH LIMIT CONTROL (PROCESS TEMPERATURE SENSING) IN THE PANEL, MOUNTED ON THE BACK PANEL UNDER THE MAIN CONTROLLER TO THE LEFT SIDE, SENSES PROCESS TEMPERATURE AND WILL DISCONNECT POWER TO THE HEATERS IF OVER TEMPERATURE OCCURS. SETPOINT SHOULD BE APROXIMATELY 20°
TO 25°F ABOVE PROCESS TEMPERATURE. WHEN THE TEMPERATURE RETURNS TO BELOW THE HIGH LIMIT SETPOINT THE POWER WILL RETURNED TO THE HEATING CIRCUIT ALLOWING THE HEATERS TO COME ON BUT THE RED HIGH LIMIT RESET PUSHBUTTON WILL BE ILLUMINATED UNTIL MANUALLY RESET (INDICATING THAT THERE WAS A HIGH LIMIT OCCURANCE). THE CAUSE OF THE MALFUNCTION SHOULD BE INVESTIGATED AT ONCE. POSSIBLE REASONS ARE:
• Thermocouple failure on the main temperature controller (indicated by “no”
in the upper display of the controller).
• “Over Ranging” of the main temperature controller (indicated by “over” in
upper display).
• Temperature controller setting higher then Hi-Limit controller setting.
• Main temperature controller out of calibration.
• Hi-Limit controller out of calibration.
• Heater magnetic contactor locked in closed position because of “welded”
contacts or mechanical binding.
5
Page 6
MAINTANENCE
1) PERIODICALLY CHECK ALL WIRING CONNECTIONS TO INSURE THEY ARE TIGHT AND FREE OF OXIDATION.
2) PERIODICALLY CHECK CONTACTS ON THE CONTACTORS FOR WEAR AND REPLACE CONTACTOR IF WORN.
3) TANK SHOULD BE CLEANED AT REGULAR INTERVALS.
4) BE SURE TO SEE THAT TANK HAS ADEQUATE INSULATION. INSULATION TENDS TO BREAK DOWN IN TIME THUS COSTING DOLLARS IN LOST EFFICIENCY.
6
Page 7
on
PHCo
Products
Manufactured by
Process Heating Company
THE ABOVE WARRANTY IS SUBJECT TO THE TERMS &
and delivered to the initial user are subject to the fol-
lowing limited warranty: PHCo warrants its Patented
Heating Elements to be free from defects in workmanship
and materials for a period of five (5) years (one (1) year
for drop-in style) after the date of delivery to the initial
user when operated under normal use and service and in
accordance with printed instructions provided by PHCo.
All other parts and components provided by PHCo as
part of the unit are warranted to be free from defects in
material and workmanship for a period of one (1) year
from date of delivery to the initial user.
CONDITIONS ON THE REVERSE SIDE OF THIS DOCUMENT
Page 8
, INCLUD-
OTHER
nship and materials
, OR FOR ANY
less the same is in writ-
o its transaction with you (the
r after tender of delivery (five (5)
f such fact within thirty (30)
y are exclusive of all other
er the purchase price paid for that
aim relating to any item sold.
lity on account of any claim as-
r with a non-defective item), then
basis, if PHCo’s liability on account
o.
that is greater than their normal.
terms of this contract.
waived or varied by course of
tute a waiver of the same or any
rules. Any action to enforce
or state court located in King
jurisdiction over them person-
be dismissed at the instance of
ontract, tort or otherwise) may be com-
-in style elements), and if Buyer notifies PHCo in writing o
OTHERS FOR ANY SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES
Unless otherwise agreed in writing by Process Heating Company (“PHCo”), all of the following terms & conditions shall apply t
“buyer”):
1. LIMITED WARRANTY; DISCLAIMERS. PHCo warrants that the goods sold under this contract shall be free from defects in workma
at the time delivery is tendered. If there is discovered any failure of goods to conform to this warranty within one (1) yea
years in the case of immersion type heating elements other than drop
days following such discovery, PHCo at its own expense either will repair the defective item, or replace it, or refund to Buy
item (with choice between repair, replacement or refund to be made solely by PHCo). The foregoing limited warranty and remed
warranties, express or implied, and constitute PHCo’s exclusive liability, and Buyer’s exclusive remedy, on account of any cl
PHCo DISCLAIMS ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. If PHCo should elect to repair or replace a
defective item and if for any reason the repair or replacement should fail in its essential purpose (which is to provide Buye
PHCo’s liability nevertheless shall be limited to the purchase price charged by PHCo for the goods. PHCo shall have no liabi
serted under principles of negligence or other tort, breach of any statutory duty, indemnity or contribution, or on any other
of such claim would exceed or in any respect differ from its liability under forgoing limited warranty and exclusive remedy.
2. LIABILITY OF PHCo UNDER THE FOREGOING LIMITED WARRANTY SHALL EXIST ONLY IF: a. The goods are installed, operated and tested in accordance with the PHCo approved installation and operation instruction. b. The goods are used and maintained in conformity with installation and operation instructions approved or published by PHC
c. Written authorization must be given by PHCo before any warranty work is done. The above limited warranty shall be void and no longer in effect if the goods are subject to abuse, strain, impact or loading
3. LIMITATION OF LIABILITY. UNDER NO CIRCUMSTANCES SHALL PHCO OR ANYONE ELSE INVOLVED IN THE MANUFACTURE OR
SALES OF THE GOODS BE LAIBLE TO BUYER OR
ING BUT NOT LIMITED TO LOST PROFITS, EVEN IF PHCO HAS BEEN ADVISED OF THE POSSIBILTY OF SUCH DAMAGES
DAMAGES OR SUMS PAID BY BUYER OR OTHER THIRD PARTIES. THE FOREGOING LIMITATION OF LIABILITY SHALL APPLY
WHETHER ANY CLAIM FOR ANY SUCH DAMAGES IS BASED UPON PRINCIPLES OF CONTRACT, WARRANTY, NEGLIGENCE OR
TORT, BREACH OF STATUTORY DUTY, PRINCIPLES OF INDEMNITY OR CONTRIBUTION, THE FAILURE OF ANY LIMITED OR EXCLUSIVE
REMEDY TO ACHIEVE ITS ESSENTIAL PURPOSE, OR ANY OTHER BASIS.
4. AUTHORITY OF PHCo’s AGENTS. No agent, employee or representative of PHCo has any authority to bind PHCo to any other affirmation, representa-
tion, promise or warranty concerning the goods sold under this contract, unless it is in writing and included as part of the
5. MODIFICATION OF WAIVER. No subsequent waiver or modification of this Limited Warranty and Liability shall be effective un
ing and signed by the party against whom such waiver or modification is asserted. No waiver in any one instance shall consti
other term or condition on any subsequent occasion. None of the express terms of this Limited Warranty and Liability may be
dealing or usage of trade.
6. DISPUTES. This agreement shall be governed by the laws of the State of Washington without reference to its choice of law
any of the terms or conditions of this agreement may be commenced or maintained at the option of either party in any federal
County, Washington having jurisdiction over the matter, and both parties consent in advance to the exercise by such courts of
ally. No action by either party arising out of or relating to this contract (including any action based upon principles of c
menced more than one (1) year after the cause of the action has accrued, and any action commenced by a party thereafter shall
the other party.
Page 9
2006-02-15
Bulletin E-90-C
5011643800-DWC0
C Series Temperature Controller
Instruction Sheet
Thank you very much for purchasing a Love Controls Series C Temperature Controller. Please read this instruction sheet before using your controller to ensure proper operation and please keep this instruction sheet handy for quick reference.
1 Precaution
DANGER! Caution! Electric Shock!
1. Do not touch the AC terminals while the power is supplied to the controller to prevent an electric shock.
2. Make sure power is disconnected while checking the unit inside.
3. The symbol (equivalent to Class II of IEC 536).
WARNING!
Mount the controller in a location that will not be subject to excessive temperature, shock, or vibration. All models are designed for mounting in an enclosed panel..
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.0mm, hole diameter 3.2mm). Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Recommended tightening torque: 0.4 N.m (4kgf.cm). Applicable wire: Solid/twisted wire of 2 mm
2. Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning.
3. Never modify or disassemble the controller.
4. Do not connect anything to the “Not used” terminals.
5. Make sure all wires are connected to the correct polarity of terminals.
6. Do not install and/or use the controller in places subject to: Dust or corrosive gases and liquid, high humidity and high radiation, vibration and shock, high voltage and high frequency
7. Power must be off when wiring and changing a temperature sensor.
8. Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires.
9. Please use wires with resistance when extending or connecting a platinum resistance sensor (RTD).
10. Please keep the wire as short as possible when wiring a platinum resistance sensor (RTD) to the controller and please route power wires as far as possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water, corrosive materials, airborne dust and electric shock or vibration.
12. Please make sure power cables and signals from instruments are all installed properly before energizing the controller, otherwise serious damage may occur.
13. Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent an electric shock.
14. Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal circuit within this period.
15. Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
16. This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required, install the protection close to the instrument. Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse type: Time-lag fuse
17. Note: This controller does not provide overcurrent protection. Use of this product requires that suitable overcurrent protection device(s) must be added to ensure compliance with all relevant electrical standards and codes. (Rated 250 V, 15 Amps max). A suitable disconnecting device should be provided near the controller in the end-use installation.
indicates this Controller is protected throughout by DOUBLE INSULATION or REINFORCED INSULATION
2
, 12AWG to 24AWG. Please be sure to tighten them properly.
2 Display, LED, and Pushbuttons
PV displays process value SV displays setpoint value.
INDEX: advances the display to the next menu item.
UP ARROW: Increments a value or changes a menu item.
DOWN ARROW: Increments a value or changes a menu item.
ENTER: stores the value or item change.
Page 10
3 Temperature Sensor Type and Temperature Range
Input Temperature Sensor Type Register Value LED Display Temperature Range
Platinum resistance (Pt100) type3 15
Platinum resistance (Pt100) type2 14
Platinum resistance (Pt100) type1 13
Platinum resistance (JPt100) type2 12
Platinum resistance (JPt100) type1 11
Thermocouple (TC) B type 10
Thermocouple (TC) S type 9
Thermocouple (TC) R type 8
Thermocouple (TC) N type 7
Thermocouple (TC) E type 6
Thermocouple (TC) T type2 5
Thermocouple (TC) T type1 4
Thermocouple (TC) J type2 3
Thermocouple (TC) J type1 2
Thermocouple (TC) K type2 1
Thermocouple (TC) K type1 0
Thermocouple (TC) L type 16
Thermocouple (TC) U type 17
Thermocouple (TC) Txk type 18
0.0 to 100.0
-20.0 to 500.0 oC
-200 to 600
0.0 to 100.0
-20.0 to 400.0
100 to 1800
0 to 1700
0 to 1700
-200 to 1300
0 to 600
-20.0 to 400.0
-200 to 400
-20.0 to 400.0
-100 to 850
-20.0 to 500.0
-200 to 1300
-200 to 850 oC
-200 to 500
-200 to 800
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
4 Operation
There are three modes of operation: operation, regulation and initial setting. When power is applied, the controller will default to the operation mode. Press the switch to the initial setting mode. Pressing the key while in the regulation mode or initial setting mode, forces the controller to return
to the operation mode. PV/SV : Sets the temperature set point and displays the temperature process value. Use the and keys to set the temperature set point.
Setting method: While in any function mode, press the key to select the desired function and use the and keys to change settings. Press
key to save the changes. Menu items are listed below.
Regulation Mode
Auto-tuning
(Set in PID control and RUN mode)
Press
Set proportional band (Kp) (in PID control) Press
Set integral time (Ki) (in PID control) Press
Set derivative time (Kt) (in PID control)
Press
or P/PD control offset (when PID control is ON and Ki=0 set the value of PdoF. If Ki≠0, AT (auto-tuning, will automatically set the value of ioF.
Press
or Heating/Cooling hysteresis.
(in ON/OFF control) Press
key to switch to regulation mode. If the key is pressed for more than 3 seconds, the controller will
set temperature set point
Press
Press
(This parameter is available only when ALA1 function enables)
Press
(This paramete r is available only when ALA1 function enables)
Press
(This parameter is available only when ALA2 function enables)
Press
(This parameter is available only when ALA2 function enables)
Press
Operation Mode
Use key to
Control setting RUN or STOP
Upper-limit alarm 1
Lower-limit alarm 1
Upper-limit alarm 2
Lower-limit alarm 2
Press
do not display when analog input
Press
Press
Press
manual.
Press
Initial Setting Mode
Set input type
Set temperature unit
Set upper-limit of temperature range
Set lowe r-li m it o f temperature range
Sets Control Method: on/off, PID, or
Select heating or cooling control.
Page 11
or
(Set in PID control mode)
Press
Regulate temperature deviation value
Press
Regulate upper-limit of analog output value
(The setting display when analog output) Press
Regulate lower-limit of analog
(The setting display when analog output)
Press
output value
to return to auto-tuning mode
Heating/Cooling control cycle setting
Press
Setting lock mode
Press
Display and adjust output value.
Alarm 1 mode setting
Press
Alarm 2 mode setting
Press
Communication write function enable/disable
Press
Communication address setting
Press
Communication baud rate setting
Press
Data length setting
Press
Pari ty bit sett ing
Press
Stop bit setting
Pres s to ret ur n in pu t ty p e se ttin g
Parameters List
1. Operation Mode: The default mode after start-up
LED Explanation Default
RUN/STOP: Control setting. Run (
ALARM 1 HIGH: Upper limit for alarm 1. (Only available when alarm is set in the initial setting mode).
ALARM 1 LOW: Lower limit for alarm 1. (Only available when alarm is set in the initial setting mode).
ALARM 2 HIGH: Upper limit for alarm 2. (Only available when alarm is set in the initial setting mode).
ALARM 2 LOW: Lower limit for alarm 2. (Only available when alarm is set in the initial setting mode).
) or Stop ( ) mode on the SV display.
RUN
o
4.0
o
4.0
o
4.0
o
4.0
C
C
C
C
Lock Function Setting: LoC1, LoC2, or OFF. LoC1 mode will lock all settings, LoC2 locks everything except the setpoint value, and OFF will not lock any settings. Press
release the lock status.
and keys simultaneously, to
OUT: The Output value adjustment and display in manual tuning control. (Not available in ON/OFF or Auto-tuning control).
OFF
0
2. Regulation Mode: Control parameters Settings LED Explanation Default
AT (Auto-Tuning): ON or OFF, when set ON, the execution of the auto-tuning function in PID control mode is automatically started. (Only available when PID control is selected in initial settings)
P (Proportional Band in PID control): Sets P value. 47.6
I (Integral Time in PID control): Sets I value. 260
D (Derivative Time in PID control): Sets D value. 41 PdoF: Offset output when P or PD control function is on. PID in initial settings is selected and the value
of Ki (Integral Time in regulation mode) is equal to zero.
OFF
0
ioF: Default value of integral volume when PID control is ON and the Ki (Integral Time in regulation mode) is not equal to zero. AT function can automatically set this parameter when PID control is active and Ki≠0.
HtS (Heating Hysteresis): Available only in ON/OFF control. Sets the value the heating hysteresis. 0
CtS (Cooling Hysteresis): Available only in ON/OFF control. Sets the value the cooling hysteresis. 0 HtPd: PID heating control cycle setting. Only available when a PID control is selected in the initial
settings. ClPd: PID cooling control cycle setting. Only available when a PID control is selected in the initial settings.
TPoF: Regulates the temperature deviation value. 0
CrHi: Regulates the 20 mA output deviation value. 0
CrLo: Regulates the 4 mA output deviation value. 0
HtS (Heating Hysteresis): Available only in ON/OFF control. Sets the value the heating hysteresis. 0
0
Output Selection: Voltage: 4 sec. Relay : 20 sec.
Page 12
3. Initial Setting Mode: Initial settings of the controller and communication parameters LED Explanation Default
INPUT: Select input temperature sensor type (Please refer to the contents of the “Temperature Sensor Type and Temperature Range” for detail)
Engineering Unit(°F or °C): Select engineering unit F or C.
T-High: Upper limit for temperature range. 500.0
T-Low: Lower limit for temperature range. -20.0
CONTROL METHOD (ON/OFF, PID, or manual tuning [ point value.
Control Action (Direct or Reverse Acting): Cooling [Cool] or heating [HEAT]. HEAT
ALARM 1: Alarm 1 setting. (See Alarm Output Section for set values and descriptions). 0
ALARM 2: Alarm 2 setting. (See Alarm Output Section for set values and descriptions).
]): Sets the control method for the set
C WE: Write-in function disabled/enabled. Can be set only when unit is equipped with serial communication. C NO: Address setting. Can be set only when unit is equipped with serial communication.
BPS: Baud rate setting. Can be set only when unit is equipped with serial communication.
Length: Data length setting. Can be set only when unit is equipped with serial communication.
Parity: Parity bit setting. Can be set only when unit is equipped with serial communication.
Stop Bit: Stop bit setting. Can be set only when unit is equipped with serial communication.
PT2
o
C
PID
0
OFF
1
9600
7
E
1
Execution : The programming execution is initiated through in the operation mode. When When
is set to , the program will start to execute in order from the step 0 of the start pattern. is set to , the program will stop and the control output is disabled
5 Heating and Cooling
Temperature control can be achieved either by heating or cooling. Please refer to the following for the operation: Settings for heat or cool operation are found in the initial settings mode under . Select Select
, for heating (reverse) control on Output 1. , for cooling (forward) control on Output 1
Input Error Indication
Setting
value
PV
SV
Temperature sensor is not connected
Measured temperature value exceeds
the temperature range
Unknown input
6 Alarm Outputs
Depending on the controller model, there can be up to two alarm outputs. Each alarm output can be configured for an alarm type listed below. Alarm types are set in the initial setting mode. The alarm output is activated whenever the process temperature value (PV) is getting higher or lower than the set point of alarm limit.
Set
Value
0 Alarm function disabled Output OFF
Deviation upper- and lower-limit: This alarm output operates when PV value is higher than the setting value
1
SV+(AL-H) or lower than the setting value SV-(AL-L). Deviation upper-limit:
2
This alarm output operates when PV value is higher than the setting value SV+(AL-H). Deviation lower-limit:
3
This alarm output operates when PV value is lower than the setting value SV-(AL-L). Reverse deviation upper- and lower-limit:
4
This alarm output operates when PV value is in the range of the setting value SV+(AL-H) and SV-(AL-L).
Alarm Type Alarm Output Operation
ON
OFF
SV-(AL-L)
ON
OFF
ON
OFF
SV-(AL-L)
ON
OFF
SV-(AL-L)
SV
SV
SV
SV
SV+(AL-H)
SV+(AL-H)
SV+(AL-H)
Page 13
Absolute value upper- and lower-limit: This alarm output operates when PV value is higher than the setting value
5
AL-H or lower than setting value AL-L. Absolute value upper-limit: This alarm output operates when PV value is higher than the setting value
6
AL-H. Absolute value lower-limit: This alarm output operates when PV value is lower than the setting value AL-
7
L. Deviation upper- and lower-limit with standby sequence: This alarm output operates when PV value reaches set point (SV value) and
8
the value is higher than the setting value SV+(AL-H) or lower than the setting value SV-(AL-L). Deviation upper-limit with standby sequence: This alarm output operates when PV value reaches set point (SV value) and
9
the reached value is higher than the setting value SV+(AL-H). Deviation lower-limit with standby sequence:
10
This alarm output operates when PV value reaches the set point (SV value) and the reached value is lower than the setting value SV-(AL-L).
Hysteresis alarm output: Heating control: This alarm output operates if PV value is higher than the
11
setting value SV+(AL-H). This alarm output is OFF when PV value is lower than the setting value SV+(AL-L).
Hysteresis alarm output: Cooling control: This alarm output operates if PV value is lower than the
12
setting value SV-(AL-H). This alarm output is OFF when PV value is higher than the setting value SV-(AL-L).
ON
OFF
AL-L
ON
OFF
ON
OFF
AL-L
ON
OFF
SV-(AL-L) SV+(AL-H)
ON
OFF
ON
OFF
SV-(AL-L)
ON
OFF
SV
ON
OFF
AL-H AL-L
SV
SV
SV
AL-L
AL-H
AL-H
SV+(AL-H)
AL-H
SV
(Note: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L)
With the standby sequence, the alarm output will be temporarily disabled until the PV value reaches the set value. Then, the alarm output will operate. Once the alarming output operation is activated, there is a 1.5 sec. delay time to avoid any malfunction.
7 Specification
Input Voltage 100 to 240VAC 50/60Hz Operation Voltage Range 85% to 110% of rated voltage Power Consumption 5VA max. Memory Protection EEPROM 4K bit (non-volatile memory (number of writes: 100,000)
Display Method
Sensor Type
2 line x 4 character 7-segment LED display Process value(PV): Red color, Set point(SV): Green color Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK 3-wire Platinum RTD: Pt100, JPt100
Control Mode PID, ON/OFF, Manual or Auto-tuning.
Relay output: SPDT (SPST on the 1/16 DIN size series16C), Max. load 250VAC, 5A resistive load
Control Output
Voltage pulse output: DC 14V, Max. output current 40mA
Current output: DC 4 ~ 20m A output (Load resistance: Max. 600Ω) Display Accuracy 0.1% of measuring range. Sampling Rate 0.5 sec. RS-485 Communication MODBUS ASCII communication protocol (only on models designated with serial communication). Vibration Resistance 10 to 55Hz, 10m/s2 for 10min, each in X, Y and Z directions Shock Resistance Max. 300m/ s2, 3 times in each 3 axes, 6 directions Ambient Temperature 32 oF to 122 oF (0 oC to +50 oC) Storage Temperature -4 oF to 150 oF (-20 oC to +65 oC) Altitude 2000m or less Relative Humidity 0% to 80% (non-condensing)
Page 14
8 Plan Cutout and External Dimensions
Panel Cutout [dimensions are in mm (in.)]
Terminals Identification
65.0 min.
16C
(2.56)
. n
)
i
6
m
3 .
0 .
2 (
0 6
+0.6
45.0
-0 +0.02
(1.77)
-0
6
. 0 +
mm (in)
2 0
. 0
0
0
-
+
-
) 7
0 .
7 .
5
1
4
(
14V
DC
or
4~20mA
or
0~10V
RTD
+
IN
-
OUT1
-
+
COM
+
Tc
-
NO
1
6
2
7
3
8
4
9
5
10
OUT2/ ALM3
NO
14V
COM
DATA-
RS-485
DATA+
-
11
12
DC
13
+
14 15
L
AC 10 0 ~ 24 0V 50/60 Hz 5VA
N
ALM 2
ALM 1
3A 250Vac
COM
3A 250Vac
8C
4C
DATA+
RS-485
DATA-
1
2
3
4
11
12
13
14
L
N
COM
AC 100~240V 50~60Hz /5VA
3A 250Vac
15
5
ALM2
16
6
COM
17
7
ALM1
18
10
8
19
9
20
COM
1
11
RTD
+
Tc
or
-
DATA+
RS-485
2
DATA-
12
3
13
COM
4
14
NC
NO
L
N
3A 250Vac
5A 250Vac
-
DC 4~20mA
AC 100~240V 50~60Hz /5VA
14Vdc
+
3A 250Vac
15
5
ALM2
16
6
COM
17
7
ALM1
18
10
8
19
9
20
COM
RTD
+
Tc
or
-
NC
NO
3A 250Vac
5A 250Vac
DC 4~20mA
-
14Vdc
+
Page 15
9 External Dimensions
g
Dimensions are in millimeter (inch)
16C
4C
8C
10 Mountin
Mounting Method
16C/8C/4C Mounting Method: Step 1: Insert the controller through the panel cutout. Step 2: Insert the mounting bracket into the mounting groove at the top and bottom of the controller Step 3: Push the mounting bracket forward until the bracket stops at panel wall. Step 4: Insert and tighten screws on bracket to secure the controller in place. (The screw torque should be 0.8kgf-cm to
1.5kgf-cm)
Mounting Bracket Installation
Page 16
Page 17
PRODUCT SPECIFICATION SHEET
MODEL:
120L-17JZ329
REV:
-
DESCRIPTION:
DIN Rail/Surface Mtg. Temp Limit Controller
CUSTOMER PN:
Process Heating
DATE:
10/17/06
Input Voltage : 115VAC ±15%, 50/60Hz, 3VA Max. Control Output: SPDT Relay, N.O. contacts rated 8 Amps Res. 240VAC, 100,000 cycles Control Mode: Relay de-energizes on temperature rise (N.O. contacts open). Control Action: Latching with manual reset (Reset terminals open) or On-Off with 2oF Hyst. (Reset terminals shorted) . Manual Reset: Cycle power off & on or momentarily short Reset terminals with N.O. momentary switch (customer supplied). . Set Point Range: 0 to 600oF Setpoint Adj.: Local SP pot with dual oF/oC graduated scales Sensor Type: “J” Thermocouple Compensation: Automatic cold junction compensation Control Stability: Typically better than ±5mV/oF ambient and .01% of span/% rated line voltage Set Point Accuracy: ±3% of FS maximum at 25oC and rated line voltage Sensor Failure Prot: Contacts open for thermocouple break Amb. Oper. Temp: 0 to 55oC (32 to 131oF )
MECHANICAL Enclosure Material: Noryl, Black color Field Terminations: Screw termininals with wire clamping plates and touch safe shield. Mounting: 35mm DIN rail and surface mounting base
AGENCY APPROVALS UL 873 & CUL per CSA C22.2 No. 24 File #E105669
DIMENSIONS:
3.30”
2.50”
Horz. Panel
Mtg. Centers
Temperature
Controller
120L
US
C
1
2 3 4 5 6 7 8 9
N.C.
L1 L2
115VAC 50/60Hz
Input Volts
LTR DESCRIPTION DATE
COM
N.O.
Relay
Output
- +
TC
Sensor
Scale shown for reference only. Actual scale graduations depend on SP range above.
Set Point
Adjust
2.53”
.387”
2.75” Max.
35mm
DIN Rail
3.00”
Vert. Panel
Mtg.Centers
ZYTRON CONTROL PRODUCTS, INC. 20 Lexington Ave. , Trenton, NJ 08618
Page 18
Page 19
1
Instruction Bulletin
Boletín de instrucciones
Directives d'utilisation
39000-285-01D
01/2005
Huntington, IN USA
Industrial Control Transformer Transformador de control industrial Transformateur de contrôle industriel
Replaces / Reemplaza / Remplace 39000-285-01C 02/1997
Class Clase Classe
Type Tipo Type
9070 T, TF
Retain for future use. / Conservar para uso futuro. / À conserver pour usage ultérieur.
*
RECEIVING RECIBO RÉCEPTION
Inspect the transformer for damage. If damaged, notify and file a claim with the carrier. Contact the supplier for repair or replacement.
Realice una inspección visual del transformador para ver si encuentra daños. Si ha encontrado daños, notifique a la compañía de transportes y presente una reclamación. Comuníquese con el proveedor para obtener detalles sobre la reparación o sustitución del equipo.
Inspecter le transformateur pour rechercher les dommages. En cas de dommage, prière d’aviser l’entreprise de transport et de faire une déclaration auprès de celle-ci. Contacter le fournisseur pour les réparations ou le remplacement.
PRECAUTIONS PRECAUCIONES PRÉCAUTIONS
1. On the nameplate, verify that the transformer kVA and voltage are correct for the line and load.
1. Consulte la placa de datos y verifique que los kVA y tensión del transformador sean los correctos para la línea y carga.
1. Sur la plaque signalétique, vérifier si les kVA et la tension du transf ormateur sont corrects pour la ligne et la charge.
Continued on next page Continúa en la siguiente página Page suivante
DANGER / PELIGRO / DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
• This equipment must only be installed and serviced by qualified electrical personnel in accordance with the National Electrical Code® (NEC®) and any other applicable codes or standards.
• Turn off all power supplying this equipment before working on or inside equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this equipment.
PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARQUEO
• Utilice equipo de protección personal (EPP) apropiado y siga las prácticas de seguridad eléctrica establecidas por su Compañía, consulte la norma 70E de NFPA.
• Solamente el personal eléctrico especializado deberá instala r y prestar servicio de mantenimiento a este equipo de acuerdo con las normas del Código nacional eléctrico de los EUA (NEC
®
) o NOM-001-SEDE así como con cualquier otra norma y código local correspondiente.
• Desenergice el equipo antes de realizar cualquier trabajo en él.
• Siempre utilice un dispositivo detector de tensión nominal adecuado para confirmar la desenergización del equipo.
• Vuelva a colocar todos los dispositivos, las puertas y las cubiertas antes de volver a energizar el equipo.
RISQUE D'ÉLECTROCUTION, D'EXPLOSION OU D'ÉCLAIR D'ARC
• Portez un équipement de protection personnelle (ÉPP) approprié et observez les méthodes de travail électrique sécuritaire. Voir NFPA 70E.
• Seul un personnel qualifié doit effectuer l'installation et l'entretien de cet appareil conformément au Code National de l’Électricité (NEC
®
; É.-U.) et tout autre
code et norme applicables.
• Coupez l'alimentation de l'appareil avant d'y travailler.
• Utilisez toujours un dispositif de détection de tension ayant une valeur nominale appropriée pour s'assurer que l'alimentation est coupée.
• Replacez tous les dispositifs, les portes et les couvercles avant de mettre l'appareil sous tension.
Failure to follow these instructions will result in death or serious injury.
El incumplimiento de estas instrucciones podrá causar la muerte o lesiones serias.
Si ces directives ne sont pas respectées, cela entraînera la mort ou des blessures graves.
Page 20
Industrial Control Transformer Transformador de control industrial 39000-285-01D Transformateur de contrôle industriel 01/2005
© 1997–2005 Schneider Electric All Rights Reserved / Reservados todos los derechos / Tous droits réservés2
2. Install the transformer only in a well-ventilated area that is free from explosive or corrosive gases, vapor, or excessive dust, dirt, and moisture.
2. Instale el transformador sólo en un área bien ventilada libre de gases e xplosivos y corrosivos, va por o de masia do polvo, suciedad y humedad.
2. Installer le transformateur seulement dans une zone bien ventilée, dépourvue de gaz ou de vapeur explosif ou corrodant, ou de poussière, de saletés et d’humidité excessives.
3. Ensure a free flow of air around the transformer. Do not exceed surrounding air temperature of 40° C (104° F).
3. Asegúrese de que circule el aire alrededor del transformador y de que no exceda la temperatura ambiente de 40° C (104° F).
3. Assurer une circulation libre de l’air autour du transformateur. Ne pas dépasser une température ambiante de 40° C (104° F).
4. Use sufficient mounting hardware to support the weight of the transformer.
4. Utilice suficiente herrajes de montaje para soportar el peso del transformador.
4. Utiliser la quincaillerie de montage suffisante pour supporter le poids du transformateur.
PROTECTION PROTECCIÓN PROTECTION
Use fuses or circuit breakers in accordance with Article 450 of the National Electrical Code
®
(NEC®) and any other applicable codes and standards.
Utilice los fusibles o interruptores automáticos necesarios para cumplir con los requisitos del artículo 450 del Código nacional eléctrico de EUA (NEC®) o NOM-001-SEDE así como con otras normas y códigos locales correspondientes.
Utiliser les fusibles ou les disjoncteurs conformément à l’article 450 du Code national de l'électricité (NEC
®
; É.-U.) et à
tout autre code ou norme applicable.
— For Type TF fusing, use only
Class CC rejection fuses on the primary .
— Para la unidades tipo TF, utilice
sólo fusibles de rechazo clase CC en el primario.
— Pour les unité s type T F, utiliser
uniquement des fusibles class CC avec dispositif de rejet sur le primaire.
— If high voltage transients are
possible, use appropriate surge suppression.
— Utilice supresores de transitorios
apropiados si existe la posibilidad de sobretensiones transitorias.
— Si des tensions transitoires élevées
sont possibles, utiliser une suppression de surtension appropriée.
ACCESSORIES ACCESORIOS ACCESSOIRES
To meet European Normalized (EN) Standards, use terminal covers (not included). Refer to the transformer section in the Schneider Electric Digest, and call 1-888-778-2733 for accessory information.
Para cumplir con las normas europeas (EN), utilice las cubiertas de terminales (no provistas). Consulte la sección de transformadores en el Compendiado de Schneider Electric y llame al 1-888-778-2733 (en los EUA) para obtener información sobre los accesorios.
Pour satisfaire aux normes européennes (NE), utiliser des couvercles de bornes (non fournis). Se reporter à la section des transformateurs dans le Digest Schneider Electric, et appeler le 1-888-778-2733 (É.-U.) pour obtenir des informations concernant les accessoires.
CONNECTION AND INSTALLATION CONEXIÓN E INSTALACIÓN CONNEXION ET INSTALLATION
DANGER / PELIGRO / DANGER
HAZARDOUS VOLTAGE
Turn off power before installing or servicing.
TENSIÓN PELIGROSA
Desconecte la alimentación antes de instalar o prestarle servicio.
TENSION DANGEREUSE
Coupez l’alimentation avant d’installer ou de procéder à l’entretien.
Failure to follow this instruction will result in death or serious injury.
El incumplimiento de esta instrucción podrá causar la muerte o lesiones serias.
Si cette directive n’est pas respectée, cela entraînera la mort ou des blessures graves.
Page 21
Industrial Control Transformer 39000-285-01D Transformador de control industrial 01/2005 Transformateur de contrôle industriel
© 1997–2005 Schneider Electric All Rights Reserved / Reservados todos los derechos / T ous droits réservés
3
1. If necessary, install jumpers to
obtain input and/or output voltages. If windings are tapped, do not use jumpers.
1. Si es necesario, instale puentes de conexión para obtener tensiones de entrada y/o salida. Si los devanados tienen derivaciones, no utilice puentes de conexión.
1. Si nécessaire, installer des cavaliers pour obtenir les tensions d’entrée ou de sortie. Si les enroulements sont munis de prises, ne pas utiliser de cavaliers.
— Figure 1 on page 4 shows a
typical parallel connection to obtain the lower of the two possible voltages. On the primary side, connect one jumper to H1 and H3 and one to H2 and H4. On the secondary side, connect one jumper to X2 and X4 and one to X1 and X3.
— La figura 1 en la página 4 muestra
una conexión paralela típica par a obtener la tensión más baja posible de las dos. En el lado del primario, conecte un puente a H1 y H3 y el otro puente a H2 y H4. En el lado del secundario, conecte un puente a X2 y X4 y el otro puente a X1 y X3.
— La figure 1 à la page 4 indique la
connexion parallèle typique pour obtenir la tension la plus faible des deux tensions possibles. Sur le côté primaire, connecter un cavalier entre H1 et H3 et un autre entre H2 et H4. Sur le côté secondaire, connecter un cavalier entre X2 et X4 et un autre entre X1 et X3.
— Figure 2 on page 4 shows
typical series connection to obtain the higher of the two possible voltages. On primary side, connect both jumpers to H2 and H3. On secondary side, connect both jumpers to X2 and X3. See the nameplate wiring diagram for connections.
— La figura 2 en la página 4 muestra
una conexión en serie típica para obtener la tensión más alta posible de las dos. En el lado del primario, conecte ambos puentes a H2 y H3. En el lado del secundario, conecte ambos puentes a X2 y X3. Consulte el diagrama de alambrado en la placa de datos para realizar las conexiones.
— La figure 2 à la page 4 indique la
connexion en série typique pour obtenir la tension la plus élevée des deux tensions possibles. Sur le côté primaire, connecter les deux cavaliers entre H 2 et H3 . Sur le côté secondaire, connecter les deux cavaliers entre X2 et X3. Voir le schéma de câblage de la plaque signalétique pour obtenir les connexions.
2. Connect only the primary according to the nameplate wiring diagram (A).
2. Conecte solamente el primario según el diagrama de alambrado en la placa de datos (A).
2. Connecter seulement le primaire conformément au schéma de câblage de la plaque signalétique (A).
3. Energize the transformer. Measure the secondary voltage to ensure transformer voltages are correct for the load.
3. Energice el transformador. Mida la tensión secundaria y asegúrese de que las tensiones del transformador sean las correctas para la carga.
3. Mettre le transformateur sous tension. Mesurer la tension secondaire pour s’assurer que les tensions du transformateur correspondent à la charge.
4. Turn off the primary supply, and connect the load to the secondary terminals (B). All terminals are not always used. See the nameplate wiring diagram.
4. Desconecte la fuente de alimentación del primario y conecte la carga a las terminales del secundario (B). No siempre se usan todas las terminales. Consulte el diagrama de alambrado en la placa de datos.
4. Couper l’alimentation primaire et connecter la charge aux bornes secondaires (B). Les bornes ne sont pas toujours toutes utilisées. Voir le schéma de câblage de la plaque signalétique.
5. Tighten all unused screws. Torque the remaining screws as follows:
5. Apriete todos los tornillos sin usar. Apriete el resto de los tornillos de la siguiente manera:
5. Serrer toutes les vis non utilisées. Serrer les autres vis aux couples suivants :
— 6–32 screw
7–9 lbs-in (0.8–1.0 N•m)
— Tornillo 6–32
0,8–1,0 N•m (7–9 lbs-pulg)
— Vis 6–32
0,8 à 1,0 N•m (7 à 9 lb-po)
— 8–32 screw
14–16 lb-in (1.6–1.8 N•m)
— Tornillo 8–32
1,6–1,8 N•m (14–16 lbs-pulg)
— Vis 8–32
1,6 à 1,8 N•m (14 à 16 lb-po)
— 10–24 screw
17–19 lb-in (1.9–2.2 N•m)
— Tornillo 10–24
1,9–2,2 N•m (17–19 lbs-pulg)
— Vis 10–24
1,9 à 2,2 N•m (17 à 19 lb-po)
6. If applicable, install the covers. 6. Si fuese aplicable, instale las cubiertas. 6. Le cas échéant, inst al ler les cou vercles.
7. Energize the transformer. 7. Energice el transformador. 7. Mettre le transformateur sous tension.
Page 22
Industrial Control Transformer Transformador de control industrial 39000-285-01D Transformateur de contrôle industriel 01/2005
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for an y con seq uen ces arising out of the use of this material.
Solamente el personal especializado deberá instalar, hacer funcionar y prestar servicios de mantenimiento al equipo eléctrico. Schneider Electric no asume responsabilidad alguna por las consecuencias emergentes de la utilización de este material.
Seul un personnel qualifié doit effectuer l’installation, l’utilisation, l’entretien et la maintenance du matériel électrique. Schneider Electric n’assume aucune responsabilité des conséquences éventuelles découlant de l’utilisation de cette documentation.
Schneider Electric USA 6 Commercial Road Huntington, IN 46750 USA 1-888-SquareD (1-888-778-2733) www.us.SquareD.com
Importado en México por: Schneider Electric México, S.A. de C.V. Calz. J. Rojo Gómez 1121-A Col. Gpe. del Moral 09300 México, D.F. Tel. 55-5804-5000 www.schneider-electric.com.mx
Schneider Electric Canada 19 Waterman Avenue, M4B 1 Y2 Toronto, Ontario 1-800-565-6699 www.schneider-electric.ca
© 1997–2005 Schneider Electric
All Rights Reserved / Reservados todos los derechos / Tous droi ts réservés
* a brand of Schneider Electric. / una marca de Schneider Electric. /
une marque de Schneider Electric.
MAINTENANCE SERVICIO DE MANTENIMIENTO ENTRETIEN
1. De-energize the transformer. 1. Desenergice el transformador. 1. Mettre le transformateur hors tension.
2. Check for loose connections and wiring, or lead deterioration. Tighten, insulate, or replace where necessary.
2. Realice una inspección para ver si encuentra conexiones y cables sueltos, o conductores dañados. Apriete las conexiones, aísle o reemplace los ca bles o conductores que sean necesarios.
2. Rechercher les connexions et les câbles desserrés, ou les conducteurs endommagés. Serrer les connexions, isoler ou remplacer les câbles ou conducteurs lorsque nécessaire.
Figure / Figura / Figure 1 : Typical parallel connection /
Conexión paralela típica / Connexion parallèle typique
Figure / Figura / Figure 2 : Typical series connection /
Conexión en serie típica / Connexion en série typique
H1
X4
X2
X3
X1
H3
H2
H4
H1-H3
H2-H4
X2-X4
X1-X3
B
A
H1
H
3
X4
X2
UL/CSA
50/60 Hz
0.25 kVA
9070T250D31
EN
61558
50/60 Hz
0.16 kVA
C
L
O
C
K
D
A
T
E
C
L
AS
S
/
C
L
ASE/C
L
AS
SE 130
˚C
H
1
X2
X1
H
3
H
2
H
4
X4
X3
T
250D
31
H
2
H4
X3
X1
220 230 240
440 460 480
H
1
H
3 H2 H4
H1 H3 H2 H4
X
2
X
4
X3
X1
11
0 115
1
2
0
X2
X
4
X3
X1
220 230 240
H1
X4
X2
X3
X1
H3
H2
H4
X2-X3
H2-H3
B
H1
H3
X4
X2
UL/CSA
50/60 Hz
0.25 kVA
9070T250D31
EN 6155
8
50/60 Hz
0.16 kVA
C
L
O
C
K
D
A
T
E
C
L
AS
S
/
C
L
ASE/C
L
AS
S
E 130
˚C
H
1
X2
X
1
H
3
H
2
H
4
X4
X3
H2
H4
X3
X1
220 230 240
440
4
60
480
H
1
H3
H
2
H4
H1 H3 H2 H4
X2
X
4
X3
X1
110 115
1
2
0
X2
X
4
X3
X1
220
230 240
T
250D
31
A
Page 23
Notes
7
Page 24
8
Loading...