This manual contains notices which you should observe to ensure your own personal safety, as well
as to protect the product and connected equipment. These notices are highlighted in the manual by a
warning sign and are marked as follows according to the level of danger:
documentation or the correct functioning of the product.
Warning
This device and its components may only be used for the applications described in this manual and
only in connection with devices or components that comply with PROFIBUS and an RS 485 interface.
This product can only function correctly and safely if it is transported, stored, set up, installed,
operated and maintained as recommended.
Qualified Technicians
Only qualified technicians should be allowed to install and work with this equipment. Qualified
technicians are defined as persons who are authorized to commission, to ground, to tag circuits and
systems in accordance with established safety practices and standards. It is recommended that the
technicians carry a Certified PROFIBUS Installer or Certified PROFIBUS Engineer certificate.
Disclaimer of Liability
We have checked the contents of this manual as much as possible. Since deviations cannot be
precluded entirely, we cannot guarantee full agreement. However, the content in this manual is
reviewed regularly and any necessary corrections included in subsequent editions. Suggestions for
improvement are welcomed.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted, in any form or by any means, electronic, mechanical, photocopying, recording or
otherwise, without the prior written permission of the publisher.
Draws your attention to important information on handling the product, a particular part of the
This manual explains how to put the ProfiHub A5 and ProfiHub B5 into operation.
Recycling and Disposal
The parts of the ProfiHub can be recycled. For further information about environment-friendly recycling
and the procedure for disposing your old equipment, please contact:
PROCENTEC
Klopperman 16
2292 JD WATERINGEN
The Netherlands
You can obtain constantly updated information on PROCENTEC products on the Internet at
www.procentec.com
You can also contact PROCENTEC Customer Support:
ProfiHub A5 and B5 are advanced, flexible
and robust network components for
PROFIBUS DP installations, to implement
long multi-device spur lines and backbone
structures with star/tree segments.
PROFIBUS DP is a high speed communication
bus that has to comply with strict rules
concerning spur lines, because of possible
reflections that could lead to communication
disturbances. If spur lines or star segments are
required, costly investments in repeaters have
to be done.
Innovative components for such applications are
the ProfiHub A5 and B5. These are perfect
economic solutions to implement reliable spur
lines in high speed DP networks. They have the
functionality of 5 galvanic isolated transparent repeaters. This allows network structures with
extended spur lines that individually can handle a
maximum of 31 devices and a length equal to the
main bus. The ProfiHub A5 and B5 refresh a
received message on one Channel and
transfer it to all the other Channels (chicken
foot topology).
Because the ProfiHub A5 and B5 create isolated
segments, the devices can now be removed and
added during operation. Also electrical bus
problems and EMC disturbances in a spur do not
spread to the other segments. The intelligent
logic and isolation circuits of the ProfiHubs do not
change the bit width. This means the ProfiHubs
do not have limitations in serial placement. The
logic also detects the transmission speed
automatically.
To assist the installation work, termination is
integrated and can be switched on/off. The
grounding concept is also selectable: direct or
capacitive grounding. The ProfiHubs are powered by a 10 to 32 DC Voltage (110/230V AC versions
are also available). For troubleshooting, maintenance and commissioning the ProfiHubs are equipped
with a display on the outside, which indicate the status of each Channel (Data and Error).
Fig. 3 - Long spur lines to instruments and the possibility to remove/insert them during
operation. Short circuit protection on each spur line is automatically provided.
1.1 Product Features
5 Galvanic isolated channels (repeater
segments).
Transparent for all PROFIBUS DP
protocols.
DP - RS 485 specifications for each
channel.
9,6 Kbps to 12 Mbps.
31 devices per channel.
1200 m spur line length (depends on
transmission speed).
No limit in serial placement or cascading of
ProfiHubs.
ProfiHub A5/B5 User Manual
No address required.
Integrated termination facilities (switches).
Configurable grounding system (direct or capacitive).
IP 65 classification (ProfiHub A5).
IP 20 classification (ProfiHub B5).
Fig. 4 - Because of the isolation and intelligence the ProfiHub provides, it can be used as
a barrier for electrically sensitive segments. This keeps the backbone and other
ProfiHub A5/B5 User Manual
1.2 Application areas
Dynamic spur lines to actuators, flow meters and pH analyzers.
Removable drives and motors.
Pull/Plug motor control centers (drawers).
Roof mounted devices in tank farms.
Dirty and humid environments.
Barrier for non galvanic isolated equipment.
Large star/tree structured networks.
Outdoor applications with device and cable stress (ProfiHub A5).
1.3 Additional Benefits
Hot slave insertion and removal during operation.
Short circuit protection on each Channel.
Compact and robust construction.
Status and error display (per Channel).
Suitable for all DP cables.
Conveniently arranged networks.
Easy extendable installations.
Standard glands can be replaced with M12 (ProfiHub A5).
On-board DB9 female connector for maintenance activities (ProfiHub A5).
Cost Savings.
Every Channel is electrically isolated and internally connected to the transparent intelligent backbone.
The termination is switchable and powered by the ProfiHub. The shielding of the PROFIBUS cable can
be directly grounded or indirectly grounded (see the next paragraph).
1.5 Grounding System
The ProfiHubs can be grounded by 3 methods:
1) Direct grounding
2) Indirect grounding (through a capacitor)
3) Combination of direct and indirect.
In most cases it is recommended always to use Direct Grounding with the power supply and the
shielding of the PROFIBUS cables. If you do not want to ground all or some cables to the common
ground, the cable shielding should be connected to pin ‘I’. A capacitor with a parallel high value
resistor will separate the 2 potentials (Fig. 5).
If by accident on 1 channel the Direct Grounding is connected with the Indirect Grounding, the Direct
Grounding “wins”.
Saksa Automaatika OUT: +372 605 2526
Peterburi Tee 49 F: +372 605 2524
Tailinn E:
in
fo@saksa-automaatika.ee
EE-11415 Estonia I: www.saksa-automaatika.ee
FINLAND
Hantekno Oy T: +358 40 8222 014
Kalliotie 2 E:
in
fo@hantekno.com
04360 Tuusula I: www.hantekno.fi
Finland
FRANCE
AGILiCOM T: +33 247 76 10 20
Bâtiment B F: +33 247 37 95 54
1, rue de la Briaudière E:
jy
.bois@agilicom.fr
Z.A. La Châtaigneraie I: www.agilicom.fr
37510 BALLAN-MIRE
France
INDIA
UL Engineering Services & Software Pvt Ltd T: +91-202 696 0050
Nirman Classic, F: +91-202 696 2079
Katraj-Kondhwa Road, E:
di
leep.miskin@ulepl.com
Katraj, Pune-411046 I: www.ulepl.com
India
IRELAND
PROFIBUS Ireland T: +353-61-202107 or +35361240240
Automation Research Centre F: +353-61-202582
University of Limerick E:
in
fo@profibus.ie
National Technology Park, Plassey I: www.profibus.ie
Limerick
Ireland
ISRAEL
Instrumetrics Industrial Control T: +972-9-8357090
8 Hamlacha St. F: +972-9-8350619
New Industrial Zone E:
in
fo@instrumetrics-ic.co.il
Netanya, 42170 I: www.inst-ic.co.il
Israel
ITALY
PROCENTEC Italy T: +39 030 200 8610
Via Branze n. 43/45 F: +39 030 238 0059
25123 Brescia E:
w
Genoa FIELDBUS Competence Centre Srl T: +39 010 86 02 580
Via Greto di Cornigliano, 6R/38 F: +39 010 65 63 233
16152 Genova E:
p
rocentec@gfcc.it
Italy
W:
w
ww.gfcc.it
JAPAN
TJ Group T: +81-3-6450-3739
C/O Japanese PROFIBUS Organisation F: +81-3-6450-3739
West World Building 4F E:
in
fo@profibus.jp
3-1-6 Higashi-Gotanda,
Shinagawa-ku,
Tokyo, 141-0022
Japan
KOREA
Hi-PRO Tech. Co., Ltd. T: +82 82-31-216-2640
#2802, U-Tower, 1029 F: +82 82-31-216-2644
Youngduk-dong, Giheung-gu E:
c
hays@hiprotech.co.kr
Yongin-Si, Kyunggi-do, I: www.profibus.co.kr
446-908 Korea
Jr. Los Silicios 5409 F: +51 1528 0454
Los Olivos - L39 E:
in
fo@controlware.com.pe
Peru I: www.controlware.com.pe
POLAND
INTEX Sp. z o.o. T: +48 32 230 75 16
ul. Portowa 4 F: +48 32 230 75 17
44-102 Gliwice E:
in
tex@intex.com.pl
Poland I: www.intex.com.pl
ROMANIA
S.C. SVT Electronics S.R.L. T: +40 365 809 305
Brǎila 7F: +40 365 809 305
540331 Tg-Mure E:
s
ajgo.tibor@svt.ro
Romania I: www.svt.ro
SAUDI ARABIA
ASM Process Automation T: +966 2 691 2741
Al-Zahra Dist. – Attas st. F: +966 2 682 8943
cross section with helmy Kutby St. E:
in
fo@asmestablishment.com
Villa no.25 I: www.asmestablishment.com
Jeddah-21553
Saudi Arabia
SINGAPORE / SOUTH EAST ASIA
Allegro Electronics T: +65 62878063
IRELAND
PROFIBUS Ireland T: +353-61-202107 or +35361240240
Automation Research Centre F: +353-61-202582
University of Limerick E:
in
fo@profibus.ie
National Technology Park, Plassey I: www.profibus.ie
Limerick
Ireland
ISRAEL
Instrumetrics Industrial Control T: +972-9-8357090
8 Hamlacha St. F: +972-9-8350619
New Industrial Zone E:
in
fo@instrumetrics-ic.co.il
Netanya, 42170 I: www.inst-ic.co.il
Israel
ITALY
PROCENTEC Italy T: +39 030 200 8610
Via Branze n. 43/45 F: +39 030 238 0059
25123 Brescia E:
w
ww.procentec.it
Italy
W:
w
ww.procentec.it
Genoa FIELDBUS Competence Centre Srl T: +39 010 86 02 580
Via Greto di Cornigliano, 6R/38 F: +39 010 65 63 233
16152 Genova E:
p
rocentec@gfcc.it
Italy
W:
w
ww.gfcc.it
JAPAN
TJ Group T: +81-3-6450-3739
C/O Japanese PROFIBUS Organisation F: +81-3-6450-3739
West World Building 4F E:
in
fo@profibus.jp
3-1-6 Higashi-Gotanda,
Shinagawa-ku,
Tokyo, 141-0022
Japan
KOREA
Hi-PRO Tech. Co., Ltd. T: +82 82-31-216-2640
#2802, U-Tower, 1029 F: +82 82-31-216-2644
Youngduk-dong, Giheung-gu E:
c
hays@hiprotech.co.kr
Yongin-Si, Kyunggi-do, I: www.profibus.co.kr
446-908 Korea
The ProfiHub A5 can be installed everywhere in a non-hazardous area that complies with IP 65 (DIN
40 050) and the specified temperature range of -40 to +75o Celsius.
4.2 Position
The ProfiHub A5 can be installed in every position, but it is recommended to install it with the cable
glands pointing down to create a more reliable protection against moist and dust (water compartment
and glands). In this position it is also easier to read the status display.
4.3 Mounting
The ProfiHub A5 has 4 mounting holes for 4..5 mm screws (Fig. 9). To reach the holes on position 1
and 2, the top lid has to be removed.
screws/bolts in position 1, 2, 3 and 4.
2) Be careful with the flat cable that connects the lid with the PCB.
Connect the DP backbone cable to the bottom connector of the Main-Channel (Fig. 11). If the ProfiHub
is not the last device on the bus segment, connect the Bus-Out cable to the top connector of the MainChannel (Fig. 11).
Pin Layout of the screw terminals
Pin “A”: Green wire
Pin “B”: Red wire
Pin “I”: Cable shielding OR
Pin “ ”: Cable shielding
Testing
- If the Main-Channel recognizes valid PROFIBUS messages from 1 or more connected devices, the
RX-OK LED of this Channel should be blinking.
The termination of the Main-Channel has been set to OFF by default. If the ProfiHub is the last/first
device on the segment, the termination should be set to ON (Fig. 13).
The termination of the Channels have been set to ON by default. Because it is assumed that the new
segment is started at the ProfiHub (Fig. 13).
powered continuously.
Don’t forget to switch the termination ON at the other end of the segment and make sure it is
The ProfiHub recognizes the transmission speed by default. If it is required that the ProfiHub is locked
to a certain transmission speed, switch S100 should be set to the required value (Fig. 14). The switch
can be reached by removing the top lid.
To set the transmission speed, you need a 3 mm screwdriver.
Switch values:
The ProfiHub B5 can be installed everywhere in a non-hazardous area that complies with IP 20 (DIN
40 050) and the specified temperature range of -20 to +60o Celsius.
5.2 Position
The ProfiHub B5 can be installed in every position, but it is recommended to install it with the cables
pointing down. In this position it is also easier to read the status display.
5.3 Mounting
The ProfiHub B5 has to be mounted on 35 mm DIN-rail with a minimum width of 167 mm.
5.4 Power Supply
The 3-pin screw type power connector is located on the bottom left of the ProfiHub B5 (Fig. 15).
1 = + (left)
2 = - (middle)
3 = Indirect grounding (right)
The power supply has to comply with the following specifications:
Procedure
To connect the 24V supply to the 3-pin screw-type terminal, proceed as follows:
- Strip the insulation from the cable or the conductors for the 24V power supply.
- Secure the conductors in the screw-type terminal.
Note: There is a grounding point that can be used.
To connect the power supply, you need a 3 mm screwdriver.
Testing
If the power is switched on it can be diagnosed by the following indicators:
- All the LEDs should be shortly blinking.
- The POWER LED is ON.
- The READY LED is ON or Blinking.
It is recommended to use a power supply with a ground lead (3-wire).
5.5 Backbone
Connect the DP backbone cable to the bottom-left connector of the Main-Channel (Fig. 16). If the
ProfiHub is not the last device on the bus segment, connect the Bus-Out cable to the right connector
of the Main-Channel (Fig. 16). The second method is to place a PROFIBUS standardized plug with an
in/out cable on the DB9 connector.
Pin layout of the screw terminals:
Pin “A”: Green wire
Pin “B”: Red wire
Pin “I”: Cable shielding OR
Pin “ ”: Cable shielding
- If the Main-Channel recognizes valid PROFIBUS messages from 1 or more connected devices, the
RX-OK LED of this Channel should be blinking.
5.6 Spur Segments
Connect the spur segments to the connectors of Channel 1 to 5 (Fig. 17). The second method is to
place a PROFIBUS standardized plug on the DB9 connector of the specific Channel.
Pin layout of the screw terminals:
Pin “A”: Green wire
Pin “B”: Red wire
Pin “I” or “Ground”: Cable shielding
Note: Connecting the cable shielding is not required when the ground clips are used.
Testing
- If the Main-Channel recognizes valid PROFIBUS messages from 1 or more connected devices, the
RX-OK LED should be blinking.
The termination of the Main-Channel has been set to OFF by default. If the ProfiHub is the last device
on the bus, the termination should be set to ON (Fig. 18).
The termination of the Channels have been set to ON by default. Because it is assumed that the new
segment is started at the ProfiHub (Fig. 18).
The termination LED of the specific Channel is activated when the termination switch is set to ON.
use the termination on the DB9 plug and NOT the ProfiHub.
When the DB9 connector is used and the cable starts at the ProfiHub, it is recommended to
The ProfiHub B5 recognizes the transmission speed by default. If it is required that the ProfiHub B5 is
locked to a certain transmission speed, the baudrate switch should be set to the required value (Fig.
19).
To set the transmission speed, you need a 3 mm screwdriver.
Switch values:
IRELAND
PROFIBUS Ireland T: +353-61-202107 or +35361240240
Automation Research Centre F: +353-61-202582
University of Limerick E: info@profibus.ie
National Technology Park, Plassey I: www.profibus.ie
Limerick
Ireland
ISRAEL
Instrumetrics Industrial Control T: +972-9-8357090
8 Hamlacha St. F: +972-9-8350619
New Industrial Zone E: info@instrumetrics-ic.co.il
Netanya, 42170 I: www.inst-ic.co.il
Israel
ITALY
PROCENTEC Italy T: +39 030 200 8610
Via Branze n. 43/45 F: +39 030 238 0059
25123 Brescia E: www.procentec.it
Italy W: www.procentec.it
Genoa FIELDBUS Competence Centre Srl T: +39 010 86 02 580
Via Greto di Cornigliano, 6R/38 F: +39 010 65 63 233
16152 Genova E: procentec@gfcc.it
Italy W: www.gfcc.it
JAPAN
TJ Group T: +81-3-6450-3739
C/O Japanese PROFIBUS Organisation F: +81-3-6450-3739
West World Building 4F E: info@profibus.jp
3-1-6 Higashi-Gotanda,
Shinagawa-ku,
Tokyo, 141-0022
Japan
KOREA
Hi-PRO Tech. Co., Ltd. T: +82 82-31-216-2640
SAUDI ARABIA
ASM Process Automation T: +966 2 691 2741
Al-Zahra Dist. – Attas st. F: +966 2 682 8943
cross section with helmy Kutby St. E: info@asmestablishment.com
Villa no.25 I: www.asmestablishment.com
Jeddah-21553
Saudi Arabia
SINGAPORE / SOUTH EAST ASIA
Allegro Electronics T: +65 62878063
The ground rail has to be mounted inside the casing to
supply a common grounding area for all cable
shielding. It improves the EMC behaviour and it
supplies a good construction for vibrations. Not useable
for capacitive grounding!
Unique number of a device connected to the network. With PROFIBUS this
can be 0 to 126. 127 is a broadcast address.
Analyzer
Software tool to observe the protocol traffic. Combi-Analyzers can also
inspect the signal quality.
Other term: Bus Monitor.
Example: ProfiTrace.
Backbone
The primary bus cable. Most of the time only the control systems, ProfiHubs
and fiber optic couplers are connected to this cable. The field devices are
connected behind the ProfiHubs and fiber optic couplers.
Bit Time (TBit)
The bit time TBit is the time, which elapses during the transmission of one
bit. It depends on the baudrate and is calculated as follows TBit = 1 (bit) /
baudrate (bps).
Examples:
12 Mbps --> TBit = 83 ns
1,5 Mbps --> TBit = 667 ns
Busparameters
Settings that define the timing behaviour on the bus. They are defined in the
master. Examples: Tslot, MaxTSDR.
C
Capacitance.
DGND
Digital Ground.
DIN
German Institute for Standardization (www.din.de).
DP-V0
DP-V0 is the basic stage of the PROFIBUS DP communication protocol. DPV0 devices (master and slaves) perform the following basic functionalities:
- Cyclic exchange of I/O data between controlling and slave devices
- Device, Identifier (module) and Channel related Diagnosis
- Parameterization of DP-slaves
- Configuration of DP-slaves
DP-V1
DP-V1 is the first stage of extension of PROFIBUS DP after DP-V0. DP-V1
devices shall comply with the following features:
- Device related diagnosis is replaced by status and alarms.
- The first three octets of the user parameterization data are now
standardized
DP-V2 is the second stage of extension of PROFIBUS DP after DP-V1. DPV2 devices shall comply with the following features:
- Data Exchange Broadcast (DxB) for slave to slave communication
(publisher/subscriber principle).
- Isochronous Mode (time tick synchronized operating slaves, e.g. drives)
- Up- and/or download of Load Region Data (domains)
- Clock Control (synchronization within slaves) and Time Stamping
- Redundancy.
Electromagnetic
Compatibility
See EMC.
EMC
The extent to which an electric or electronic device will tolerate electrical
interference from other equipment (immunity), and will interfere with other
equipment. Within the European Community as well as in other countries it is
regulated by law that electric and electronic components and equipment
comply with basic standards such as IEC 61000-6-2 or IEC 61326 or
corresponding individual product standards.
Hub
A Hub refreshes a signal and passes the information on to all nodes which
are connected to the Hub. Data frames which were received on one port are
transferred to all the other ports (chicken foot topology).
MPI
Multiple Protocol Interface. Protocol defined by Siemens which uses the
layer 1 and 2 of PROFIBUS (FDL).
PCB
Printed Circuit Board.
PROFIBUS DP
Acronym for "PROFIBUS for Decentralized Peripherals". Specification of an
open fieldbus system with the following characteristics:
- Flying masters with robin round token passing coordination (MM)
- Connection based (MS1) and connectionless (MS2, MS3) acyclic
communication between masters and slaves
Options (e.g.):
- Data exchange broadcast (DXB), i.e. slave to slaves communication
- Isochronous mode of slaves
- Clock synchronization
- Redundancy
PROFIBUS DP is standardized within IEC 61158 and IEC 61784,
communication profile families 3/1 and 3/2
The term "PROFIBUS DP" also is a synonym for the RS485 based
deployments within factory automation.
Repeater
Active physical layer device that receives and retransmits all signals over a
different port to increase the distance and number of devices for which
signals can be correctly transferred for a given medium.
Spur line
A cable attached to a bus segment with a T-connection . Spurs are not
recommended with PROFIBUS DP. They are prohibited with 12 Mbps and
PROFIsafe operations. German term is "Stichleitung".
Suitable for 4- and 8-wire PROFINET and regular Ethernet
cables.
Suitable for straight and 90°, metal or plastic PROFINET
plugs.
Tests cable shielding!
Detects short circuits, wire breaks, swaps, miswiring and
split pairs.
Large LCD clearly indicates the test results.
150 hours on one 9 V battery.
Operating temperature: 0 to 50 °C.
Just 1-key-press to start continuous testing.
It can also test telephone and coax cable.
www.profinetcabletester.com
Compact PROFIBUS Repeater
Single channel PROFIBUS repeater.
Transparent.
Latest RS 485 technology.
Max. 12 Mbps.
Auto baudrate detection.
Redundant power supply.
Digital glitch filtering.
No limit in cascading.
Integrated switchable termination.
Diagnostic LEDs.
DB9 connector for measurements.
IP 20 with DIN-rail mounting.
www.procentec.com/profihub/b1/en