Primus D11, D15, D13 Service Manual

Page 1
SERVICE MANUAL INDUSTRIAL DRYERS PUBLICATION DATE: 12/03 70284701
D11, 13, 15
Page 2
Page 3
Section 1 – Safety Information
Locating an authorized service person.....................4
Section 2 – Introduction
Model identification.................................................5
Serial plate location..................................................6
Parts ordering information .......................................6
Wiring diagram ........................................................6
How a tumbler works...............................................7
Section 3 – Troubleshooting
1. Tumbler does not start.......................................9
2. Motor does not start...........................................9
3. Motor overload protector cycles repeatedly....10
4. Motor runs but cylinder does not turn.............10
5. Motor does not stop.........................................10
6. Burner does not ignite .....................................11
7. Burner ignites and goes out repeatedly ...........12
8. Burner does not shut off ..................................12
9. Clothes do not dry ...........................................13
10. Tumbler overheating .......................................13
11. Burners not burning properly ..........................14
12. Loading door opens during operation .............14
Section 4 – Grounding
Grounding Instructions ..........................................15
Section 5 – Service Procedures
13. Loading door assembly ...................................17
14. Door hinge.......................................................17
15. Door handle .....................................................17
16. Front panel.......................................................18
17. Door switch .....................................................19
18. European door switch......................................19
19. Control and coin drop assembly......................20
20. Lint panel.........................................................20
21. Lint screen .......................................................20
22. Lint panel switch .............................................21
23. Junction box/control box.................................21
24. Fuse and fuse holder assembly........................21
25. Cylinder rollers................................................22
26. Roller shaft ......................................................22
27. Cylinder...........................................................23
28. Cylinder belt....................................................24
29. Rear cylinder seal............................................25
30. Roller support and baffle assembly.................26
31. Airflow switch.................................................27
32. Stove high limit thermostat .............................27
33. Complete gas valve assembly .........................28
34. Burner tube assembly......................................30
35. Viewer window ...............................................30
36. Igniter assembly ..............................................30
37. Electronic ignition control...............................31
38. Thermistor .......................................................32
39. Cabinet thermostat...........................................32
40. Heater element.................................................33
41. Contactors........................................................34
42. Terminal block ................................................34
43. Motor relay......................................................34
44. Transformer.....................................................34
45. Ignition control................................................34
46. Steam coil........................................................35
47. Steam solenoid valve.......................................35
48. Drive belt.........................................................36
49. Fan...................................................................37
50. Fan motor assembly ........................................37
51. Drive motor .....................................................38
Section 6 – Adjustments
52. Leveling legs ...................................................39
53. Airflow switch adjustment ..............................39
54. Loading door switch........................................40
55. Loading door strike .........................................41
Section 7 – Electronic Control Troubleshooting
56. Theory of operation of instant
electronic ignition............................................43
57. Cannot perform infrared (IR)
communication................................................44
58. Coins ignored when entered............................45
59. Control display – Door open light “on” ..........46
60. Control display – “Door” error on 25, 30, stacked 30 and 35 pound tumblers with 24 volt
EDC controls...................................................47
61. Control Display – No visible display – OPL
microprocessor models....................................48
62. Control display – No visible display
– Power on.......................................................49
70284701 1
(continued)
Page 4
63. Will not start – Electric – Manual timer..........50
64. Will not start – Electric – Rotary coin drop ....51
65. Will not start – Gas – Manual timer................53
66. Will not start – Gas – Rotary coin drop...........54
67. Will not start – Steam – Manual timer ............56
68. Will not start – Steam – Rotary coin drop.......57
69. Will not start/continue running
– EDC control..................................................59
70. Will not start/continue running – OPL
microprocessor control....................................62
71. Will not run – Electric – Manual timer ...........65
72. Will not run – Electric – Rotary coin drop......68
73. Will not run – Gas – Manual timer..................71
74. Will not run – Gas – Rotary coin drop ............73
75. Will not run – Steam – Manual timer..............75
76. Will not run – Steam – Rotary coin drop ........77
77. Will not heat – Electric – Manual timer..........79
78. Will not heat – Electric....................................81
79. Will not heat – Electric – Rotary coin drop
(With and without time delay board) ..............83
80. Will not heat – Electric/gas – OPL
microprocessor ................................................85
81. Will not heat – Gas – EDC models .................88
82. Will not heat – Gas – Manual timer ................90
83. Will not heat – Gas – Rotary coin drop...........92
84. Will not heat – Steam – EDC models..............94
85. Will not heat – Steam – Manual timer ............96
86. Will not heat – Steam
– OPL microprocessor.....................................98
87. Will not heat – Steam – Rotary coin drop.....101
Section 9 – NetMaster Troubleshooting
97. No IR communication ...................................129
98. Coins ignored when entered..........................130
99. Control has no display...................................131
100. Door open indicator.......................................134
101. Motor will not start/run .................................138
102. Unit will not heat (Gas).................................144
103. Unit will not heat (Steam) .............................148
104. Unit will not heat (Electric)...........................152
Section 8 – Micro Display Control Troubleshooting
88. Coins ignored when entered..........................103
89. Control has no display...................................104
90. Door open indicator.......................................106
91. Motor will not start/run .................................108
92. Unit will not heat (Gas).................................112
93. Unit will not heat (Gas).................................114
94. Unit will not heat (Steam) .............................115
95. Unit will not heat (Electric)...........................118
96. Error codes ....................................................121
Gas models...........................................................122
Schematic..........................................................122
Connection diagram..........................................123
Steam models.......................................................124
Schematic..........................................................124
Connection diagram..........................................125
Electric models.....................................................126
Schematic..........................................................126
Connection diagram..........................................127
2 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 5
Section 1
Safety Information
Throughout this manual and on machine decals, you will find precautionary statements (“CAUTION”, “WARNING”, and “DANGER”) followed by specific instructions. These precautions are intended for the personal safety of the operator, user, servicer, and those maintaining the machine.
DANGER
DANGER indicates the presence of a hazard that will cause severe personal injury, death, or substantial property damage if the danger is ignored.
WARNING
WARNING indicates the presence of a hazard that can cause severe personal injury, death, or substantial property damage if the warning is ignored.
In the interest of safety, some general precautions relating to the operation of this machine follow.
WARNING
• Failure to install, maintain and/or operate this product according to the manufacturer’s instructions may result in conditions which can produce serious injury, death and/or property damage.
• Do not repair or replace any part of the product or attempt any servicing unless specifically recommended or published in this Service Manual and unless you understand and have the skills to carry out the servicing.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the product is properly grounded and to reduce the risk of fire, electric shock, serious injury or death.
W006R2
CAUTION
CAUTION indicates the presence of a hazard that will or can cause minor personal injury or property damage if the caution is ignored.
Additional precautionary statements (“IMPORTANT” and “NOTE”) are followed by specific instructions.
IMPORTANT: The word “IMPORTANT” is used to inform the reader of specific procedures where minor machine damage will occur if the procedure is not followed.
NOTE: The word “NOTE” is used to communicate installation, operation, maintenance or servicing information that is important but not hazard related.
70284701 3
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 6
Section 1 Safety Information
IMPORTANT INFORMATION: During the lifetime of a tumbler, it may require service. The information contained in this manual was written and is intended for use by qualified service technicians who are familiar with the safety procedures required in the repair of a tumbler, and who are equipped with the proper tools and testing equipment.
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Never start the tumbler with any guards/ panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W240
WARNING
NOTE: The WARNING and IMPORTANT instructions appearing in this manual are not meant to cover all possible conditions and situations that may occur. It must be understood that common sense, caution and carefulness are factors which CANNOT be built into this tumbler. These factors MUST BE supplied by the person(s) installing, maintaining or operating the tumbler.
Always contact your dealer, distributor, service agent or the manufacturer on any problems or conditions you do not understand.
Locating an authorized service person
Alliance Laundry Systems is not responsible for personal injury or property damage resulting from improper service. Review all service information before beginning repairs.
Warranty service must be performed by an authorized technician, using authorized factory parts. If service is required after the warranty expires, Alliance Laundry Systems also recommends contacting an authorized technician and using authorized factory parts.
Repairs that are made to your products by unqualified persons can result in hazards due to improper assembly or adjustments subjecting you or the inexperienced person making such repairs to the risk of serious injury, electrical shock or death.
W007
CAUTION
If you or an unqualified person perform service on your product, you must assume the responsibility for any personal injury or property damage which may result. The manufacturer will not be responsible for any injury or property damage arising from improper service and/or service procedures.
W008
4 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 7
Section 2
Introduction
Model identification
Information in this manual is applicable to these models:
Gas Steam Electric
25 Pound
(220 Liter)
30 Pound
(270 Liter)
35 Pound
(350 Liter)
HA025L HA025N HT025L HT025N HU025L HU025N LT025L LT025N PA025L
HA030L HA030N HT030L HT030N HU030L HU030N LT030L LT030N LU030L LU030N
AT035L AT035N HA035L HA035N HT035L HT035N HU035L HU035N LT035L LT035N
PA025N PT025L PT025N PU025L PU025N SA025L SA025N ST025L ST025N
PA030L PA030N PT030L PT030N PU030L PU030N SA030L SA030N ST030L
LU035L LU035N PA035L PA035N PT035L PT035N PU035L PU035N SA035L SA035N
SU025L SU025N UA025L UA025N UT025L UT025N UU025L UU025N
ST030N SU030L SU030N UA030L UA030N UT030L UT030N UU030L UU030N
ST035L ST035N SU035L SU035N UA035L UA035N UT035L UT035N UU035L UU035N
HT025S HU025S PT025S PU025S
HT030S HU030S PT030S PU030S
AT035S HT035S HU035S PT035S PU035S
ST025S SU025S UT025S UU025S
ST030S SU030S UT030S UU030S
ST035S SU035S UT035S UU035S
HT025E HU025E PT025E PU025E
HT030E HU030E LU030E PT030E PU030E
AT035E HT035E HU035E LU035E PT035E PU035E
ST025E SU025E UT025E UU025E
ST030E SU030E UT030E UU030E
ST035E SU035E UT035E UU035E
Includes models with the following control suffixes (7th and 8th characters):
BC – basic electronic, coin EC – EDC electronic coin NY – NetMaster card ready BL – basic electronic, central pay EX – EDC coin ready OM – OPL micro BX – basic electronic, prep for coin EY – EDC card ready ZC – NetMaster coin network BY – basic electronic, prep for card MT – manual timer ZR – NetMaster card network CD – rotary coin drop NC – NetMaster coin ZX – NetMaster coin ready network CX – prep for coin drop NR – NetMaster card ZY – NetMaster card ready network CY – prep for card NX – NetMaster coin ready
70284701 5
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 8
Section 2 Introduction
Serial plate location
When calling or writing about your product, be sure to mention model and serial numbers. Model and serial numbers are located on serial plate as shown.
ANS 72152 CLOTHES DRYER.
MODEL NO:
SERIAL NO:
V-/ HERTZ/ PHASE
AMPS, WIRES + GROUND
TOTAL kW, MOTOR kW
REQ'D CIRCUIT BREAKER: AMPS
FAN OUTPUT: @MAX "WC STATIC PRESSURE
EQUIPPED FOR: GAS@ "WC MANIFOLD PRESS.
MIN SUPPLY PRESSURE:
INPUT: BTU/hr @ BTU/cu.ft.
MADE IN U.S.A./FABRIQUE AU ETATS UNIS/FABRICADO EN LOS ESTADOS UNIDOS 70051001
MODEL NO:
SERIAL NO:
MAX SUPPLY
"WC. "WC.
PRESSURE:
VOL II
TESTED FOR NATURAL & LIQUID PETROLEUM GASSES
AMPLFIEDRER
CGA 72
Parts ordering information
If replacement parts are required, contact the source from whom you purchased the unit or contact Alliance Laundry Systems at (920) 748-3950 for the name and address of the nearest authorized parts distributor. For technical assistance, call (920) 748-3121.
TMB1823N
Wiring diagram
The wiring diagram is located inside the contactor or junction box.
6 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 9
How a tumbler works
Section 2 Introduction
A tumbler uses heated air to dry loads of laundry.
1
2
room temperature air in through the air intake at the rear of the tumbler and over the heat source (burner flame for gas, heating element for electric, and coil for steam).
The heated air moves into the cylinder, where it is
When the motor is started, the exhaust fan pulls
circulated through the wet load by the tumbling action of the cylinder.
The air then passes through the lint filter, exhaust
fan, and is vented to the outdoors.
3
T001CE3A
70284701 7
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 10
Section 2 Introduction
Notes
8 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 11
Section 3
Troubleshooting
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
IMPORTANT: Refer to wiring diagram for aid in testing tumbler components.
1. TUMBLER DOES NOT START
POSSIBLE CAUSE TO CORRECT
Inoperative motor relay. • Test relay and replace if necessary. Loading door is open. • Close loading door completely. Drying timer is in an off position. (Manual Timer
Models) Incorrect amount of coins inserted into coin drop. • Check that proper amount of coins are inserted. Inoperative coin drop. • Test coin drop and replaced if inoperative. PUSH-TO-START button not properly activated.
(Manual Timer Models) Electrical power off or circuit breaker or fuse
blown. Lint panel open. • Close and lock lint panel. Blown fuse on tumbler. • Check fuse (in junction box) and replace if necessary.
• Turn drying timer on.
• Press and hold in push-to-start button for three seconds.
• Check power supply, or replace fuses.
W002
2. MOTOR DOES NOT START
POSSIBLE CAUSE TO CORRECT
Electrical power off or circuit breaker fuse blown. • Check power supply, or replace fuses. Loading door switch or lint panel switch not closed
or inoperative switch. Door switch improperly adjusted. • Refer to Adjustments Section for door switch adjustment. Start circuit not complete. • Press and hold in push-to-start button for three seconds. Inoperative motor. • Have motor tested and replace if inoperative. Broken, loose, or incorrect wiring. • Refer to wiring diagram. Fan or fan motor binding. • Replace fan or motor assembly. Cylinder or cylinder motor binding. • Replace cylinder, bearing, rollers, or motor assembly. Inoperative transformer. • Test and replace if necessary. Inoperative motor relay. • Test relay and replace if inoperative. Inoperative airflow switch. (Only on manual timer
and rotary coin drop.)
70284701 9
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
• Close door or test switch and replace if inoperative.
• Test switch, replace or adjust as required.
Page 12
Section 3 Troubleshooting
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
3. MOTOR OVERLOAD PROTECTOR CYCLES REPEATEDLY
POSSIBLE CAUSE TO CORRECT
Incorrect voltage • Refer to Installation Manual for electrical requirements. Clothes load is too large. • Remove part of load. Clothes cylinder is binding. • Check cylinder for binding. Inadequate wiring. • Electrician should verify that wiring and voltage is
adequate.
Inadequate make-up air. • Refer to Installation Manual for make-up air
requirements. Lint buildup around tumbler, poor maintenance. • Clean lint accumulation on and around the motors. Broken, loose or incorrect wiring. • Refer to wiring diagram.
W002
4. MOTOR RUNS BUT CYLINDER DOES NOT TURN
POSSIBLE CAUSE TO CORRECT
Broken cylinder belt. • Replace cylinder belt. Cylinder is binding. • Check cylinder for binding.
5. MOTOR DOES NOT STOP
POSSIBLE CAUSE TO CORRECT
Inoperative door switch. • Test switch and replace if inoperative. Inoperative coin drop. • Test coin drop and replace if inoperative. Incorrect wiring. • Refer to wiring diagram. Electronic control inoperative. • Replace electronic control. Inoperative motor relay. • Test relay and replace if inoperative.
10 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 13
Section 3 Troubleshooting
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
6. BURNER DOES NOT IGNITE
POSSIBLE CAUSE TO CORRECT
Improper or inadequate exhaust system. • Refer to Installation Manual for exhaust system
requirements.
Drying selector in the “Cool Down” or “No Heat”
• Add dry time or select heat.
portion of cycle. Inoperative cabinet thermostat or stove. • Test thermostats and replace if inoperative. Insufficient gas supply. • Open partially closed gas shut-off valve, or correct low
gas pressure. Check manifold pressure and adjust to pressure specified on serial plate. If pressure cannot be obtained, have your local gas company check main gas pressure.
Incorrect orifices. • Tumbler is equipped for type of gas specified on serial
plate. If orifices are different from that specified on serial plate, obtain and install correct orifices.
Lint buildup. • Clean lint compartment. Check damper for lint
accumulation. Check ductwork for lint build-up.
Inadequate duct work and make-up air. • Refer to Installation Manual to ensure that ductwork and
make-up air openings are sized accurately.
Inoperative airflow switch. • Test switch and replace if inoperative. Airflow switch out of adjustment. • Refer to Adjustments Section for airflow switch
adjustment.
Broken, loose, or incorrect wiring. • Refer to wiring diagram. Improper igniter to burner tab clearances. • Set gap as described in Service Procedures Section. Valve coils inoperative. • Check valve coils and replace if necessary. Gas shut-off valve in the closed position. • Open shut-off valve. Ground wire from Instant Electronic Ignition (IEI)
• Connect ground wire to ground terminal.
board not connected to ground terminal. Inoperative IEI control. • Replace IEI control. Inoperative motor switch. • Replace motor. Inoperative microprocessor, accumulator switch
• Test and replace as needed.
(rotary coin drop) or C1 relay (timer models). Instant Electronic Ignition (IEI) control in safety
lockout.
• Reset IEI control by opening and closing loading door. (Non-European models only)
W002
70284701 11
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
• Reset IEI by pressing reset button on back of unit. (European models only)
Page 14
Section 3 Troubleshooting
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
7. BURNER IGNITES AND GOES OUT REPEATEDLY
POSSIBLE CAUSE TO CORRECT
Insufficient gas pressure. • Check gas supply and pressure. Inoperative cabinet or stove thermostat. • Test thermostat and replace if inoperative. Improper or inadequate exhaust system. • Refer to Installation Manual for exhaust systems
requirements.
Improper orifices. • Tumbler is equipped for type of gas specified on serial
plate. If orifices are different from that specified on serial plate, obtain and install correct orifices.
Broken, loose or incorrect wiring. • Refer to wiring diagram. Excessive igniter to burner clearance. • Set gap as described in Service Procedures Section. Inadequate make-up air. • Refer to Installation Manual for make-up air
requirements.
W002
8. BURNER DOES NOT SHUT OFF
POSSIBLE CAUSE TO CORRECT
Impurities on gas valve seat, preventing valve from
• Replace gas valve.
closing. Incorrect wiring. • Refer to wiring diagram.
12 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 15
Section 3 Troubleshooting
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
9. CLOTHES DO NOT DRY
POSSIBLE CAUSE TO CORRECT
Not enough heating time allocated for the load. • Start cycle again with enough time to dry load. Burner does not ignite. • Refer to Paragraph 6. Too much water in articles being dried. • Remove excess water. Clothes load too large. • Remove part of load. Maximum load is 25 pound dry
weight (cotton load) for 25 pound Tumbler, etc.
Improper or inadequate exhaust system. • Refer to Installation Manual for exhaust system
requirements. Burner ignites and goes out repeatedly. • Refer to Paragraph 7. Drying selector improperly set. • Set selector for higher setting. Incorrect voltage. • Refer to Installation Manual for electrical requirements. Inadequate make-up air. • Refer to Installation Manual for make-up air
requirements. Exhaust duct to the outside blocked. • Clean duct to remove blockage. Clogged lint screen. • Clean lint screen. Inoperative thermistor • Replace thermistor. Exhaust damper binding. • Adjust damper so it turns freely.
W002
10. TUMBLER OVERHEATING
POSSIBLE CAUSE TO CORRECT
Incorrect main burner orifices. • Obtain and install correct orifices. Gas pressure too high or low. • Adjust gas pressure as specified on serial plate. Inadequate make-up air. • Refer to Installation Manual for make-up air
Lint buildup. • Clean lint compartment. Check damper for lint
Restricted or inadequate exhaust system. • Remove obstruction or lint build up from exhaust
Inoperative thermistor. • Check wiring to ensure thermistor is connected. Replace
Exhaust damper binding. • Adjust damper so it turns freely.
70284701 13
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
requirements.
accumulation. Check ductwork for lint build-up.
ductwork. Refer to Installation Manual for exhaust
system requirements.
thermistor if necessary.
Page 16
Section 3 Troubleshooting
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
11. BURNERS NOT BURNING PROPERLY
POSSIBLE CAUSE TO CORRECT
Dirt in burner. • Remove burner and blow out the dirt. Gas pressure too high or low. • Check serial plate on back of tumbler for correct gas
pressure.
Incorrect orifices. • Tumbler is equipped for the type of gas specified on serial
plate. If orifices are different from that specified on serial plate, obtain and install correct orifices.
Restricted or blocked exhaust duct. • Disassemble and clean exhaust system. Inadequate make-up air. • Refer to Installation Manual for make-up air
requirements.
W002
12. LOADING DOOR OPENS DURING OPERATION
POSSIBLE CAUSE TO CORRECT
Tumbler improperly leveled. • Refer to Adjustments Section for leveling leg adjustment. Excessive load in tumbler. • Remove part of load and restart tumbler. Incorrect loading door strike adjustment. • Refer to Adjustments Section for strike adjustment.
NOTE: All tumbler panels must be in place and on the machine for proper operation.
14 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 17
Section 4
Grounding
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
WARNING
To reduce the risk of fire and electric shock, check with a qualified serviceperson for proper grounding procedures. Improper connection of the equipment grounding conductor may result in a risk of electric shock.
W002
W068R1
Grounding Instructions
This tumbler must be grounded. In the event of malfunction or breakdown, grounding will reduce the risk of electric shock by providing the path of least resistance for electric current. This tumbler must be connected to a grounded metal, permanent wiring system; or an equipment grounding conductor must be run with the circuit conductors and connected to the appropriate ground location.
WARNING
All electrical connections should be made by a qualified electrician.
To reduce the risk of electrical shock, de­energize the electrical circuit being connected to the tumbler before making any electrical connections. Never attempt to connect a live circuit.
W070
NOTE: To ensure protection against shock, this tumbler MUST be electrically grounded in accordance with local codes, or in the absence of local codes, with the latest edition of the National Electrical Code ANSI/NFPA No. 70. In Canada the electrical connections are to be made in accordance with CSA C22.1 or the latest edition of the Canadian Electrical Code, Part I and/or local codes. Electrical work should be done by a qualified electrician.
IMPORTANT: To avoid a short to ground on the control transformer line, or voltage output that could run the control or cause it to run on a reduced voltage; DO NOT connect a “High Leg” or “Stinger Leg” to a single phase machine with an electrical supply coming from a three phase service. A “High Leg” or “Stinger Leg” on three phase machines should be connected to L3.
70284701 15
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 18
Section 4 Grounding
Notes
16 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 19
Section 5
Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
IMPORTANT: When reference is made to the left or right hand direction in this manual, it is from the service person’s position facing the front of the tumbler.
13. LOADING DOOR ASSEMBLY
Refer to Figure 1. a. Open loading door. b. While supporting door, remove two screws
from hinge cam at top of door and slide door out of the bottom hinge.
c. Remove door.
HINGE CAM
SCREW
14. DOOR HINGE
Refer to Figures 1 and 2. a. Open loading door. b. While supporting door, remove two screws
from hinge cam at top of door and slide door out
of the bottom hinge. c. Remove door. d. Remove nuts and screws holding hinge to door
frame. Refer to Figure 2.
15. DOOR HANDLE
Refer to Figure 2. a. Open loading door. b. Remove screws holding door handle to door.
DOOR FRAME
DOOR
FRAME
NUT
DOOR
HANDLE
SCREW
SCREW
DOOR
HINGE LUG
Figure 1
70284701 17
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
T252SE1B
HINGE
TMB1821S
DOOR
HANDLE
Figure 2
Page 20
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
16. FRONT PANEL
Refer to Figure 3. a. Unlock and remove top access panel. b. Unlock and remove lint panel. c. Remove two screws at the loading door hinge
lug. Refer to Figure 1.
d. Remove eight screws holding front panel to
cabinet, leaving one screw on the top.
TOP
ACCESS
PANEL
PANEL
SCREW
e. Support front panel and pull bottom of panel
away from the tumblers far enough to disconnect door switch wires.
f. Remove remaining screw at top.
g. Remove front panel.
NOTE: Ensure front baffle gaskets are in place. Refer to Figure 21.
NOTE: Refer to wiring diagram when rewiring door switch.
1
S E L E TE
C T
M
P
2
IN S
E R
C
T
O
IN
3
P U S H STA RT
H IG H TE M P
STA
25
M ED
RT
C
T E M P
L O W TE M P
NO H E A T
18 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
FRONT PANEL
DOOR
SWITCH
LINT
PANEL
TMB1752S
Figure 3
Page 21
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
17. DOOR SWITCH
Refer to Figure 4. a. Remove two screws from loading door hinge
lug. Refer to Figure 1.
b. Remove screws from bottom of front panel.
Refer to Figure 3. c. Tilt front panel out and away from tumbler. d. Disconnect wires to door switch.
NOTE: Refer to wiring diagram when rewiring door switch.
e. Press switch tabs in and push switch out
through front panel.
WARNING
To reduce the risk of serious injury the door switch MUST be reinstalled after service is complete.
W241
18. EUROPEAN DOOR SWITCH
Refer to Figure 5.
NOTE: European Models prior to Serial Number 0208002174 are equipped with a second door switch.
a. Remove two screws from the loading door
hinge lug. Refer to Figure 1.
b. Remove screws from top and sides of front
panel and loosen screws at bottom of front panel. Refer to Figure 3.
c. Tilt front panel out and away from tumbler only
far enough to permit disconnecting wires from door switch.
NOTE: Refer to wiring diagram when rewiring door switch.
d. Remove two screws and nuts holding door
switch to bracket on inside of front panel.
EU DOOR
SWITCH
SCREWS
DOOR
SWITCH
Figure 4
70284701 19
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
SWITCH
TABS
T258SE1A
T386I
Figure 5
Page 22
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
19. CONTROL AND COIN DROP ASSEMBLY
Refer to Figure 6. a. Unlock top access panel over control and
remove. Refer to Figure 3. b. Remove two screws from control door. c. Swing out control. d. Push up on control until top hinge clears slot. e. Disconnect wire harness from cabinet harness.
f. Remove control and place in a clean dry
location where it cannot be damaged.
IMPORTANT: Refer to wiring diagram when rewiring control.
CONTROL
DOOR
SCREWS
1
SELECT TEMP
2
INSERT COIN
3
PUSH START
H IG H TE M
P
25
STA
C
M E
RT
D T E M
P
L O W T E M P
N O H E A T
20. LINT PANEL Coin
Unlock panel and remove. Refer to Figure 6.
OPL
Pull panel down from top. Refer to Figure 6.
CLIP
CLIP
SCREW
LINT
SCREEN
Figure 7
TMB1819S
COIN
VAU LT
(Obtain
Locally)
LINT
PA NE L
LINT
PANEL
LOCK
Figure 6
20 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB1753S
21. LINT SCREEN
Refer to Figure 7. a. Unlock and remove lint panel. Refer to
Figure 6.
b. Apply pressure on top of screen to release
screen from clip.
c. Remove screen.
TO REPLACE SCREEN
a. Drop bottom of screen between lugs on bottom.
Refer to Figure 7.
b. Secure top of screen behind clip.
Page 23
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
22. LINT PANEL SWITCH
Refer to Figure 8. a. Remove front panel. Refer to Figure 3. b. Disconnect wires from lint panel switch. c. Remove two screws holding switch to switch
mounting bracket.
NOTE: When installing switch, switch lever must point toward rear of tumbler.
LINT
PANEL
SWITCH
NUT
SCREW
LINT PANEL
SWITCH
BRACKET
TMB1851S
Figure 8
23. JUNCTION BOX/CONTROL BOX
a. Remove four screws holding control tray cover
in place. Refer to Figure 21.
b. Remove control tray cover.
24. FUSE AND FUSE HOLDER ASSEMBLY
Refer to Figures 9 and 10.
c. Disconnect wires from fuse holder.
NOTE: Refer to wiring diagram when rewiring fuse.
d. Remove retaining nut holding fuse holder
assembly to junction box and remove assembly.
FUSE
HOLDERS
Figure 9
RETAINING
FUSE
FUSE
CAP
Figure 10
T277SE1A
NUT
FUSE
HOLDER
T259SE1A
NOTE: Fuse holder is located in the junction box at the rear of the machine. There is a fuse access door in the junction box cover for changing fuses.
a. Remove junction box cover. Refer to
Paragraph 23.
b. Turn fuse cap counterclockwise to remove fuse.
70284701 21
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 24
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
25. CYLINDER ROLLERS
Refer to Figure 11. a. Unlock and remove lint panel. Refer to
Figure 8. b. Remove top access panel. c. Remove front panel. d. Remove nuts from end of roller shafts. Refer to
Figure 11.
e. Lift cylinder slightly and remove rollers from
shafts. Refer to Figure 11.
ROLLER
SHAFT
CYLINDER
ROLLER
NUT
26. ROLLER SHAFT
Refer to Figure 11. a. Unlock and remove lint panel. Refer to
Figure 8. b. Remove front panel. Refer to Figure 3. c. Remove cylinder rollers. Refer to
Paragraph 25. d. Remove nuts from back of roller shaft. e. Slide shaft back out of air duct roller support
assembly.
NUT
22 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Figure 11
AIR DUCT
ROLLER SUPPORT
ASSEMBLY
T262SE3A
Page 25
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
27. CYLINDER
a. Unlock and remove lint panel. Refer to
Paragraph 20. b. Remove front panel. Refer to Paragraph 16. c. Remove palnut, jamnut and washer from
cylinder shaft. Refer to Figure 12. d. Remove drive access cover at rear of tumbler.
Refer to Figure 26. e. Pivot motor upward and run belt off motor
pulley and carefully lower motor. Refer to
Figure 26.
f. Pull cylinder out through front of cabinet.
.
W002
PALNUT
JAMNUT
Figure 12
70284701 23
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
WASHER
T261SE1A
Page 26
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
28. CYLINDER BELT
Refer to Figure 13. a. Unlock and remove lint panel. b. Remove front panel. c. Remove palnut, jamnut and washer from
trunnion shaft.
d. Remove drive belt service door at rear of
tumbler.
WASHER
e. Raise motor assembly and run belt off motor
pulley.
f. Pull cylinder out through front of cabinet.
NOTE: Before reassembling cylinder, clean interior of cabinet, checking to make sure all tools have been removed.
BELT
MOTOR
PULLEY
CYLINDER
IDLER
PULLEY
SPRING
24 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
DRIVE
ACCESS
COVER
MOTOR
ASSEMBLY
TMB1847S
Figure 13
Page 27
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
29. REAR CYLINDER SEAL
Refer to Figure 14. a. Remove cylinder assembly. Refer to
Paragraph 27. b. Remove seal from seal support on rear panel. c. Degrease area where new seal is to be placed.
Scrape any remaining adhesive remnants from seal support.
d. Apply generous amount of adhesive into seal
support.
REAR
CYLINDER
SEAL
SUPPORT
e. Carefully install seal into adhesive surface.
Apply pressure until glue is able to support seal and hold it in position.
WARNING
For personal safety use degreaser/solvent only in a well ventilated area away from any open flames or sources of ignition.
WASHER
PALNUT
JAM NUT
BEARING
W242
TRUNNION
ASSEMBLY
70284701 25
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Figure 14
CYLINDER
ASSEMBLY
CENTER
CYLINDER
SEAL
TMB1791S
Page 28
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
30. ROLLER SUPPORT AND BAFFLE ASSEMBLY
Refer to Figure 15. a. Remove cylinder assembly. Refer to
Paragraph 27. b. Remove center partition seal. c. Remove screws holding roller support to
cabinet.
BAFFLE
GASKET
d. Remove screws holding lower baffles to center
partition.
e. Remove lower baffles.
f. Remove screws holding roller support to center
partition.
g. Remove roller support.
ROLLERS
26 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
ROLLER
SUPPORT
GASKET
BAFFLE
CENTER
PARTITION
SEAL
CENTER
PARTITION
TMB1969P
Figure 15
Page 29
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
SCREW
AIRFLOW
SWITCH PLATE
SCREW
AIRFLOW
SWITCH
AIRFLOW
VANE
31. AIRFLOW SWITCH
Refer to Figure 16. a. Remove two screws on airflow switch guard
and remove guard.
b. Disconnect wires from switch.
NOTE: Refer to wiring diagram when rewiring switch.
BRACKET
TWIN
SPEED NUT
Figure 16
NOTE: Refer to wiring diagram when rewiring thermostat.
TMB1846S
32. STOVE HIGH LIMIT THERMOSTAT
Refer to Figure 17. a. Remove cover screws holding gas valve cover
to stove and remove cover.
b. Disconnect wires from stove limit thermostat.
c. Remove two screws and one speed nut holding
switch to mounting bracket.
70284701 27
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
c. Remove screws holding stove limit thermostat
to stove.
Page 30
Section 5 Service Procedures
S
75%
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
STOVE
LIMIT
THERMOSTAT
THERMOSTAT
ATTACHING
SCREW
STOVE
Figure 17
TMB35S
TMB35
33. COMPLETE GAS VALVE ASSEMBLY
Refer to Figure 18. a. Remove gas valve cover. b. Disconnect gas valve wire connections. c. Disconnect gas valve pipe union holding gas
shut-off valve to gas valve nipple.
d. Remove screws holding gas valve to gas valve
bracket and remove valve.
IMPORTANT: When reinstalling gas valve, purge air and sediment from gas service line before connecting to tumbler. Purge remaining air until odor of gas is detected, then tighten connection. Use pipe compound resistant to action of L.P. gas on all pipe threads.
WARNING
To reduce risk of fire or explosion, check pipe connections for gas leaks with a non­corrosive leak detection fluid. Do not use an open flame to check for gas leaks!
W310
28 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 31
Section 5 Service Procedures
GAS
VALV E
GAS
VALV E
BRACKET
MANUAL
SHUT-OFF
VALV E
CLOSE NIPPLE
UNION
ADAPTER
NIPPLE
ELBOW
TMB1942P
PIPE
GAS
VALVE
GAS VALVE
BRACKET
RIVET
GAS VALVE
COVER
ORIFICE HOLDER
BRACKET
TMB1973P
European and Australian Models Non-European and Non-Australian Models
Figure 18
70284701 29
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 32
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
34. BURNER TUBE ASSEMBLY
Refer to Figure 19. a. Remove complete gas valve assembly. Refer to
Paragraph 33.
b. Remove stove guard screws holding stove
guard to bottom of stove and remove guard. c. Remove screws holding burner to stove. d. Remove burner by sliding burner tube away
from gas valve end of stove. e. Pull down on gas valve end of burner tube and
remove from bottom of stove.
BURNER
TUBE
ASSEMBLY
IGNITER SCREW
36. IGNITER ASSEMBLY
a. Remove screws holding gas valve cover to
stove and remove cover. Refer to Paragraph 33.
b. Remove two screws holding igniter to stove
and remove igniter.
IMPORTANT: When reinstalling igniter to burner, gap should be .110 inch - .140 inch (2.79 - 3.55 mm). Refer to Figure 20.
IGNITER
ASSEMBLY
GAP
.110 inch - .140 inch
(2.79 - 3.55 mm)
IGNITER
VIEWER
WINDOW
STOVE GUARD
STOVE
GUARD
SCREWS
Figure 19
35. VIEWER WINDOW
Refer to Figure 19. a. Loosen screw in upper left corner. b. Remove lower screw. c. Turn plate counterclockwise in order to view
burner tube and igniter gap.
30 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
SCREW
TMB36S
TMB36S
BURNER
TUBE
Figure 20
T276SE1C
Page 33
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
37. ELECTRONIC IGNITION CONTROL
Refer to Figure 21. a. Remove screws holding control tray cover to
control box and remove cover. b. Disconnect wire harness. c. Remove high tension lead. d. Remove screws holding ignition control to
control box and remove ignition control.
W002
IGNITION
CONTROL
SCREW
ELECTRONIC
IGNITION
CONTROL
HIGH
VOLTAGE
LEAD
TRANSFORMER
70284701 31
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
CONTROL
BOX COVER
T273SE3A
Figure 21
Page 34
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
38. THERMISTOR
Refer to Figure 22. a. Remove screws holding guard to tumbler and
remove cover.
b. Remove screw from belt service door and
remove door. c. Disconnect wires to thermistor. d. Unscrew thermistor by turning
counterclockwise.
NOTE: Do not turn thermistor by spade terminals.
IMPORTANT: Do not damage thermistor during removal.
39. CABINET THERMOSTAT
Refer to Figure 22. a. Remove screws holding guard to tumbler and
remove guard.
b. Remove screw from belt service door and
remove door. c. Disconnect wires from cabinet thermostat. d. Remove screws holding cabinet thermostat to
cabinet and remove cabinet thermostat.
BELT
SERVICE DOOR
THERMISTOR
CABINET HIGH
LIMIT THERMOSTAT
32 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB37S
VIEW FROM INSIDE TUMBLER
Figure 22
Page 35
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
40. HEATER ELEMENT (Electric Models)
Refer to Figure 23. a. Remove three screws holding connector cover
in place. Remove guard.
b. Remove nuts attaching element wires and
jumper bars to elements. Disconnect element wires.
ELEMENT
ATTACHING
SCREW
NUT
JUMPER
BAR
c. Remove six screws holding element guard to
back of heater box. Remove guard.
d. Remove element attaching screw holding
element to the left side of stove (viewed from rear of tumbler).
e. Slide element to right and pull left side of
element down and out to the left to remove element (viewed from rear of tumbler).
CONNECTOR
COVER
ELEMENT
GUARD
ATTACHING
SCREW
70284701 33
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
HEATER
ELEMENT
TMB1757S
Figure 23
Page 36
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
41. CONTACTORS
Refer to Figure 24. a. Remove screws holding cover and remove
cover.
b. Loosen terminal screws and disconnect all
wires from contactor.
c. Remove four contactor attaching screws and
remove contactor.
NOTE: Refer to wiring diagram when rewiring contactor.
42. TERMINAL BLOCK
Refer to Figure 24. a. Remove screws holding cover and remove
cover.
b. Loosen screws and disconnect all wires from
terminal block.
c. Remove attaching screws and remove terminal
block.
43. MOTOR RELAY
Refer to Figure 24. a. Remove screws holding cover and remove
cover.
b. Loosen screws and disconnect all wires from
motor relay.
c. Remove attaching screws and remove motor
relay.
44. TRANSFORMER
Refer to Figure 24. a. Remove screws holding cover and remove
cover.
b. Loosen screws and disconnect all wires from
transformer.
c. Remove attaching screws and remove
transformer.
45. IGNITION CONTROL
Gas Models Only Refer to Figure 24. a. Remove screws holding cover and remove
cover.
b. Loosen screws and disconnect all wires from
ignition control.
c. Remove attaching screws and remove ignition
control.
IGNITION
CONTROL
TERMINAL
BLOCK
34 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
CONTACTOR/
RELAY
Figure 24
TRA NSFO RMER
T408P
T408P
Page 37
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
46. STEAM COIL
Refer to Figure 25.
CAUTION
Allow steam coils and valve to cool down before attempting any service procedures.
a. Disconnect pipes to steam coil. b. Remove bottom screws holding steam coil to
back of tumbler cabinet.
c. Support steam coil and remove top screws, then
remove steam coil.
STEAM
COIL
W249
47. STEAM SOLENOID VALVE
Refer to Figure 25.
CAUTION
Allow steam coils and valve to cool down before attempting any service procedures.
W249
a. Disconnect pipes. b. Disconnect wires. c. Remove valve by turning valve
counterclockwise.
70284701 35
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
STEAM
SOLENOID
VALVE
TMB2038P
Figure 25
Page 38
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
48. DRIVE BELT
Refer to Figure 26. a. Unlock and remove lint panel. Refer to
Paragraph 20. b. Remove front panel. Refer to Paragraph 16. c. Remove palnut, jamnut and washer from
trunnion shaft. Refer to Figure 12. d. Install cylinder guide tool on cylinder shaft.
Refer to Figure 14.
WASHER
BELT
e. Remove drive access cover at rear of tumbler.
Refer to Figure 22.
f. Raise motor assembly and run belt off motor
pulley.
g. Pull cylinder out through front of cabinet. Refer
to Paragraph 27.
NOTE: Before reassembling cylinder, clean interior of cabinet, checking to make sure all tools have been removed.
MOTOR
PULLEY
CYLINDER
IDLER
PULLEY
SPRING
36 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
DRIVE
ACCESS
COVER
MOTOR
ASSEMBLY
TMB1847S
Figure 26
Page 39
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
49. FAN
Refer to Figure 27. a. Remove four nuts and six screws holding fan to
rear of tumbler. b. Tip fan up from bottom to remove. c. Remove jamnut and palnut holding fan to
motor shaft. Refer to Figure 28.
d. Slide fan off shaft.
NOTE: Before attempting to service fan, always remove thermistor to prevent damage.
50. FAN MOTOR ASSEMBLY
Refer to Figure 28.
IMPORTANT: Before attempting to service fan, always remove thermistor to prevent damage.
a. Remove six screws and four nuts holding fan
motor mounting plate to cabinet. b. Remove motor mounting plate, fan assembly c. Remove palnut and jamnut from motor shaft
and remove fan from motor shaft. d. Remove bolts holding mounting plate to motor
and remove motor.
FAN
MOTOR
PALNUT
MOTOR
SHAFT
FAN
MOTOR
Figure 27
70284701 37
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
T305SE1A
JAMNUT
FAN
Figure 28
MOUNTING
PLATE
TMB1850S
Page 40
Section 5 Service Procedures
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
51. DRIVE MOTOR
Refer to Figure 29.
CAUTION
To reduce the risk of injury, use care when reaching into cabinet through belt service door. The idler pulley could snap into place, causing injury.
W230
WASHER
BELT
a. Remove two screws holding drive access cover
in place. Remove door. Refer to Figure 22. b. Disconnect spring. c. Lift motor up. d. Reach into cabinet and disconnect belt by
rolling off pulley. e. Unscrew nut at end of shaft.
f. Remove plate and motor from shaft to service.
g. Set down motor, remove four bolts on top of
motor. h. Remove motor from plate.
MOTOR
PULLEY
IDLER
PULLEY
CYLINDER
38 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
SPRING
DRIVE
ACCESS
COVER
MOTOR
ASSEMBLY
T163KE3B
Figure 29
Page 41
Section 6
Adjustments
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
52. LEVELING LEGS
NOTE: Keep the tumbler as close to the floor as possible. All legs must rest firmly on the floor so weight of tumbler is evenly distributed. Tumbler must not rock.
a. Check front to rear level by rotating clothes
cylinder until one of the cylinder ribs is at the bottom. Place a level on the rib. Adjust legs as necessary.
W002
NOTE: The front of the tumbler should be slightly higher than the rear (approximately 1/8 inch,
3.18 mm). This will prevent the clothes, while tumbling, from wearing on the door glass gasket.
b. Check side to side level by placing a level on
front and rear of top panel. Adjust legs as necessary.
IMPORTANT: Do not remove plastic caps covering leveling legs in lint compartment.
53. AIRFLOW SWITCH ADJUSTMENT
The airflow switch is set at the factory for proper operation. No adjustment necessary.
70284701 39
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 42
Section 6 Adjustments
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
54. LOADING DOOR SWITCH
The door switch should be adjusted so the cylinder stops when door is opened 2 inches (51 mm), plus or minus 1/4 inch (6 mm). The switch is normally open and is closed when the door is closed. If adjustment is needed, proceed as follows:
a. Close door and start tumbler. Slowly open
loading door. Cylinder and heat system should shut off when door is open 2 inches (51 mm), plus or minus 1/4 inch (6 mm).
b. Slowly close loading door. When door is 2
inches or less from being fully closed, the switch actuator on the door should contact the switch plunger and depress it enough to close the switch with an audible “click”.
If tab does not depress the switch plunger enough to operate the switch, bend tab on loading door OUTWARD and repeat steps “a” and “b.”.
EUROPEAN MODELS (Prior to Serial Number 0208002174)
European tumblers, prior to Serial Number 0208002174, have a second door switch near the top of the door. Refer to Figure 30. This switch also should be adjusted so the cylinder stops when door is opened 2 inches (51 mm), plus or minus 1/4 inch (6 mm). This switch is normally closed and is opened by the hinge cam when the door is opened. If adjustment is needed, proceed as follows:
EUROPEAN DOOR
SWITCH
DOOR SWITCH
SCREWS
SWITCH
PLUNGER
SWITCH
ACTUATOR
Figure 30
DOOR
T275SE1B
a. Remove switch actuator so door switch click
can be heard.
b. Loosen door switch screws just enough so
switch can be moved left or right. Move door switch right if door opens too far before switch clicks. Move door switch left if door doesn’t open far enough before switch clicks.
c. Retighten door switch screws and retest. Repeat
step “b” if further adjustment is needed.
d. Reinstall switch actuator.
40 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 43
Section 6 Adjustments
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
55. LOADING DOOR STRIKE
Refer to Figure 31. The door strike must be adjusted so that sufficient
tension holds loading door closed against the force of a load tumbling against it. The door is properly adjusted when 8-15 lbs. (3.60-6.75 kg) of pull is required to open door.
To adjust, open door, loosen jamnut and turn door strike screw in or out as required. Retighten jamnut.
W002
Figure 31
LOADING
DOOR
JAMNUT
DOOR STRIKE
SCREW
T280SE3A
70284701 41
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 44
Section 6 Adjustments
Notes
42 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 45
Section 7
Electronic Control Troubleshooting
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
56. THEORY OF OPERATION OF INSTANT ELECTRONIC IGNITION
IMPORTANT: The Non-CE Marked Instant Electronic Ignition system will attempt to light the gas by sparking for approximately 12 seconds. If gas ignition does not take place within approximately 12 seconds, the Instant Electronic Ignition control will go into safety lockout and the valve will no longer open until Instant Electronic Ignition control is reset. To reset Instant Electronic Ignition control, remove power from control by opening and closing the tumbler door. If condition persists, check that the gas shut-off valve is in “on” position and that the gas service is properly connected.
If condition persists:
1. Check resistance of high tension lead (approximately 1000 ohms/inch), and replace if not within resistance range.
2. Check voltage present at valve.
3. Check that machine is properly grounded.
4. Check the igniter gap (gap should be .110 to .140 inch).
5. Check that burner ports are not blocked or plugged under the igniter.
70284701 43
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 46
Section 7 Electronic Control Troubleshooting
57. CANNOT PERFORM INFRARED (IR) COMMUNICATION
Single and stacked.
Gas and electric heat.
Attempt to
communicate with
the electronic
control from the
microwand.
Is there a response of
any kind from the
electronic control?
YES
Single and three phase
supply.
NO
Aim microwand
closer and try again.
Does the control
respond?
YES
Check the following:
- low battery on microwand.
- is the IR window covered or
NO
blocked on the control.
- if needed replace the electronic control.
- is the IR cap properly attached
to the microwand.
Does the electronic
control display E:OF
or -C-?
E:OF
Check the following:
- IR communication disabled by manual programming.
- Is the IR window on the control covered or blocked.
- if needed, change electronic control board.
-C-
Communication
sequence checks
out.
T027D
T027D
44 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 47
58. COINS IGNORED WHEN ENTERED
Start coin drop
diagnostic tests.
Single and stacked units. Gas and electric heat. Single and three
phase voltage.
Section 7 Electronic Control Troubleshooting
Does the display on the
EDC control increment
properly?
NO
Is connector H2 firmly
seated in its receptacle?
YES
Is the 3 pin connector
between coin drop and
control connected
correctly?
YES
Are wires exiting coin
drop optical sensor
cracked or broken?
YES
NO
NO
YES
Exit diagnostic
testing and reset
control. (Prompting
for vend price)
Reconnect and run
diagnostic test
again.
Reconnect and run
diagnostic test
again.
Replace coin drop
or optic switch.
NO
Replace coin drop or optic switch.
If problem still
exists then replace
the EDC control.
TMB1822S
TMB1822S
70284701 45
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 48
Section 7 Electronic Control Troubleshooting
59. CONTROL DISPLAY – DOOR OPEN LIGHT “ON”
(1)
Is there voltage at
H4-6 on the
Is there power supplied
Is there voltage to input
Is there voltage across
Is there voltage across
electronic
control?
NO
to the unit?
YES
(2)
of primary fuses?
YES
(3)
Is there voltage to output side of the
primary fuses?
YES
(4)
terminals 1 & 2 of
transformer primary?
YES
(5)
terminals 2 & 3 of
transformer secondary?
YES
Single and stacked units. Gas and electric heat. Single and three
phase supply.
YES
Replace
NO
NO
NO
NO
NO
between primary fuses and power
Replace primary
between primary
Reference voltage
checks to transformer
electronic
control.
Plug unit in and
run it.
Correct wiring
supply.
fuse(s).
Correct wiring
fuses and
transformer.
Replace
transformer.
neutral.
Is there voltage at
the input of the
secondary fuse?
YES
Is there voltage to
output side of
secondary fuse?
YES
Is there voltage to
N.O. of door
switch?
YES
With door closed is
there voltage to
COM of door
switch?
YES
Is there voltage to
N.O. of lint drawer
switch?
YES
Is there voltage to
COM of lint drawer
switch with lint
panel closed?
YES
Correct wiring
between H4-6 of
electronic
control and
COM of lint drawer
switch.
(6)
(7)
(8)
(9)
(10)
(11)
NO
NO
NO
NO
NO
NO
Correct wiring
between secondary
fuse and
transformer.
Replace secondary
fuse.
Correct wiring
between N.O. and
output of secondary
fuse.
Check for proper
function of door
switch replace if
necessary.
Correct wiring
between N.O. on lint
drawer and COM on
door switch.
Check for proper
operation replace if
necessary.
T028D
46 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
T028D
Page 49
Section 7 Electronic Control Troubleshooting
60. CONTROL DISPLAY – “DOOR” ERROR ON 25, 30, STACKED 30 AND 35 POUND TUMBLERS WITH 24 VOLT EDC CONTROLS
TMB1788S
3
2
4
70284701 47
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
1
11
10
9
8
7
5
6
Page 50
Section 7 Electronic Control Troubleshooting
61. CONTROL DISPLAY – NO VISIBLE DISPLAY – OPL MICROPROCESSOR MODELS
Gas, steam and electric heat. Single and three
phase supply.
Is there voltage
supplied to the unit?
YES
Note: Reference voltage to
Is there voltage to the
input side of the
primary fuse(s)?
YES
Is there voltage to the
output side of the
primary fuse(s)?
YES
Is there voltage
across the primary side
of the transformer?
NO
supply neutral.
NO
NO
NO
Connect supply
voltage and run unit.
Correct wiring
between primary
fuse and supply.
Replace primary
fuse.
Correct wiring
between transformer
and primary fuse.
Is there voltage across
fuse on OPL Micro?
YES
Replace fuse.
NO
Replace OPL Micro.
YES
Is there voltage across
1 & 4 of transformer
secondary?
YES
Is there voltage across
terminals H3-3 &
H3-4 on OPL Micro?
YES
NO
NO
Replace transformer
Correct wiring
between OPL Micro
and transformer
secondary.
TMB1823S
TMB1823S
48 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 51
Section 7 Electronic Control Troubleshooting
62. CONTROL DISPLAY – NO VISIBLE DISPLAY – POWER ON
Single and stacked
units. Gas and electric
heat. Single and three
phase supply.
Is there voltage across
H4-2 & H4-5 on the
EDC control?
Replace EDC
Control.
Is there voltage at
the input of the
secondary fuse?
NOYES
Correct wiring
between secondary
fuse and
transformer.
NO
Is there power supplied
to the unit?
YES
Is there voltage to input
of primary fuses?
YES
Is there voltage to output side of the
primary fuses?
YES
Is there voltage across
terminals 1 & 2 of
transformer primary?
NO
NO
NO
NO
Plug unit in and run
it.
Correct wiring between primary fuses and power
supply.
Replace primary
fuse(s).
Correct wiring between primary
fuse and
transformer.
YES
Is there voltage to
output side of
secondary fuse?
YES
Correct wiring
between H4-2 and
secondary fuse.
NO
Replace secondary
fuse.
YES
Is there voltage across
terminals 2 & 3 of
transformer secondary?
YES
70284701 49
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
NO
Replace
transformer.
T025D
T025D
Page 52
Section 7 Electronic Control Troubleshooting
63. WILL NOT START – ELECTRIC – MANUAL TIMER
Manual Timer, with and without time delay board. Single and
stacked units. Single and three phase power supply.
Is there power supply
voltage coming to the
tumbler?
YES
Is there
voltage at the primary side
of the transformer at
terminals 1 and 2?
YES
Is
there voltage at the
secondary side of the
transformer at terminal
2 and 3?
YES
Is there voltage to the
output side of the
secondary fuse?
NOTE: White wires are
YES
transformer "neutral"
NO
NO
NO
NO
Connect power
and run the cycle.
Change the primary
fuse to the
transformer.
Replace the transformer.
Change the
secondary fuse.
Still no voltage
For stacked units.
Correct the wiring
NO
secondary fuse and
the transformer.
Correct wiring
between power
supply and
transformer.
Correct wiring
between upper and
lower pocket.
between the
Is there voltage to the
N.O. terminal of the
door switch?
NO
Correct the wiring between the door
switch and the secondary fuse.
With lint panel
closed is there votlage to
N.O. terminal of the
liint panel switch?
NO
YES
YES
With door closed Is
there voltage at COM
of the door switch?
Check for proper
operation,
replace the door
necessary.
Replace lint
panel switch.
NO
switch if
YES
Refer to NO MOTOR RUN (run circuit.)
Is there voltage to the
COM of the lint panel
switch?
NO
Correct wiring
between lint panel
switch and door
switch.
YES
T050D
T050D
50 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 53
64. WILL NOT START – ELECTRIC – ROTARY COIN DROP
(Sheet 1 of 2)
Coin Drop with and without time delay boards.
Single and stacked units. Single and three phase
power supply.
Section 7 Electronic Control Troubleshooting
Is there power supply
voltage coming to the
unit?
YES
Is there voltage at
the primary side of the
transformer at terminals
1 & 2?
YES
Is there voltage
at the secondary side of the
transformer at terminal
2 and 3?
YES
Is there voltage
to the output side of the
secondary fuse?
YES
Note: Reference voltage
to transformer neutral.
(White wire)
Is there voltage to
N.C. terminal of
switch A on rotary
coin drop?
YES
NO
NO
between transformer
NO
NO
NO
Connect power to
the unit and run
cycle.
Is the primary
fuse good?
YES
Correct wiring
and power supply.
Replace the transformer.
Is the
secondary
fuse good?
YES
Correct wiring
between secondary
of transformer and
fuse.
Correct wiring
between rotary
coin drop and
secondary fuse.
NO
NO
Replace fuse and
run
machine.
Replace fuse and
run
machine.
Is there voltage
across coinmeter timer
motor?
YES
Does the
coinmeter timer motor
advance?
YES
Is there voltage at
N.O. terminal of the
door switch?
YES
With the door
closed is there
voltage across the
door switch?
NO
Is there voltage to
the N.O. terminal of
the lint panel
switch?
YES
NO
NO
NO
YES
NO
Correct wiring
between coinmeter timer motor and COM
on switch A.
Replace coinmeter
timer motor.
Correct wiring
between N.O. on
door switch and
COM on switch A.
Check door switch for proper operation, replace if necessary.
Correct wiring
between N.O. on the
lint panel switch and
COM of door switch.
Is the unit equipped
with time delay
boards?
NO
the vend price satisfied.
Is there voltage on the
COM terminal of switch
A?
YES
70284701 51
YES
Note: The following
checks are made with
NO
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Continued on next
page at step 1.
Replace switch A.
With the lint
panel closed is there
voltage across the
lint panel switch?
NO
Continued on next
page at step 2.
Step 3 continuation.
YES
Check lint panel
switch for proper
operation and
replace if necessary.
T075D
T075D
Page 54
Section 7 Electronic Control Troubleshooting
WILL NOT START – ELECTRIC – ROTARY COIN DROP
(Sheet 2 of 2)
STEP 1
Is there voltage to
H1-2 on TMR1
board?
YES
Note: Following tests
With vend price
satisfied is there
voltage across N.C. &
COM of switch A?
NO
Is there voltage across
the timer motor?
YES
Does coinmeter timer
motor advance?
NO
are conducted with
vend price satisfied.
YES
NO
NO
Correct wiring
between
H1-2 and
output of
secondary
fuse.
Replace switch A.
Correct wiring between timer
motor and COM on
switch A.
Replace timer
motor.
3 phase
STEP 2
Is there voltage at
2A of the start
switch?
YES
Does the unit have single phase or three phase power supply?
Single phase
Is there voltage at
terminal 7 of the
motor relay?
YES
NO
NO
Refer to NO
MOTOR RUN
(run circuit).
Correct wiring
between 2A of start
switch and COM of
lint panel switch.
Correct wiring
between 7 of
motor relay and COM
of lint panel switch.
YES
Is there voltage across
H1-6 & H1-8 of
TMR1?
YES
Is there voltage across
H1-2 & H1-3 of
TMR1?
NO
Is there voltage to N.O.
of door switch?
YES
Continue at step 3
on previous page.
NO
YES
NO
Correct wiring
between H1-6 and
COM on switch A.
Replace TMR1.
Correct wiring between N.O. of door switch and
H1-3 of TMR1.
Is there voltage at terminal 14 of the
motor control relay?
YES
Refer to NO
MOTOR RUN (Run
Circuit).
NO
Correct wiring to
terminal 14 of
motor control
relay.
T076D
T076D
52 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 55
65. WILL NOT START – GAS – MANUAL TIMER
Section 7 Electronic Control Troubleshooting
No motor run (start circuit) Manual Tumblers. Single and stacked units
with and without time delay.
Is there power supply voltage coming to the
tumbler?
YES
Is there voltage
at the primary side of the
transformer at
terminals 1 and 2?
YES
Is there voltage
secondary side of the
at the transformer at terminal
2 and 3?
YES
Is there voltage to the
output side of the
secondary fuse?
NO
NO
NO
NO
Connect power
and run the cycle.
Change the primary
fuse to the
transformer.
Replace the transformer.
Change the
secondary fuse.
Still no voltage
For stacked units.
Correct the wiring
NO
secondary fuse and
the transformer
Correct wiring
between power
supply and
transformer.
Correct wiring
between upper and
lower pocket.
between the
.
NOTE: White wires are
YES
Is there voltage to the
input side of the door
switch?
NO
Correct the wiring between the door
switch and the
secondary fuse.
Is there voltage to the output side of the lint
panel switch?
NO
transformer "neutral"
YES
YES
Is there voltage to the
output side of the door
switch?
Replace the door switch.
Replace lint
panel switch.
NO
YES
Refer to NO
MOTOR RUN
(run circuit).
Is there voltage to the
input side of the lint
panel switch?
NO
Correct wiring
between lint panel
switch and door
switch.
YES
T041D
T041D
70284701 53
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 56
Section 7 Electronic Control Troubleshooting
66. WILL NOT START – GAS – ROTARY COIN DROP
(Sheet 1 of 2)
Single &
stacked tumblers
with and without time delay.
Is there power supply
voltage coming to the
unit?
YES
Is there voltage
at the primary side of the
transformer at terminals
1 & 2?
YES
Is there voltage at the secondary side of the
transformer at terminal
2 and 3?
YES
Is there voltage to the
output side of the secondary fuse?
YES
Note: Reference voltage to
transformer neutral.
Is there voltage to
N.C. terminal of
switch A on rotary
coin drop?
YES
NO
NO
NO
NO
(White wire)
NO
Connect power to
the unit and run
cycle.
Is the primary
fuse good?
YES
Correct wiring
between transformer
and power supply.
Replace the
transformer.
Is the secondary fuse good?
YES
Correct wiring
between secondary
of transformer and
fuse.
Correct wiring between rotary coin drop and secondary
fuse.
NO
NO
Replace fuse and
run
machine.
Replace
fuse and
run
machine.
Is there voltage across coinmeter timer motor?
YES
Does the coinmeter
timer motor
advance?
YES
Is there voltage at
N.O. terminal of the
door switch?
YES
With the door
closed is there
voltage across the
door switch?
NO
Is there voltage to
the N.O. terminal of
the lint panel
switch?
YES
NO
NO
NO
YES
NO
Correct wiring
between
coinmeter timer
motor and COM
on switch A.
Replace coinmeter
timer motor.
Correct wiring between N.O on door switch and
COM on switch A.
Check door switch for proper operation, replace if necessary.
Correct wiring between N.O. on the lint panel switch and COM of door switch.
Is the unit equipped
with time delay
boards?
NO
checks are made with
the vend price satisfied.
Is there voltage on the
COM terminal of switch
A?
YES
54 70284701
YES
Note: The following
NO
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Continued on next
page at step 1.
Replace switch A.
With the lint
panel closed is there
voltage across the lint
panel switch?
NO
Continued on next
page at step 2.
Step 3 continuation.
YES
Check lint panel
switch for proper
operation and replace if necessary.
T086D
T086D
Page 57
WILL NOT START – GAS – ROTARY COIN DROP
(Sheet 2 of 2)
Section 7 Electronic Control Troubleshooting
STEP 1
Is there voltage to
H1-2 on TMR1
board?
YES
Note: Following tests
With vend price
satisfied is there
voltage across N.C. &
COM of switch A?
NO
Is there voltage across
the timer motor?
YES
Does coinmeter timer
motor advance?
NO
are conducted with vend price satisfied.
YES
NO
NO
Correct wiring
between H1-2 and output of
secondary
fuse.
Replace switch A.
Correct wiring
between timer motor
and COM on switch
A.
Replace timer
motor.
STEP 2
Is there voltage at
2A of the start
switch?
YES
Is there voltage at
terminal 7 of the
motor relay?
YES
NO
NO
Refer to NO
MOTOR RUN
(run circuit).
Correct wiring between 2A of start switch and COM of
lint panel switch.
Correct wiring
between 7 of motor
relay and COM of
lint panel switch.
YES
Is there voltage across
H1-6 & H1-8 of
TMR1?
YES
Is there voltage across
H1-2 & H1-3 of
TMR1?
NO
Is there voltage to N.O.
of door switch?
YES
Continue at step 3
on previous page.
NO
YES
NO
Correct wiring
between H1-6 and
COM on switch A.
Replace TMR1.
Correct wiring between N.O. of door switch and
H1-3 of TMR1.
T087D
T087D
70284701 55
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 58
Section 7 Electronic Control Troubleshooting
67. WILL NOT START – STEAM – MANUAL TIMER
Single and stacked units with and without
time delay boards.
Is there power supply voltage coming to the
tumbler?
YES
Is there voltage
at the primary side of the
transformer at
terminals 1 and 2?
YES
Is there voltage
at the secondary side of the
transformer at terminal
2 and 3?
YES
Is there voltage
to the output side of the
secondary fuse?
NO
NO
NO
NO
Connect power
and run the cycle.
Change the primary
fuse to the
transformer
Replace the transformer.
Change the
secondary fuse.
Still no voltage
For stacked units.
Correct the wiring
NO
secondary fuse and
the transformer.
Correct wiring
between power
supply and
transformer.
Correct wiring
between upper and
lower pocket.
between the
NOTE: White wires are
YES
transformer "neutral"
Is there voltage
to the N.O. terminal of the
door switch?
NO
Correct the wiring between the door
switch and the secondary fuse
Is there voltage to the
N.O. terminal of the
lint panel switch?
NO
YES
YES
Is there voltage to the
COM terminal of the
door switch?
Replace the
door switch.
Replace lint
panel switch.
NO
YES
Refer to NO MOTOR RUN (run circuit) .
Is there voltage to the
COM terminal of the
lint panel switch?
NO
Correct wiring
between lint panel
switch and door
switch.
YES
T016D
T016D
56 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 59
68. WILL NOT START – STEAM – ROTARY COIN DROP
(Sheet 1 of 2)
Single and
stacked tumblers
with and without time delay.
Section 7 Electronic Control Troubleshooting
Is there power supply
to the unit?
YES
Is there voltage
at the primary side of the
transformer at terminals
1 & 2?
YES
Is there voltage
at the secondary side of the
transformer at terminal
2 and 3?
YES
Is there voltage to the
output side of the
secondary fuse?
YES
Note: Reference voltage to
transformer neutral.
Is there voltage to
N.C. terminal of
switch A on rotary
coin drop?
YES
NO
NO
NO
NO
(White wire)
NO
Connect power to
the unit and run
cycle.
Is the primary
fuse good?
YES
Correct wiring
between transformer
and power supply.
Replace the transformer.
Is the
secondary
fuse good?
YES
Correct wiring
between secondary
of transformer and
fuse.
Correct wiring between rotary coin drop and secondary
fuse.
NO
NO
Replace
fuse and
run
machine.
Replace
fuse and
run
machine.
Is there voltage across
coinmeter timer motor?
YES
Does the coinmeter
timer motor
advance?
YES
Is there voltage at
N.O. terminal of the
door switch?
YES
With the door
closed is there
voltage across the
door switch?
NO
Is there voltage to
the N.O. terminal of
the lint panel
switch?
YES
NO
NO
NO
YES
NO
Correct wiring
between coinmeter timer motor and COM
on switch A.
Replace coinmeter
timer motor.
Correct wiring
between N.O on
door switch and
COM on switch A.
Check door switch for proper operation, replace if necessary.
Correct wiring between N.O. on the lint panel switch and
COM of door switch.
Is the unit equipped
with time delay
boards?
NO
checks are made with
the vend price satisfied.
Is there voltage on the
COM terminal of switch
A?
YES
70284701 57
YES
Note: The following
NO
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Continued on next
page column 1.
Replace switch A.
With the lint
panel closed is there
voltage across the
lint panel switch?
NO
Continued on next
page column 2.
Step 3 continuation.
YES
Check lint panel
switch for proper
operation and
replace if necessary.
T062D
T062D
Page 60
Section 7 Electronic Control Troubleshooting
WILL NOT START – STEAM – ROTARY COIN DROP
(Sheet 2 of 2)
COLUMN 1
Is there voltage to
H1-2 on TMR1
board?
YES
Note: Following tests
are conducted with
vend price satisfied.
With
vend price satisfied is
there voltage across N.C. &
COM of switch A?
NO
Is there voltage across
the timer motor?
YES
Does coinmeter timer
motor advance?
NO
YES
NO
NO
Correct wiring
between
H1-2 and
output of
secondary
fuse.
Replace switch A.
Correct wiring
between timer motor
and COM on switch
A.
Replace timer
motor.
COLUMN 2
Is there voltage at
2A of the start
switch?
YES
Is there voltage at
terminal 7 of the
motor relay?
YES
NO
start switch and COM
NO
motor relay and COM
Refer to NO
MOTOR RUN
(run circuit).
Correct wiring
between 2A of
of lint panel switch.
Correct wiring
between 7 of
of lint panel switch.
YES
Is there voltage across
H1-6 & H1-8 of
TMR1?
YES
Is there voltage across
H1-2 & H1-3 of
TMR1?
NO
Is there voltage to N.O.
of door switch?
YES
Continue at step 3
on previous page.
NO
YES
NO
Correct wiring
between H1-6 and
COM on switch A.
Replace TMR1.
Correct wiring
between N.O. of
door switch and
H1-3 of TMR1.
T063D
T063D
58 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 61
Section 7 Electronic Control Troubleshooting
69. WILL NOT START/CONTINUE RUNNING – EDC CONTROL
(Sheet 1 of 3)
Single and stacked
Note: Test conducted with vend
price satisfied and start button
Is there voltage at
H4-4 on the EDC
control to transformer
neutral?
pressed.
YES
Continued on next
units. Gas, electric and steam heat. Single and
three phase supply.
page.
Is there voltage at the
input of the secondary
fuse?
NO
Correct wiring
between secondary
fuse and
transformer.
NO
Is there power supplied
to the unit?
YES
Is there voltage to input
of primary fuse(s)?
YES
Is there voltage to
output side of the
primary fuse(s)?
YES
NO
NO
NO
Plug unit in and run
it.
Correct wiring
between primary
fuse(s) and power
supply.
Replace primary
fuse.
YES
Is there voltage to
output side of
secondary fuse?
YES
Is there voltage to N.O.
of door switch?
YES
With door closed is
there voltage to COM
of door switch?
YES
Is there voltage to N.O.
of lint drawer switch?
NO
NO
NO
NO
Replace secondary
fuse.
Correct wiring
between N.O. and
output of secondary
fuse.
Check for proper
function of door
switch replace if
necessary.
Correct wiring between N.O. on lint drawer and COM on
door switch.
YES
Is there voltage
across terminals 1 & 2 of
transformer primary?
YES
Is there voltage
across terminals 2 & 3 of
transformer secondary?
YES
70284701 59
NO
NO
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Correct wiring
between primary
fuse and
transformer.
Replace
transformer.
Is there voltage to
COM of lint drawer
switch with lint panel
closed?
YES
Is there voltage at
H4-1 on the EDC
control board?
YES
Replace EDC
Control.
NO
NO
Check for proper
operation replace if
necessary.
Correct wiring between H4-1 and COM of lint drawer
switch.
T029D
T029D
Page 62
Section 7 Electronic Control Troubleshooting
WILL NOT START/CONTINUE RUNNING – EDC CONTROL
(Sheet 2 of 3)
Note: Tests conducted with vend
price satisfied and start button
pressed.
Is there voltage across
terminals 1 & 4 of
the fan motor?
NO
Correct wiring
between fan motor
and motor control
relay.
Three phase.
Refer to Note
on next page
Is there voltage on B
terminal of motor
control relay?
YES
Is the unit equipped with single phase or three phase power?
Single phase
Is there voltage to
terminal 5 of the
motor control relay?
YES
Is there voltage to
terminal 8 of motor
control relay?
YES
NO
NO
NO
Correct wiring
between B and
H4-4.
Correct wiring
between terminal 5
and power supply.
Replace motor
control relay.
YES
Does the fan motor
run?
YES
Is unit equipped with single phase or three phase power supply?
Three phase.
Refer to Note
on next page
Is there supply voltage
to L2 & L3 of motor
control relay?
YES
Is there voltage across
terminals L2 & T2 and
L3 & T3?
NO
Single phase
NO
YES
Replace fan motor.
Correct wiring
between L2, L3 and
supply.
Replace motor
control relay.
NO
Is there supply voltage
to L1 and L2 of the
motor control relay?
YES
Is there votlage across
L1 & T1 and L2 & T2?
NO
60 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
NO
YES
Correct wiring
between L1, L2 and
power supply.
Replace motor
control relay.
Is there voltage at
terminal 6 of motor
control relay?
YES
Is there voltage at
terminal 9 of motor
control relay?
YES
NO
NO
Continued on next
Correct wiring
between terminal 6
of motor control
relay and supply.
Replace motor
control relay.
page.
T030D
T030D
Page 63
Section 7 Electronic Control Troubleshooting
WILL NOT START/CONTINUE RUNNING – EDC CONTROL
(Sheet 3 of 3)
Is there voltage across
terminals 1 & 4 of
cylinder motor?
YES
Does the cylinder
motor run?
YES
Motors are
operational.
Note: For high voltage three phase supply (380 volts
or higher), the cylinder and fan motors are supplied
by L1, L2, L3 through the motor relay terminals T1,
T2, T3. Make the appropriate adjustments when
doing voltage checks.
NO
NO
Correct wiring
between cylinder
motor and motor
control relay.
Replace cylinder
motor.
T031D
T031D
70284701 61
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 64
Section 7 Electronic Control Troubleshooting
70. WILL NOT START/CONTINUE RUNNING – OPL MICROPROCESSOR CONTROL
(Sheet 1 of 3)
Gas, steam and
electric heat.
Single and three phase
supply.
Reference voltage to
supply neutral.
Is power supplied to
unit?
NO
Connect supply
and run unit.
Is there voltage to
output of secondary
fuse?
NO
Replace secondary
fuse.
YES
Is there voltage to input
of primary fuse(s)?
YES
Is there voltage to
output of primary
fuse(s)?
YES
Is there voltage
across terminals 1 & 2
on primary of
transformer?
YES
NO
NO
NO
between transformer
Correct wiring
between primary
fuse and supply.
Change primary
fuse.
Correct wiring
and primary fuse.
YES
Is there voltage to
N.O. terminal of door
switch?
YES
With door closed is
there voltage to COM
of door switch?
YES
Is there voltage to
N.O. of lint panel
switch?
YES
NO
NO
NO
Correct wiring between N.O.
terminal of door
switch and
secondary fuse.
Check for proper
operation, replace
door switch if
necessary.
Correct wiring between N.O. of lint panel switch
and COM of door switch.
Is there voltage
across terminals 2 & 3
of transformer
secondary?
YES
Note: Reference voltage to
transformer secondary neutral
Is there voltage to input
of secondary fuse?
YES
62 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
NO
terminal 3.
NO
Replace
transformer.
Correct wiring
between secondary
fuse and
transformer.
Is there voltage to COM of lint panel
switch with lint panel
closed?
YES
Is there voltage at terminal 8 of OPL
Micro?
YES
Continued on next
page.
NO
NO
Check for proper
operation and
replace lint panel
switch if necessary.
Correct wiring
between terminal
8 of OPL Micro
and COM of lint
panel switch.
T099D
T099D
Page 65
Section 7 Electronic Control Troubleshooting
WILL NOT START/CONTINUE RUNNING – OPL MICROPROCESSOR CONTROL
(Sheet 2 of 3)
Tests conducted with cycle selected and
start key pad activated.
Is there voltage at terminal 7 on OPL
Micro?
NO
Replace OPL Micro.
Is there voltage
across terminals
1 & 4 of fan
motor?
YES
NO
Correct wiring
between fan motor
and motor control
relay.
YES
Is
there voltage
across terminals
B & A of motor control relay
for OM model and terminals
0 & 1 for RM
models?
YES
Is unit supplied with
single phase or three
phase power?
Three phase. Gas and steam. Refer to Note on next page.
Is there voltage to L1
and L2 of the motor
control relay?
YES
Is there voltage to T1
and T2 of the motor
control relay?
YES
NO
Single phase
Reference voltage to
supply neutral.
NO
NO
Correct wiring to
motor control relay.
Correct wiring
between L1, L2 and
power supply.
Replace motor
control relay.
Single phase
Does the fan
motor run?
YES
Does the unit
have reversing
capabilities?
NO
Does the unit
have single
phase or three
phase supply?
Three phase. Gas and steam. Refer to Note on next page.
Is
there voltage
to L2 and L3 on
the motor control
relay?
YES
Is
there voltage
to T2 and T3 on
the motor control
relay?
NO
YES
NO
NO
Replace fan motor.
See cylinder
rotation. Either
forward or reverse.
Correct wiring
between L2, L3 and
power supply.
Replace motor
control relay.
Is there
voltage at terminal
5 on the motor control
relay for OM models and
terminal 2 for RM
models?
YES
Is there
voltage across
terminals 5 & 8 of
the motor control relay for OM
models and terminals 2
& 4 for RM
models?
NO
70284701 63
NO
YES
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Correct wiring
between motor
control relay and
power supply.
Replace motor
control relay.
Is there voltage to
terminal 6 of motor
control relay?
YES
Is there voltage
across terminals 6 & 9 of
motor control relay?
NO
between terminal
NO
6 motor control
relay and supply
YES
Continued on next
page.
Correct wiring
voltage.
Replace motor
control relay.
TMB1824S
TMB1824S
Page 66
Section 7 Electronic Control Troubleshooting
WILL NOT START/CONTINUE RUNNING – OPL MICROPROCESSOR CONTROL
(Sheet 3 of 3)
Is there voltage
across terminals 1 & 4 of
the cylinder motor?
YES
Does the cylinder
motor run?
YES
Unit operational.
NOTE: For three phase high voltage (380 volts or
higher), the cylinder and fan motors are supplied L1, L2,
L3 through the motor relay terminals T1, T2, T3. Make
the appropriate voltage checks while doing trouble
shooting.
NO
NO
Correct the wiring
between the
cylinder motor and
control relay.
Replace cylinder
motor.
T009D
T009D
64 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 67
71. WILL NOT RUN – ELECTRIC – MANUAL TIMER
(Sheet 1 of 3)
With and without time delay boards.
Single and stacked units.
Single and three phase power supply.
Section 7 Electronic Control Troubleshooting
Is there voltage at terminal C on the
drying timer?
YES
Is there voltage at
terminal B on the
drying timer?
YES
Is there voltage across
terminals 7 and 8 of
CR1 relay?
YES
Is there voltage across
terminal 3 and 5 of
CR1 relay?
NO
NOTE: make sure drying
timer is in the "on"
position.
NO
NO
YES
between drying
timer and lint panel
Replace drying
Correct the wiring
between CR1 relay
and terminal B on
Replace CR1 relay.
Correct wiring
switch.
timer.
drying timer.
NO
Is there voltage across
Is the unit equipped
with a time delay
board?
YES
H1-6 & H1-8 on
TMR1?
YES
**
Is there voltage across
terminals H1-4 &
H1-8 on TMR2?
YES
**
Is there voltage across
DOB contacts on
TMR2?
NO
NO
YES
Correct wiring to
TMR1.
Check for proper
operation of
airflow switch.
Replace time
delay board.
NO
NOTE: This test to be
made with push to start
switch pressed in.
Is there voltage
across terminals 2A
& 1A of push to
start switch?
NO
NOTE: The N.O. contact is closed in the rest
**
Is there voltage across
COM and N.O. of
the airflow switch?
NO
Tested with the start switch pressed in.
**
YES
position due to the physical
mounting of the switch.
YES
Replace push to
start switch.
Adjust the airflow
switch or replace if
inoperative.
CONTINUED
ON NEXT
PAGE.
YES
NO
**
Is there voltage across
terminals 7 & 8 of
CR2 relay?
YES
Is there voltage across
terminals 5 & 3 on
the CR2 relay?
NO
**
Is there voltage across
coils B & A of the
motor control relay?
NO
YES
NO
Correct wiring
between CR2
relay and
airflow switch.
Replace CR2
relay.
Correct wiring
between motor
control relay
and airflow
switch.
T051D
T051D
70284701 65
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 68
Section 7 Electronic Control Troubleshooting
WILL NOT RUN – ELECTRIC – MANUAL TIMER
(Sheet 2 of 3)
Is this a single phase
or three phase unit?
Single phase
**
Is there voltage
across terminal 7 & 4 of
the motor control
relay?
NO
NO
Is there
voltage at terminal 5
on the motor control relay
across terminals 5 & 3
to supply
neutral?
YES
Is
there voltage
of the motor control
relay?
NO
Three phase
YES
NO
YES
Replace motor
control relay.
Correct wiring between terminal 5 and supply voltage.
Replace motor
control relay.
Is there
voltage across terminals 14 & 13 of motor control relay?
NO
Is there voltage to L1 of motor control relay?
YES
Is there voltage to L2 of motor control relay?
YES
Is there
voltage across
L1 to T1 and L2 to
T2 on the motor
control relay?
NO
YES
NO
NO
YES
Replace motor
control relay.
Correct wiring
between L1 and
power supply.
Correct wiring
between L2 and
power supply.
Replace motor
control relay.
Is
there voltage
across terminals 1 & 4
of fan motor?
YES
Does the fan motor
run?
YES
**
Tested with the start switch pressed in.
NO
NO
Correct wiring
between fan
motor and contact
8 on the motor
control relay.
Replace the fan
motor.
Is there
voltage across terminals
3 & 5 of the fan motor
centrifugal switch with
the fan motor
running?
NO
Continued on next
page.
Note: Only for non time
delay machines
YES
Replace fan
motor.
TMB1825S
TMB1825S
66 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 69
WILL NOT RUN – ELECTRIC – MANUAL TIMER
(Sheet 3 of 3)
Section 7 Electronic Control Troubleshooting
Is unit single phase or
three phase?
Single phase.
Is there voltage to terminal 6 on the
motor control relay?
YES
Is there
voltage across terminal 6 & 9 of the motor control relay?
NO
Is there voltage at terminals 1 & 4 of
the cylinder motor?
YES
Three phase.
NO
YES
NO
Correct wiring
between terminal
6 and power
supply.
Replace motor
control relay.
Correct wiring
between cylinder
motor and contact
9 on the motor
control relay.
Is there voltage to L2
on motor control relay?
YES
Is there voltage to L3
on motor control relay?
YES
Is there
voltage across
L2 to T2 and L3 to
T3 on the motor
control relay?
NO
NO
NO
YES
Correct wiring
between motor
control relay and
supply.
Correct wiring
between motor
control relay and
supply.
Replace motor
control relay.
Does the cylinder
motor run?
YES
The cylinder and
fan motors are
operational.
NO
Replace the
cylinder motor.
T053D
T053D
70284701 67
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 70
Section 7 Electronic Control Troubleshooting
72. WILL NOT RUN – ELECTRIC – ROTARY COIN DROP
(Sheet 1 of 3)
Single and Stack with and without
time delay. Single and three phase power.
Tested with vend price
**
satisfied and with start
**
Is there voltage across
terminals 2A & 1A
of push to start
switch?
NO
Is there voltage to
COM of the airflow
switch?
YES
**
Is there voltage across
COM and N.O. of
the airflow switch?
NO
switch pressed in.
YES
Note: Reference
voltage to transformer
neutral.
NOTE: The N.O. contact is closed in the rest
position due to the physical mounting
YES
NO
of the switch.
Replace push to
start switch.
Correct wiring
between COM of airflow switch and 1A on start switch.
Replace inoperative
switch or correct
airflow vane
operation.
**
Is there voltage across
terminals 7 & 8 of
CR2 relay?
YES
**
Is there voltage across
terminals 5 & 3 on
the CR2 relay?
NO
**
Is there voltage across
the coil of the motor
control relay?
YES
Is unit single
phase or three
phase?
Single phase
NO
YES
NO
Three phase Refer to note.
Correct wiring
between CR2
relay and
airflow switch.
Replace CR2
relay.
Correct wiring
between motor
control relay
and airflow
switch.
Continued on
next page
COLUMN 2.
Is the unit equipped
with a time delay
board?
YES
**
Is there voltage across
terminals H1-4 &
H1-8 on TMR2?
YES
**
Is there voltage across
DOB contacts on
TMR2?
NO
NO
NO
YES
Check for proper
operation of
airflow switch and
check wiring.
Replace time
delay board.
Tested with the start switch pressed in.
**
**
Is there voltage across
terminal 7 & 4 of the
motor control relay?
NO
Is there voltage at
terminal 5 on the
motor control relay?
YES
Continued on next page COLUMN 1.
YES
NO
Replace motor
control relay.
Correct wiring
between
terminal 5
and supply
voltage.
T072D
T072D
68 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 71
WILL NOT RUN – ELECTRIC – ROTARY COIN DROP
(Sheet 2 of 3)
Section 7 Electronic Control Troubleshooting
COLUMN 1
Is there voltage across
terminal 5 & 8 of the
motor control relay?
NO
Is there voltage across
terminals 1 & 4 of
fan motor?
YES
Does the fan motor
run?
YES
Is there
voltage across
terminals 3 & 5 of
the fan motor
centrifugal switch with
the fan motor
running?
YES
Replace motor
control relay.
Correct wiring
NO
NO
YES
between fan
motor and contact
8 on the motor
control relay.
Replace the fan
For units without time
delay boards.
Replace fan
motor.
motor.
COLUMN 2
Is there voltage across
terminal 14 & 13 of
motor control relay?
NO
Is there voltage to L1 &
L2 terminals on motor
control relay?
YES
Is there voltage to T1 &
T2 terminals on motor
control relay?
NOTE: For Hi voltage three phase supply (380volts or higher), the cylinder and fan motor are supplied L1, L2, L3 through the motor relay
terminals T1, T2, T3. Make the appropriate
adjustments when doing trouble shooting.
YES
NO
NOYES
Replace motor
control relay.
Correct wiring
between L1, L2
and supply.
Replace motor
control relay.
NO
Is the machine
supplied with single
phase or three phase
power?
Single phase
Is there voltage to
terminal 6 on the
motor control relay?
YES
Continued on next
page COLUMN 1.
Three phase Refer to Note.
NO
Correct wiring
between terminal
6 and power
supply.
Is there voltage to L2 & L3 terminals
on motor control
relay?
YES
Is there voltage
across L2 to T2 and
L3 to T3?
NO
Does the cylinder
motor run?
YES
CYLINDER AND
FAN MOTORS ARE
OPERATIONAL.
NO
YES
NO
Correct wiring
between supply
and L2 & L3
terminals.
Replace motor
control relay.
Replace cylinder
motor.
T073D
T073D
70284701 69
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 72
Section 7 Electronic Control Troubleshooting
WILL NOT RUN – ELECTRIC – ROTARY COIN DROP
(Sheet 3 of 3)
COLUMN 1
Is there
voltage across
terminals 6 & 9 of
motor control relay?
NO
YES
Replace motor
control relay.
Is there voltage at terminals 1 & 4 of
the cylinder motor?
YES
Does the cylinder
motor run?
YES
The cylinder and
fan motors are
operational.
NO
NO
Correct wiring
between cylinder
motor and contact
9 on the motor
control relay.
Replace the
cylinder motor.
T074D
T074D
70 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 73
73. WILL NOT RUN – GAS – MANUAL TIMER
(Sheet 1 of 2)
No motor run (run circuit).
and stacked units with and without
Single
time delay boards.
Section 7 Electronic Control Troubleshooting
Is there voltage at
terminal c on the
drying timer?
YES
Is there voltage at
terminal b on the
drying timer?
YES
Is there voltage across
terminals 7 and 8 of
CR1 relay?
YES
Is there voltage across
terminal 3 and 5 of
CR1 relay?
NO
NOTE: make sure drying
timer is in the “on”
position.
NO
NO
YES
between drying
timer and lint panel
Replace drying
Correct the wiring
between CR1 relay
and terminal b on
Replace CR1 relay.
Correct wiring
switch.
timer.
drying timer.
NO
Is the unit equipped
with a time delay
board?
YES
Is there voltage across
H1-6 & H1-8 on
TMR1?
YES
**
Is there voltage across
terminals H1-4 &
H1-8 on TMR2?
YES
**
Is there voltage across
DOB contacts on
TMR2?
NO
NO
YES
Correct wiring to
TMR1.
Check for proper
operation of
airflow switch.
Replace time
delay board.
NO
NOTE: This test to be
made with push to start
switch pressed in.
Is there voltage
across terminals 2A
& 1A of push to
start switch?
NO
**
Is there voltage across
COM and N.O. of
the airflow switch?
NO
Tested with the start switch pressed in.
**
YES
NOTE: The N.O. contact is closed in the rest
position due to the physical mounting
of the switch.
YES
Replace push to
start switch.
Adjust the airflow
switch or replace if
inoperative.
CONTINUED
ON NEXT
PAGE.
YES
NO
**
Is there voltage across
terminals 7 & 8 of
CR2 relay?
YES
Is there voltage across
terminals 5 & 3 on
the CR2 relay?
NO
**
Is there voltage across
coils B & A of the
motor control relay?
NO
YES
NO
Correct wiring
between CR2
relay and
airflow switch.
Replace CR2
relay.
Correct wiring
between motor
control relay
and airflow
switch.
T042D
T042D
70284701 71
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 74
Section 7 Electronic Control Troubleshooting
WILL NOT RUN – GAS – MANUAL TIMER
(Sheet 2 of 2)
**
Is there voltage across
terminal 7 & 4 of the motor control relay?
YES
Does the fan motor
run?
NO
Replace the fan
motor.
NO
Is there voltage at terminal 5 on the
motor control relay to
to supply neutral?
YES
Is there voltage across
terminal 5 & 8 of the
motor control relay?
NO
Is there voltage across
terminals 1 & 4 of
fan motor?
NO
YES
NO
Replace motor
control relay.
Correct wiring
between terminal 5
and supply voltage.
Replace motor
control relay.
Correct wiring
between fan
motor and contact
8 on the motor
control relay.
YES
Is there
voltage across
terminals 3 & 5 of
the fan motor
centrifugal switch with
the fan motor
running?
NO
Is there voltage to
terminal 6 on the
motor control relay and
supply neutral?
YES
Is there voltage across
terminal 6 & 9 of the motor control relay?
NO
Is there voltage at terminals 1 & 4 of
the cylinder motor?
YES
Note: Only for non time
delay machines
YES
Replace fan
motor.
Correct wiring
NO
between terminal
6 and power
supply.
YES
Replace motor
control relay.
Correct wiring
between cylinder
NO
motor and contact
9 on the motor
control relay.
YES
Tested with the start switch pressed in.
**
72 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Does the cylinder
motor run?
YES
The cylinder and
fan motors are
operational.
NO
Replace the
cylinder motor.
T043D
T043D
Page 75
74. WILL NOT RUN – GAS – ROTARY COIN DROP
(Sheet 1 of 2)
Single and stack with and
without time delay.
Section 7 Electronic Control Troubleshooting
**
**
Is there voltage across
terminals 2A & 1A
of push to start
switch?
NO
voltage to transformer
Is there voltage to
COM of the airflow
switch?
YES
NOTE: The N.O. contact is closed in the rest position due to the physical
**
Is there voltage across
COM and N.O. of
the airflow switch?
NO
Is the unit equipped
with a time delay
board?
YES
Tested with start switch
pressed in.
YES
Note: Reference
neutral.
NO
mounting of the switch.
YES
NO
Replace push to
between COM of airflow switch and 1A on start switch.
Adjust the airflow
switch or replace if
start switch.
Correct wiring
inoperative.
**
Is there voltage across
DOB contacts (H1-4
and H1-5) on TMR2?
NO
**
Is there voltage across
terminals 7 & 8 of
CR2 relay?
YES
**
Is there voltage across
terminals 5 & 3 on
the CR2 relay?
NO
**
Is there voltage across
coils B & A of the
motor control relay?
YES
**
Is there voltage across
terminal 7 & 4 of the
motor control relay?
YES
NO
YES
NO
YES
Replace time
delay board.
Correct wiring
between CR2
relay and
airflow switch.
Replace CR2
relay.
Correct wiring
between motor
control relay
and airflow
switch.
Replace motor
control relay.
NO
Is there voltage across
H1-6 & H1-8 on
TMR1?
YES
**
Is there voltage across
terminals H1-4 &
H1-8 on TMR2?
NO
NO
Correct wiring to
TMR1.
Check for proper
operation of
airflow switch
and check wiring.
Is there voltage at
terminal 5 on the
motor control relay?
YES
CONTINUED
NO
Correct wiring
between
terminal 5
and supply
voltage.
ON NEXT
PAGE.
YES
**
Tested with the start switch pressed in.
70284701 73
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
T088D
T088D
Page 76
Section 7 Electronic Control Troubleshooting
WILL NOT RUN – GAS – ROTARY COIN DROP
(Sheet 2 of 2)
Is there voltage across
terminal 5 & 8 of the
motor control relay?
NO
Is there voltage across
terminals 1 & 4 of
fan motor?
YES
Does the fan motor
run?
YES
Is there voltage
across terminals 3 &
5 of the fan motor centrifugal
switch with the fan
motor running?
YES
NO
NO
YES
Replace motor
control relay.
Correct wiring
between fan
motor and contact
8 on the motor
control relay.
Replace the fan
motor.
Replace fan
motor.
Is there voltage at
terminals 1 & 4 of
the cylinder motor?
YES
Does the cylinder
motor run?
YES
The cylinder and
fan motors are
operational.
NO
NO
Correct wiring
between cylinder
motor and contact
9 on the motor
control relay.
Replace the
cylinder motor.
NO
Is there voltage to
terminal 6 on the
motor control relay?
YES
Is there voltage across
terminal 6 & 9 of the
motor control relay?
NO
NO
YES
Correct wiring
between terminal
6 and power
supply.
Replace motor
control relay.
**
Tested with the start switch pressed in.
T089D
T089D
74 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 77
75. WILL NOT RUN – STEAM – MANUAL TIMER
(Sheet 1 of 2)
Section 7 Electronic Control Troubleshooting
Single and stacked units with and without
time delay board.
Is there voltage at
terminal C on the
drying timer?
YES
Is there voltage at terminal B on the
drying timer?
YES
Is there voltage across
terminals 7 and 8 of
CR1 relay?
YES
Is there voltage across
terminal 3 and 5 of
CR1 relay?
NO
NOTE: Make sure drying
timer is in the "on"
position.
NO
NO
YES
Correct wiring
between drying
timer and lint panel
switch.
Replace drying
timer.
Correct the wiring
between CR1 relay
and terminal B on
drying timer.
Replace CR1 relay.
NO
Is the unit equipped
with a time delay
board?
YES
Is there voltage across
H1-6 & H1-8 on
TMR1?
YES
**
Is there voltage across
terminals H1-4 &
H1-8 on TMR2?
YES
**
Is there voltage across
DOB contacts on
TMR2?
NO
NO
YES
Correct wiring to
TMR1.
Check for proper
operation of
airflow switch.
Replace time
delay board.
NO
NOTE: This test to be
made with push to start
switch pressed in.
Is there voltage
across terminals 2A
& 1A of push to
start switch?
NO
NOTE: The N.O. contact is closed in
the rest position due to the physical
**
Is there voltage across
COM and N.O. of
the airflow switch?
NO
Tested with the start switch pressed in.
**
mounting of the switch.
YES
YES
Replace push to
start switch.
Adjust the airflow
switch or replace if
inoperative.
CONTINUED
ON NEXT
PAGE.
YES
NO
**
Is there voltage across
terminals 7 & 8 of
CR2 relay?
YES
Is there voltage across
terminals 5 & 3 on
the CR2 relay?
NO
**
Is there voltage across
B & A of the motor
control relay?
NO
YES
NO
Correct wiring between CR2
relay and
airflow switch.
Replace CR2
relay..
Correct wiring
between motor
control relay
and airflow
switch.
T017D
T017D
70284701 75
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 78
Section 7 Electronic Control Troubleshooting
WILL NOT RUN – STEAM – MANUAL TIMER
(Sheet 2 of 2)
**
Is there voltage across
terminal 7 & 4 of the
motor control relay?
YES
Does the fan motor
run?
NO
Replace the fan
motor.
NO
Is there voltage at
terminal 5 on the
motor control relay to
to supply neutral?
YES
Is there voltage across
terminal 5 & 8 of the
motor control relay?
NO
Is there voltage across
terminals 1 & 4 of
fan motor?
NO
YES
NO
Replace motor
control relay.
Correct wiring
between terminal
5 and supply
voltage.
Replace motor
control relay.
Correct wiring
between fan
motor and contact
8 on the motor
control relay.
YES
Is there
voltage across
terminals 3 & 5 of
the fan motor
centrifugal switch with
the fan motor
running?
NO
Is there voltage to
terminal 6 on the
motor control relay and
supply neutral?
YES
Is there voltage across
terminal 6 & 9 of the
motor control relay?
NO
Is there voltage at
terminals 1 & 4 of
the cylinder motor?
YES
Note: Only for non time
delay machines
YES
Replace fan
motor.
Correct wiring
NO
between terminal
6 and power
supply.
YES
Replace motor
control relay.
Correct wiring
NO
between cylinder
motor and contact
9 on the motor
control relay.
YES
Tested with the start switch pressed in.
**
76 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Does the cylinder
motor run?
YES
The cylinder and
fan motors are
operational.
NO
Replace the
cylinder motor.
T018D
T018D
Page 79
76. WILL NOT RUN – STEAM – ROTARY COIN DROP
(Sheet 1 of 2)
Single and stack
with and without time delay.
**
Tested with start switch
pressed in and vend
**
Is there voltage across
terminals 2A & 1A
of push to start
switch?
NO
Is there voltage to
COM of the airflow
switch?
satisfied.
YES
Note: Reference
voltage to transformer
neutral.
NO
Replace push to
start switch.
Correct wiring
between COM of airflow switch and 1A on start switch.
Section 7 Electronic Control Troubleshooting
**
Is there voltage across
DOB contacts on
TMR2?
NO
**
Is there voltage across
terminals 7 & 8 of
CR2 relay?
YES
YES
NO
Replace time
delay board.
Correct wiring
between CR2
relay and
airflow switch.
YES
NOTE: The N.O. contact is closed in the rest
position due to the physical mounting
**
Is there voltage across
COM and N.O. of
the airflow switch?
NO
Is the unit equipped
with a time delay
board?
YES
Is there voltage across
H1-6 & H1-8 on
TMR1?
YES
of the switch.
YES
NO
NO
Adjust the airflow
switch or replace if
inoperative.
Correct wiring to
TMR1.
**
Is there voltage across
terminals 5 & 3 on
the CR2 relay?
NO
**
Is there voltage across
B & A of the motor
control relay?
YES
**
Is there voltage across
terminal 7 & 4 of the motor control relay?
NO
Is there voltage at
terminal 5 on the
motor control relay?
YES
NO
YES
NO
Replace CR2
relay.
Correct wiring
between motor
control relay
and airflow
switch.
Replace motor
control relay.
Correct wiring
between
terminal 5
and supply
voltage.
**
Is there voltage across
terminals H1-4 &
H1-8 on TMR2?
YES
70284701 77
NO
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Check for proper
operation of
airflow switch and
check wiring.
**
Tested with the start switch pressed in.
YES
CONTINUED
ON NEXT
PAGE.
T064D
T064D
Page 80
Section 7 Electronic Control Troubleshooting
WILL NOT RUN – STEAM – ROTARY COIN DROP
(Sheet 2 of 2)
Is there voltage across
terminal 5 & 8 of the
motor control relay?
NO
Is there voltage across
terminals 1 & 4 of
fan motor?
YES
Does the fan motor
run?
YES
Is there
voltage across
terminals 3 & 5 of
the fan motor
centrifugal switch with
the fan motor
running?
YES
NO
Only for units without
YES
Replace motor
control relay.
Correct wiring
NO
time delay boards.
between fan
motor and contact
8 on the motor
control relay.
Replace the fan
Replace fan
motor.
motor.
Is there voltage at terminals 1 & 4 of
the cylinder motor?
YES
Does the cylinder
motor run?
YES
The cylinder and
fan motors are
operational.
NO
NO
Correct wiring
between cylinder
motor and contact
9 on the motor
control relay.
Replace the
cylinder motor.
NO
Is there voltage to terminal 6 on the
motor control relay?
YES
Is there voltage across
terminal 6 & 9 of the
motor control relay?
NO
NO
YES
Correct wiring
between terminal
6 and power
supply.
Replace motor
control relay.
**
Tested with the start switch pressed in.
T065D
T065D
78 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 81
77. WILL NOT HEAT – ELECTRIC – MANUAL TIMER
(Sheet 1 of 2)
With and without time delay board.
Single and stacked units. Single and
NOTE: The following tests are conducted with
the heat timer in the "ON" position with the
machine running and calling for heat. Voltage
checks are referenced to transformer neutral.
Is there voltage across
terminals 1 & 6 of
the temp control bd?
NO
three phase power supply.
Section 7 Electronic Control Troubleshooting
Is there
voltage at
airflow switch
N.C. terminal to
transformer
neutral?
Replace inoperative
NO
switch or correct
airflow vane operation.
YES
YES
Is there voltage across
terminals 5 & 6 of
the temp control bd?
NO
Is the thermistor shorted or open?
NO
Is temperature
selection switch
shorted or open?
NO
Replace the
temperature
control board.
YES
YES
voltage to
terminal 3 of
fan motor?
Replace thermistor.
Replace selection
switch.
Is there
YES
Correct wiring
NO
between fan motor
terminal 3 and CR1 terminal 4.
YES
YES
Is there voltage at terminal 6 on CR1 to transformer neutral?
YES
Is there voltage from terminal 4 on CR1 to transformer neutral?
YES
Is unit equipped with
time delay board?
NO
Is there voltage from terminal 6 on CR2 to transformer neutral?
YES
Correct wiring between
NO
airflow switch and
terminal 6 on CR1.
NO
Replace CR1.
Correct wiring
NO
between terminal 6
on CR2 to terminal
4 on CR1.
CONTINUED
ON NEXT
PAGE
70284701 79
Is there voltage
at terminal 3 & 5
of fan motor?
Correct wiring between motor terminal 5 and
temp control
board terminal 1.
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
YES
NO
Replace fan motor.
Is there voltage from terminal 4 on CR2 to transformer neutral?
YES
Correct wiring
between CR2
terminal 4 &
terminal 1 on
temp control
board.
NO
Replace CR2.
T054D
T054D
Page 82
Section 7 Electronic Control Troubleshooting
WILL NOT HEAT – ELECTRIC – MANUAL TIMER
(Sheet 2 of 2)
Note: Voltage checks are referenced to
transformer neutral.
Is there voltage to the
input side of the
cabinet limit?
YES
Is there voltage to the
output side of the
cabinet limit?
YES
Is there voltage to the
input side of the stove
limit?
YES
Is there voltage to the
output side of the stove
limit?
NO
NO
NO
NO
Correct wiring
between cabinet
limit and temp
control board.
Replace the cabinet
limit.
Correct wiring
between stove limit
and cabinet limit.
Replace the stove
limit.
Do the elements
produce heat?
YES
UNIT
OPERATIONAL
NO
Replace elements.
YES
Is there voltage across
HC1 & HC2
element contactor
coils?
YES
Is there voltage across
the elements?
YES
NO
NO
Correct wiring
between element
contactor coils and
stove limit.
Check wiring
between elements,
contactors and
supply. Correct if
necessary.
T055D
T055D
80 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 83
78. WILL NOT HEAT – ELECTRIC
(Sheet 1 of 2)
Section 7 Electronic Control Troubleshooting
Note: Tests are conducted with unit running
and calling for heat.
All voltage checks are referenced to
transformer neutral.
Is there voltage on
FS-2 of EDC control?
YES
Replace
thermistor.
Is there voltage
on FS-1 of
EDC control?
YES
Is there voltage on
COM of airflow
switch?
YES
NO
thermistor
operational?
NO
Correct wiring
between FS-2 and
COM of lint drawer.
NONO
Is the
Correct wiring
between COM of
airflow switch and
Single and stacked units with single and three
Replace EDC
control.
YES
FS-1 of EDC
control.
phase supply.
Is there voltage on
terminal 3 of fan
motor centrifugal
switch?
YES
Is there voltage at
terminal 5 of fan
motor centrifugal
switch?
YES
Is there voltage to the
input side of the
cabinet limit?
YES
NO
NO
NO
Correct wiring
between terminal
3 of fan motor
centrifugal switch
and terminal 4 of
motor control relay.
Replace fan motor.
Correct wiring
between cabinet
limit and terminal
5 of fan motor
centrifugal switch.
Is there voltage at
N.C. terminal of
airflow switch?
YES
Is there voltage on terminal 7 of motor
control relay?
YES
Is there voltage at
terminal 4 of motor
control relay?
YES
NO
NO
NO
Check for proper
function of airflow
switch and replace
if necessary.
Correct wiring
between terminal 7
on motor control
relay and N.C.
terminal on airflow
switch.
Replace motor
control relay.
Is there voltage at the
output of the cabinet
limit?
YES
Is there voltage to the input side of the stove
limit?
YES
Continued on next
page.
NO
NO
Replace cabinet
limit.
Correct wiring
between stove limit
and cabinet limit.
T034D
T034D
70284701 81
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 84
Section 7 Electronic Control Troubleshooting
WILL NOT HEAT – ELECTRIC
(Sheet 2 of 2)
Is there voltage to the
output side of the stove
limit?
YES
Is there voltage across
coils HC1 & HC2?
YES
Is there voltage across
the heating elements?
YES
Do the elements
produce heat?
NO
NO
NO
NO
Replace the stove
limit.
Correct wiring to
the coils of HC1
and HC2.
Correct wiring
between elements
and supply. Replace
HC1 and or HC2
if necessary
Replace elements.
YES
Unit operational.
T035D
T035D
82 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 85
Section 7 Electronic Control Troubleshooting
79. WILL NOT HEAT – ELECTRIC – ROTARY COIN DROP (With and without time delay board)
(Sheet 1 of 2)
Single and stacked tumblers with and without time delay.
Single and three phase
units.
Is there voltage across across terminals 1 &
6 of the temp
control board?
NO
Is there voltage at
airflow switch N.C.
terminal to transformer
neutral?
Adjust the airflow
NO
switch or replace if
inoperative.
YES
YES
Is there voltage across across terminals 5 &
6 of the temp
control board?
NO
Is the thermistor
shorted or open?
NO
Is temperature
selection switch
shorted or open?
NO
Replace the
temperature
control board.
Is there voltage on terminal 3 of fan motor to transformer
neutral?
YES
YES
Replace thermistor.
YES
Replace selection
NO
switch.
Correct wiring
between terminal
3 of fan motor
and N.C. terminal
on switch B.
YES
YES
Is there voltage at
COM on switch B to
transformer neutral?
YES
Is there voltage from
N.C. on switch B to
transformer neutral?
YES
Is the unit equipped
with a time delay
board?
NO
Is there voltage from terminal 6 on CR2 to transformer neutral?
YES
NO
between airflow
switch and COM on
NO
Replace switch B.
NO
between terminal 6 on CR2 to terminal
Correct wiring
switch B.
Correct wiring
N.C. on switch B.
With fan motor
running is there voltage
from terminal 5 to
transformer neutral?
YES
Is there voltage on
terminal 1 of temp
board to transformer
neutral?
YES
CONTINUED
ON NEXT
PAGE
70284701 83
Power supply to
temp control board
is good.
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
NO
Replace fan motor.
Correct wiring
between terminal
NO
1 of temp board
to terminal 5 of fan motor.
Is there voltage from terminal 4 on CR2 to transformer neutral?
YES
Correct wiring
between terminal
4 on CR2 & terminal 1 on temp control
board.
NO
Replace CR2.
T077D
T077D
Page 86
Section 7 Electronic Control Troubleshooting
WILL NOT HEAT – ELECTRIC – ROTARY COIN DROP (With and without time delay board)
(Sheet 2 of 2)
Note: Voltage checks are referenced to
transformer neutral.
Is there voltage to the
input side of the
cabinet limit?
YES
Is there voltage to the
output side of the
cabinet limit?
YES
Is there voltage to the
input side of the stove
limit?
YES
Is there voltage to the
output side of the stove
limit?
NO
NO
NO
NO
Correct wiring
between cabinet
limit and temp
control board.
Replace the cabinet limit.
Correct wiring
between stove limit
and cabinet limit.
Replace the stove
limit.
Do the elements
produce heat?
YES
UNIT
OPERATIONAL
NO
Replace elements.
YES
Is there voltage across
the coils of HC1 &
HC2?
YES
Is there voltage across
the elements?
YES
NO
NO
Correct the wiring
to the coils.
Check the wiring
between elements,
contactors and
supply. Correct if
necessary.
T078D
T078D
84 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 87
Section 7 Electronic Control Troubleshooting
80. WILL NOT HEAT – ELECTRIC/GAS – OPL MICROPROCESSOR
(Sheet 1 of 3)
Note: Testing conducted with unit running
Single and three phase supply.
Reference voltage to
transformer neutral
Is there voltage at
terminal 5 on OPL
Micro?
terminal 3.
YES
and calling for heat.
Continued on next
page column 2.
Is there voltage across
terminals 2 & 3 of
transformer secondary?
NO
Replace
transformer.
NO
Is the thermister
operating properly?
YES
Reference voltage to
supply neutral.
Is power supplied to
unit?
YES
Is there voltage to input
of primary fuse(s)?
YES
Test conducted with unit
running and calling for heat.
NO
Replace thermister.
NO
Connect supply and
run unit.
NO
Correct wiring
between primary
fuse and supply.
YES
Note: Reference voltage to
transformer secondary neutral
Is there voltage to input
of secondary fuse?
YES
Is there voltage to
output of secondary
fuse?
YES
Is there voltage to
N.O. terminal of door
switch?
YES
terminal 3.
NO
NO
NO
Correct wiring
between secondary
fuse and
transformer.
Replace secondary
fuse.
Correct wiring
between N.O.
terminal of door
switch and
secondary fuse.
Is there voltage to
output of primary
fuse(s)?
YES
Is
there voltage across
terminals 1 & 2 on
primary of
transformer?
YES
70284701 85
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
NO
NO
between transformer
Change primary
fuse.
Correct wiring
and primary fuse.
With door closed is
there voltage to COM
of door switch?
YES
Is there voltage to
N.O. of lint panel
switch?
YES
Continued on next
page Column 1.
NO
NO
Check for proper
operation, replace
door switch if
necessary.
Correct wiring
between N.O. of
lint panel switch
and COM of door
switch.
T010D
T010D
Page 88
Section 7 Electronic Control Troubleshooting
WILL NOT HEAT – ELECTRIC/GAS – OPL MICROPROCESSOR
(Sheet 2 of 3)
Column 1
Is there voltage to COM of lint panel
switch with lint panel
closed?
YES
Is there voltage at
terminal 8 of OPL
Micro?
YES
Is there voltage to
terminal 13 of OPL
Micro?
YES
Is there voltage at
terminal 6 of OPL
Micro?
YES
Replace OPL Micro.
Is there voltage to
terminal 14 on motor
control relay?
YES
NO
NO
NO
NO
NO
Check for proper
operation and
replace lint panel
switch if necessary.
Correct wiring
between terminal
8 of OPL Micro
and COM of lint
panel switch.
Replace OPL Micro.
Correct wiring
between terminal
6 & 13 on OPL
Micro.
Correct wiring
between terminal
14 on motor
control relay and
N.C. terminal of
airflow switch.
Three phase
Column 2
Is there voltage at
COM of airflow
switch?
Is there voltage at
N.C. terminal of
airflow switch?
Is the unit supplied with
single phase or three
phase power?
there voltage at
terminal 7 of motor control relay for OM models or terminal 8
for RM
models?
there voltage at
terminal 4 of motor control relay for OM models or terminal 6
for RM
models?
Is there voltage at
terminal 3 of fan
motor centrifugal
switch?
conducted with the unit running
YES
YES
single phase
Is
YES
Is
YES
The following tests are
and calling for heat.
NO
NO
NO
NO
NO
Correct wiring
between COM &
Check for proper
operation and
Correct wiring
between terminal
control relay and
N.C. of airflow
Replace motor
Correct wiring
between fan motor
centrifugal switch and motor control
OPL Micro.
replace if
necessary.
7/8 of motor
switch.
control relay.
relay.
Is there voltage across
terminals 14 & 13 of motor control relay?
YES
Replace motor
control relay.
86 70284701
NO
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
YES
Is there voltage at
terminal 5 of fan
motor centrifugal
switch?
YES
Continued on next
page.
NO
Replace fan motor.
T011D
T011D
Page 89
Section 7 Electronic Control Troubleshooting
WILL NOT HEAT – ELECTRIC/GAS – OPL MICROPROCESSOR
(Sheet 3 of 3)
Continued from column 2 of
previous page.
Is there voltage to the
input of the cabinet
limit?
YES
Is there voltage to
output of cabinet limit?
YES
Is there voltage to input
of stove limit?
YES
Is there voltage to the
output side of the stove
limit?
YES
NO
NO
NO
NO
Correct wiring
between cabinet
limit and terminal
5 of fan motor
centrifugal switch.
Replace cabinet
limit.
Correct wiring
between stove limit
and cabinet limit.
Replace stove limit.
Is there voltage to
terminal 1 of ICM
board?
YES
Is there voltage across
the coils of the gas
valve?
YES
Is there gas flow
through the valve?
YES
NO
Does the ignitor spark?
NO
NO
NO
YES
YES
Replace ICM board.
Correct wiring to
gas valve coils.
Replace the coils or
complete gas valve.
Unit is operational.Is there a flame?
Check gas
pressures and
adjust if necessary.
NO
Is the unit equipped
with gas heat or
electric heat?
GAS
Is there voltage to
terminal 2 of ICM
board?
YES
70284701 87
ELECTRIC
NO
Correct wiring
between ICM board
and stove limit.
UNIT
OPERATIONAL.
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Replace igniter or
ignition cable.
Is there voltage across
HC1 & HC2 coils?
YES
Do the elements
produce heat?
YES
NO
NO
Correct the wiring
to the HC1 and/or
HC2 coils.
Correct wiring
between supply,
contacts and
elements. Replace
contactors and/or
elements if necessary.
T012D
T012D
Page 90
Section 7 Electronic Control Troubleshooting
81. WILL NOT HEAT – GAS – EDC MODELS
(Sheet 1 of 2)
Note: Tests are conducted with unit
running and calling for heat.
All voltage checks are referenced
to transformer neutral.
Is there voltage on
FS-2 of EDC control?
YES
Replace
thermistor.
Is there voltage
on FS-1 of
EDC control?
YES
Is there voltage on
COM of airflow
NO
switch?
YES
Single and stacked
NO
NO
Is the
thermistor
operational?
NO
units.
Correct wiring
between FS-2 and
COM of lint
panel switch.
Replace EDC
control.
YES
Correct wiring
between COM of
airflow switch and
FS-1 of EDC
control.
Is there voltage on
terminal 3 of fan
motor centrifugal
switch?
YES
Is there voltage across
terminals 3 & 5 of
fan motor centrifugal
switch?
NO
Is there voltage to the
input side of the
cabinet limit?
YES
NO
YES
NO
Correct wiring
between terminal
3 of fan motor
centrifugal switch
and terminal 4 of
motor control relay.
Replace fan motor.
Correct wiring
between cabinet
limit and terminal
5 of fan motor
centrifugal switch.
Is there voltage across
COM & N.C. terminal
of airflow switch?
NO
Is there voltage on
terminal 7 of motor
control relay?
YES
Is there voltage across
terminals 7 & 4 of
motor control relay?
NO
YES
NO
YES
Check for proper
function of airflow
switch and replace
if necessary.
Correct wiring
between terminal
7 on motor
control relay and
N.C. terminal on
airflow switch.
Replace motor
control relay.
Is there voltage across
cabinet limit?
NO
Is there voltage to the
input side of the stove
limit?
YES
Continued on next
page.
YES
NO
Replace cabinet
limit.
Correct wiring
between stove limit
and cabinet limit.
TMB1833S
TMB1833S
88 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 91
WILL NOT HEAT – GAS – EDC MODELS
(Sheet 2 of 2)
Section 7 Electronic Control Troubleshooting
Is there voltage to the
output side of the stove
limit?
YES
Is there voltage to
terminal 2 of the ICM
board?
YES
Is there voltage at terminal 1 of ICM
board?
YES
Is there voltage across
the coils of the gas
valve?
NO
NO
NO
NO
Replace the stove
limit.
Correct wiring
between terminal
2 of ICM board
and stove limit.
Replace ICM board.
Correct wiring
between gas valve
and ICM board.
NO
YES
Unit operational.Is there a flame?
YES
Is there gas flow
through the gas valve?
YES
Does the igniter spark?
YES
NO
NO
Replace gas valve
coils or complete
gas valve.
Replace high voltage ignition cable or igniter.
T033D
T033D
70284701 89
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 92
Section 7 Electronic Control Troubleshooting
82. WILL NOT HEAT – GAS – MANUAL TIMER
(Sheet 1 of 2)
NOTE: The following tests are conducted with
the Heat Timer in the "ON" position with the
machine running and calling for heat. Voltage
checks are referenced to transformer neutral.
Is there voltage across
terminals 1 & 6 of
the temp control bd?
YES
YES
Is there voltage across
terminals 5 & 6 of
the temp control bd?
NO
Is the thermistor
shorted or open?
NO
NO
YES
Single and stacked units with and without time
Replace thermistor.
delay boards.
YES
Is
there voltage at
airlow switch
N.C. terminal to
transformer
neutral?
YES
Is there voltage at terminal 6 on CR1 to transformer neutral?
YES
Is there voltage from
terminal 4 on CR1 to
transformer neutral?
YES
Is unit equipped with
time delay board?
Replace inoperative
NO
switch or correct
airflow vane operation.
Correct wiring between
NO
airlow switch and
terminal 6 on CR1.
NO
Replace CR1.
Is the temperature
selection switch
shorted or open?
temperature
control board.
CONTINUED
ON NEXT
PAGE
NO
Replace the
YES
temp control board
Replace selection
Is there
voltage to
terminal 3 of
fan motor?
YES
Is
there voltage
across terminal
3 & 5 of fan
motor?
NO
Correct wiring
between motor
terminal 5 and
terminal 1.
switch.
NO
YES
Correct wiring
between fan motor
terminal 3 and CR1
terminal 4.
Replace fan motor.
NO
Is there voltage from terminal 6 on CR2 to transformer neutral?
YES
Is there voltage from terminal 4 on CR2 to transformer neutral?
YES
Correct wiring
between CR2
terminal 4 &
terminal 1 on
temp control
board.
NO
NO
Correct wiring between terminal 6 on CR2 to terminal
4 on CR1.
Replace CR2.
T044D
T044D
90 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 93
WILL NOT HEAT – GAS – MANUAL TIMER
(Sheet 2 of 2)
Note: Voltage checks are referenced to
transformer neutral.
Section 7 Electronic Control Troubleshooting
Is there voltage to the
input side of the
cabinet limit?
YES
Is there voltage to the
output side of the
cabinet limit?
YES
Is there voltage to the
input side of the stove
limit?
YES
Is there voltage to the
output side of the stove
limit?
NO
NO
NO
NO
Correct wiring
between cabinet
limit and temp
control board.
Replace the cabinet
limit.
Correct wiring
between stove limit
and cabinet limit.
Replace the stove
limit.
NO
Is there voltage across
the coils of the gas
valve?
YES
Is there gas flow
through the gas valve?
YES
Does the igniter spark?
YES
Is there a flame?
NO
between gas valve
NO
NO
Correct wiring
and ICM board.
Replace gas valve
or gas valve coils.
Replace high
voltage cable or
igniter.
YES
Is there voltage across
terminals 2 & 3 of
ICM board?
YES
Is there voltage across
terminals 1 & 3 of
the ICM board?
YES
NO
NO
Correct wiring
between ICM board
and stove limit.
Replace ICM board
YES
UNIT OPERATIONAL
TMB1834S
TMB1834S
70284701 91
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 94
Section 7 Electronic Control Troubleshooting
83. WILL NOT HEAT – GAS – ROTARY COIN DROP
(Sheet 1 of 2)
Single and stacked
tumblers with
and without time delay.
YES
Is there voltage across
terminals 1 & 6 of
the temp control bd?
YES
Is there voltage across
terminals 5 & 6 of
the temp control bd?
NO
Is the thermistor
shorted or open?
NO
Is temperature
selection switch
shorted or open?
NO
Replace the
temperature
control board.
Is there voltage on
terminal 3 of fan motor
to transformer
neutral?
YES
NO
YES
Replace thermistor.
YES
NO
Replace selection
switch.
Correct wiring
between terminal
3 of fan motor
and N.C. terminal
on switch B.
YES
Is there voltage at
airflow switch N.C.
terminal to transformer
neutral?
YES
Is there voltage at
COM on switch B to
transformer neutral?
YES
Is there voltage from
N.C. on switch B to
transformer neutral?
YES
Is the unit equipped
with a time delay
board?
NO
Is there voltage from
terminal 6 on CR2 to
transformer neutral?
YES
Replace inoperative
NO
switch or correct
airflow vane operation.
Correct wiring
NO
between airflow
switch and COM on
switch B.
NO
Replace switch B.
Correct wiring
NO
between terminal 6
on CR2 to terminal
N.C. on switch B.
With fan motor
running is there voltage
from terminal 5 to
transformer
neutral?
YES
Is there voltage on
terminal 1 of temp
board to transformer
neutral?
YES
CONTINUED
ON NEXT
PAGE
92 70284701
Power supply to
temp control
board is good.
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
NO
Replace fan motor.
Correct wiring
between terminal
NO
1 of temp board
to terminal 5 of fan motor.
Is there voltage from
terminal 4 on CR2 to
transformer neutral?
YES
Correct wiring
between terminal
4 on CR2 &
terminal 1 on
temp control
board.
NO
Replace CR2.
T090D
T090D
Page 95
WILL NOT HEAT – GAS – ROTARY COIN DROP
(Sheet 2 of 2)
Note: Voltage checks are referenced to
transformer neutral.
Section 7 Electronic Control Troubleshooting
Is there voltage to the
input side of the
cabinet limit?
YES
Is there voltage to the
output side of the
cabinet limit?
YES
Is there voltage to the
input side of the stove
limit?
YES
Is there voltage to the
output side of the stove
limit?
NO
NO
NO
NO
Correct wiring
between cabinet
limit and temp control board.
Replace the cabinet limit.
Correct wiring
between stove limit
and cabinet limit.
Replace the stove
limit.
Is there voltage across
through the gas valve?
Does the igniter spark?
NO
the coils of the gas
valve?
YES
Is there gas flow
YES
YES
Is there a flame?
NO
between gas valve
NO
NO
Correct wiring
and ICM board.
Replace gas valve
coils or complete
gas valve.
Replace high
voltage ignition
cable or igniter.
YES
Is there voltage across
terminals 2 & 3 of
the ICM board?
YES
Is there voltage across
terminals 1 & 3 of
the ICM board?
YES
NO
NO
Correct wiring
between ICM
board and stove
limit or neutral.
Replace the ICM
board.
YES
UNIT
OPERATIONAL
T091D
T091D
70284701 93
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 96
Section 7 Electronic Control Troubleshooting
84. WILL NOT HEAT – STEAM – EDC MODELS
(Sheet 1 of 2)
Note: Tests are conducted with unit running
and calling for heat.
All voltage checks are referenced to
transformer neutral.
Is there voltage on
FS-2 of EDC control?
NO
Single and stacked
units.
Correct wiring
between FS-2 and
COM of lint drawer.
Is there voltage on
terminal 3 of fan
motor centrifugal
switch?
NO
Correct wiring
between terminal 3
of fan motor
centrifugal switch
and terminal 4 of
motor control relay.
Is there voltage
on FS-1 of
EDC control?
YES
Is there voltage on
COM of airflow
switch?
Is there voltage across
COM & N.C. terminal
of airflow switch?
YES
YES
NO
NO
Replace
thermistor.
Is the
thermistor
operational?
NO
YES
Replace EDC
control.
NO
YES
Correct wiring
between COM of
airflow switch and
FS-1 of EDC
control.
Check for proper
function of airflow
switch and replace if
necessary.
YES
Is there voltage across
terminals 3 & 5 of
fan motor centrifugal
switch?
NO
Is there voltage to the
input side of the
cabinet limit?
YES
Is there voltage across
cabinet limit?
NO
YES
NO
YES
Replace fan motor.
Correct wiring
between cabinet
limit and terminal 5
of fan motor
centrifugal switch.
Replace cabinet
limit.
Is there voltage on
terminal 7 of motor
control relay?
YES
Is there voltage across
terminals 7 & 4 of
motor control relay?
NO
94 70284701
NO
YES
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Correct wiring
between terminal 7
on motor control
relay and N.C.
terminal on airflow
switch.
Replace motor
control relay.
Is there voltage to the input side of the stove
limit?
YES
Continued on next
page.
NO
Correct wiring
between stove limit
and cabinet limit.
T096D
T096D
Page 97
WILL NOT HEAT – STEAM – EDC MODELS
(Sheet 2 of 2)
Section 7 Electronic Control Troubleshooting
Is there voltage to the
output side of the stove
limit?
YES
Is there voltage across
steam valve coil?
YES
Does steam valve
operate properly?
YES
NO
NO
NO
Replace the stove
limit.
Correct wiring to
steam valve coil.
Repair or replace
steam valve.
Is heat produced?
YES
Unit operational.
NO
Check for proper
steam supply.
Correct if necessary.
T097D
T097D
70284701 95
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 98
Section 7 Electronic Control Troubleshooting
85. WILL NOT HEAT – STEAM – MANUAL TIMER
(Sheet 1 of 2)
NOTE: The following tests are conducted with
the Heat Timer in the "ON" position with the
machine running and calling for heat. Voltage
checks are referenced to transformer neutral.
Is there voltage across
terminals 1 & 6 of
the temp control bd?
YES
YES
Is there voltage across
terminals 5 & 6 of
the temp control bd?
NO
Is the thermistor
shorted or open?
NO
NO
YES
Single and stacked units with and without time
delay boards, manual timers.
Replace thermistor.
YES
Is there voltage at
airflow switch N.C.
terminal to transformer
neutral?
YES
Is there voltage at
terminal 6 on CR1 to
transformer neutral?
YES
Is there voltage from terminal 4 on CR1 to transformer neutral?
YES
Is unit equipped with
time delay board?
Adjust the airflow
NO
switch or replace if
NO
terminal 6 on CR1.
NO
inoperative.
Correct wiring
between airflow
switch and
Replace CR1.
Is temperature
selection switch
shorted or open?
temperature
control board.
CONTINUED
ON NEXT
PAGE
NO
Replace the
YES
Replace selection
Is there
voltage to
terminal 3 of
fan motor?
YES
Is there voltage across terminal
3 & 5 of fan
motor?
NO
Correct wiring between motor terminal 5 and
temp control
board terminal 1.
switch.
NO
YES
Correct wiring
between fan motor
terminal 3 and
CR1 terminal 4.
Replace fan motor.
NO
Is there voltage from terminal 6 on CR2 to transformer neutral?
YES
Is there voltage from terminal 4 on CR2 to transformer neutral?
YES
Correct wiring
between CR2
terminal 4 & terminal 1 on temp control
board.
NO
between terminal 6
on CR2 to terminal
NO
Correct wiring
4 on CR1.
Replace CR2.
T019D
T019D
96 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 99
WILL NOT HEAT – STEAM – MANUAL TIMER
(Sheet 2 of 2)
Note: Voltage checks are referenced to
transformer neutral.
Section 7 Electronic Control Troubleshooting
Is there voltage to the
input side of the
cabinet limit?
YES
Is there voltage to the
output side of the
cabinet limit?
YES
Is there voltage to the
input side of the stove
limit?
YES
Is there voltage to the
output side of the stove
limit?
NO
NO
NO
NO
Correct wiring
between cabinet
limit and temp
control board.
Replace the cabinet
limit.
Correct wiring
between stove limit
and cabinet limit.
Replace the stove
limit.
Is heat produced?
YES
UNIT OPERATIONAL
Check for proper
NO
steam supply.
Correct if necessary.
YES
Is there voltage across
the coil of the steam
valve?
YES
Do the steam valves
operate properly?
YES
NO
NO
Correct wiring to
the steam valve.
Replace steam
valve.
T020D
T020D
70284701 97
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 100
Section 7 Electronic Control Troubleshooting
86. WILL NOT HEAT – STEAM – OPL MICROPROCESSOR
(Sheet 1 of 3)
Testing conducted with unit running and calling for heat.
Reference voltage to
transformer neutral
terminal 3.
Is there votlage at
terminal 5 on OPL
Micro?
YES
Continued on next
page column 2.
Is there voltage across
terminals 2 & 3 of
transformer
secondary?
NO
Replace
transformer.
NO
Is the thermister
operating properly?
YES
Reference voltage to
supply neutral.
Is power supplied to
unit?
YES
Is there voltage to input
of primary fuse(s)?
YES
NO
NO
NO
Replace thermister.
Connect supply
and run unit.
Correct wiring
between primary
fuse and supply.
YES
Note: Reference voltage to
transformer secondary neutral
Is there voltage to input
of secondary fuse?
YES
Is there voltage to
output of secondary
fuse?
YES
Is there voltage to
N.O terminal of door
switch?
YES
terminal 3.
NO
NO
NO
Correct wiring
between secondary
fuse and
transformer.
Replace secondary
fuse.
Correct wiring between N.O.
terminal of door
switch and
secondary fuse.
Is there voltage to
output of primary
fuse(s)?
YES
Is
there voltage across
terminals 1 & 2 on
primary of
transformer?
YES
98 70284701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
NO
NO
between transformer
Change primary
fuse.
Correct wiring
and primary fuse.
With door closed is
there voltage to COM
of door switch?
YES
Is there voltage to
N.O. of lint panel
switch?
YES
Continued on next
page column 1.
NO
NO
Check for proper
operation, replace
door switch if
necessary.
Correct wiring
between N.O. of
lint panel switch
and COM of door
switch.
T003D
T003D
Loading...