Pridiom POM273HX, POM365HX, POM182HX Service Manual

Page 1
CONTENTS
1. General information of Outdoor Units................................................................................................... 3
2. Dimensions.............................................................................................................................................. 4
3. Wiring Diagram........................................................................................................................................ 5
4. Refrigeration Cycle Diagram.................................................................................................................. 7
5. Indoor units combination ....................................................................................................................... 8
6. Electronic control function..................................................................................................................... 9
7. Troubleshooting.................................................................................................................................... 14
Page 2
1. General information of Outdoor Units
The hydrophilic fin can improve the heating efficiency at operation mode.
It is only operated in the heating operation mode except defrosting operation.
It protects the valves and prevents water from dripping.
Outdoor unit
Power relay control
Hydrophilic aluminum fin
Anti-rust cabinet
Valve protection cover
4 way valve control
Low noise air flow system
Discharge pipe temperature protection
Compressor crankcase heater
Page 3
2. Dimensions
a)320+;
b) 320+;
Page 4
3. Wiring Diagram
3.1 320+;
3.2 320+;
Page 5
3.3 320+;
Page 6
4. Refrigeration Cycle Diagram
4.1 Refrigeration circuit drawing of inverter binary type
4.2 Refrigeration circuit drawing of inverter trinary type
4.3 Refrigeration circuit drawing of inverter quadplex type
Liquid valve A
Gas valve C
EXV C
4-way valve
Compressor
Condense
r
A
xial flow fan
EXV B
EXV A
Gas valve A
Gas valve B
Liquid valve C
Liquid valve B
Evaporato
r
Cross
flow fan
Indoor Unit
Capillary A
Capillary B
Capillary C
Filter A
Filter B
Filter C
Main Capillary
A
uxiliary
Capillary
Check Valve
Exhaust temp. senso
r
Indoor pipe out temp. sensor B
Indoor pipe ou
t
temp. sensor A
Indoor pipe out temp. sensor C
Outdoor Unit
Coil temp. senso
r
Indoor Unit
Cross
flow fan
Evaporato
r
Liquid valve A
Liquid valve B
Gas valve B
Gas valve A
EXVA
EXVB
A
xial
flow fan
Condense
r
Compressor
4-way valve
A
uxiliary
Capillary
Capillary A
Capillary B
Exhaust temp. senso
r
Indoor pipe ou
t
temp. sensor A
Indoor pipe out temp. sensor B
Filter A
Filter B
Outdoor Unit
Main Capillary
Check Valve
Coil temp. senso
r
Page 7
5. Indoor units combination
5.1 Indoor unit combination for 320+;
One unit Two unit
9 9+9 9+12
12
5.2 Indoor unit combination for 320+;
One unit Two unit Three unit
9 9+9 9+12 9+9+9 9+9+12
12 12+12
5.3 Indoor unit combination for 320+;
One unit Two unit Three unit Four unit
9 9+9 9+12 9+9+9 9+9+12 9+9+9+9 9+9+9+12 9+9+12+12
12 12+12 9+12+12 12+12+12
Page 8
6. Electronic control function
6.1 Abbreviation
T1: Indoor ambient temperature
T2: Coil temperature of indoor heat exchanger middle.
T2B: Coil temperature of indoor heat exchanger outlet.
T3: Coil temperature of outdoor heat exchanger
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
Ts: Setting temp.
6.2 Electric control working environment.
6.2.1 Input voltage: 230V.
6.2.2 Input power frequency:60Hz.
6.2.3 Indoor fan normal working amp. is less than 1A.
6.2.4 Outdoor fan. Normal working amp. is less than 1.5A.
6.2.5 Four-way valve normal working amp. is less than 1A.
6.2.6 Swing motor: DC12V.
6.3 Outdoor unit’s digital display tube
There is a digital display tube in outdoor PCB. Digital display tube display function
In standby , the LED displays “- -”
In compressor operation, the LED display the running frequency,
In defrosting mode, The LED displays “dF” or alternative displays between running frequency and
“dF”(each displays 2s)
In compressor pre-heating, The LED displays “- -”
In protection or malfunction, the LED displays error code or protection code.
6.4 Outdoor unit point check function
There is a check switch in outdoor PCB. Push the switch SW1 to check the states of unit when the unit is running. The digital display tube will display
the follow procedure when push SW1 each time.
Display Remark
1
Indoor unit capacity demand code
2
Outdoor unit running mode code Off:0, Cooling:1, Heating:2
3
Amendatory capacity demand code
4
Outdoor unit fan motor state Off:0, Low speed:1, High speed:2
5
Evaporator outlet temp. for 1# indoor unit Actual data
6
Evaporator outlet temp. for 2# indoor unit Actual data
7
Evaporator outlet temp. for 3# indoor unit Actual data
8
Evaporator outlet temp. for 4# indoor unit Actual data
9
Condenser pipe temp. Actual data
10
Ambient temp. Actual data
11
Compressor discharge temp. Actual data
12
Inverter current Actual data
13
EXV open angle for 1# indoor unit Actual data divide 8
Page 9
14
EXV open angle for 2# indoor unit Actual data divide 8
15
EXV open angle for 3# indoor unit Actual data divide 8
16
EXV open angle for 4# indoor unit Actual data divide 8
17
Power supply of outdoor unit AD data
18 Indoor unit number The indoor unit can communicate with outdoor unit well.
19 The last error or protection code 00 means no malfunction
20
frequency value Actual data
21 Ambient temp. of 1# indoor unit Actual data
22 Condenser pipe temp. of 1# indoor unit Actual data
23
Ambient temp. of 2# indoor unit Actual data
24 Condenser pipe temp. of 2# indoor unit Actual data
25 Ambient temp. of 3# indoor unit Actual data
26
Condenser pipe temp. of 3# indoor unit Actual data
27 Ambient temp. of 4# indoor unit Actual data
28 Condenser pipe temp. of 4# indoor unit Actual data
29
―― Check point over
The following items from 6.4.1 to 6.4.6 are for the explanation of the point check functions.
6.4.1 Frequency of compressor:
Display Frequency of compressor (Hz)
30 30
-- Stand by
60 60
6.4.2 Running mode:
Display Corresponding mode
0 Off
1 Cooling mode
2 Heating mode
6.4.3 Capacity demand: Cooling mode
Capacity 2000-2
500
2000-2 500
3000-3 800
4500-5 000
5000-5 500
5500-6 100
6100-7 000
7000-7 500
7500-8 000
>7500
Correspondi ng Code
1 2 3 4 5 6 7 8 9 >=10
Heating mode
Capacity 2000-2
500
2000-2 500
3000-3 800
4500-5 000
5500-6 100
6100-7 000
6100-7 000
7000-7 500
7500-8 000
>8000
Correspondin g Code
1 2 3 4 5 6 7 8 9-10 >=11
Note: The capacity is just for reference.
Page 10
6.4.4Number of indoor unit
Display Number of indoor unit
1 1
2 2
3 3
6.4.5 Outdoor ambient temp:
Display Corresponding temp. Display
Corresponding
temp.
Display
Corresponding
temp.
15 -7.5 50 10 80 25
16 -7 51 10.5 81 25.5
17 -6.5 52 11 82 26
18 -6 53 11.5 83 26.5
19 -5.5 53 11.5 84 27
20 -5 54 12 85 27.5
21 -4.5 55 12.5 86 28
22 -4 56 13 87 28.5
23 -3.5 57 13.5 88 29
24 -3 58 14 89 29.5
26 -2 59 14.5 90 30
27 -1.5 60 15 91 30.5
28 -1 61 15.5 92 31
29 -0.5 62 16 93 31.5
30 0 63 16.5 93 31.5
31 0.5 63 16.5 94 32
32 1 64 17 95 32.5
33 1.5 65 17.5 96 33
34 2 65 17.5 97 33.5
35 2.5 66 18 98 34
36 3 67 18.5 99 34.5
37 3.5 68 19
10.
35~40
38 4 69 19.5
11.
40~45
39 4.5 70 20
12.
45~50
40 5 71 20.5
13.
50~55
41 5.5 72 21
14.
55~60
42 6 73 21.5
15.
60~65
43 6.5 74 22
16.
65~70
44 7 75 22.5
45 7.5 75 22.5
46 8 76 23
47 8.5 77 23.5
48 9 78 24
49 9.5 79 24.5
Page 11
6.4.6 Opening degree of electronic expansion valve: Actual opening degree equals the display data divided 8
6.5 Protection
6.5.1 Three minutes delay at restart for compressor.
6.5.2 Temperature protection of compressor discharge.
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
----If 102<T5<115 , decrease the freq uency to the lower level every 2 minutes till to F1.
---If T5>115 for 10 seconds, the compressor will stop and restart till T5<90℃.
6.5.3 Low voltage protection
VOLLIMT1
VOLTAGE
No li mit
VOLLIMT2
VOLLIMT3
Off
VOLFRE2
VOLFRE1
VOLREL1
VOLREL2
VOLREL3
Model VOLLIMT1 VOLLIMT2 VOLLIMT3 VOLREL1 VOLREL2 VOLREL3 VOLFRE1 VOLFRE2
320+; 230 200 120 260 210 135 62 54 32M3+; 245 220 120 265 240 135 78 45
POM365HX 200 185 120 210 195 135 54 42
Note: if the low voltage protection occurs and not resumes within 3min, it will keep the protection always after restart the machine.
6.5.4 Compressor current limit protection
If the compressor current exceeds the current limit value for 10 seconds, the compressor frequency will be limited as below table.
Cooling mode:
Current frequency(Hz) Current limit value(A) Frequency limit
COOL_F10 ICOOLLMT6
COOL_F9 ICOOLLMT5
COOL_F8 ICOOLLMT4
COOL_F7 ICOOLLMT3
COOL_F6 ICOOLLMT2
COOL_F5 ICOOLLMT1
Decrease the frequecny to COOL_F4 and run at COOL_F4 for 3 minutes.
After that,the frequency will be adjusted according to the capacity demand and rise to the upper level every 3 minutes
(When the frequency>COOL_F4 via capacity demand).
If the current frequency is lower than COOL_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>ICOOL,the AC will display the failure for 30 seconds and stop. The AC will restart 3 minutes later.
Heating mode:
Current frequency(Hz) Current limit value(A) Frequency limit
HEAT_F12 IHEATLMT8
HEAT_F11 IHEATLMT7
HEAT_F10 IHEATLMT6
HEAT_F9 IHEATLMT5
HEAT_F8 IHEATLMT4
Decrease the frequency to HEAT_F4 and run at HEAT_F4 for 3 minutes.
After that, the frequency will be adjusted according to the capacity demand and rise to the upper level every 3 minutes
Page 12
HEAT_F7 IHEATLMT3
HEAT_F6 IHEATLMT2
HEAT_F5 IHEATLMT1
(When the frequency>Heat_F4 via capacity demand).
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT,the AC will display the failure for 30 seconds and stop. The AC will restart 3 minutes later.
6.5.5 Indoor / outdoor units communication protection
If the indoor units can not receive the feedback signal from the outdoor units for 2 minutes, the AC will stop and display the failure.
6.5.6 High condenser coil temp. protection.
When T3>65 for 3 seconds, the compressor will stop while the indoor fan and outdoor fan will continue.
When T3<52 , the protection will release and the compressor will restart after 3 minutes.
6.5.7 Outdoor unit anti-freezing protection
When T2B<0 for 250 seconds, the indoor unit capacity demand will be zero and resume to normal when T2B>10 .
6.5.8 Oil return Running rules:
1. If the compressor frequency keeps lower than RECOILINFRE for 2hours,the AC will rise the frequency to RECOILFRE for 3mins and then resume to former frequency.
Model RECOILINFRE
POM182HX 45
POM273HX 45
POM365HX 40
2. During the oil return process, the EXV and indoor units keep the current running mode, the frequency will not be limited by the compressor discharge temp. and the current.
6.5.9 Compressor preheating functions
----Preheating permitting condition:
If T4(outdoor ambient temperature)3 and newly powered on or if T4<3 and compressor has stopped
for over 3 hours, the compressor heating cable will work.
----Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of compressor, then the
compressor is heated without operation.
----Preheating release condition:
If T45 or the compressor starts running, preheating function will stop.
6.5.10 Compressor crankcase heater
When T4<3 and the compressor is not running,the crankcase heater will be active. When T4≧5 or the compressor starts up,the crankcase heater will stop work.(For M5OA-36HRDN1-Q,T4
8)
Page 13
7. Troubleshooting
7.1 Indoor unit error code explanation:
Vertu series:
Display LED STATUS
E0 EEPROM error
E1 Communication error between indoor and outdoor unit
E2 Zero-crossing examination error
E3 Fan speed beyond control
E5 Outdoor units temp. sensor or connector of temp. sensor is defective
E6 Indoor units temp. sensor or connector of temp. sensor is defective
P0 Inverter module protection
P1 Outdoor voltage too low protection
P2 Compressor discharge temp. protection
P3 Outdoor temp. too low protection
P4 Compressor driving protection
7.2
Outdoor unit error code explanation:
Display LED STATUS
E0 EEPROM error
E1 No 1 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
E2 No 2 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
E3 No 3 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
E6 No 4 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
E4 Outdoor temp. sensor or connector of temp. sensor is defective
E5 Compressor volt protection
E7 Communication error between outdoor IC and DSP
P0 Compressor discharge temp. protection
P1 High pressure protection (just for 36K 1x4 units.)
P2 Low pressure protection (just for 36K 1x4 units.)
P3 Compressor current protection
P4 Inverter module protection
P5 Outdoor temp. too low protection
P6 Condenser high-temperature protection
P7 Compressor driving protection
PF PFC protection
Page 14
7.3Trouble shooting
7.3.1 Indoor unit trouble shooting
Indoor unit display LED STATUS
E0 EEPROM error
Indoor unit display LED STATUS
E1 outdoor communication error
Indoor unit display LED STATUS
E2 Zero-crossing examination error
Circuit or software error on indoor PCB
Replace indoor PCB
Disconnect the power supply, after 1 minute, connect the power supply, turn on the unit with remote controller
Does the unit work normally ?
Check the wiring between indoor and outdoor unit. Is the connection of L, N, S and GND good?
Is the GND connection on outdoor PCB good?
NO
NO
Reconnect and retest again
Is the LED4(red) on outdoor PCB bright and LED1(yellow) blinking?
Replace outdoor e-box.
Ye s
Ye s
The power supply for outdoor PCB is fail. Check the wiring on outdoor PCB comparing with wiring plate. Is the connection good?
No
Correc
t the connection.
Ye s
No
Replace indoor PCB and repower on. Is
Page 15
Indoor unit display LED STATUS
E3 Fan speed beyond control
Indoor unit display LED STATUS
E5 Outdoor units temp. sensor or connector of temp. sensor is defective
Indoor unit display LED STATUS
E6 Indoor units temp. sensor or connector of temp. sensor is defective
Is the outdoor temperature sensor connector and
connection good
?
Repair the connector and
Replace the sensor and check if E5 dis
play ag
ain?
NO
YES
Replace outdoor e-box
YES
Is the indoor fan motor connector and connection
good
?
Repair the connector and
Is voltage being applied to the fan motor?
(rang 90v-160v between mid pin and N on CN1
NO
YES
Indoor PCB is defective.
YES
Replace the indoor fan
NO
Is power supply and connection of connectors
good
?
Indoor PCB is defective. Replace the indoor PCB.
Be sure the power supply is good and correct the connection
NO
YES
Page 16
Indoor unit display LED STATUS
P0 Inverter module protection
Indoor unit display LED STATUS
P1 Outdoor voltage protection
Is the power supply good?
Be sure the power supply is
NO
YES
Replace the outdoor e-box.
Revise the power and retest.
Is voltage normal?
NO
YES
Is all connection good?
NO
Revise the power and retest.
YES
Is the wiring to compressor ri
g
ht?
YES
Check the modular if some components blow out or be failure?
YES
Repair or replace the modular.
YES
Is it breakdown between P-N, P-V, P-W, N-V,N-W or V-W of inverter moduler?
YES
Replace the modular.
YES
Check the compressor.
Is the indoor temperature and evaporator sensor connector and connection good?
Repair the connector and
Replace the sensor and check if E6 dis
play ag
ain?
NO
YES
Replace the.indoor PCB
YES
Page 17
Indoor unit display LED STATUS
P2 Compressor top protection against temperature
Indoor unit display LED STATUS
P3 Compressor current protection
The trouble shooting is same with one of outdoor unit P3 protection.
8.4.1 Outdoor unit trouble shooting
Outdoor unit display LED STATUS
E0 EEPROM error
Outdoor unit display LED STATUS
E1
No 1 Indoor units pipe temp. sensor or connector of pipe temp. sensor is
defective
Circuit or software error on indoor
Replace indoor
YES
Does compressor
Is the connection
g
ood?
Is refrigerant circulation
NO
NO
Charge refrigerant
Is abnormality the same after
NO
Check refrigerant system
(such as clogging of cap
illary,
Reconnect and retest.
NO
YES
Is protector normal?
Replace the protector.
NO
YES
Check the outdoor main PCB. Is there
Replace the outdoor PCB.
YES
Page 18
Outdoor unit display LED STATUS
E2
No 2 Indoor units pipe temp. sensor or connector of pipe temp. sensor is
defective
Outdoor unit display LED STATUS
E3
No 3 Indoor units pipe temp. sensor or connector of pipe temp. sensor is
defective
Outdoor unit display LED STATUS
E6
No 4 Indoor units pipe temp. sensor or connector of pipe temp. sensor is
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
Replace the sensor
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
Replace the sensor
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
Replace the sensor
Page 19
defective
Outdoor unit display LED STATUS
E4 Outdoor units temp. sensor or connector of temp. sensor is defective
Outdoor unit display LED STATUS
E5 Compressor volt protection
Yes
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Replace the sensor
Is connection to connector of pipe temp. sensor good?
Check the resistance of the temp. sensor according to Annex 1
Repair connector
No
Yes
Replace the sensor
Page 20
Yes
Check the voltage of power supply, if the voltage is about 220V, turn off the power supply to indoor unit and turn it on again after 1 minute
Does the trouble occur again?
Check the voltage of secondary of T3 transformer in outdoor power board , is this voltage 12-14V(AC)
No
Replace the outdoor power board
Page 21
Outdoor unit display LED STATUS
E7 outdoor units communication protection
Outdoor unit display
LED STATUS
P0 Compressor top protection against temperature
Is the LED in outdoor main PCB light?
1.Is the +5 voltage in outdoor main board?
Power Board: CN4, Red wire and yellow (GND)
Outdoor main PCB: CZ1
2.Is the +3.3v voltage in outdoor main board?
Power Board: CN1, Purple wire and yellow (GND)
Inverter module defective.
Rectifier circuit is bad connection or defective when the voltage in outdoor is abnormal .
D and N: 310V(DC);
No
Yes
No
Yes
Check the signal wires between outdoor
PCBs, is it connected good.
Check the IC6, IC7 (at Outdoor power PCB)
Normally:
Input voltage: <5V, changeable
Output voltage:<5V, changeable
Outdoor power PCB is defective.
No
Page 22
Off: 105c; On: 90c
The trouble shooting is same with the one of indoor unit P2 protection.
Outdoor unit display
LED STATUS
P3 Compressor current protection
Outdoor unit display
LED STATUS
P4
Compressor drive malfunctiondrive protection arose
Check the resistance of compressor, normally
U and V is 1 ohm
U and W is 1 ohm
V and W is 1ohm
Turn one indoor unit only, Does the compressor start after 3 minutes?
Does the trouble occur again after compressor running some time?
No
Yes
No
The compressor is defective
Check the refrigerant circulation volume and pressure
No
The compressor is defective
Yes
If refrigerant circulation volume and pressure is OK, change the outdoor main PCB.
Page 23
Outdoor unit display LED STATUS
P4(LED flashes for nine times)
Compressor drive malfunctionmodule protection arose
Outdoor unit display LED STATUS
Are the U,V,W connected to compressor and inverter module
Replace the module to see if it is normal
Replace the outdoor power board
If the problem comes to again, check wingding resistance of inverter compressor, is it right?
Replace inverter compressor
Repair connector
Yes No
No
Replace inverter compressor
Repair connector
If the problem comes to again, check wingding resistance of inverter compressor, is it 1 ohm?
Replace the outdoor power board
Are the U,V,W connected to compressor and inverter module right?
Yes
No
No
Page 24
P6 Condenser high-temperature protection
When outdoor pipe temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temp. less than 52°C.
Annex 1
Characteristic of temp. sensor
Temp. Resistance K Temp. Resistance K Temp. Resistance K
-10 62.2756 17 14.6181 44 4.3874
-9 58.7079 18 13.918 45 4.2126
-8 56.3694 19 13.2631 46 4.0459
-7 52.2438 20 12.6431 47 3.8867
-6 49.3161 21 12.0561 48 3.7348
-5 46.5725 22 11.5 49 3.5896
-4 44 23 10.9731 50 3.451
-3 41.5878 24 10.4736 51 3.3185
-2 39.8239 25 10 52 3.1918
-1 37.1988 26 9.5507 53 3.0707
0 35.2024 27 9.1245 54 2.959
1 33.3269 28 8.7198 55 2.8442
2 31.5635 29 8.3357 56 2.7382
Is the outdoor pipe temp. more than 65°C ?
Is the outdoor pipe temp sensor right according to the annex 1
Replace the outdoor main board
No
Yes
Replace the outdoor pipe temp sensor
No
Page 25
3 29.9058 30 7.9708 57 2.6368
4 28.3459 31 7.6241 58 2.5397
5 26.8778 32 7.2946 59 2.4468
6 25.4954 33 6.9814 60 2.3577
7 24.1932 34 6.6835 61 2.2725
8 22.5662 35 6.4002 62 2.1907
9 21.8094 36 6.1306 63 2.1124
10 20.7184 37 5.8736 64 2.0373
11 19.6891 38 5.6296 65 1.9653
12 18.7177 39 5.3969 66 1.8963
13 17.8005 40 5.1752 67 1.830
14 16.9341 41 4.9639 68 1.7665
15 16.1156 42 4.7625 69 1.7055
16 15.3418 43 4.5705 70 1.6469
Page 26
Annex 2
1. Reference voltage data:
a) Rectifier : Input :220-230V(AC), output :310V(DC)
b) Inverter module: U,V, W 3ph.
Result
U-V 60-150V(AC)
U-W 60-150V(AC)
V-W 60-150V(AC)
P-N DC
31 0V
c) Photo-couple PC817, PC851: Control side <+5V, AC side :< 24V(AC)
d) S terminal and N: changeable from 0-24V
2. Check the Diode Bridge component ( In wiring diagram, rectifier)
Remark: If this part is abnormal, the LED will not light.
Result
Multi-meter
Forward Resistance Backward Resistance
+ _ Infinite Infinite ~ ~
+
~500 ohm Infinite
~ ­~
~500 ohm Infinite
~ +
- ~