TEST OPERATION.................................................................
1
2
3
4
4
11
15
18
19
20
21
1. PRECAUTIONS
Keep this manual where the operator can easily find them.
Read this manual attentively before starting up the units.
For safety reason the operator must read the following
cautions carefully.
The safty precautions listed here are divided into two categories.
WARNING
If you do not follow these instrutions exactly, the unit may
cause property damage, personal injury or loss of life.
CAUTION
If you do not follow these instrutions exactly, the unit may
cause minor or moderate property damage, personal
After completing the installation, make sure that the unit operates
properly during the start-up operation. Please instruct the customer
on how to operate the unit and keep it maintained.Also, inform
customers that they should store this installation manual along with
the owner's manual for future reference.
WARNING
Be sure only trained and qualified service personnel to
install, repair or service the equipment.
Improper installation, repair, and maintenance may result in
electric shocks, short-circuit, leaks, fire or other damage to
the equipment.
electrical shock and fire.
When installing the unit in a small room, take measures
against to keep refrigerant concentration from exceeding
allowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for more information.
Excessive refrigerant in a closed ambient can lead to oxygen
deficiency.
Use the attached accessories parts and specified parts
for installation.
otherwise, it will cause the set to fall, water leakage,
electrical shock and fire.
Install at a strong and firm location which is able to
withstand the set' s weight.
If the strength is not enough or installation is not properly
done, the set will drop to cause injury.
The appliance must be installed 2.3m above floor.
The appliance shall not be installed in the laundry.
Before obtaining access to terminals, all supply circuits
must be disconnected.
The appliance must be positioned so that the plug is
accessible.
The enclosure of the appliance shall be marked by word,
or by symbols, with the direction of the fluid flow.
For electrical work, follow the local national wiring
standard, regulation and this installation instructions. An
independent circuit and single outlet must be used.
If electrical circuit capacity is not enough or defect in
electrical work, it will cause electrical shock or fire.
Use the specified cable and connect tightly and clamp
the cable so that no external force will be acted on the
terminal.
If connection or fixing is not perfect, it will cause heat-up or
fire at the connection.
Wiring routing must be properly arranged so that control
board cover is fixed properly.
If control board cover is not fixed perfectly, it will cause
heat-up at connection point of terminal, fire or electrical
shock.
If the supply cord is damaged, it must be replaced by the
manufacture or its service agent or a similarly qualified
person in order to avoid a hazard.
An all-pole disconnection switch having a contact
separation of at least 3mm in all poles should be
connected in fixed wiring.
When carrying out piping connection, take care not to let
air substances go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high
pressure in the refrigeration cycle, explosion and injury.
Do not modify the length of the power supply cord or use
of extension cord, and do not share the single outlet with
other electrical appliances.
Otherwise, it will cause fire or electrical shock.
Carry out the specified installation work after taking into
account strong winds, typhoons or earthquakes.
Improper installation work may result in the equipment falling
and causing accidents.
installation manual
1
If the refrigerant leaks during installation, ventilate the
area immediately.
Toxic gas may be produced if the refrigerant comes into the
place contacting with fire.
The temperature of refrigerant circuit will be high, please
keep the interconnection cable away from the copper
tube.
After completing the installation work, check that the
refrigerant does not leak.
Toxic gas may be produced if the refrigerant leaks into the
room and comes into contact with a source of fire, such as a
fan heater, stove or cooker.
CAUTION
2. INSTALLATION INFORMATION
To install properly, please read this "installation manual" at
first.
The heat pump must be installed by qualified persons.
When installing the indoor unit or its tubing, please follow
this manual as strictly as possible.
If the heat pump is installed on a metal part of the building,
it must be electrically insulated according to the relevant
standards to electrical appliances.
When all the installation work is finished, please turn on
the power only after a thorough check.
Ground the heat pump.
Do not connect the ground wire to gas or water pipes,
lightning rod or a telephone ground wire.Inappropriate
grounding may result in electric shocks.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in
electric shocks.
Connect the outdoor unit wires , then connect the indoor
unit wires.
You are not allowed to connect the heat pump with the power
supply until the wiring and piping is done.
While following the instructions in this installation
manual, install drain piping in order to ensure proper
drainage and insulate piping in order to prevent
condensation.
Improper drain piping may result in water leakage and
property damage.
Install the indoor and outdoor units, power supply wiring
and connecting wires should be at least 1 meter away
from televisions or radios in order to prevent image
interference or noise.
Depending on the radio waves, a distance of 1 meter may not
be sufficient enough to eliminate the noise.
The appliance is not intended for use by young children
or infirm persons without supervision.
Regret for no further announcement if there is any change
of this manual caused by product improvement.
INSTALLATION ORDER
Select the location;
Install the indoor unit;
Install the outdoor unit;
Install the connecting pipe ;
Connect the drain pipe;
Wiring;
Test operation.
Don't install the heat pump in the following
circumstance:
There is petrolatum existing.
There is salty air surrounding (near the coast).
There is caustic gas (the sulfide, for example) existing
in the air (near a hot spring).
The Volt vibrates violently (in the factories).
In buses or cabinets.
In kitchen where it is full of oil gas.
There is strong electromagnetic wave existing.
There are inflammable materials or gas.
There is acid or alkaline liquid evaporating.
Other special conditions.
installation manual
2
3. ATTACHED FITTINGS
Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully.
Installation Fittings
Tubing & Fittings
Drainpipe Fittings
Remote controller & Its Frame
(The product you have might not be
provided the following accessory)
NAME
1. Installation paper board
(on some models)
2. Soundproof / insulation sheath
(on some models)
3. Out-let pipe sheath
(on some models)
4. Out-let pipe clasp
(on some models)
5. Drain joint(on some models)
6. Seal ring(on some models)
7. Remote controller
8. Remote controller holder
9. Mounting screw(ST2.9×
10. Alkaline dry batteries (AM4)
11. Owner's manual
12. Installation manual
10-C-H)
SHAPE
QUANTITY
1
1
1
1
1
1
1
1
2
2
1
1
Installation accessory
(The product you have might not be
provided the following accessory)
13. Expansible hook
14. Installation hook
15 .Orifice
16 .Transfer connector( 12.7- 16)
(Packed with the indoor unit )
(NOTE: Pipe size differ from appliance
to appliance.To meet different pipe size
requirement, sometimes the pipe
connections need the transfer connector
to install on the outdoor unit .)
17 .Transfer connector( 6- 9.52)
(Packed with the indoor unit )
(NOTE: Pipe size differ from appliance
to appliance.To meet different pipe size
requirement, sometimes the pipe
connections need the transfer connector
to install on the outdoor unit .)
18 .Transfer connector( 9.52- 12.7)
(Packed with the indoor unit ,used for
multi-type models only)
(NOTE: Pipe size differ from appliance
to appliance.To meet different pipe size
requirement, sometimes the pipe
connections need the transfer connector
to install on the outdoor unit .)
4
4
1
1
(on some models)
1
(on some models)
1
(on some models)
installation manual
3
4. INSPECTING AND HANDLING THE UNIT
At delivery, the package should be checked and any damage should
be reported immediately to the service agent.
When handling the unit, take into account the following:
Fragile, handle the unit with care.
1
Keep the unit upright in order to avoid compressor
damage.
Choose on before hand the path along which the unit is to be
2
brought in.
Move this unit as originally package as possible.
3
4
When lifting the unit , always use protectors to prevent belt
damage and pay attention to the position of the unit’s centre
of gravity.
5. INDOOR UNIT INSTALLATION
5.1 Installation place
(Refer to Fig.5-1,Fig.5-2,Fig.5-3 and Table 5-1 for specification.)
The indoor unit should be installed in a location that meets
the following reauirements:
There is enough room for installation and maintenance.
The ceiling is horizontal, and its structure can endure the
weight of the indoor unit.
The outlet and the inlet are not impeded, and the
influence of external air is the least.
The air flow can reach throughout the room.
The connecting pipe and drainpipe could be extracted out
easily.
There is no direct radiation from heaters.
5.3.1 Install the main body(cassette type
heat pump)
The existing ceiling (to be horizontal)
1
Cut a quadrangular hole of 880x880mm in the ceiling
according to the shape of the installation paper board.
(Refer to Fig.5-2)
The center of the hole should be at the same position of
that of the heat pump body.
Determine the lengths and outlets of the connecting pipe,
drainpipe and cables.
To balance the ceiling and to avoid vibration, please
enforce the ceiling when necessary.
2
Select the position of installation hooks according to the
hook holes on the installation board.
Drill four holes of Ø12mm, 45~50mm deep at the selected
positions on the ceiling. Then embed the expansible
hooks (fittings).
Face the concave side of the installation hooks toward the
expansible hooks. Determine the length of the installation
hooks from the height of ceiling, then cut off the
unnecessary part.
If the ceiling is extremely high, please determine the
length of the installation hook according to facts.
3
Adjust the hexangular nuts on the four installation hooks
evenly, to ensure the balance of the body.
If the drainpipe is awry, leakage will be caused by the
malfunction of the water-level switch.
Adjust the position to ensure the gaps between the body
and the four sides of ceiling are even. The body's lower
part should sink into the ceiling for 10~12 mm (Refer to Fig.5-6).
In general, L is half of the screw length of the installation
hook.(Refer to Fig.5-6)
Locate the heat pump firmly by wrenching the nuts after
having adjusted the body's position well.(Refer to Fig.5-7)
New built houses and ceilings
CAUTION
Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and radios. This is to prevent image interference and
noise in those electrical appliances. (Noise may be
generated depending on the conditions under which the
electric wave is generated, even if 1 meter is kept.)
5.2 Installation procedures for fresh air
intake duct connection
Preparing the connection hole
Cut off the knockout hole on the side plate with a nipper.
Cut the inner insulation of the hole portion with a cutter.
(Refer to Fig.5-4)
Placing the insulation
Put the insulation tightly around the hole of the unit as
shown.
The ends of the side plate and the inner insulation must be
completely adhered without leaving any clearance along the
circumference of the hole.
Make sure the inner surface of insulation tightly contacts the
inner insulation edge and the side plate. (Refer to Fig.5-5)
installation manual
4
1
In the case of new built house, the hook can be embedded
in advance (refer to 2 mentioned above). But it should be
strong enough to bear the indoor unit and will not become
loose because of concrete shrinking.
After installing the body, please fasten the installation paper
2
board onto the heat pump with bolts(M6X12) to determine in
advance the sizes and positions of the hole opening on
ceiling.(Refer to Fig.5-8)
Please first guarantee the flatness and horizontal of
ceiling when installing it.
Refer to 1 mentioned above for others.
3
Refer to 3 above for installation.
4
Remove the installation paper board.
CAUTION
After installing the body, the four bolts(M6x12)must be
fastened to the heat pump onto ensure the body is
grounded well.
Tubing side
780(Hook-location)
840(Body)
950(Panel)
Connecting point of drain pipe
H
Table 5-1
Drain side
) n o i t a c o l -
k
o o H ( 0 8 6
(Unit: mm)
) l e n a P
) y d o B ( 0 4 8
(
0 5
9
MODEL A H
18
24
30~60
piping
230
300
300
Drain piper
Fig.5-1
Connecting point of
refrigerant pipe
(Liquid side ØC)
Connecting point of
refrigerant pipe
A
(Gas side ØB)
Inner insulation
>260
>260230
>330
>330
mm
Remark
R410A &R22 Cooling/Cooling & Heating
R410A &R22 Cooling/Cooling & Heating
R410A &R22 Cooling/Cooling & Heating
R410A &R22
Inner insulation
Side plate
Cooling/Cooling & Heating
Slit
Side plate
Fig.5-4
Ceiling
Ground
m
Outlet
m 0 0 5 2 >
>1000mm
m m 0 0 0 1 >
Inlet
880mm (ceiling hole)
Outlet
m m 0 0 0 1 >
>1000mm
Panel
Fig.5-2
Insulation(local)
Ceiling
Side plate
Inner insulation
±10mm
Insulation(local)
Fig.5-5
Body
L
m
m
m
2
m
1 -
6
0 1
3
1
Fig.5-7 Fig.5-6
Body
Central hole
Fig.5-3
Bolt M6X12
Installation
paper board
Fig.5-8
installation manual
5
Leakage
Ceiling
Grid switch
Pollution
Fig.5-9
4
Gap not allowed
Water condensation
Fig.5-14
Loosen upper nut
Adjust lower nut
Fig.5-10
Fig.5-15
Fig.5-11
Installation cover’s rope
Tap Screw
Slide the four sliders
in the corresponding
channel when installing
the cover
Swing Motor
Ceiling
panel sponge
panel
Tubing joint
Outlet joint
Hook-bolt
Cross-screwdriver
body
panel foam1
air out
Hook panel
Fan
Water-receiver
Fig.5-12
outlet foam
panel foam 2
Fig.5-16
<200mm
1-1.5m
Pump-pipe clasp
(the fittings)
m
m 0 5 7
<
Lean over 1/50
Fig.5-17
Pump joint
Test mouth
m
m 6
4
Body
Water-receiver
Test cover
Stow tube
installation manual
6
Fig.5-13
Drain plug
Fig.5-18
5.3.2 Install the main body(small cassette
type heat pump)
Necessary room
0
8
2
A
Outlet
Inlet
Outlet
0 0 3 2 >
Ground
Fig.5-19
Colourless
trans parent pipe
Body
Horizontal
indicator
Fig.5-24
Drain side
Body
Nut
>1000
0
0
0
1 >
545(Hook-location)
570(Body)
647(Panel)
A
L
>1000
Ceiling
m
m 2
m
m
1 -
6
0 1
3
1
Fig.5-25
Body
1 >
0
0
0
Fig.5-20
A
Fixing hole
installation paper board
Screw M5x16
(Accessory)
Fresh air intake (ф65)
Central hole
Hook hole
Installation paper board
Fig.5-26
NOTE
570(Body)
647(Panel)
523(Hook-location)
All the pictures in this manual are for explanation purpose only.
They may be slightly different from the heat pump you
purchased(depend on model).The actual shape shall prevail.
(Unit: mm)
5.4.1 Install The Panel(cassette type heat
pump)
Fig.5-21
CAUTION
Hook
0
6 2
Never put the panel face down on floor or against the
wall, or on bulgy objects.
Never crash or strike it.
Ceiling
) t h g i e h g n
i l
i
e
c ( H
Ceiling
50
600
Panel
Remove the air-in grill.
1
Slide two grill switches toward the middle at the same time,
Fig.5-22
4
3
L
Body
2
1 - 0 1
6 7 1
and then pull them up. (Refer to Fig.5-9)
Draw the grill up to an angle of about 45, and remove it.
(Refer to Fig.5-10)
Remove the installation covers at the four corners
2
Wrench off the bolts, loose the rope of the installation covers,
and remove them. (Refer to Fig.5-11)
Fig.5-23
installation manual
7
Install the panel
3
Align the swing motor on the panel to the tubing joints of the
body properly. ( Refer to Fig.5-12)
Fix hooks of the panel at swing motor and its opposite sides
to the hooks of corresponding water receiver. ( Refer to Fig.5-12.1) Then hang the other two panel hooks onto
corresponding hangers of the body. ( Refer to Fig.5-12.2)
CAUTION
Do not coil the wiring of the swing motor into the seal
sponge.
Adjust the four panel hook screws to keep the panel
horizontal, and screw them up to the ceiling evenly. ( Refer to Fig.5-12.3)
Regulate the panel in the direction of the arrow in Fig.5-12.4
slightly to fit the panel's center to the center of the ceiling's
opening. Guarantee that hooks of four corners are fixed well.
Keep fastening the screws under the panel hooks, until the
thickness of the sponge between the body and the panel's
outlet has been reduced to about 4~6mm. The edge of the
panel should contact with the ceiling well. (Refer to Fig.5-13)
Malfunction described in Fig.5-14 can be caused by
inappropriate tightness the screw.
If the gap between the panel and ceiling still exists after
fastening the screws, the height of the indoor unit should
be modified again. ( Refer to Fig.5-15-left)
You can modify the height of the indoor unit through the
openings on the panel's four corners, if the lift of the
indoor unit and the drainpipe is not influenced (Refer to Fig.5-16-right).
Grid switch
4
5
Install the panel
2
Align the swing motor on the panel to the tubing joints of the
body properly. ( Refer to Fig.5-29)
Hang the four fixed rope of the main body to the installation
cover and the other three covers of the swing motor: (Refer
to Fig.5-29
and )
CAUTION
The installation cover of the swing motor must sink into
the corresponding water receiver.
Fig.5-27
Fig.5-28
Hang the air-in grill to the panel, then connect the lead
4
terminator of the swing motor and that of the control box
with corresponding terminators on the body respectively.
Relocate the air-in grill in the procedure of reversed order.
5
Relocate the installation cover.
6
Fasten the rope of installation cover on the bolt of the
installation cover. (Refer to Fig.5-16-left)
Press the installation cover into the panel slightly. (Refer to Fig.5-16-right)
5.4.2 Install The Panel(samll cassette type
heat pump)
CAUTION
Never put the panel face down on floor or against the
wall, or on bulgy objects.
Never crash or strike it.
Remove the air-in grill.
1
Slide two grill switches toward the middle at the same time,
and then pull them up. (Refer to Fig.5-27)
Draw the grill up to an angle of about 45, and remove it.
(Refer to Fig.5-28)
Install the panel on the main body with bolt (M5×16) and
washer. (Refer to Fig.5-29
Adjust the four panel hook screws to keep the panel
horizontal, and screw them up to the ceiling evenly.
Regulate the panel in the direction of the arrow in Fig.5-29.
slightly to fit the panel's center to the center of the ceiling's
opening. Guarantee that hooks of four corners are fixed well.
Keep fastening the screws under the panel hooks, until the
thickness of the sponge between the body and the panel's
outlet has been reduced to about 4~6mm. The edge of the
panel should contact with the ceiling well. (Refer to Fig.5-30)
Malfunction described in Fig.5-31 can be caused by
inappropriate tightness the screw.
If the gap between the panel and ceiling still exists after
fastening the screws, the height of the indoor unit should
be modified again. ( Refer to Fig.5-32-left)
You can modify the height of the indoor unit through the
openings on the panel's four cor ners, if the lift of the
indoor unit and the drainpipe is not influenced (Refer to
Fig.5-32-right).
4
Hang the air-in grill to the panel, then connect the lead
terminator of the swing motor and that of the control box
with corresponding terminators on the body respectively.
5
Relocate the air-in grid in the procedure of reversed order,
install the air-in grid.
)
installation manual
8
Drain side
1
Ceiling
Panel foam
Steel rope
Cover
Panel foam2
Outlet air
Body
Steel rope
1
3
Cover
Please operate according
to the direction of the arrow,
or it can not be disassembled
when it is necessary.
Air plate
Inlet air
2
3
3
Swing motor installation cover
Swing motor side
4
Panel sealing foam
Panel
Panel foam1
2
Swing motor installation cover
Bolt, washer
Fig.5-29
Fig.5-30
Ceiling
Leakage
Dew
Hexagon nut
Horizontal adjust ment
Ceiling
Fig.5-31
Fig.5-32
5.5.1 Install the distribution duct(cassette type heat pump)
Conditioned air can be distributes by means of a distribution duct.
Fresh air intake ( 75)
Distribution duct
Distribution duct
Distribution duct
Distribution duct
Fresh air
MODLE
Ø75mm
80mm
(18-60)
80mm
Fig.5-33
installation manual
9
NOTE
model 18 to 24 Series A=350mm; Series B=85mm
model 36 to 60 Series A=350mm; Series B=155mm
Distribution duct
Fresh air
Distribution duct
One-way
Two- way
In case of one duct connection
The air volume in duct is around 300-360m3/h for model 18
to 24 unit.
The air volume in duct is around 400-640m3/h for model 36
to 60 unit.
The max. length of duct is 2m.
The original air outlet with the same direction of duct should
be sealed In case of two duct connection.
In case of two duct connection
The air volume in one duct is around 200-260m3/h for model
18 to 24 unit.
The air volume in one duct is around 300-500m3/h for model
36 to 60 unit.
The max. length of duct is 1.5m for one duct.
The original air outlet with the same direction of duct should
be sealed.
Fig.5-34
Fresh air intake ( 75)
MODLE (12-18)
Ø65mm
Ø75mm
NOTE
model 12 to 18 Series A=150mm
One-way
Fig.5-35
5.5.1 Install the distribution duct(small
cassette type heat pump)
Conditioned air can be distributes by means of a distribution
duct.
In case of one duct connection
The air volume in duct is around 180-300m3/h for model 12
to 18 unit.
The max. length of duct is 1m.
The original air outlet with the same direction of duct should
be sealed In case of two duct connection.
In case of two duct connection
The air volume in one duct is around 100-200m3/h for model
12 to 18 unit.
The max. length of duct is 0.75m for one duct.
The original air outlet with the same direction of duct should
be sealed.
installation manual
10
Two- way
Fig.5-36
6. OUTDOOR UNIT INSTALLATION
6.1 Installation Place
The outdoor unit should be installed in the location that
meets the following requiements:
There is enough room for installation and maintenance.
The air outlet and the air inlet are not impeded, and can
not be reached by strong wind.
It must be a dry and well ventilating place.
The support is flat and horizontal and can stand the
weight of the outdoor unit. And will no additional noise or
vibration.
Your neighborhood will not feel uncomfortable with the
noise or expelled air.
It is easy to install the connecting pipes or cables.
Determine the air outlet direction where the discharged
air is not blocked.
There is no danger of fire due to leakage of inflammable
gas.
The piping length between the outdoor unit and the indoor
unit may not exceed the allowable piping length.
In the case that the installation place is exposed to strong
wind such as a seaside, make sure the fan operating
properly by putting the unit lengthwise along the wall or
using a dust or shield.(Refer to Fig.6-1)
If possible, do not install the unit where it is exposed to
direct sunlight.
If necessary, install a blind that does not interfere with the
air flow.
During the heating mode, the water drained off the
outdoor unit ,The condensate should be well drained
away by the drain hole to an appropriate place, so as not
to interfere other people.
Select the position where it will not be subject to snow
drifts, accumulation of leaves or other seasonal debris. If
unavoidable, please cover it with a shelter.
Locate the outdoor unit as close to the indoor unit as
possible.
If possible, please remove the obstacles nearby to
prevent the performance from being impeded by too little
of air circulation.
The minimum distance between the outdoor unit and
obstacles described in the installation chart does not
mean that the same is applicable to the situation of an
airtight room. Leave open two of the three
directions.(Refore to Fig.6-4, Fig.6-5)
Strong wind
O
X
Fig.6-1
NOTE
All the figures in this manual are for explanation
purpose only. They may be slightly different from the
heat pump you purchased.The actual unit shall prevail.
installation manual
11
6.2 Figure of body size
1. Split type outdoor unit
Table 6-1mm
MODEL A B C D E H F
762 530 290 315 270 593 282
12
780 548 266 300 241 547 250
Fig.6-2
Fig.6-2
695
Fig.6-2
Fig.6-2
Fig.6-2
762 530 290 315 270 593 282
18
842
560
335
360
852 582 368 390 328 660 340
312
324
H
24
895 590 333 355 302 862 313
990 624 366 396 340 966 354
990 624 366 396 340 966 354
30
895 590 333 355 302 862 313
A
Fig.6-2
A
990 624 366 396 340 966 354
36
940 600 376 400 340 1245 360
990 624 366 396 340 966 354
42
940
600
376
400
340
360
990 624 366 396 340 966 354
600
376
400
340
48
360 940
590 378 400 330 1167 340 900
600 376 400 340 1245 360 940
60
590 378 400 330 1167 340 900
1245
1245
Fig.6-2
Fig.6-2
Fig.6-2
Fig.6-2
Fig.6-2
Fig.6-3
Fig.6-2
Fig.6-3
Fig.6-2
Fig.6-3
Fig.6-3
Fig.6-3
Fig.6-3
F
H
B
Fig.6-3
E
C
643 404 448 368 1369 392 938
2. Vertical discharge type outdoor unit
D
Fig.6-3
A
Fig.6-5
C
B
installation manual
12
Fig.6-4
Fig.6-6
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.