Pridiom PCM183HX Installation Manual

Page 1
INSTALLATION MANUAL
Four-way Cassette Type
PCM123HX PCM183HX
Page 2
Install according to this installation instructions strictly. If installation is defective, it will cause water leakage,
CONTENTS PAGE
CONTENTS PAGE
PRECAUTIONS......................................................................
INSTALLATION INFORMATION.............................................
ATTACHED FITTINGS............................................................
INSPECTING AND HANDLING THE UNIT.............................
INDOOR UNIT INSTALLATION..............................................
OUTDOOR UNIT INSTALLATION..........................................
INSTALL THE CONNECTING PIPE.......................................
CONNECT THE DRAIN PIPE................................................
CONNECTIVE DIAGRAM .....................................................
WIRING...................................................................................
TEST OPERATION.................................................................
1
2
3
4
4
11
15
18
19
20
21
1. PRECAUTIONS
Keep this manual where the operator can easily find them.
Read this manual attentively before starting up the units.
For safety reason the operator must read the following cautions carefully.
The safty precautions listed here are divided into two categories.
WARNING
If you do not follow these instrutions exactly, the unit may cause property damage, personal injury or loss of life.
CAUTION
If you do not follow these instrutions exactly, the unit may cause minor or moderate property damage, personal
After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained.Also, inform customers that they should store this installation manual along with the owner's manual for future reference.
WARNING
Be sure only trained and qualified service personnel to install, repair or service the equipment.
Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.
electrical shock and fire.
When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.
Use the attached accessories parts and specified parts for installation.
otherwise, it will cause the set to fall, water leakage, electrical shock and fire.
Install at a strong and firm location which is able to withstand the set' s weight.
If the strength is not enough or installation is not properly done, the set will drop to cause injury.
The appliance must be installed 2.3m above floor.
The appliance shall not be installed in the laundry.
Before obtaining access to terminals, all supply circuits must be disconnected.
The appliance must be positioned so that the plug is accessible.
The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the fluid flow.
For electrical work, follow the local national wiring standard, regulation and this installation instructions. An independent circuit and single outlet must be used.
If electrical circuit capacity is not enough or defect in electrical work, it will cause electrical shock or fire.
Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal.
If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
Wiring routing must be properly arranged so that control board cover is fixed properly.
If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
If the supply cord is damaged, it must be replaced by the manufacture or its service agent or a similarly qualified person in order to avoid a hazard.
An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring.
When carrying out piping connection, take care not to let air substances go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances.
Otherwise, it will cause fire or electrical shock.
Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.
Improper installation work may result in the equipment falling and causing accidents.
installation manual
1
Page 3
If the refrigerant leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant comes into the place contacting with fire.
The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
After completing the installation work, check that the refrigerant does not leak.
Toxic gas may be produced if the refrigerant leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
CAUTION
2. INSTALLATION INFORMATION
To install properly, please read this "installation manual" at first.
The heat pump must be installed by qualified persons.
When installing the indoor unit or its tubing, please follow this manual as strictly as possible.
If the heat pump is installed on a metal part of the building, it must be electrically insulated according to the relevant standards to electrical appliances.
When all the installation work is finished, please turn on the power only after a thorough check.
Ground the heat pump.
Do not connect the ground wire to gas or water pipes, lightning rod or a telephone ground wire.Inappropriate grounding may result in electric shocks.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks.
Connect the outdoor unit wires , then connect the indoor unit wires.
You are not allowed to connect the heat pump with the power supply until the wiring and piping is done.
While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation.
Improper drain piping may result in water leakage and property damage.
Install the indoor and outdoor units, power supply wiring and connecting wires should be at least 1 meter away from televisions or radios in order to prevent image interference or noise.
Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.
The appliance is not intended for use by young children or infirm persons without supervision.
Regret for no further announcement if there is any change of this manual caused by product improvement.
INSTALLATION ORDER
Select the location;
Install the indoor unit;
Install the outdoor unit;
Install the connecting pipe ;
Connect the drain pipe;
Wiring;
Test operation.
Don't install the heat pump in the following circumstance:
There is petrolatum existing.
There is salty air surrounding (near the coast).
There is caustic gas (the sulfide, for example) existing in the air (near a hot spring).
The Volt vibrates violently (in the factories).
In buses or cabinets.
In kitchen where it is full of oil gas.
There is strong electromagnetic wave existing.
There are inflammable materials or gas.
There is acid or alkaline liquid evaporating.
Other special conditions.
installation manual
2
Page 4
3. ATTACHED FITTINGS
Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully.
Installation Fittings
Tubing & Fittings
Drainpipe Fittings
Remote controller & Its Frame
(The product you have might not be
provided the following accessory)
NAME
1. Installation paper board (on some models)
2. Soundproof / insulation sheath (on some models)
3. Out-let pipe sheath
(on some models)
4. Out-let pipe clasp
(on some models)
5. Drain joint(on some models)
6. Seal ring(on some models)
7. Remote controller
8. Remote controller holder
9. Mounting screw(ST2.9×
10. Alkaline dry batteries (AM4)
11. Owner's manual
12. Installation manual
10-C-H)
SHAPE
QUANTITY
1
1
1
1
1
1
1
1
2
2
1
1
Installation accessory
(The product you have might not be
provided the following accessory)
13. Expansible hook
14. Installation hook
15 .Orifice
16 .Transfer connector( 12.7- 16) (Packed with the indoor unit ) (NOTE: Pipe size differ from appliance to appliance.To meet different pipe size requirement, sometimes the pipe connections need the transfer connector to install on the outdoor unit .)
17 .Transfer connector( 6- 9.52) (Packed with the indoor unit ) (NOTE: Pipe size differ from appliance to appliance.To meet different pipe size requirement, sometimes the pipe connections need the transfer connector to install on the outdoor unit .)
18 .Transfer connector( 9.52- 12.7) (Packed with the indoor unit used for multi-type models only) (NOTE: Pipe size differ from appliance to appliance.To meet different pipe size requirement, sometimes the pipe connections need the transfer connector to install on the outdoor unit .)
4
4
1
1
(on some models)
1
(on some models)
1
(on some models)
installation manual
3
Page 5
4. INSPECTING AND HANDLING THE UNIT
At delivery, the package should be checked and any damage should be reported immediately to the service agent.
When handling the unit, take into account the following:
Fragile, handle the unit with care.
1
Keep the unit upright in order to avoid compressor damage.
Choose on before hand the path along which the unit is to be
2
brought in.
Move this unit as originally package as possible.
3
4
When lifting the unit , always use protectors to prevent belt damage and pay attention to the position of the unit’s centre of gravity.
5. INDOOR UNIT INSTALLATION
5.1 Installation place
(Refer to Fig.5-1,Fig.5-2,Fig.5-3 and Table 5-1 for specification.)
The indoor unit should be installed in a location that meets the following reauirements:
There is enough room for installation and maintenance.
The ceiling is horizontal, and its structure can endure the weight of the indoor unit.
The outlet and the inlet are not impeded, and the influence of external air is the least.
The air flow can reach throughout the room.
The connecting pipe and drainpipe could be extracted out easily.
There is no direct radiation from heaters.
5.3.1 Install the main body(cassette type heat pump)
The existing ceiling (to be horizontal)
1
Cut a quadrangular hole of 880x880mm in the ceiling according to the shape of the installation paper board.
(Refer to Fig.5-2)
The center of the hole should be at the same position of that of the heat pump body.
Determine the lengths and outlets of the connecting pipe, drainpipe and cables.
To balance the ceiling and to avoid vibration, please enforce the ceiling when necessary.
2
Select the position of installation hooks according to the hook holes on the installation board.
Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the expansible hooks (fittings).
Face the concave side of the installation hooks toward the expansible hooks. Determine the length of the installation hooks from the height of ceiling, then cut off the unnecessary part.
If the ceiling is extremely high, please determine the length of the installation hook according to facts.
3
Adjust the hexangular nuts on the four installation hooks evenly, to ensure the balance of the body.
If the drainpipe is awry, leakage will be caused by the malfunction of the water-level switch.
Adjust the position to ensure the gaps between the body and the four sides of ceiling are even. The body's lower part should sink into the ceiling for 10~12 mm (Refer to Fig.5-6).
In general, L is half of the screw length of the installation hook.(Refer to Fig.5-6)
Locate the heat pump firmly by wrenching the nuts after having adjusted the body's position well.(Refer to Fig.5-7)
New built houses and ceilings
CAUTION
Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 meter away from televisions and radios. This is to prevent image interference and noise in those electrical appliances. (Noise may be generated depending on the conditions under which the electric wave is generated, even if 1 meter is kept.)
5.2 Installation procedures for fresh air intake duct connection
Preparing the connection hole
Cut off the knockout hole on the side plate with a nipper. Cut the inner insulation of the hole portion with a cutter.
(Refer to Fig.5-4)
Placing the insulation
Put the insulation tightly around the hole of the unit as shown. The ends of the side plate and the inner insulation must be completely adhered without leaving any clearance along the circumference of the hole. Make sure the inner surface of insulation tightly contacts the inner insulation edge and the side plate. (Refer to Fig.5-5)
installation manual
4
1
In the case of new built house, the hook can be embedded in advance (refer to 2 mentioned above). But it should be strong enough to bear the indoor unit and will not become loose because of concrete shrinking.
After installing the body, please fasten the installation paper
2
board onto the heat pump with bolts(M6X12) to determine in advance the sizes and positions of the hole opening on ceiling.(Refer to Fig.5-8)
Please first guarantee the flatness and horizontal of ceiling when installing it.
Refer to 1 mentioned above for others.
3
Refer to 3 above for installation.
4
Remove the installation paper board.
CAUTION
After installing the body, the four bolts(M6x12)must be fastened to the heat pump onto ensure the body is grounded well.
Page 6
Tubing side
780(Hook-location)
840(Body)
950(Panel)
Connecting point of drain pipe
H
Table 5-1
Drain side
) n o i t a c o l -
k o o H ( 0 8 6
(Unit: mm)
) l e n a P
) y d o B ( 0 4 8
( 0 5
9
MODEL A H
18
24
30~60
piping
230
300
300
Drain piper
Fig.5-1
Connecting point of
refrigerant pipe
(Liquid side ØC)
Connecting point of
refrigerant pipe
A
(Gas side ØB)
Inner insulation
260
260230
330
330
mm
Remark
R410A &R22 Cooling/Cooling & Heating
R410A &R22 Cooling/Cooling & Heating
R410A &R22 Cooling/Cooling & Heating
R410A &R22
Inner insulation
Side plate
Cooling/Cooling & Heating
Slit
Side plate
Fig.5-4
Ceiling
Ground
m
Outlet
m 0 0 5 2 >
>1000mm
m m 0 0 0 1 >
Inlet
880mm (ceiling hole)
Outlet
m m 0 0 0 1 >
>1000mm
Panel
Fig.5-2
Insulation(local)
Ceiling
Side plate
Inner insulation
±10mm
Insulation(local)
Fig.5-5
Body
L
m m
m
2
m
1 -
6
0 1
3 1
Fig.5-7 Fig.5-6
Body
Central hole
Fig.5-3
Bolt M6X12
Installation
paper board
Fig.5-8
installation manual
5
Page 7
Leakage
Ceiling
Grid switch
Pollution
Fig.5-9
4
Gap not allowed
Water condensation
Fig.5-14
Loosen upper nut
Adjust lower nut
Fig.5-10
Fig.5-15
Fig.5-11
Installation cover’s rope
Tap Screw
Slide the four sliders in the corresponding channel when installing the cover
Swing Motor
Ceiling
panel sponge
panel
Tubing joint
Outlet joint
Hook-bolt
Cross-screwdriver
body
panel foam1
air out
Hook panel
Fan
Water-receiver
Fig.5-12
outlet foam
panel foam 2
Fig.5-16
<200mm
1-1.5m
Pump-pipe clasp
(the fittings)
m m 0 5 7
<
Lean over 1/50
Fig.5-17
Pump joint
Test mouth
m
m 6
­4
Body
Water-receiver
Test cover
Stow tube
installation manual
6
Fig.5-13
Drain plug
Fig.5-18
Page 8
5.3.2 Install the main body(small cassette type heat pump)
Necessary room
0
8
2 A
Outlet
Inlet
Outlet
0 0 3 2 >
Ground
Fig.5-19
Colourless trans parent pipe
Body
Horizontal indicator
Fig.5-24
Drain side
Body
Nut
>1000
0 0 0 1 >
545(Hook-location)
570(Body)
647(Panel)
A
L
>1000
Ceiling
m m 2
m m
1 -
6
0 1
3 1
Fig.5-25
Body
1 > 0 0 0
Fig.5-20
A
Fixing hole installation paper board
Screw M5x16 (Accessory)
Fresh air intake (ф65)
Central hole
Hook hole
Installation paper board
Fig.5-26
NOTE
570(Body)
647(Panel)
523(Hook-location)
All the pictures in this manual are for explanation purpose only. They may be slightly different from the heat pump you purchased(depend on model).The actual shape shall prevail.
(Unit: mm)
5.4.1 Install The Panel(cassette type heat pump)
Fig.5-21
CAUTION
Hook
0 6 2
Never put the panel face down on floor or against the wall, or on bulgy objects. Never crash or strike it.
Ceiling
) t h g i e h g n
i l i e c ( H
Ceiling
50
600
Panel
Remove the air-in grill.
1
Slide two grill switches toward the middle at the same time,
Fig.5-22
4 3
L
Body
2 1 - 0 1
6 7 1
and then pull them up. (Refer to Fig.5-9)
Draw the grill up to an angle of about 45, and remove it.
(Refer to Fig.5-10)
Remove the installation covers at the four corners
2
Wrench off the bolts, loose the rope of the installation covers, and remove them. (Refer to Fig.5-11)
Fig.5-23
installation manual
7
Page 9
Install the panel
3
Align the swing motor on the panel to the tubing joints of the body properly. ( Refer to Fig.5-12)
Fix hooks of the panel at swing motor and its opposite sides to the hooks of corresponding water receiver. ( Refer to Fig.5-12.1) Then hang the other two panel hooks onto corresponding hangers of the body. ( Refer to Fig.5-12.2)
CAUTION
Do not coil the wiring of the swing motor into the seal sponge.
Adjust the four panel hook screws to keep the panel horizontal, and screw them up to the ceiling evenly. ( Refer to Fig.5-12.3)
Regulate the panel in the direction of the arrow in Fig.5-12.4 slightly to fit the panel's center to the center of the ceiling's opening. Guarantee that hooks of four corners are fixed well.
Keep fastening the screws under the panel hooks, until the thickness of the sponge between the body and the panel's outlet has been reduced to about 4~6mm. The edge of the panel should contact with the ceiling well. (Refer to Fig.5-13)
Malfunction described in Fig.5-14 can be caused by inappropriate tightness the screw.
If the gap between the panel and ceiling still exists after fastening the screws, the height of the indoor unit should be modified again. ( Refer to Fig.5-15-left)
You can modify the height of the indoor unit through the openings on the panel's four corners, if the lift of the indoor unit and the drainpipe is not influenced (Refer to Fig.5-16-right).
Grid switch
4
5
Install the panel
2
Align the swing motor on the panel to the tubing joints of the body properly. ( Refer to Fig.5-29)
Hang the four fixed rope of the main body to the installation cover and the other three covers of the swing motor: (Refer
to Fig.5-29
and )
CAUTION
The installation cover of the swing motor must sink into the corresponding water receiver.
Fig.5-27
Fig.5-28
Hang the air-in grill to the panel, then connect the lead
4
terminator of the swing motor and that of the control box with corresponding terminators on the body respectively.
Relocate the air-in grill in the procedure of reversed order.
5
Relocate the installation cover.
6
Fasten the rope of installation cover on the bolt of the installation cover. (Refer to Fig.5-16-left)
Press the installation cover into the panel slightly. (Refer to Fig.5-16-right)
5.4.2 Install The Panel(samll cassette type heat pump)
CAUTION
Never put the panel face down on floor or against the wall, or on bulgy objects.
Never crash or strike it.
Remove the air-in grill.
1
Slide two grill switches toward the middle at the same time, and then pull them up. (Refer to Fig.5-27)
Draw the grill up to an angle of about 45, and remove it.
(Refer to Fig.5-28)
Install the panel on the main body with bolt (M5×16) and washer. (Refer to Fig.5-29
Adjust the four panel hook screws to keep the panel horizontal, and screw them up to the ceiling evenly.
Regulate the panel in the direction of the arrow in Fig.5-29. slightly to fit the panel's center to the center of the ceiling's opening. Guarantee that hooks of four corners are fixed well.
Keep fastening the screws under the panel hooks, until the thickness of the sponge between the body and the panel's outlet has been reduced to about 4~6mm. The edge of the panel should contact with the ceiling well. (Refer to Fig.5-30)
Malfunction described in Fig.5-31 can be caused by inappropriate tightness the screw.
If the gap between the panel and ceiling still exists after fastening the screws, the height of the indoor unit should be modified again. ( Refer to Fig.5-32-left)
You can modify the height of the indoor unit through the openings on the panel's four cor ners, if the lift of the indoor unit and the drainpipe is not influenced (Refer to
Fig.5-32-right).
4
Hang the air-in grill to the panel, then connect the lead terminator of the swing motor and that of the control box with corresponding terminators on the body respectively.
5
Relocate the air-in grid in the procedure of reversed order, install the air-in grid.
)
installation manual
8
Page 10
Drain side
1
Ceiling
Panel foam
Steel rope
Cover
Panel foam2
Outlet air
Body
Steel rope
1
3
Cover
Please operate according to the direction of the arrow, or it can not be disassembled when it is necessary.
Air plate
Inlet air
2
3
3
Swing motor installation cover
Swing motor side
4
Panel sealing foam
Panel
Panel foam1
2
Swing motor installation cover
Bolt, washer
Fig.5-29
Fig.5-30
Ceiling
Leakage
Dew
Hexagon nut
Horizontal adjust ment
Ceiling
Fig.5-31
Fig.5-32
5.5.1 Install the distribution duct(cassette type heat pump)
Conditioned air can be distributes by means of a distribution duct.
Fresh air intake ( 75)
Distribution duct
Distribution duct
Distribution duct
Distribution duct
Fresh air
MODLE
Ø75mm
80mm
(18-60)
80mm
Fig.5-33
installation manual
9
Page 11
NOTE
model 18 to 24 Series A=350mm; Series B=85mm model 36 to 60 Series A=350mm; Series B=155mm
Distribution duct
Fresh air
Distribution duct
One-way
Two- way
In case of one duct connection
The air volume in duct is around 300-360m3/h for model 18 to 24 unit.
The air volume in duct is around 400-640m3/h for model 36 to 60 unit.
The max. length of duct is 2m.
The original air outlet with the same direction of duct should be sealed In case of two duct connection.
In case of two duct connection
The air volume in one duct is around 200-260m3/h for model 18 to 24 unit.
The air volume in one duct is around 300-500m3/h for model 36 to 60 unit.
The max. length of duct is 1.5m for one duct.
The original air outlet with the same direction of duct should be sealed.
Fig.5-34
Fresh air intake ( 75)
MODLE (12-18)
Ø65mm
Ø75mm
NOTE
model 12 to 18 Series A=150mm
One-way
Fig.5-35
5.5.1 Install the distribution duct(small cassette type heat pump)
Conditioned air can be distributes by means of a distribution duct.
In case of one duct connection
The air volume in duct is around 180-300m3/h for model 12 to 18 unit.
The max. length of duct is 1m.
The original air outlet with the same direction of duct should be sealed In case of two duct connection.
In case of two duct connection
The air volume in one duct is around 100-200m3/h for model 12 to 18 unit.
The max. length of duct is 0.75m for one duct.
The original air outlet with the same direction of duct should be sealed.
installation manual
10
Two- way
Fig.5-36
Page 12
6. OUTDOOR UNIT INSTALLATION
6.1 Installation Place
The outdoor unit should be installed in the location that meets the following requiements:
There is enough room for installation and maintenance.
The air outlet and the air inlet are not impeded, and can not be reached by strong wind.
It must be a dry and well ventilating place.
The support is flat and horizontal and can stand the weight of the outdoor unit. And will no additional noise or vibration.
Your neighborhood will not feel uncomfortable with the noise or expelled air.
It is easy to install the connecting pipes or cables.
Determine the air outlet direction where the discharged air is not blocked.
There is no danger of fire due to leakage of inflammable gas.
The piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length.
In the case that the installation place is exposed to strong wind such as a seaside, make sure the fan operating properly by putting the unit lengthwise along the wall or using a dust or shield.(Refer to Fig.6-1)
If possible, do not install the unit where it is exposed to direct sunlight.
If necessary, install a blind that does not interfere with the air flow.
During the heating mode, the water drained off the outdoor unit ,The condensate should be well drained away by the drain hole to an appropriate place, so as not to interfere other people.
Select the position where it will not be subject to snow drifts, accumulation of leaves or other seasonal debris. If unavoidable, please cover it with a shelter.
Locate the outdoor unit as close to the indoor unit as possible.
If possible, please remove the obstacles nearby to prevent the performance from being impeded by too little of air circulation.
The minimum distance between the outdoor unit and obstacles described in the installation chart does not mean that the same is applicable to the situation of an airtight room. Leave open two of the three directions.(Refore to Fig.6-4, Fig.6-5)
Strong wind
O
X
Fig.6-1
NOTE
All the figures in this manual are for explanation purpose only. They may be slightly different from the heat pump you purchased.The actual unit shall prevail.
installation manual
11
Page 13
6.2 Figure of body size
1. Split type outdoor unit
Table 6-1 mm
MODEL A B C D E H F
762 530 290 315 270 593 282
12
780 548 266 300 241 547 250
Fig.6-2
Fig.6-2
695
Fig.6-2
Fig.6-2
Fig.6-2
762 530 290 315 270 593 282
18
842
560
335
360
852 582 368 390 328 660 340
312
324
H
24
895 590 333 355 302 862 313
990 624 366 396 340 966 354
990 624 366 396 340 966 354
30
895 590 333 355 302 862 313
A
Fig.6-2
A
990 624 366 396 340 966 354
36
940 600 376 400 340 1245 360
990 624 366 396 340 966 354
42
940
600
376
400
340
360
990 624 366 396 340 966 354
600
376
400
340
48
360 940
590 378 400 330 1167 340 900
600 376 400 340 1245 360 940
60
590 378 400 330 1167 340 900
1245
1245
Fig.6-2
Fig.6-2
Fig.6-2
Fig.6-2
Fig.6-2
Fig.6-3
Fig.6-2
Fig.6-3
Fig.6-2
Fig.6-3
Fig.6-3
Fig.6-3
Fig.6-3
F
H
B
Fig.6-3
E
C
643 404 448 368 1369 392 938
2. Vertical discharge type outdoor unit
D
Fig.6-3
A
Fig.6-5
C
B
installation manual
12
Fig.6-4
Fig.6-6
Page 14
Table 6-2 mm
DIMENSIONS
MODEL
REMARK
B A C
18
636 554 554
2. Vertical discharge type outdoor unit
(Wall or obstacle)
t e
m
l t u m 0
O r
0 2 1
i
A >
24
36
48
60
636 554 554
840
852
843 740 740
3. Centrifugal fan outdoor unit
I
A
B
C
G
Table 6-3
A
B
MODEL
C
554 554
740 740
J
D
E
H
D
E
F
G
H
Refore to
Fig.6-5 Fig.6-6
F
Fig.6-7
mm
I
J
>300mm
Air inlet
(Wall or obstacle)
m m
t e
l
0
n i r
0
i A
3 >
Fig.6-9
>300mm
Air inlet
18
1174
1120
680
720
750
475
300
430
265
24
1174 1120 680 720 750 475 300 430 265 393
30
1381
1328
702
740
770
520
336
500
296
36
1381 1328 702 740 770 520 336 500 296 443
1394
1338
783
820
850
568
398
574
48
60
1338 783 820 850 568 398 574 342 463
1394
342
6.3 Space of installation and maintenance
1. Split type outdoor unit
(Wall or obstacle)
m m
0 0 3 >
Maintain channel
>600mm
P
Fig.6-8
Air inlet
>300mm
N
Air inlet
m m
0
M
0 0 2 >
Air outlet
393
443
463
m
t e
m
l
0
n
i
0 3 >
r i A
Fig.6-10
3. Centrifugal fan outdoor unit
a) In case that suspending in the ceiling
4
m 0 0
m
m m 0 0
3
m
m
0 0 3
Fig.6-11
installation manual
13
Page 15
b)In case that installing on the floor
3
0
m m 0
m
0 0 4
To change air outlet is necessary to interchange panels too.
Fan outlet panel is attached to fan structure, which must be
mounted as follow .
3
m
m 0 0
m
Fig.6-12
NOTE
All the figures in this manual are for explanation purpose only. They may be slightly different from the heat pump you purchased.
The actual unit shall prevail.
6.4 Available configuration
Four different configuration are available for oudoor unit only
changing the panels and fan position.
NOTE
Keep in mind that fan unit weight is aprox 30kg ,the unit as
well as relevant equipment covered with the vinyl cover
during installation work.
Air inlet modification
To change air inlet is only necessary to interchange the
indicated panels position. Both panels use screws to be fixed
to unit chas s is.
Fig.6-14
6.5 Moving and installation
Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling.
Never hold the inlet of the outdoor unit to prevent it from deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation accoding to the sepecifications of the outdoor units.
Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind.(Refer to Fig.6-15)
60cm
Fix with bolt
installation manual
14
Fig.6-15
NOTE
All the figures in this manual are for explanation purpose only. They may be slightly different from the heat pump you purchased.The actual unit shall prevail.
Change Panel
Fig6-13
Page 16
Concrete Foundation
Foundation could be on flat and is recommended be 100-300mm
1
higher than ground level. Install a drainage around foundation for smooth drain
2
When installing the outdoor unit fix the unit by anchor bolts of
3
M10. When installing the unit on a roof or a veranda,drain water
4
sometimes turns to ice on a cold morning. Therefore, avoid draining in an area that people often use because it is slippery.
0 0 3
100
0 0 1
Fig.6-16
Table 6-4
No Description
1 Outdoor Unit
2 Vibration-proof rubber
3 Anchor Bolt M10
4 Drainage (Wide 100×Depth 150)
5 Drainage
7. INSTALL THE CONNECTING PIPE
Check whether the height drop between the indoor unit and outdoor unit, the length of refrigerant pipe, and the number of the bends meet the following requirements:
(The number of the bends less than 15.)
Table 7-1
The type of models
50Hz T1 condition/R22 Split type heat pump
50Hz Vertical discharge heat pump /60Hz T1 condition/R22 Split type heat pump and Vertical discharge heat pump
R410A inverter Split type heat pump and Centrifugal fan outdoor unit
R410A Split type heat pump and and Centrifugal fan outdoor unit
50Hz/60Hz T3 condition (outdoor unit down)
50Hz/60Hz T3 condition (outdoor unit up)
the unit with quick joint
Model
12K
18K-24K
30K-42K
48K-60K
12K
18K-24K
30K-60K
12K
18K-24K
30K
36K
48K-60K
12K
18K-30K
36K
48K-60K
18K-24K
30K
36K
42K-60K
18K-24K
30K
36K
42K
48K-60K
12K-18K
The length of
refrigerant pipe
15
30
50
50
15
30
30
10
25
25
30
50
15
25
30
50
25
30
30
50
25
30
30
50
50
5
unit: m
The max
height drop
8
10
20
25
8
10
20
5
12
15
20
25
8
15
20
25
10
15
20
25
15
20
25
30
35
5
6 Mortar Hole (Φ100×Depth 150)
Table 6-5
MODEL
Unit
18~24
30~36
48
BC
1120 720
1328 740
1338 820
mm
Suspended unit
1. Suspend the unit as the drawing indicates.
2. Ensure that ceiling can resist the Outdoor unit weight indicated
in specification label plate.
Sling Bolt
Suspension Bracket
CAUTION
All field piping must be provided by a licensed refrigeration technician and must comply with the relevant local and national codes.
Prevent let air, dust, or other impurities enter the pipe system during installation.
Insulation pipe shall be used to the gas piping and the liquid piping. Otherwise, the condensate may happen
The Procedure of Connecting Pipes
7.1
Drill a hole in the wall (suitable just for the size of the wall
1
conduit), then set on the fittings such as the wall conduit and its cover.
R410A
Fig.6-17
installation manual
15
Page 17
Bind the connecting pipe and the cables together tightly with
2
binding tapes. Pass the bound connecting pipe through the wall conduct from outside. Be careful of the pipe allocation to do on damage to the tubing.
Connect the pipes. Refer to "How to Connect the pipes" for
3
details.
4
Expel the air with a vacuum pump. Refer to "How to expel the air with a vacuum pump" for details.
open the stop values of the outdoor unit to make the
5
refrigerant pipe connecting the indoor unit with the outdoor unit in fluent flow.
6
Check the leakage. Check all the joints with the leak detector or soap water.
Cover the joints of the connecting pipe with the soundproof /
7
insulating sheath (fittings), and bind it well with the tapes to prevent leakage.
CAUTION
Be sure to with insulating materials cover all the exposed parts of the flare pipe joints and refrigerant pipe on the liquid-side and the gas-side. Ensure that there is no gap between them. Incomplete insulation may cause water condensation.
3
Remove the protection cover of stop valve
Liquid Valve
Gas Valve
Connect the indoor unit at first, then the outdoor unit.
4
Bend the tubing in proper way. Do not harm to them.
Bend the pipe with thumb
min-radius 100mm
The bending angle should not exceed 90.
Bending position is preferably in the middle of the bendable pipe. The larger the bending radius the better it is.
Do not bend the pipe more than three times.
When connecting the flare nut, coat the flare both inside and outside with either oil or ester oil and initially tighten by hand 3 or 4 turns before tighting firmly.
Fig.7-3
Fig.7-4
How to Connect the pipes
Flaring
1
Cut a pipe with a pipe cutter. (Refer to Fig.7-1)
Lean crude burr
90
Insert a flare nut into a pipe and flare the pipe.
Refer to Table 4 for the dimension of flare nut spaces.
Table 7-2
Pipe gauge
Ø6.4 8.3 8.7
Ø9.5 12.0
Ø12.7 15.4
Ø15.9
Ø19.1
2
Tightening torque
15
~16 N.m
~163 kgf.cm)
(153
25
~26N.m
(255
~265 kgf.cm)
35~36 N.m
(357
~367 kgf.cm)
~47 N.m
45
~480 kgf.cm)
(459
65~67N.m
~684 kgf.cm)
(663
Remove the Cycle Service Panel and the Cover Board, unscrewing the screws which secure it to the structure
Cycle Service Panel
Cover Board
Flare dimensin A
(mm)
min max
12.4
15.8
18.6
22.9
19.0
23.3
Fig.7-1
Flare shape
°
4
±
90
45
°
±
2
A
R0.4~0.8
Fig.7-2
Fig.7-5
Be sure to use both a spanner and torque wrench together when connecting or disconnecting pipes to /from the unit.
Fig.7-6
CAUTION
Too large torque will harm the bellmouthing and too small will cause leakage. Please determine the torque according to Table 7-2. After the connecting work is finished, be sure to check that there is no gas leak.
How to expel the air with a vacuum pump
Stop valve operation introduction
1. Opening stop valve
1.
Remove the cap and turn the valve counterclock-wise with the hexagon wrench.
2.
Turn it until the shaft stops.Do not apply excessive force to the stop valve. Doing so may breakthe valve body, as the valve is not a backseat type. Always use the special tool.
3.
Make sure to tighten the cap securely.
2. Closing stop valve
1.
Remove the cap and turn the valve clockwise with the hexagon wrench.
Securely tighten the valve until the shaft contacts the main bodyseal.
2. Make sure to tighten the cap securely. For the tightening torque, refer to the table below.
installation manual
16
Page 18
Table 7-3
Tightening torque N M (Turn clockwise to close)
Stop
Valve size
Ø6.4
Ø9.5
Ø12.7
Ø15.9
Ø19.1
Shaft (valve body)
Hexagonal
wrench 4 mm
79
911
11~13
Hexagonal
wrench 6 mm
Hexagonal
wrench 6 mm
Cap
(Valve lid)
13.516.5 57
1822
2327
3540
Maintenance nut
11.513.9
CAUTION
Always use a charge hose for service port connection.
After tightening the cap, check that no refrigerant leaks arepresent.
7.2
Additional Refrigerant Charge
CAUTION
Refrigerant cannot be charged until field wiring has been completed.
Refrigerant may only be charged after performing the leak test and the vacuum pumping.
When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer.
Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the appropriate refrigerant is charged.
service port
maintenance nut
cap
hexagon holeshaftseal
Using the vacuum pump
Loosen and remove the maintenance nuts of stop valves A
1
and B, and connect the charge hose of the manifold valve to the service port of stop valve A. (Be sure that stop valves A and B are both closed)
2
Connect the joint of the charge hose with the vacuum pump.
Open the Lo-lever of the manifold value completely.
3
Turn on the vacuum pump. At the beginning of pumping,
4
loosen the maintenance nut of stop valve B a little to check whether the air comes in (the sound of the pump changes, and the indicator of compound meter turns below zero). Then fasten the maintenace nut.
When the pumping has finished, close the Lo-lever of the
5
manifold valve completely and turn off the vacuum pump.Make pumping for 15 minutes or more and check that the compound meter indicates -76cmHg(-1X10 Pa)
6
Loosen and remove the cap of stop valves A and B to open stop valve A and B completely, then fasten the cap.
Disassemble the charge hose from the service port of stop
7
valve A, and fasten the nut.
Outdoor
unit
Stop valve
A
B
Manifold valve
Gas side
Liquid side
Pressure meterMulti-meter
5
Indoor
unit
C
D
Fig.7-7
Fig.7-8
Refrigerant containers shall be opened slowly.
Always use protective gloves and protect your eyes when charging refrigerant.
The outdoor unit is factory charged with refrigerant. Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit/indoor unit connection.
Table 7-2
Brass tube(mm)
orifice in the indoorunit
Ø6.35
orifice in the outdoorunit
orifice in the indoorunit
Ø9.53
orifice in the outdoorunit
orifice in the indoorunit
Ø12.7
orifice in the outdoorunit
orifice in the indoorunit
Ø15.9
orifice in the outdoorunit
orifice in the indoorunit
Ø19.0
orifice in the outdoorunit
R410A R22
0.022kg/m×(L-5)
0.011kg/m×(L-5)
0.060kg/m×(L-5)
0.030kg/m×(L-5)
0.110kg/m×(L-5)
0.060kg/m×(L-5)
0.170kg/m×(L-5)
0.085kg/m×(L-5)
0.250kg/m×(L-5)
0.125kg/m×(L-5)
0.030kg/m×(L-5)
0.015kg/m×L
0.065kg/m×(L-5)
0.030kg/m×L
0.115kg/m×(L-5)
0.060kg/m×L
0.190kg/m×(L-5)
0.095kg/m×L
0.290kg/m×(L-5)
0.145kg/m×L
NOTE:the table above refer to the liquid tube. NOTE:The number of bends is up to the length of the max
height drop.Usually for each 10m need a bend.
NOTE
If a negative result is gotten for R from Table 7-4, no refrigerant needs to be added nor removed. Additional refrigerant will be twice of R from Table 7-4 if the indoor unit installed throttle assembly.
Outdoor unit is equiped with a drain piping. Its position is shown figure below.
-76 cmHg
Lo-lever
Charge hose Charge hose
Hi-lever
Vacuum pump
Lo-lever
Fig.7-9
Drain Piping
Fig.7-10
installation manual
17
Page 19
Table7-6
MODEL
A B
Unit
mm
18~24 595 1200
30~36 624 1381
48 646 1385
Prepare a polyviny chloride with 21mm inner diameter
Fasten the tube to the drain hose with an adhesive and the field-supplied clamp. The drain piping must be performed with a DOWN-SLOPE pitch of 1/25 to 1/100
Connect a siphon, as shown in figure below
75
Slope 2 %
Plug
Fig.7-11
Drainage test Drainage test
Check whether the drainpipe is unhindered. New built house should have this test done before paving
the ceiling.
Remove the test cover, and stow water of about 2000ml to the
1
water receiver through the stow tube. ( Refer to Fig.5-18 in the
figure page)
2
Turn on the power, and operate the heat pump under the "COOLING" mode. Listen to the sound of the drain pump. Check whether the water is discharger well (a lag of 1min is allowed before discharging, according to the length of the drain pipe), and check whether water leaks from the joints.
3
Stop the heat pump, turn off the power, and reset the test cover to its original position.
NOTE
The drain plug is used to empty the water-receiver for maintenance of the heat pump. Please stuff it imposition at all times during operation to avoid leakage.
Install the drain joint of the outdoor unit
8. CONNECT THE DRAIN PIPE
Install the drainpipe of the indoor unit
You can use a polyethylene tube as the drainpipe (out-dia.37-39mm, in-dia.32mm). It could be bought at local market or from your dealer.
Set the mouth of the drainpipe onto the root of the body's pump-pipe, and clip the drainpipe and the out-let pipe sheath (fittings) together firmly with the out-let pipe clasp (fitting).
The body's pump pipe and the drainpipe (especially the indoor part) should be covered evenly with the out-let pipe sheath (fittings) and be bound tightly with the constrictor to prevent condensation caused by entered air.
To prevent water from flowing backwards into the heat pump while the heat pump stops, please lean the drainpipe down toward outdoor (outlet-side) at a degree of over 1/ 50. And please avoid any bulge or water deposit. ( Refer to Fig.5-17.a
in the figure page)
Do not drag the drainpipe violently when connecting to prevent the body from being pulled. Meanwhile, one supportpoint should be set every 1~1.5m to prevent the drainpipe from yielding (Refer to Fig.5-17a in the figure page). Or you can tie the drainpipe with the connecting pipe to fix it.(Refer to Fig.5-17.c in the figure page)
In the case of prolonged drainpipe, you had better tighten its indoor part with a protection tube to prevent it from loosing.
If the outlet of the drainpipe is higher than the body's pump joint, the pipe should be arranged as vertically as possible. And the lift distance must be less than 200mm, otherwise the water will overflow when the heat pump stops. (Refer to
Fig.5-18 in the figure page)
The end of the drainpipe should be over 50mm higher than the ground or the bottom of the drainage chute, and do not immerse it in water. If you discharge the water directly into sewage, be sure to make a U-form aquaseal by bending the pipe up to prevent the smelly gas entering the house through the drain pipe.
Fit the seal into the drain joint, then insert the drain joint into the base pan hole of outdoor, rotate 90° to securely assemble them.
Fit the seal into the drain joint, then insert the drain joint into the base pan hole of outdoor, rotate 90° to securely assemble them. Connect the drain joint with an extension drain hose (Locally purchased), in case of the condensate draining off the outdoor unit during the heating mode.
Seal
Drain joint
The base pan
of outdoor unit
The base pan hole
of outdoor unit
Seal
Drain
joint
Fig.8-1
NOTE
All the figures in this manual are for explanation purpose only. They may be slightly different from the heat pump you purchased.The actual unit shall prevail.
installation manual
18
Page 20
9. CONNECTIVE DIAGRAM
2. Cooling only
Liquid side
Gas side
Liquid side
Orifice
NOTE
For ensuring throttled efficiency , Please mount the Orifice assembly as horizontally as possible; and anti-shock rubber should be wrapped at external of the Orifice for denoise.
CAUTION
Mark the data plate with the Orifice installed(for some models).
Please purchase the fittings according to the requirements in the manual strictly.
Refer the diagram when installing.
1. Cooling&heating
Liquid side
Fig. 9-1
Indoor
Indoor
Indoor
Outdoor
Liquid side
Outdoor
Liquid side
Outdoor
X
Fig. 9-3
Indoor
Indoor
Indoor
X
X
Outdoor
Liquid side
Outdoor
Liquid side
Outdoor
Fig. 9-2
installation manual
19
Page 21
10. WIRING
The appliance shall be installed in accordance with national wiring regulations.
The heat pump should use separate power supply with rated voltage.
The external power supply to the heat pump should have ground wiring, which is linked to the ground wiring of the indoor and outdoor unit.
The wiring work should be done by qualified persons according to circuit drawing.
An all-pole disconnection device which has at least 3mm sepaaration distance in all pole and a residual current device (RCD) with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule.
Be sure to locate the power wiring and the signal wring well to avoid cross-disturbance.
Do not turn on the power until you have checked carefully after wiring.
1. Split type outdoor unit
Cover
Protection board
Fig.10-1
2. Vertical discharge type outdoor unit
The power cord type designation is H07RN-F.
NOTE
Remark per EMC Directive 2004/108/EC For to prevent flicker impressions during the start of the compressor (technical process)following installation conditions do apply.
1
The power connection for the heat pump has to be done at the main power distribution. The distribution has to be of a low impedance, normally the required impedance reaches at a 32 A fusing point.
2
No other equipment has to be connected with this power line.
For detailed installation acceptance please refer to your
3
power supplier, if restrictions do apply for products like washing machines, heat pumps or electrical ovens.
For power details of the heat pump refer to the rating
4
plate of the product.
For any question contact your local dealer.
5
Connect the cable
10.1
Dissemble the bolts from the cover.(If there isn't a cover on the outdoor unit, disassemble the bolts from the maintenance board, and pull it in the direction of the arrow to remove the protection board.)
Connect the connective cables to the terminals as identified with their respective mached numbers on the terminal block of indoor and outdoor units.
Protection Board
3. Centrifugal fan outdoor unit
Protection Board
All the figures in this manual are for explanation purpose only. They may be slightly different from the heat pump you purchased.The actual unit shall prevail.
Fig.10-2
Fig.10-3
NOTE
Re-install the cover or the protection board.
The Specification of Power
10.2
(Refer to Table10-1Table 10-8)
Wiring figure
10.3
(Refer to Fig.10-1Fig.10-6)
installation manual
20
Page 22
11. TEST OPERATION
1
The test operation must be carried out after the entire installation has been completed.
Please confirm the following points before the test operation:
2
The indoor unit and outdoor unit are installed properly.
Tubing and wiring are correctly completed.
The refrigerant pipe system is leakage-checked.
The drainage is unimpeded.
The heating insulation works well.
The ground wiring is connected correctly.
The length of the tubing and the added stow capacity of the refrigerant have been recorded.
The power voltage fits the rated voltage of the heat pump.
There is no obstacle at the outlet and inlet of the outdoor and indoor units.
The gas-side and liquid-side stop valves are both opened.
The heat pump is pre-heated by turning on the power.
According to the user's requirement, install the remote controller frame where the remote controller's signal can reach the indoor unit smoothly
3
4
Test operation
Set the heat pump under the mode of "COOLING" with the remote controller, and check the following points. If there is any malfunction, please resolve it according to the chapter "Troubleshooting" in the "Owner's Manual".
1) The indoor unit a. Whether the switch on the remote controller works well. b. Whether the buttons on the remote controller works well. c. Whether the air flow louver moves normally. d. Whether the room temperature is adjusted well. e. Whether the indicator lights normally. f. Whether the temporary buttons works well. g. Whether the drainage is normal. h. Whether there is vibration or abnormal noise during operation. I. Whether the heat pump heats well in the case of the HEATING/COOLING type.
2) The outdoor unit a. Whether there is vibration or abnormal noise during operation. b. Whether the generated wind, noise, or condensed of by the heat pump have influenced your neighborhood. c. Whether any of the refrigerant is leaked.
CAUTION
A protection feature prevents the heat pump from being activated for approximately 3 minutes when it is restarted immediately after shut off.
installation manual
21
Page 23
The Specification of Power(indoor power supply)
Table 10-1
MODEL
POWER
CIRCUIT BREAKER/FUSE(A)
Table 10-2
POWER
CIRCUIT BREAKER/FUSE(A)
FREQUENCY AND VOLT
MODEL
PHASE
PHASE
FREQUENCY AND VOLT
18 24 60 30~36 42~48
1Phase 1Phase 208-240V 208-2 40V
20/16 40/25 50/30 60/45 60/50
30~36 30~36
3Phase 380-420 V
25/20 25/20 40/25 45/35
42~60 42~60
3Phase 3Phase 380-420 V
The Specification of Power(outdoor power supply)
Table 10-3
MODEL
24 60 30~36 42~48
1Phase 208-240V
208-240V
1Phase 208-240V
3Phase 208-240V
1Phase 208-240V
POWER
CIRCUIT BREAKER/FUSE(A)
Table 10-4
POWER
CIRCUIT BREAKER/FUSE(A)
FREQUENCY AND VOLT
MODEL
PHASE
PHASE
FREQUENCY AND VOLT
1Phase 208-240V
40/30 60/40 70/55 70/60
30~36 30~36
3Phase 380-420 V
25/20 25/20 40/25 45/35
1Phase 208-240V
1Phase 208-240V
1Phase 208-240V
42~60 42~60
3Phase 3Phase 380-420 V
208-240V
3Phase 208-240V
installation manual
22
Page 24
The Specification of Power(independence power supply)
Table 10-5
MODEL
POWER
(indoor)
CIRCUIT BREAKER/FUSE(A)
POWER (outdoor)
CIRCUIT BREAKER/FUSE(A)
Table 10-6
POWER
POWER
(indoor)
(indoor)
CIRCUIT BREAKER/FUSE(A)
POWER
POWER
(outdoor)
(outdoor)
CIRCUIT BREAKER/FUSE(A)
FREQUENCY AND VOLT
FREQUENCY AND VOLT
MODEL
FREQUENCY AND VOLT
FREQUENCY AND VOLT
PHASE
PHASE
PHASE
PHASE
18 24 60 30~36 42~48
1Phase 1Phase 208-240V 208-2 40V 20/16 20/16 20/16 20/16 20/16 1Phase 1Phase
208-240V 208-2 40V
1Phase 208-240V
1Phase
208-240V
1Phase 208-240V
1Phase
208-240V
1Phase 208-240V
1Phase 208-240V
20/16 40/25 50/30 60/45 60/50
30~36 30~36
1Phase 208-240V
20/16 20/16 20/16 20/16 3Phase 380-420 V
42~60 42~60
1Phase 208-240V
3Phase 3Phase 380-420 V
1Phase 208-240V
208-240V
1Phase 208-240V
3Phase 208-240V
25/20 25/20 40/25 45/35
The Specification of Power for the invert type heat pump(independence power supply)
Table 10-7
MODEL
POWER
(indoor)
CIRCUIT BREAKER/FUSE(A)
POWER (outdoor)
CIRCUIT BREAKER/FUSE(A)
Table 10-8
POWER
POWER
(indoor)
(indoor)
CIRCUIT BREAKER/FUSE(A)
FREQUENCY AND VOLT
MODEL
FREQUENCY AND VOLT
PHASE
PHASE
FREQUENCY AND VOLT
PHASE
18 24 60 30~36 42~48
1Phase 1Phase 220-240V 220-2 40V
15/10 15/10 15/10 15/10 15/10 1Phase 1Phase 208-240V 208-2 40V
1Phase 220-240V
1Phase 208-240V
1Phase 220-240V
1Phase 208-240V
1Phase 220-240V
1Phase 208-240V
30/20 30/20 40/30 40/35 50/40
30~36 30~36
1Phase 220-240V
15/10 15/10 15/10 15/10
42~60 42~60
1Phase 220-240V
1Phase 220-240V
1Phase 220-240V
POWER
POWER (outdoor)
(outdoor)
CIRCUIT BREAKER/FUSE(A)
FREQUENCY AND VOLT
PHASE
3Phase 380-420 V
3Phase 3Phase 380-420 V
208-240V
3Phase 208-240V
30/20 30/25 50/40 50/40
installation manual
23
Page 25
CAUTION
The power supply is included in the power supply above mentioned can be applied to the table.
Wiring figure
Fig.10-4
Power supply
Switch/Fuse (Available locally)
Power wiring (indoor)
Power linking wiring (Outdoor)
Indoor Unit
Outdoor Unit
Ground wiring
Gr ound wiri ng
Strong elec-signal link wiring
Weak elec-signal link wiring
Ground the heat pump properly in case to affect its anti-interference function
Fig.10-5
Power supply
Power linking wiring (Outdoor)
Indoor Unit
Outdoor
Unit
Switch/Fuse
(Available locally)
Power wiring (indoor)
Ground wiring
installation manual
24
Gr ound wiri ng
Strong elec-signal link wiring
Weak elec-signal link wiring
Ground the heat pump properly in case to affect its anti-interference function
Page 26
Fig.10-6
Power supply
Power supply
Switch/Fuse (Available locally)
Power wiring (indoor)
Power linking wiring (Outdoor)
Indoor Unit
Out door Unit
Gr ound wiring
Gr ound wiring
We ak elec-signal link wiring
Ground the heat pump properly i n case to affect its anti-interference function
CAUTION
A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation.
When wiring, please choose the corresponding chart, or it may cause damage.The signs of the indoor terminal block in the some of following fugures may be replaced by L N L1 N1.
installation manual
25
Page 27
QSQ4I-017AEN
The design and specifications are subject to change without prior notice for product improvement.Consult with the sales agency or manufacturer for details.
2012.12.20
202000192506
Page 28
Page 29
Page 30
installation manual
29
Page 31
installation manual
30
Page 32
installation manual
31
Page 33
installation manual
32
Page 34
installation manual
33
Page 35
installation manual
34
Page 36
installation manual
35
Page 37
installation manual
36
Page 38
installation manual
37
Page 39
installation manual
38
Page 40
installation manual
39
Page 41
installation manual
40
Loading...