Price RDV Series, RDVQ Series, RDVQ 5000 Installation, Operation And Maintenance Manual

Page 1
MANUAL – INSTALLATION, OPERATION, AND MAINTENANCE
Air Volume Control Valve
RDV / RDVQ Series
v004 – Issue Date: 07/14/16
© 2016 Price Industries Limited. All rights reserved.
Page 2
AIR VOLUME CONTROL VALVE
TABLE OF CONTENTS
Product Overview
General ......................................................................... 1
Receiving Inspection ..................................................... 1
Wiring ........................................................................... 1
Installing the RDV/RDVQ 5000 Terminal Unit ................. 2
Air Volume Ranges ........................................................ 2
SP300 Cal. Curves - RDV ............................................. 3
SP300 Cal. Curves - RDVQ w/Absorptive Silencer ........ 4
SP300 Cal. Curves - RDVQ w/Packless Silencer ........... 5
Page 3
OPTIONAL NEMA1 CONTROLS ENCLOSURE (SEE NOTE)
OPTIONAL NEMA1 CONTROLS ENCLOSURE (SEE NOTE)
20”
(508)
MULTI-POINT SENSOR C/W GAUGE TAPS
PACKLESS SILENCER
20”
(508)
4
3
/4” (121)
9
1
/2” (241)
9
1
/2” (241)
MULTI-POINT SENSOR C/W GAUGE TAPS
ABSORPTIVE SILENCER
DIA = A + 8”
4
3
/4” (121)
DIA = A - 1/8” (3)
DIA = A -
1
/8” (3)
181/2” (470)
INLET SILENCER
SECTION
DIA = A - 1/8” (3)
AIR FLOW
2”
(51)
B
2” (51)
36” (914)
CONNECTION COLLAR
UP
AIR VOLUME CONTROL VALVE
PRODUCT OVERVIEW
General
The RDV/RDVQ is supplied with the duct, damper, and airflow sensor. The RDV/RDVQ assembly is designed to accept Direct Digital Controls (DDC) for VAV pressure independent operation.
The terminal unit controls are supplied by the controls contractor and either factory or field mounted and wired. For information concerning controls, components, sequence of operation, etc., please refer to the documentation provided by the controls contractor.
Receiving Inspection
After unpacking the assembly, check it for shipping damage. If any shipping damage is found, report it immediately to the delivering carrier. During unpacking and installation do not handle by the inlet velocity sensor, damper shaft, or tubing. Damage may result.
Wiring
If controls have been factory mounted, a wiring diagram will be included with the unit indicating the factory mounted components. For field wiring of room sensors and other accessories, refer to the controls contractor's documentation. If the controls have been field mounted, refer to the controls contractor's documentation for all wiring information.
Damper rotation is always clockwise to the open position. An identification mark on the end of the shaft indicates the damper position.
The factory supplied sensing lines are color coded. Red indicates the total pressure or ”HI“ line which should be located on the upstream side. Green indicates the static pressure or ”LO“ line which should be located on the downstream side.
An optional protective enclosure may be provided to house the terminal unit control components. The enclosure cover is removable with two sheet metal screws.
RDV
AIR
DIA = A - 1/8” (3)
FLOW
RDVQ
PACKLESS SILENCER
20”
(508)
MULTI-POINT SENSOR C/W GAUGE TAPS
DIA = A - 1/8” (3)
4 1/2” (114)
DAMPER SHAFT
MULTI-POINT SENSOR C/W GAUGE TAPS FOR PNEUMATIC CONTROLS
NEMA1 OPTIONAL CONTROLS ENCLOSURE
20”
(508)
AIR FLOW
2”
(51)
3
/4” (121)
4
1
9
/2” (241)
OPTIONAL NEMA1 CONTROLS ENCLOSURE (SEE NOTE)
36” (914)
INLET SILENCER
SECTION
ABSORPTIVE SILENCER
DIA = A + 8”
MULTI-POINT SENSOR C/W GAUGE TAPS
2” (51)
DIA = A - 1/8” (3)
18 1/2” (470)
UP
CONNECTION COLLAR
DIA = A -
1 1/2” (38)
4
1
/2” (241)
9
OPTIONAL NEMA1 CONTROLS ENCLOSURE (SEE NOTE)
181/2” (470)
UP
1
/8” (3)
3
/4” (121)
B
priceindustries.com | AIR VOLUME CONTROL VALVE - Manual
1
Page 4
AIR VOLUME CONTROL VALVE
INSTALLATION INSTRUCTIONS
Installing the RDV/RDVQ Terminal Unit
The basic RDV is light enough that it can be supported by the ductwork in which it is installed. The RDVQ is supplied with silencers and should be supported directly. Use the support method prescribed for the round duct in the job specifications.
NOTE: For optimum performance there should be a minimum
of three duct diameters of straight inlet duct, same size as the inlet, between the inlet and any transition, take off or fitting.
The assembly should be mounted right side up. It should be level within ±10 degrees of horizontal, both parallel to the air flow and at right angles to the air flow. The side of the assembly is labelled with an arrow indicating UP. Do not mount the control side of the assembly tight to a wall, pipe or other obstruction. Allow sufficient room for access to the controls
If the RDV/RDVQ is mechanically fastened to the duct work an approved duct sealer should be used to seal all connections.
Damper rotation is always clockwise to the open position. An identification mark on the end of the shaft indicates the damper position.
The air volume ranges listed are recommended for optimum performance. A minimum value of zero is also acceptable if no heating coils are attached.
Selection of air flow limits below the listed values is not recommended. Stability and accuracy may not be acceptable at lower than recommended air flow limits. The actual performance will vary depending on the terminal unit controls supply.
Air Volume Ranges
RDV Basic
Size
4 45 225 21 106 5 60 350 28 165 6 65 450 31 212 7 95 650 45 307 8 125 800 59 378
9 160 1050 76 496 10 210 1350 99 637 12 300 2100 142 991 14 430 3000 203 1416 16 575 4000 271 1888
RDVQ - Absorptive
Size
4 -- -- -- --
5 -- -- -- --
6 80 450 38 212
7 110 650 52 307
8 160 800 76 378
9 200 1050 94 496 10 270 1350 127 637 12 350 2100 165 991 14 500 3000 236 1416 16 650 4000 307 1888
RDVQ - Absorptive
Size
4 -- -- -- --
5 -- -- -- --
6 65 380 31 179
7 95 650 45 307
8 125 790 59 373
9 160 1050 76 496 10 210 1350 99 637 12 300 2025 142 956 14 430 2400 203 1133 16 575 3425 271 1616
CFM L/S
MIN MAX MIN MAX
CFM L/S
MIN MAX MIN MAX
CFM L/S
MIN MAX MIN MAX
2
AIR VOLUME CONTROL VALVE - Manual | priceindustries.com
NOTE: Factory calibrated controls must be selected
within the above flow range limits. A minimum value of zero is also available. When an auxiliary flow setting is specified, the value must be greater than the minimum setting and within the range limits.
On controls mounted by Price but supplied by others, the air volume ranges are guidelines only.
Selection of air flow limits below the listed values is not recommended. Stability and accuracy may not be acceptable at lower than recommended air flow limits. The actual performance will vary depending on the terminal unit controls supplied.
Page 5
AIR VOLUME CONTROL VALVE
INSTALLATION INSTRUCTIONS
SP300 Calibration Curves - RDV
Calibration Equation
2
VP =
VP - differential
Q - air flow
K - calibration
Q
( )
K
pressure at sensor, inches w.g.
rate, cfm at standard density.
constant
Unit Size K
4 340
5 426
6 468
7 673
8 890
9 1155
10 1487
12 2141
14 3045
16 4074
Notes:
1. Gauge taps are normally supplied with the pneumatic controls to allow field measurement of the differential pressure at the sensor with a manometer, magnahelic or other measuring device.
If the terminal velocity controls utilize a flow-through transducer, a proper
velocity pressure reading will NOT be read at the gauge taps and the calibration curves CANNOT be used for field measurement. The flow­through transducer operates on the principle of mass flow rather than pressure differential.
priceindustries.com | PRICE FUME HOOD CONTROLLER - Manual
Controls utilizing a dead-ended pressure transducer will allow field measurement with the gauge taps and calibration curves provided.
2. Setting flow limits for a differential pressure of less than 0.02 inches in NOT recommended. Stability and accuracy of flow limits may not be acceptable due to low velocity pressure signal. Performance will vary depending on the terminal unit controls provided.
3. For field calibration of air flow limits refer to the control contractors documentation.
3
Page 6
AIR VOLUME CONTROL VALVE
INSTALLATION INSTRUCTIONS
SP300 Calibration Curves - RDVQ w/Absorptive Silencer
Calibration Equation
VP =
Unit Size K
6 570
7 790
8 1100
9 1325
10 1770
12 2450
14 3500
16 4600
4
AIR VOLUME CONTROL VALVE - Manual | priceindustries.com
Q 2
( )
K
VP - differential pressure
at sensor, inches w.g.
Q - air flow rate, cfm at standard density.
K - calibration constant
Notes:
1. Gauge taps are normally supplied with the pneumatic controls to allow field measurement of the differential pressure at the sensor with a manometer, magnahelic or other measuring device.
If the terminal velocity controls utilize
a flow-through transducer, a proper velocity pressure reading will NOT be read at the gauge taps and the calibration curves CANNOT be used for field measurement. The flow­through transducer operates on the principle of mass flow rather than pressure differential.
Controls utilizing a dead-ended
pressure transducer will allow field measurement with the gauge taps and calibration curves provided.
2. Setting flow limits for a differential pressure of less than 0.02 inches is NOT recommended. Stability and accuracy of flow limits may not be acceptable due to low velocity pressure signal. Performance will vary depending on the terminal unit controls provided.
3. For field calibration of air flow limits refer to the control contractors documentation.
Page 7
AIR VOLUME CONTROL VALVE
INSTALLATION INSTRUCTIONS
SP300 Calibration Curves - RDVQ w/Packless Silencer
Calibration Equation
VP =
Unit Size K
6 382
7 690
8 790
9 1130
10 1380
12 2025
14 2415
16 3425
Q 2
( )
K
VP - differential pressure
at sensor, inches w.g.
Q - air flow rate, cfm at standard density.
K - calibration constant
Notes:
1. Gauge taps are normally supplied with the pneumatic controls to allow field measurement of the differential pressure at the sensor with a manometer, magnahelic or other measuring device.
If the terminal velocity controls utilize
a flow-through transducer, a proper velocity pressure reading will NOT be read at the gauge taps and the calibration curves CANNOT be used for field measurement. The flow­through transducer operates on the principle of mass flow rather than pressure differential.
priceindustries.com | AIR VOLUME CONTROL VALVE - Manual
Controls utilizing a dead-ended
pressure transducer will allow field measurement with the gauge taps and calibration curves provided.
2. Setting flow limits for a differential pressure of less than 0.02 inches is NOT recommended. Stability and accuracy of flow limits may not be acceptable due to low velocity pressure signal. Performance will vary depending on the terminal unit controls provided.
3. For field calibration of air flow limits refer to the control contractors documentation.
5
Page 8
This document contains the most current product information as of this printing.
For the most up-to-date product information, please go to priceindustries.com
© 2016 Price Industries Limited. All rights reserved.
Loading...