Pribusin IUC-7X-SLX Instruction Manual

Manufacturers of Process
Controls and Instrumentation
Instruction Manual
Model:
IUC-7X-SLX
Function: Isolated Slidewire Transmitter
Input:
Output:
Power:
X=1: 0-100 Ohm X=2: 0-500 Ohm X=3: 0-1 K Ohm
X=7:
X=1: 1-5 mA X=2: 4-20mA X=3: 0-1 mA
X=7:
X=4: 0-2K Ohm X=5: 0-5K Ohm
X=6: 0-10K Ohm
X=4: 10-50 mA X=5: 1-5 VDC
X=6: 0-10 VDC
Serial #:
For Technical Assistance And Questions Call
USA: (231) 788-2900 CANADA: (905) 660-5336
24 VDC, 160 mA
(If special or required)
Restocking Policy
All product returned to Pribusin Inc. in prime condition (not damaged, scratched or defaced in any way) within seven (7) months from the original date of shipment is subject to a 50% restocking charge. All product must be accompanied by a Return Authorization number (RA number) which must be obtained from Pribusin Inc. prior to returning any product.
After seven (7) months from the original date of shipment, products cannot be returned for restocking.
Custom designed products, modified products or all nonĀ­standard products may not be returned for restocking.
Warranty Policy
Pribusin Inc. warrants equipment of its own manufacture to be free from defects in material and workmanship, under normal conditions of use and service, and will replace any component found to be defective, on its return to Pribusin Inc., transportation charges prepaid, within one year of its original purchase. Pribusin Inc. will extend the same warranty protection on equipment, peripherals and accessories which is extended to Pribusin Inc. by the original manufacturer. Pribusin Inc. also assumes noliability, expressed or implied, beyond its obligation to prelace any component involved. Such warranty is in lieu of all other warranties, expressed or implied.
Page v
Manufacturers of Process
Controls and Instrumentation
Model: IUC-7X-SLX
Isolated Slidewire Transmitter
Standard Features:
High Input-Output-Power Isolation (1500VAC Test)
Standard Slidewire Inputs (see back)
Industry Standard Output: 4-20 mA, 1-5 VDC, more (see back)
Special Input Ranges Available
High Output Drive on Current Outputs
Easy Field Calibration
Two Wire Supply Option for Two Wire Transmitters
Power: 117 VAC 50/60 Hz (Optional 24 VDC)
High Noise Rejection
CSA and NRTL Approved (LR 51078)
NRTL/C
Function:
The IUC-7X-SLX is an isolated slidewire transmitter that provides high isolation and rugged design for many control applications. Three-way isolation is provided between the input, the output and the power. The signal isolation takes place through state-of-the-art optical isolators to ensure high accuracy and repeatability. Special output drive circuitry allows the IUC-7X-SLX to drive loads of up to 1600 Ohms which makes it ideal for driving multi instrument loops.
Several standard slidewire ranges are available and special ranges are available upon consultation with the factory or your representative.
R
Calibration:
Calibration is via easily accessible multi-turn potentiometers.. All instruments are shipped fully calibrated and tested, but can easily be field adjusted. A Zero and Span pot are available on all units to adjust the output signal.
Specifications:
Isolation: Input to Output to Power 1500 VAC (test) Accuracy/Linearity:+/- 0.1% max., +/- 0.05% typ. Operating Temperature: -40 Deg.C. to +50 Deg.C. Temperature Effects: +/-0.5% max., +/-0.2% typ.
(for 40 Deg.C. change) Output Ripple: less than 0.1% p-p value Common Mode Rejection: 120 dB @ 60 Hz Loop Drive: Max. 1600 Ohms at 20 mA
Page A17
IUC-7X-SLX
Enclosures & Dimensions:
Standard Metal Enclosure NEMA 4X Option
Connection:
Shown here for 4-20mA Output
Conduit Cover Option for Metal Enclosure
Model Designation:
IUC
-7X-SLX
Output
1: 1-5 mA (4000 Ohm Drive) 2: 4-20 mA (1000 Ohm Drive) 3: 0-1 mA (20000 Ohm Drive) 4: 10-50 mA (250 Ohm Drive) 5: 1-5 VDC (Zout=250 Ohm) 6: 0-10 VDC (Zout=500 Ohm) 7: Special Output
Example:
If no options specified, unit is 117 VAC Power in metal enclosure
Options:
Slidewire transmitter with 1K Ohm Slidewire and 4-20 mA Output in standard metal enclosure and 117VAC Power is designated by: IUC-72-SL3
(Add letters to end of Model Number)
Input
1: 100 Ohm 2: 500 Ohm 3: 1K Ohm 4: 2K Ohm 5: 5K Ohm 6: 10K Ohm 7: Special Input
Manufactured By:
USA:
USA:
Pribusin Inc. 743 Marquette Ave.
www.pribusin.com
www.pribusin.com info@pribusin.com
info@pribusin.com
Page A17
Muskegon, MI 49442 Ph: (231) 788-2900 Fx: (231) 788-2929
A - 24 VDC Prime Power B - 240 VAC Prime Power (not CSA approved) T - 200 mA Two Wire Supply (24 VDC unreg.) C - Conduit Cover for Metal Enclosure (see above) N - NEMA 4X enclosure (see above)
CANADA:
Pribusin Inc. 101 Freshway Dr. Unit 57 Concord, Ontario, L4K 1R9 Ph: (905) 660-5336 Fx: (905) 660-4068
Rev.A Subject to change without notice