Prestige Solo 110, Solo 80, Solo 250, Solo 299, Solo 399 Installation And Maintenance Manual

...
prestige
Solo 80 250 110 299 155 399 175
Water Boiler
L
I
S
T
E
D
* I N S T A L L A T I O N A N D M A I N T E N A N C E *
* I N S T A L L A T I O N A N D M A I N T E N A N C E *
M A N U A L
M A N U A L
NOTICE
WARNING
Warranty Registration Card must be filled out by the customer and mailed within thirty (30) days of installa­tion in order to gain warranty coverage.
When receiving the PRESTIGE Solo unit, any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
Leave all documentation received with appliance with owner for future reference.
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor ’s phone. Follow the gas
- If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the
Revised Date: 12/15/15
gas supplier.
FOR YOUR SAFETY
supplier ’s instructions.
2015-9 Prestige ACVMax Install Manual
Table of Contents
Product & Safety Information
Definitions .........................................................................................................1
Qualified Installer: .........................................................................................................2
Homeowner: .........................................................................................................2
Section I - Pre-Installation Items
1.1 Code Compliance..................................................................................................3
1.2 Determining Product Location..............................................................................3
1.3 Boiler Replacement...............................................................................................3
1.4 Recommended Clearances ....................................................................................4
1.5 Residential Garage Installations ...........................................................................4
1.6 Boiler Freeze Protection Feature ..........................................................................4
SECTION II - Combustion Air and Venting
2.1 Combustion Air Contamination ............................................................................5
2.2 Ventilation and Combustion Air Requirements - Direct Vent ..............................6
2.3 Ventilation and Combustion Air Requirements - Category IV.............................6
2.4 Methods of Accessing Combustion Air Into A Space - Category IV...................7
2.4.1 Indoor Combustion Air Opening Size and Location...................................7
2.4.2 Outdoor Combustion Air Opening Size and Location................................7
2.4.2.1 One Permanent Opening Method ...................................................7
2.4.2.2 Two Permanent Openings Method ................................................8
2.4.3 Combination of Indoor and Outdoor Combustion Air ..............................9
2.5 Combustion Air and Vent Piping ..........................................................................9
2.6 Removal of an Existing Boiler from a Common Vent System ............................10
2.7 Commonwealth of Massachusetts Installations Only...........................................11
SECTION III - Unit Preparations
3.1 Handling Instructions............................................................................................12
3.2 Wall Mounting Installation ...................................................................................12
3.3 Wall Mounting Guidelines ....................................................................................12
3.4 Stud Walls - Installation .......................................................................................13
3.4.1 PRESTIGE Solo 80/110/155/175/250.........................................................13
3.4.2 PRESTIGE Solo 299/399 ...........................................................................13
3.5 Wall Bracket Installation - Solid Walls.................................................................13
3.6 Boiler Mounting....................................................................................................13
SECTION IV - Boiler Piping
4.1 General Piping Requirements ...............................................................................14
4.2 Pressure Relief Valve ............................................................................................14
4.3 Boiler Air Vent ......................................................................................................14
4.4 Low Water Cutoff Device .....................................................................................15
4.5 Additional Limit Control ......................................................................................15
i
Table of Contents
4.6 Backflow Preventer...............................................................................................16
4.7 Boiler System Piping Applications .......................................................................16
4.8 Expansion Tank and Makeup Water .....................................................................16
4.8.1 Diaphragm Expansion Tank ........................................................................16
4.8.2 Closed-Type Expansion Tank......................................................................16
4.9 Circulator .........................................................................................................19
4.10 Sizing Primary Piping ...........................................................................................19
4.11 Domestic Hot Water System Piping .....................................................................19
4.12 System Piping - Zone Circulators.........................................................................19
4.13 System Piping - Zone Valves ................................................................................19
4.14 System Piping - Through Boiler ...........................................................................19
4.15 System Piping - Radiant Heating..........................................................................19
4.16 System Piping - Special Application ....................................................................20
4.17 System Piping - Multiple Units Installation .........................................................20
SECTION V - Installing Vent / Combustion Air & Condensate Drain
5.1 Installing Vent and Combustion Air .....................................................................24
5.2 Installing Condensate Drain Assembly.................................................................24
SECTION VI - Gas Piping
6.1 Gas Supply Piping Connection .............................................................................26
6.2 Natural Gas .........................................................................................................27
6.2.1 Pipe Sizing...................................................................................................27
6.2.2 Supply Pressure Requirements ....................................................................27
6.3 Propane Gas 28
6.3.1 Pipe Sizing - Propane Gas...........................................................................28
6.3.2 Propane Gas Supply Pressure Requirements ..............................................28
SECTION VII - Internal Wiring
7.1 General Requirements...........................................................................................30
7.2 Fuse Locations ......................................................................................................30
SECTION VIII - External Wiring
8.1 Installation Compliance ........................................................................................32
8.2 Line Voltage Connections .....................................................................................32
8.3 Circulator Wiring ..................................................................................................32
8.4 Alarm Wiring ........................................................................................................33
8.5 Low Voltage Connections .....................................................................................33
8.6 Thermostat Wiring ................................................................................................33
8.7 Outdoor Sensor Wiring .........................................................................................34
8.8 Domestic Hot Water Wiring..................................................................................34
8.9 Additional Boiler Limits .......................................................................................34
8.10 External Modulation Control ................................................................................34
ii
Table of Contents
8.11 System Sensor Wiring...........................................................................................34
8.12 Cascade Wiring .....................................................................................................35
8.13 Modbus Wiring .....................................................................................................35
SECTION IX - ACVMax Operation
9.1 ACVMax Navigation ............................................................................................41
9.2 ACVMax Menu Structure.....................................................................................42
9.3 Home Screen .........................................................................................................43
9.4 Status Line Messages ............................................................................................44
9.5 Main Menu .........................................................................................................45
9.6 EZ Setup .........................................................................................................46
9.7 Heating EZ Setup .................................................................................................46
9.7.1 Select CH Demand ......................................................................................46
9.7.2 CH1 Setpoint ...............................................................................................46
9.7.3 CH2 Setpoint ...............................................................................................46
9.7.4 Select CH1 Reset Curve..............................................................................47
9.7.5 Select CH2 Reset Curve..............................................................................47
9.7.6 Set Warm Weather Shutdown Temperature.................................................47
9.7.7 CH EZ Setup Complete ...............................................................................47
9.8 Domestic Hot Water EZ Setup .............................................................................48
9.8.1 Select DHW Demand ..................................................................................48
9.8.2 Boiler DHW Setpoint ..................................................................................48
9.8.3 DHW Storage Setpoint ................................................................................48
9.8.4 DHW Priority Timeout................................................................................49
9.9 EZ Setup Reset......................................................................................................49
9.10 Display EZ Setup ..................................................................................................49
9.11 CH/DHW Operation .............................................................................................50
9.12 Boiler Information ...............................................................................................50
9.12.1 Boiler Information Logging ........................................................................50
9.12.2 Information Items ........................................................................................51
9.13 Lockout History ...................................................................................................52
9.13.1 Lockout Details ...........................................................................................52
9.13.2 Lockout Screen............................................................................................53
SECTION X - Start-Up Preparation
10.1 Boiler System Fluid Requirements .......................................................................56
10.1.1 Boiler Fluid pH Level 6.0 to 8.0 .................................................................56
10.1.2 Boiler Fluid Hardness Less Than 7 Grains .................................................56
10.1.3 Chlorinated Water........................................................................................56
10.1.4 Flush Boiler to Remove Sediment ..............................................................56
10.1.5 Cleaning of Old Boiler/System: .................................................................56
10.1.6 Cleaning of New Boiler/System: ..............................................................56
10.1.7 Check and Test Antifreeze...........................................................................57
iii
Table of Contents
10.1.8 Use of Antifreeze in the Boiler System.......................................................57
10.2 Filling the Boiler System ......................................................................................57
10.3 Check Low Water Cut-Off Device .......................................................................58
10.4 Check For Gas Leaks............................................................................................58
10.5 Check Thermostat Circuit .....................................................................................58
10.6 Inspection of Condensate Drain Assembly...........................................................58
SECTION XI - Start-Up Procedures
11.1 Final Checks Before Start-Up...............................................................................59
11.2 PRESTIGE Solo Start-Up.....................................................................................59
11.3 Check the PRESTIGE Solo and System...............................................................59
SECTION XII - Outdoor Reset Control
12.1 Mounting the Outdoor Sensor...............................................................................64
12.2 Wiring the Sensor..................................................................................................64
SECTION XIII - External Modulating Control
13.1 Wiring the Modulating Controller ........................................................................65
13.2 ACVMax Adjustment ...........................................................................................65
13.3 Programming of External Modulating Control.....................................................65
SECTION XV - Installation Record
SECTION XVI - Maintenance Schedule
16.1 Service Technician ................................................................................................69
16.2 Owner Maintenance ..............................................................................................69
SECTION XVII- Maintenance Procedures
17.1 Maintenance Procedures .......................................................................................70
17.2 Reported Problems................................................................................................70
17.3 Check Surrounding Area .....................................................................................70
17.4 Inspect Burner Area ..............................................................................................70
17.5 Check System Piping ............................................................................................70
17.6 Clean Condensate Drain Assembly.......................................................................71
17.7 Check Ventilation Air Openings ...........................................................................71
17.8 Inspect Vent and Combustion Air Piping..............................................................71
17.9 Check Boiler System.............................................................................................71
17.10 Check Expansion Tank..........................................................................................72
17.11 Check Boiler Relief Valve ....................................................................................72
17.12 Inspection of Ignitor..............................................................................................72
17.13 Check Ignition Wiring and Ground Wiring ..........................................................72
17.14 Check Control Wiring...........................................................................................73
iv
Table of Contents
17.15 Check Control Settings .........................................................................................73
17.16 Perform Start-up and Checkout Procedures .........................................................73
17.17 Check Burner Flame .............................................................................................73
17.18 Check Flame Signal ..............................................................................................74
17.19 Check Combustion Levels ....................................................................................74
17.20 Check Flue Gas Temperature................................................................................74
17.21 Clean Heat Exchanger...........................................................................................74
17.22 Review With Owner..............................................................................................75
17.23 Handling Previously Fired Combustion Chamber Insulation...............................75
17.24 Torque Specifications Table..................................................................................75
Section XVIII Replacement Parts
PRESTIGE Solo 80/110 Jacket Components..................................................................77
PRESTIGE Solo 175/250 Jacket Components................................................................78
PRESTIGE Solo 299/399 Jacket Components................................................................79
PRESTIGE Solo 80/110 Internal Components ...............................................................80
PRESTIGE Solo 155/175/250 Internal Components ......................................................81
PRESTIGE Solo 399 Internal Components ....................................................................82
PRESTIGE Solo 80/110 Burner Components.................................................................83
PRESTIGE Solo 155/175/250 Burner Components........................................................84
PRESTIGE Solo 299/399 Burner Components...............................................................85
PRESTIGE Solo Display Enclosure................................................................................86
PRESTIGE Solo Control Enclosure ................................................................................86
Section XIX Product Specifications
PRESTIGE Solo 80/110 Front View ...............................................................................88
PRESTIGE Solo 80/110 Right Side View.......................................................................89
PRESTIGE Solo 155/175/250 Front View......................................................................90
PRESTIGE Solo 155/175/250 Right Side View .............................................................91
PRESTIGE Solo 299/399 Front View.............................................................................92
PRESTIGE Solo 299/399 Right Side View.....................................................................93
Section XX Notes
General Notes .........................................................................................................97
v
Product & Safety Information
PRODUCT & SAFETY INFORMATION

Definitions

The following terms are used throughout this manual to bring attention to the presence of potential hazards or important information concerning the product.
DANGER
Indicates the presence of a hazardous situation which, if ignored, will result in death, serious injury or substantial property damage.
WARNING
Indicates a potentially hazardous situa­tion which, if ignored, can result in death, serious injury or substantial property damage.
CAUTION
Indicates a potentially hazardous situa­tion which, if ignored, may result in minor injury or property damage.
NOTICE
Indicates special instructions on installa­tion, operation or maintenance, which are important to equipment but not related to personal injury hazards.
BEST PRACTICE
Indicates recommendations made by ACV-Triangle Tube for the installers which will help to ensure optimum oper­ation and longevity of the equipment
NOTICE
ACV-Triangle Tube reserves the right to modify the technical specifications and compo­nents of its products without prior notice.
1
Product & Safety Information
DANGER
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system which has been under water.
WARNING
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas suppli­er, call the fire department.
Installation and service must be per­formed by a qualified installer, service agency or the gas supplier.
WARNING

Qualified Installer:

Prior to installing this product read all instruc­tions included in this manual and all accompa­nying manuals/documents with this appliance. Perform all installation steps required in these manuals in the proper order given. Failure to adhere to the guidelines within these manuals can result in severe personal injury, death or substantial property damage.

Homeowner:

- This product should be maintained / serviced and inspected annually by a qualified service technician.
- This manual is intended for use by a qualified Installer/Service Technician.
NOTICE
Please reference the unit’s model number and the serial number from the rating label when inquiring about service or trou­bleshooting.
WARNING
Should overheating occur or the gas supply fails to shut off, turn OFF the manual gas control valve external to the appliance.
WARNING
DO NOT add cold make up water when the appliance is hot. Thermal shock can potentially cause cracks in the heat exchanger.
CAUTION
When servicing the appliance:
- Avoid electrical shock by discon­necting the electrical supply prior to performing maintenance.
WARNING
ACV-Triangle Tube accepts no liability for any damage, injury or loss of life resulting from incorrect installation, from alter­ation of any factory supplied parts or from the use of parts or fittings not specified by ACV-Triangle Tube. If there is a conflict or doubt about the proper installation of the unit or any factory supplied or replacement parts please contact ACV­Triangle Tube Technical Support.
WARNING
A byproduct of any gas fired appliance is carbon monoxide. In the absence of any state or local codes requiring the installation of carbon monoxide detec­tor and alarms, ACV-Triangle Tube’s recommendation is to follow the requirements of the Commonwealth of Massachusetts, see page 11.
2
1.0 Pre-Installation Items

SECTION I - PRE-INSTALLATION ITEMS

1.1 Code Compliance
This product must be installed in accordance to the following:
- All applicable local, state, national and provincial codes, ordinances, regula­tions and laws.
- For installations in Massachusetts, code requires the boiler to be installed by a licensed plumber or gas fitter, and if antifreeze is utilized, the installation of a reduced pressure backflow preventer device is required in the boiler’s cold water fill or make up water supply line.
- For installation in Massachusetts all direct vented appliances must comply with the guidelines as outlined on page 11.
- The National Fuel Gas Code NFPA54/ ANSI Z 223.1 - Latest edition.
- National Electric Code ANSI/NFPA 70.
Before locating the PRESTIGE SOLO check for convenient locations to:
- Heating system piping
- Venting
- Gas supply piping
- Electrical service
Ensure the boiler location allows the combus­tion air/vent piping to be routed directly through the building and terminate properly outside with a minimum amount of length and bends.
Ensure the area chosen for the installation of the PRESTIGE Solo is free of any combustible materials, gasoline and other flammable liquids.
WARNING
Failure to remove or maintain the area free of combustible materials, gasoline and other flammable liquids or vapors can result in severe personal injury, death or substantial property damage.
- For installations in Canada -“Installation Code for Gas Burning Equipment” CGA/B149.1 or B149.2 Canadian Electrical Code Part 1 CSA C22.1.
- Standards for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, when required.
NOTICE
The PRESTIGE Solo boiler gas manifold and gas controls meet the safe lighting and other performance requirements as speci­fied in ANSI Z21.13 latest edition.

1.2 Determining Product Location

NOTICE
The PRESTIGE boiler is certified for indoor, conditioned space installations ONLY.
Ensure the PRESTIGE Solo and its controls are protected from dripping or spraying water during normal operation or service.
The PRESTIGE Solo should be installed in a location so that any water leaking from the boiler or piping connections or relief valve will not cause damage to the area surrounding the unit or any lower floors in the structure.

1.3 Boiler Replacement

If the PRESTIGE Solo is replacing an existing boiler, the following items should be checked and corrected prior to installation:
- Boiler piping leaks and corrosion.
- Improper location and sizing of the expansion tank on the boiler heating loop.
- If applicable, level and quality of antifreeze within the boiler system.
3
1.0 Pre-Installation Items

1.4 Recommended Clearances

The PRESTIGE Solo is approved for zero clearance to combustibles, excluding vent and boiler piping.
- Boiler Piping - 1/4 inch from com­bustible materials.
- Reference the appropriate vent supple­ment for clearance requirements.
BEST PRACTICE
To provide serviceability to the unit it is recommended that the following clear­ances be maintained:
Top boiler jacket - 24 inches [610 mm].
Front - 24 inches [610 mm].
Bottom boiler piping - 24 inches [610 mm].
Rear - 0 inches
Sides - 6 inches [153 mm]

1.5 Residential Garage Installations

When installing the PRESTIGE Solo in a resi­dential garage, the following special precautions per NFPA 54/ANSI Z223.1 must be taken:
- Mount the unit a minimum 18 inches [458 mm] above the floor level of the garage. Ensure the burner and ignition devices / controls are no less than 18 inches [458 mm] above the floor level.
- Locate or protect the unit in a manner so it cannot be damaged by a moving vehicle.

1.6 Boiler Freeze Protection Feature

The ACVMax boiler management system has a freeze protection feature built in. This feature monitors the boiler water temperature and responds as follows when no call for heat is pre­sent:
- 46ºF [8ºC] Pump outputs configured to respond to a CH1 Call are enabled.
WARNING
If the clearances listed above cannot be maintained or the enclosure in which the boiler is installed is less than 85 cubic feet, the space must be ventilated. See page 6 for ventilation requirements.
NOTICE
When maintaining less than recom­mended serviceability clearances, some product labeling, including the rating label, may become hidden and unread­able.
WARNING
When installing the PRESTIGE Solo in a confined space, sufficient air must be provided for proper combustion and venting and to allow, under normal oper­ating conditions, proper air flow around the product to maintain ambient temper­atures within safe limits to comply with the National Fuel Gas Code NFPA 54 ­latest edition.
- 42ºF [6ºC] Pump outputs configured to respond to a CH1 or CH2 Call are enabled, Burner operates at low fire.
- 60ºF [15ºC] Freeze protection ends. Burner & all pumps turn off after com­pleting CH Post Pump Time.
CAUTION
The boiler freeze protection feature is disabled during a hard lockout, however the circulators will operate.
CAUTION
The boiler freeze protection feature is designed to protect the boiler. The boiler should be installed in a primary/sec­ondary piping arrangement if it is installed in an unheated space or exposed to water temperatures of 46ºF or less. See Section IV for primary/sec­ondary piping examples. See Section X for antifreeze guides.
4
2.0 Combustion Air & Venting

SECTION II - COMBUSTION AIR AND VENTING

2.1 Combustion Air Contamination
WARNING
If the PRESTIGE Solo combustion air inlet is located in any area likely to cause or contain contamination, or if products, which would contaminate the air cannot be removed, the combustion air must be repiped and terminated to another loca­tion. Contaminated combustion air will damage the unit and its burner system, resulting in possible severe personal injury, death or substantial property damage.
WARNING
Do not operate a PRESTIGE Solo if its combustion air inlet is located near a laundry room or pool facility. These areas will always contain hazardous con­taminants.
Potential contaminating products
- Spray cans containing chloro/fluorocar­bons
- Permanent Wave Solutions
- Chlorinated wax
- Chlorine - based swimming pool chem­icals / cleaners
- Calcium Chloride used for thawing ice
- Sodium Chloride used for water soft­ening
- Refrigerant leaks
- Paint or varnish removers
- Hydrochloric acid / muriatic acid
- Cements and glues
- Antistatic fabric softeners used in clothes dryers
- Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
- Adhesives used to fasten building prod­ucts and other similar products
Pool and laundry products and common household and hobby products often contain fluorine or chlorine compounds. When these chemicals pass through the burner and vent system, they can form strong acids. These acids can create cor­rosion of the heat exchanger, burner components and vent system, causing serious damage and presenting a possi­ble threat of flue gas spillage or water leakage into the surrounding area.
Please read the information listed below. If contaminating chemicals are located near the area of the combustion air inlet, the installer should pipe the combustion air inlet to an outside area free of these chemicals per SECTION V of this installation manual.
Areas likely to contain these products
- Dry cleaning / laundry areas and estab­lishments
- Beauty salons
- Metal fabrication shops
- Swimming pools and health spas
- Refrigeration Repair shops
- Photo processing plants
- Auto body shops
- Plastic manufacturing plants
- Furniture refinishing areas and estab­lishments
- New building construction
- Remodeling areas
- Garages with workshops
5
2.0 Combustion Air Venting

2.2 Ventilation and Combustion Air Requirements - Direct Vent

A Direct Vent appliance utilizes uncontaminat­ed outdoor air (piped directly to the appliance) for combustion.
For Direct Vent installations, involving only the PRESTIGE Solo, in which the minimum service clearances are maintained as listed on page 4, no ventilation openings are required.
For Direct Vent, zero clearance installations involving only the PRESTIGE Solo, the space / enclosure must provide two openings for ven­tilation. The openings must be sized to provide 1 square inch of free area per 1,000 BTUH of boiler input. The openings shall be placed 12 inches from the top of the space and 12 inches from the floor of the space.
For installations in which the PRESTIGE Solo shares the space with air movers (exhaust fan, clothes dryers, fireplaces, etc.) and other com­bustion equipment (gas or oil) the space must be provided with adequate air openings to pro­vide ventilation and combustion air to the equipment. To properly size the ventilation / combustion air openings, the installer must comply with the National Fuel Gas Code NFPA 54, ANSI Z223.1 for installations in the U.S or CSA B149.1 and B149.2 for installa­tions in Canada.
WARNING
The space must be provided with venti­lation / combustion air openings proper­ly sized for all make-up air requirements (exhaust fans, clothes dryers, fireplaces, etc.) and the total input of all appliances located in the same space as the PRES­TIGE Solo, excluding the input of a Direct Vent PRESTIGE Solo which uses combustion air directly from the outside, thus additional free area for the open­ings is not required. Failure to provide or properly size the openings could result in severe personal injury, death or substantial property damage.

2.3 Ventilation and Combustion Air Requirements - Category IV

A Category IV appliance utilizes uncontami­nated indoor or outdoor air (surrounding the appliance) for combustion.
BEST PRACTICE
In order to reduce the potential risks associated with indoor contaminates (listed on page 5), flammable vapors and tight housing construction (little or no infiltration air), it is recommended to pipe uncontaminated combustion air directly from the outdoors to the appli­ance. This practice also promotes higher system efficiency by reducing heated indoor air from being exhausted from the house and replaced by cold infiltra­tion air into the house.
For installations in which the PRESTIGE Solo shares the space with air movers (exhaust fan, clothes dryers, fireplaces, etc.) and other com­bustion equipment (gas or oil) the space must be provided with adequate air openings to provide ventilation and combustion air to the equipment. To properly size the ventilation / combustion air openings, the installer must comply with the National Fuel Gas Code NFPA 54, ANSI Z223.1 for installations in the U.S or CSA B149.1 and B149.2 for installations in Canada, as referenced in this section of the manual and titled Methods of Accessing Combustion Air into a Space.
WARNING
The space must be provided with venti­lation / combustion air openings proper­ly sized for all make-up air requirements (exhaust fans, clothes dryers, fireplaces, etc.) and the total input of all appliances, including the PRESTIGE Solo when located in the same space. Failure to pro­vide or properly size the openings could result in severe personal injury, death or substantial property damage.
6
2.0 Combustion Air Venting

2.4 Methods of Accessing Combustion Air Into A Space - Category IV

2.4.1 Indoor Combustion Air
NOTICE
The methods listed in this section for accessing Indoor Combustion Air assume that the infiltration rate is ade­quate and not less than .40 ACH. For infiltration rates less than .40 ACH, ref­erence the NFPA 54 National Fuel Gas Code for additional guidance.

Opening Size and Location

Openings used to connect indoor spaces shall be sized and located in accordance with the following, see Fig. 1:
- Combining spaces on the same story. Each opening shall have a minimum free area of 1 sq. in./1000 Btu/hr of the total input rating of all gas utilization equipment in the space, but not less than 100 sq. inches. One opening shall com­mence within 12 inches of the top, and one opening shall commence within 12 inches of the bottom of the enclosure. The minimum dimension of air open­ings shall be not less than 3 inches.
- Combining spaces in different stories. The volumes of spaces in different sto­ries shall be considered as communicat­ing spaces where such spaces are con­nected by one or more openings in doors or floors having a total minimum free area of 2 sq. in./1000 Btu/hr of total input rating of all gas utilization equipment.
2.4.2 Outdoor Combustion Air
BEST PRACTICE
Isolating the combustion appliance room from the rest of the building and bring­ing in uncontaminated outside air for combustion and ventilation is always preferred.

Opening Size and Location

The minimum dimension of air openings shall be not less than 3 inches
Openings used to supply combustion and ven­tilation air shall be sized and located in accor­dance with the following:

2.4.2.1 One Permanent Opening Method

One permanent opening, commencing within 12 in. of the top of the enclosure, shall be provided as shown in Fig 2 on page 8. The equipment shall have clearances of at least 1 inch from the sides and 6 in. from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following:
Fig. 1:
- 1sq. in./3000 Btu/hr of the total input rating of all equipment located in the enclosures, and
- Not less than the sum of the areas of all vent connectors in the space.
All Combustion Air from Adjacent Indoor Spaces Through Indoor Combustion Openings
7
2.0 Combustion Air Venting
Fig. 2:
All Combustion Air from Outdoors Through One Permanent Air Opening

2.4.2.2 Two Permanent Openings Method

Two permanent openings, one commencing within 12 in. of the top and one commencing within 12 in. of the bottom of the enclosure, shall be provided. The openings shall commu­nicate directly, or by ducts, with the outdoors or spaces that freely communicate with the out­doors, as follows:
- Where directly communicating with the outdoors or where communication to the outdoors is through vertical ducts, each opening shall have a minimum free area of 1 sq. in./4000 Btu/hr of total input rat­ing of all equipment in the enclosure. See Fig.3.
- Where communicating with the out­doors is through horizontal ducts, each opening shall have a minimum free area of not less than 1 sq.in./2000 Btu/hr of total input rating of all equip­ment in the enclosure. See Fig. 4.
Fig. 3:
Fig. 4:
All Combustion Air from Outdoors Through Ventilated Attic
All Combustion Air from Outdoors Through Horizontal Ducts
8
2.0 Combustion Air Venting

2.4.3 Combination of Indoor and Outdoor Combustion Air

Indoor Openings: Where used, openings con­necting the interior spaces shall comply with the Indoor Combustion Air section on page 7.
Outdoor Opening(s) Location. Outdoor open­ing(s) shall be located in accordance with the Outdoor Combustion Air section.
Outdoor Opening(s) Size. Outdoor opening(s) shall be calculated in accordance with the following:
- The ratio of the interior spaces shall be the available volume of all communi­cating spaces divided by the required volume.
- The outdoor size reduction factor shall be 1 minus the ratio of interior spaces.
- The minimum size of outdoor open­ing(s) calculated in accordance with the above outdoor air section multiplied by the reduction factor. The minimum dimension of air openings shall not be less than 3 in.
ed outdoor air (piped directly to the appliance) for combustion.
BEST PRACTICE
In order to reduce the potential risks associated with indoor contaminates (listed on page 5), flammable vapors and tight housing construction (little or no infiltration air), it is recommended to pipe uncontaminated combustion air directly from the outdoors to the appli­ance. This practice also promotes higher system efficiency by reducing heated indoor air from being exhausted from the house and replaced by cold infiltra­tion air into the house.
NOTICE
Install combustion air and vent pipe as detailed in the PRESTIGE Solo Vent Supplement included in the boiler installation envelope. Refer to optional vent kit instructions for additional vent installation instructions.
DANGER
DANGER
Do not install the PRESTIGE Solo into a common vent with other gas or oil appli­ances. This may cause flue gas spillage or appliance malfunction, resulting in possi­ble severe personal injury, death or sub­stantial property damage.

2.5 Combustion Air and Vent Piping

The PRESTIGE Solo requires a Category IV venting system, which is designed for pressur­ized venting and condensate.
The PRESTIGE Solo is certified per ANSI Z21.13 as a Category IV or Direct Vent (sealed combustion) appliance. A Category IV appli­ance utilizes uncontaminated indoor or outdoor air (surrounding the appliance) for combustion. A Direct Vent appliance utilizes uncontaminat-
Verify installed combustion air and vent piping are sealed gas tight and meet all provided instructions and applicable codes, failure to comply will result in severe personal injury of death.
9
2.0 Combustion Air Venting
2.6 Removal of an Existing Boiler from a Common Vent System
EST PRACTICE
B
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the remaining appliances. At the time of removal of an existing boiler, the fol­lowing steps shall be followed with each appliance remaining connected to the com­mon venting system placed in operation, while the other appliances remaining con­nected to the common venting system are not in operation.
1. Seal any unused openings in the common
venting system.
2. Visually inspect the venting system for
proper size and horizontal pitch and deter­mine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or can­dle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the com­mon venting system properly vents when tested as outlined above, return doors, win­dows, exhaust fans, fireplace dampers, and any other gas-burning appliance to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CGA B149, Installation codes. When resizing any portion of the common venting system, the common venting sys­tem should be resized to approach the min­imum size as determined using the appro­priate tables in Part II of the National Fuel Gas Code ANSI Z223.1/NFPA 54 and/or CAN/CGA B149, Installation codes.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remain­ing connected to the common venting sys­tem are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
DANGER
Do not install the PRESTIGE Solo into a common vent with other gas or oil appli­ances. This may cause flue gas spillage or appliance malfunction, resulting in possi­ble severe personal injury, death or sub­stantial property damage.
10
2.0 Combustion Air Venting

2.7 Commonwealth of Massachusetts Installations Only

For direct-vent appliances, mechanical­vent heating appliances or domestic hot water equipment, where the bottom of the vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfied:
1. If there is not one already present, on
each floor level where there are bed­room(s), a carbon monoxide detector and alarm shall be placed in the living area outside the bedroom(s). The car­bon monoxide detector shall comply with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall also
be located in the room that houses the appliance or equipment and shall:
a. Be powered by the same electrical cir-
cuit as the appliance or equipment such that only one service switch services both the appliance and the carbon monoxide detector;
b. Have battery back-up power;
c. Meet ANSI/UL 2034 Standards and
comply with NFPA 720 (2005 Edition); and
d. Have been approved and listed by the
Nationally Recognized Testing Laboratory as recognized under 527 CMR.
3. A Product-approved vent terminal must
be used, and if applicable, a Product­approved air intake must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
4. A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the location of vent terminal. The plate shall be of sufficient size to be easily read from a distance of eight feet away, and read “Gas Vent Directly Below”.
NOTICE
Installer must provide tag identification plate and ensure the lettering meets code requirements.
For direct-vent appliances, mechanical­vent heating appliances or domestic hot water equipment, where the bottom of the vent terminal and the air intake are installed above four feet above grade the following requirements must be satisfied:
1. If there is not one already present, on each floor level where there are bed­room(s), a carbon monoxide detector and alarm shall be placed in the living area outside the bedroom(s). The car­bon monoxide detector shall comply with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall:
a. Be located in the room that houses the
appliances or equipment;
b. Be either hard wired or battery powered
or both; and
c. Shall comply with NFPA 720 (2005
Edition)
3. A Product-approved vent terminal must be used, and if applicable, a Product­approved air intake must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
11
3.0 Unit Preparations
SECTION III - UNIT PREPARATIONS
3.1 Handling Instructions
The PRESTIGE Solo is generally easier to handle and maneuver once removed from the shipping carton.
To remove the shipping carton:
CAUTION
Use care not to drop, bump or rotate the boiler upside down, as damage to the boiler will result.
1. Remove any shipping straps and open the side of the shipping carton.
2. Slide the unit with the foam inserts out of the carton.
3. Discard all packing materials.

3.2 Wall Mounting Installation

The PRESTIGE Solo should be wall mounted using the bracket provided with the boiler. The PRESTIGE Solo is not designed for floor installation. If floor installation is required an optional floor stand is available through ACV­Triangle Tube.

3.3 Wall Mounting Guidelines

1. The wall-mounting bracket is designed for stud spacing of 12 inch or 16 inch on cen­ters. For unconventional stud spacing, a solid / secure mounting surface must be provided for installation of the bracket.
2. For applications using wood studs, install the bracket using the lag screws provided with the boiler. Ensure both lag screws are installed securely in the studs.
3. For applications using metal studs, install the bracket to the studs using 3/16” toggle bolts and washers.
4. DO NOT mount or attempt to mount the wall bracket to hollow sheet rock or lath walls using anchors. Only install boiler to studs or equivalent wood structure.
5. For applications using solid walls (rock, concrete, brick, cinder block, etc.), install the wall bracket using anchors (double expansion shields) and bolts with washers provided with the boiler.
6. The boiler is too heavy and bulky for a sin­gle person to lift and attempt to mount; a minimum of 2 people is required for mounting the boiler.
NOTICE
NOTICE
The wall used for mounting the PRES­TIGE Solo must be vertically plumbed and capable of supporting a minimum 130 pounds [59 kg] for the PRESTIGE Solo 80/110, 175 pounds [80 kg] for PRESTIGE Solo 155/175/250 and 265 pounds [120 Kg] for PRESTIGE Solo 299/399. Failure to comply with these requirements could result in personal injury, death or substantial property damage.
Use extreme care not to drop the boiler or cause bodily injury while lifting or mounting the boiler onto the bracket. Once mounted verify that the boiler is securely attached to the bracket and wall. Failure to comply with the above guidelines could result in property dam­age, personal injury or death.
12
3.0 Unit Preparations

3.4 Stud Walls - Installation

3.4.1 PRESTIGE Solo 80/110/155/175/250

1. Locate the studs in the general area of the boiler placement.
2. Place the wall-mounting bracket on the wall centering the mounting slots with the stud centers and ensuring the upper edge of the bracket is away from the wall.
3. Level the bracket, while maintaining it’s centering with the studs and use a pencil to mark the location of the mounting slots.
4. Remove the bracket from the wall and drill 1/4” diameter hole by 3” deep positioned in the center of each mark. For applications using metal studs and 3/16” toggle bolts, drill the required clearance hole.
5. Reposition the bracket onto the wall and align mounting slots/holes. Insert the two lag screws provided (or toggle bolts for metal studs) through the mounting slots/holes and loosely tighten.
6. Level bracket and tighten screws (bolts for metal studs) securely making sure not to over-tighten to avoid damaging drywall or plaster.

3.5 Wall Bracket Installation - Solid Walls

1. Locate the general area of the boiler place­ment.
2. Place the wall-mounting bracket on the wall ensuring the upper edge of the bracket is away from the wall.
3. Level the bracket and use a pencil to mark the location of the mounting slots on the wall.
4. Remove the bracket from the wall and drill a 5/8” diameter hole by 1-3/8” deep posi­tioned in the center of each mark.
5. Install the anchors (provided) flush or slightly recessed in the drilled holes with threaded side facing down.
6. Reposition the bracket on the wall and align mounting slots/holes. Insert the two bolts (provided) through the mounting slots/holes and loosely tighten.
7. Level bracket and tighten bolts securely.

3.6 Boiler Mounting

1. Obtain assistance in lifting the boiler onto the wall bracket.

3.4.2 PRESTIGE Solo 299/399

1. To distribute the weight of the boiler even­ly when mounting onto a stud wall it is rec­ommended to use the PRESTIGE Solo Wall Frame kit.
2. When using the wall frame to mount the boiler reference the kit installation instruc­tions and ensure the frame is securely fas­tened to the wall.
3. If the structure of the wall is questionable in supporting a minimum weight of 265 pounds [120 kg.], it is recommended to use the optional floor stand.
2. Install the boiler making sure the boiler mounting lip located along the upper edge of the rear jacket panel engages the wall­mounting bracket. Ensure the boiler is seated properly and is secure.
13
4.0 Boiler Piping
SECTION IV - BOILER PIPING
4.1 General Piping Requirements
- All plumbing must meet or exceed all local, state and national plumbing codes.
- Support all piping using hangers. DO NOT support piping by the unit or its components.
- Use isolation valves to isolate system com­ponents.
- Install unions for easy removal of the PRESTIGE Solo from the system piping.
WARNING
Use a two wrench method when tighten­ing piping onto the boiler connections. Use one wrench to prevent the boiler piping from turning / twisting. Failure to support the boiler piping and connec­tions in this manner could cause damage to the boiler and its components.

4.2 Pressure Relief Valve

1. The PRESTIGE Solo is supplied with a 30 psi pressure relief valve and must be piped using the PRV connection as shown in Fig. 5 page 15.
2. To avoid potential water damage to the sur­rounding area or potential scalding hazard due to the operation of the relief valve, the discharge piping:
- Should terminate with a plain end, not with a threaded end. The material of the piping should have a serviceable temperature rating of 250ºF or greater.
- Should not be subject to conditions where freezing could occur.
- Should not contain any shut-off valves or obstructions. No shut-off valve should be piped between the boiler and relief valve.
WARNING
Failure to comply with the guidelines on installing the pressure relief valve and discharge piping can result in personal injury, death or substantial property damage.

4.3 Boiler Air Vent

NOTICE
This boiler is supplied with a special automatic air vent that will provide reli­able operation in purging air from the boiler. The hygroscopic cap supplied with the automatic air vent MUST remain tight at all times on the air vent body. The hygroscopic cap has a mem­brane which expands upon contact with water and seals the air vent until the membrane dries up due to new air form­ing in the air vent.
- Must be connected to the discharge out­let of the relief valve and directed to a safe place of disposal.
- Length should be as short and direct as possible. The size of the discharge line should not be reduced, maintain the same size as the outlet of the relief valve.
- Should be directed downward towards the floor at all times. The piping should terminate at least 6 inches [153 mm] above any drain connection to allow clear visibility of the discharge.
1. Make sure to fully tighten the cap on the air vent on initial installation.
2. Never loosen the hygroscopic cap to allow air to escape the air vent. Air will exit with the cap fully tightened in place.
3. If the hygroscopic cap is not fully tight­ened, water may leak from the cap. Simply tighten the cap securely.
14
4.0 Boiler Piping
Fig. 5: Pressure Relief Valve and Boiler Drain Valve Installation

4.4 Low Water Cutoff Device

- The PRESTIGE Solo is equipped with a fac­tory installed pressure sensor type Low Water Cut Off device.
- The minimum operating system pressure allowable with this device is 10 psig.
- Check local codes if a Low Water Cutoff Device is required. If so, determine if this device meets the requirements of the local codes.
NOTICE
The PRESTIGE Solo control system also senses the water temperatures entering and exiting the heat exchanger to pro­vide protection against low water condi­tions. Where local codes and jurisdic­tion do not accept a pressure device for low water protection, the jurisdictions may accept these PRESTIGE Solo inte­gral control functions as a means of pro­viding low water protection.

4.5 Additional Limit Control

If a separate LWCO device is required by the local jurisdiction or when the boiler is installed above the system piping, the following guide­lines must be followed:
- The LWCO device must be designed for water installations, electrode probe­type is recommended.
- The LWCO device must be installed in a tee connection on the boiler supply piping above the boiler.
- Wiring of the LWCO device to the PRES­TIGE Solo is done directly onto the low voltage terminal strip, reference Fig. 19 page 31 for available terminals for an external limit (manual or auto reset).
If the installation is to comply with ASME or Canadian requirements, an additional high temperature limit may be needed. Consult local code requirements to determine compli­ance. The limit should be installed as follows:
- Install the limit in the boiler supply pip­ing between the boiler and any isolation valve.
15
4.0 Boiler Piping
- Consult heat exchanger for maximum set point of limit.
- For wiring of the limit, reference Fig. 19, page 31, using the external manual reset terminals on the low voltage terminal strip. This will provide a "hard" lockout requiring a manual reset of the control.

4.6 Backflow Preventer

- Use a backflow preventer valve in the make-up water supply to the unit as required by local codes.

4.7 Boiler System Piping Applications

BEST PRACTICE
It is recommended on all piping applica­tions to utilize a primary/secondary pip­ing arrangement as a means to provide freeze protection of the boiler, which is an integral function of the boiler control. Maintain the minimum boiler flow rate shown in Graphs 1 through 6 on pages 94 through 96. For other piping arrange­ments, contact ACV-Triangle Tube Technical Support or consult other approved/recognized design arrange­ments.
CAUTION
Undersized expansion tanks will cause system water to be lost through the pres­sure relief valve and cause additional makeup water to be added to the system. Eventual boiler heat exchanger failure can result due to this excessive makeup water addition.
The expansion tank must be located as shown in Fig. 7 and Fig. 8 on page 18 when using a primary/secondary piping arrangement or as per recognized design methods. Refer to the expansion tank manufacturer instructions for additional installation details.
Connect the expansion tank to an air separator only if the air separator is located on the suc­tion side (inlet) of the system circulator. Always locate and install the system fill con­nection at the same location as the expansion tank connection to the system.

4.8.1 Diaphragm Expansion Tank

Always install an automatic air vent on the top of the air separator to remove residual air from the system.
BEST PRACTICE
On piping applications utilizing a single zone or other recognized piping design arrangements, it is recommended that the installer uses flow/check valves with weighted seats at or near the appliance to prevent gravity circulation.

4.8 Expansion Tank and Makeup Water

Ensure the expansion tank is properly sized for the boiler volume (3 gallons [12 L] for the PRESTIGE Solo 80/110, 5 gallons [19 L] for the PRESTIGE Solo 155/175/250, 7 gallons [26 L] for PRESTIGE Solo 299/399) and the system volume and temperature.

4.8.2 Closed-Type Expansion Tank

It is recommended to pitch any horizontal piping upwards toward the expansion tank 1 inch per 5 feet of piping. Use 3/4” piping for the expansion tank to allow air within the system to rise.
CAUTION
DO NOT install automatic air vents on a closed-type expansion tank system. Air must remain in the system and be returned to the expansion tank to pro­vide an air cushion. An automatic air vent would cause air to be vented from the system resulting in a water-logged expansion tank.
16
4.0 Boiler Piping
Fig. 6: Piping Component Legend
17
B
oiler
Supply
B
oiler
Return
S
ystem
Supply
Cold
Water
Fill
S
ystem
Return
12"
Max.
Boiler
Supply
Boiler
Return
System
Supply
Cold
Water
Fill
System
Return
12"
Max.
Minimum ¾” Piping
4.0 Boiler Piping
Fig. 7: Near Boiler Piping - Diaphragm Expansion Tank
Fig. 8 : Near Boiler Piping - Closed Type Expansion Tank
Note: Pitch horizontal piping
upwards (1” of pitch per 5 ft of piping) towards expansion tank.
18
4.0 Boiler Piping

4.9 Circulator

The PRESTIGE Solo requires an external circula­tor to provide circulation through the boiler. The circulator, when wired directly to the PRESTIGE Solo, will allow for domestic hot water priority and provide circulation for the freeze protection feature of the boiler control. See Graphs 1 through 6 on pages 94 through 96 for pressure drop and minimum flow rate through the boiler.

4.10 Sizing Primary Piping

See Fig. 9 through 13, pages 21 - 23, for rec­ommended piping arrangements based on vari­ous applications. Size the piping and system components required in the space heating sys­tem using recognized design methods.

4.11 Domestic Hot Water System Piping

See Fig. 9 through 12 on pages 21-22 for recom­mended piping to a DHW system. This recom­mended piping configuration ensures priority is given to the production and recovery of the DHW.
The piping for the DHW is separate from the boiler system piping and does not require a pri­mary / secondary piping configuration.
NOTICE
To ensure an adequate flow rate through the PRESTIGE Solo, the boiler supply and return piping size must be a minimum of 1 inch for the PRESTIGE Solo 80/110, 1-1/4 inch for the PRESTIGE Solo 155/175/250 and 1-1/2 inch for the PRESTIGE Solo299/
399.

4.13 System Piping - Zone Valves

Connect the PRESTIGE Solo to the system pip­ing as shown in Fig. 10 on page 21 when zoning with zone valves. The primary / secondary piping ensures that the boiler loop has sufficient flow.
NOTICE
To ensure an adequate flow rate through the PRESTIGE Solo, the boiler supply and return piping size must be a minimum of 1 inch for the PRESTIGE Solo 80/110, 1-1/4 inch for the PRESTIGE Solo 155/175/250 and 1-1/2 inch for the PRES­TIGE Solo 299/399.

4.14 System Piping - Through Boiler

To wire the DHW circulator to the boiler control module, reference Section VIII - External Wiring.

4.12 System Piping - Zone Circulators

Connect the PRESTIGE Solo to the system piping as shown in Fig. 9 on page 21 when zon­ing with zone circulators.
The installer must provide a separate circulator for each zone of space heating as well as the boiler circulator.
In applications in which primary/secondary arrangement is not utilized, the PRESTIGE Solo allows this flexibility due to a lower boiler pres­sure drop, see Graphs 1 through 6 on pages 94 through 96.
Figure 11 on page 22 illustrates a multiple zone valve system with a single system/boiler circula­tor. A by-pass loop with a pressure differential valve must be installed on the system piping.
Figure 12 on page 22 illustrates a single zone uti­lizing the boiler circulator as the system circulator.

4.15 System Piping - Radiant Heating

The heat exchanger design of the PRESTIGE allows operation in a condensing mode. This feature requires no regulation of the return tem-
19
4.0 Boiler Piping
perature back to the boiler in radiant heating applications.
The design and construction of the PRESTIGE heat exchanger allows the installation of the boil­er on systems with non - oxygen barrier tubing.
CAUTION
DO NOT install a SMART tank along with the PRESTIGE in systems with non-oxygen barrier tubing. Failure to comply could result in premature failure of the SMART tank.
The boiler water supply temperature can be maintained by the PRESTIGE, eliminating the need for a mix system to achieve the desired temperature.
It is recommended for the installer to install a high temperature limit to ensure that the pri­mary supply temperature does not exceed the maximum allowable temperature for the radi­ant tubing.
Size the system piping and circulator to pro­vide the flow needed for the radiant system.

4.16 System Piping - Special Application

If the boiler is used in conjunction with a chilled water/medium system, the boiler and chiller must be piped in parallel. Install flow/check valves to prevent the chilled medi­um from entering into the boiler.
If the boiler is used to supply hot water to the heating coils of an air handler where they may be exposed to chilled air circulation, install flow/check valves or other automatic means to prevent gravity circulation of the boiler water during cooling cycles.

4.17 System Piping - Multiple Units Installation

Use a balanced manifold system as the prima­ry / secondary connection to the space heating piping as shown in Fig. 13 page 23.
Maintain a minimum of 6 inches [153 mm] of clearance between units to allow for servicing.
For the space heating piping refer to the appli­cations mentioned in this manual or use recog­nized design methods.
NOTICE
To ensure an adequate flow rate through the PRESTIGE Solo, the boiler supply and return piping size must be a mini­mum of 1 inch for the PRESTIGE Solo 80/110, 1-1/4 inch for the PRESTIGE Solo 155/175/250 and 1-1/2 inch for the PRES­TIGE Solo 299/399.
NOTICE
The addition of the high temperature limit is important if the PRESTIGE is connect­ed to a domestic hot water system, which requires a high primary supply water temperature.
20
4.0 Boiler Piping
smart
P G
P3 P4
CH
D
HW
DHW
Hot
DHW
Cold
smart
P G
Z.V.
Z.V.
DHW
P3
CH
DHW
Hot
DHW
Cold
Note: Reference Fig. 25, page 38 for Prestige Wiring.
Fig. 9: System Piping - Zoning with Zone Circulators
Note: Reference Fig. 26, page 38 for Prestige Wiring.
Fig. 10: System Piping - Zoning with Zone Valves
NOTICE
The boiler system piping shown must be a “closed” system to avoid any oxygen contamination and potential failure of the outer tank of the Smart.
21
4.0 Boiler Piping
smart
P G
Z.V.
Z.V.
DHW
CH
DHW
Hot
DHW
Cold
smart
P G
CH
DHW
DHW
Hot
DHW
Cold
Note: Reference Fig. 27, page 39 for Prestige Wiring.
Note: Verify CH circulator is properly sized to overcome the system pressure drop and pro­vide adequate flow through the boiler system.
Fig. 11: System Piping - Multiple Zone Valve with Single System/Boiler Circulator
Note: Reference Fig. 28, page 39 for Prestige Wiring.
Note: Verify CH circula­tor is properly sized to overcome the system pres­sure drop and provide ade­quate flow through the boiler system.
Fig. 12: System Piping - Single Zone System with Single System/Boiler Circulator
NOTICE
The boiler system piping shown must be a “closed” system to avoid any oxygen contamination and potential failure of the outer tank of the Smart.
22
4.0 Boiler Piping
P G
System
Supply
System
Return
12"
Max.
ACVMax Control Supplement
Note: Consult the PRESTIGE
built-in Cascade function
for information on wiring and
configuring the boilers using the
23
Fig. 13: Multiple PRESTIGE Solo Boiler Piping - Primary / Secondary
5.0 Installing Vent/Combustion Air & Condensate Drain
SECTION V - INSTALLING VENT / COMBUSTION AIR & CONDENSATE DRAIN

5.1 Installing Vent and Combustion Air

DANGER
WARNING
Ensure installation of the condensate drain assembly included the metal wash­er. Failure to comply could result in the trap assembly dislocating from the boiler.
The PRESTIGE Solo must be vented and supplied with combustion air as shown in the PRESTIGE Solo Vent Supplement, included in the boiler installation enve­lope. Refer to optional vent kit instruc­tions for additional vent installation instructions. Once installation is complet­ed, inspect the vent and combustion air system thoroughly to ensure systems are airtight and comply with the instructions given in the venting supplement and are within all requirements of applicable codes. Failure to comply with the installa­tion requirements on the venting and combustion air piping will cause severe personal injury or death.

5.2 Installing Condensate Drain Assembly

1. Locate the condensate drain assembly and ensure the metal washer is installed as shown in Fig. 14 on page 25.
NOTICE
The installer may want to fill the con­densate trap with water prior to assem­bling on the unit.
WARNING
Ensure the condensate drain assembly contains the plastic seated ball. Do not install the condensate drain assembly if the ball is lost or missing, replace the entire assembly.
4. Remove the compression nut and rubber seal from the condensate drain assembly
drain outlet.
5. Using 3/4” x 2’ flexible PVC tube provid-
ed, slide the compression nut and rubber seal over the pipe
NOTICE
The use of 3/4” PVC or CPVC pipe is also acceptable. If 3/4” pipe is used deburr and chamfer pipe to allow mat­ing onto the drain assembly.
6. Thread the rubber seal into the compres-
sion nut to ease installation of the pipe to the drain assembly.
7. Seat the pipe onto the drain assembly and tighten the compression nut. Hand tight
only!
2. Install the condensate drain assembly on the boiler condensate drain by pushing the con­densate drain assembly up until it stops.
3. Tighten the condensate drain assembly retaining nut with rubber seal.
NOTICE
The installer may opt to use 13/16" ID tubing in lieu of rigid piping.
24
Loading...
+ 74 hidden pages