N o . 9 1 1 6 V 1 0 0 - I N ( 1 0 1 0 )
P roduct versio n : 9 1 16-001
DK
UK
FR
DE
Side 1
Page 33
Page 65
Seite 97
PENDING
S I G N A L S T H E B E S T
PENDING
PENDING
PENDING
PENDING
DK
PR electronics A/S tilbyder et bredt program af analoge og digitale
signalbehandlingsmoduler til industriel automation. Programmet
består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere,
Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv
barske miljøer med elektrisk støj, vibrationer og temperaturudsving,
og alle produkter opfylder de strengeste internationale standarder.
Vores motto »Signals the Best« er indbegrebet af denne filosofi –
og din garanti for kvalitet.
UK
PR electronics A/S offers a wide range of analogue and digital
signal conditioning modules for industrial automation. The product
range includes Isolators, Displays, Ex Interfaces, Temperature
Transmitters, and Universal Modules. You can trust our products
in the most extreme environments with electrical noise, vibrations
and temperature fluctuations, and all products comply with the
most exacting international standards. »Signals the Best« is the
epitome of our philosophy – and your guarantee for quality.
FR
PR electronics A/S offre une large gamme de produits pour le
traite ment des signaux analogiques et numériques dans tous
les domaines industriels. La gamme de produits s’étend des
transmetteurs de température aux afficheurs, des isolateurs aux
interfaces SI, jusqu’aux modules universels. Vous pouvez compter
sur nos produits même dans les conditions d’utilisation sévères,
p.ex. bruit électrique, vibrations et fluctuations de température.
Tous nos produits sont conformes aux normes internationales les
plus strictes. Notre devise »SIGNALS the BEST« c’est notre ligne
de conduite - et pour vous l’assurance de la meilleure qualité.
DE
PR electronics A/S verfügt über ein breites Produktprogramm
an analogen und digitalen Signalverarbeitungsmodule für die industrielle Automatisierung. Dieses Programm umfasst Displays,
Temperaturtransmitter, Ex- und galvanische Signaltrenner, und
Universalgeräte. Sie können unsere Geräte auch unter extremen
Einsatzbedingungen wie elektrisches Rauschen, Erschütterungen
und Temperaturschwingungen vertrauen, und alle Produkte von
PR electronics werden in Überein stimmung mit den strengsten
internationalen Normen produziert. »Signals the Best« ist Ihre
Garantie für Qualität!
Følgende operationer bør kun udføres på modulet i spændings-
ADVARSEL
løs tilstand og under ESD-sikre forhold:
Installation, ledningsmontage og -demontage.
Fejlfinding på modulet.
Reparation af modulet og udskiftning af sikringer må kun
foretages af PR electronics A/S.
Modulets frontplade må ikke åbnes, da dette vil medføre skade
på stikforbindelsen til display- / programmeringsfronten PR
4501. Modulet indeholder ingen DIP-switche eller jumpere.
SIGNATURFORKLARING
ADVARSEL
Trekant med udråbstegn: Læs manualen før installation og idriftsættelse
af modulet for at undgå hændelser, der kan føre til skade på personer
eller materiel.
CE-mærket er det synlige tegn på modulets overensstemmelse med
EU-direktivernes krav.
Dobbelt isolation er symbolet for, at modulet overholder ekstra krav til
isolation.
Ex - Modulet er godkendt efter ATEX-direktivet til brug i forbindelse
med installationer i eksplosionsfarlige områder. Se installationstegning i
appendiks.
SIKKERHEDSREGLER
DEFINITIONER
Farlige spændinger er defineret som områderne: 75...1500 Volt DC og
50...1000 Volt AC.
Teknikere er kvalificerede personer, som er uddannet eller oplært til at kunne
udføre installation, betjening eller evt. fejlfinding både teknisk og sikkerhedsmæssigt forsvarligt.
Operatører er personer, som under normal drift med produktet skal indstille og
betjene produktets trykknapper eller potentiometre, og som er gjort bekendt
med indholdet af denne manual.
2 9116 - Product Version 9116-001
MODTAGELSE OG UDPAKNING
Udpak modulet uden at beskadige det. Kontrollér ved modtagelsen, at modultypen svarer til den bestilte. Indpakningen bør følge modulet, indtil dette er monteret på blivende plads.
MILJØFORHOLD
Undgå direkte sollys, kraftigt støv eller varme, mekaniske rystelser og stød, og
udsæt ikke modulet for regn eller kraftig fugt. Om nødvendigt skal opvarmning,
ud over de opgivne grænser for omgivelsestemperatur, forhindres ved hjælp af
ventilation.
Modulet skal installeres i forureningsgrad 2 eller bedre.
Modulet er designet til at være sikkert mindst op til en højde af 2000 m.
INSTALLATION
Modulet må kun tilsluttes af teknikere, som er bekendte med de tekniske
udtryk, advarsler og instruktioner i manualen, og som vil følge disse.
Hvis der er tvivl om modulets rette håndtering, skal der rettes henvendelse til
den lokale forhandler eller alternativt direkte til:
PR electronics A/S, Lerbakken 10, 8410 Rønde,
Danmark, tlf: +45 86 37 26 77.
Det er ikke tilladt at benytte flerkoret ledning ved tilslutning af forsyningsspænding med mindre ledningsenderne er forsynet med ledningstyller.
Beskrivelse af indgang / udgang og forsyningsforbindelser findes på blokdiagrammet og sideskiltet.
Modulet er forsynet med skrueterminaler og skal forsynes fra en dobbeltisoleret/
forstærket isoleret spændingsforsyning. En afbryder placeres let tilgængeligt og
tæt ved modulet. Afbryderen skal mærkes således, at der ikke er tvivl om, at
den afbryder spændingen til modulet.
Ved installation på Power Rail 9400 bliver forsyningsspændingen leveret af
Power Control Unit type 9410.
Produktionsår fremgår af de to første cifre i serienummeret.
KALIBRERING OG JUSTERING
Under kalibrering og justering skal måling og tilslutning af eksterne spændinger
udføres i henhold til denne manual, og teknikeren skal benytte sikkerhedsmæssigt korrekte værktøjer og instrumenter.
9116 - Product Version 9116-001 3
BETJENING UNDER NORMAL DRIFT
Operatører må kun indstille eller betjene modulerne, når disse er fast installeret
på forsvarlig måde i tavler el. lignende, så betjeningen ikke medfører fare for liv
eller materiel. Dvs., at der ikke er berøringsfare, og at modulet er placeret, så
det er let at betjene.
RENGØRING
Modulet må, i spændingsløs tilstand, rengøres med en klud let fugtet med
destilleret vand.
ANSVAR
I det omfang instruktionerne i denne manual ikke er nøje overholdt, vil kunden
ikke kunne rette noget krav, som ellers måtte eksistere i henhold til den indgåede salgsaftale, mod PR electronics A/S.
AFMONTERING AF SYSTEM 9000
Billede 1:
Modulet frigøres fra DIN-skinnen ved
at løfte i den nederste lås.
4 9116 - Product Version 9116-001
EF-OVERENSSTEMMELSESERKLÆRING
Som producent erklærer
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
hermed at følgende produkt:
Type: 9116
Navn: Universalkonverter
er i overensstemmelse med følgende direktiver og standarder:
EMC-direktivet 2004/108/EF og senere tilføjelser
EN 61326-1 : 2006
For specifikation af det acceptable EMC-niveau henvises til modulets
elektriske specifikationer.
Lavspændingsdirektivet 2006/95/EF og senere tilføjelser
EN 61010-1 : 2001
ATEX-direktivet 94/9/EF og senere tilføjelser
EN 61241-0 : 2006, EN 61241-11 : 2006, EN 60079-0 : 2006,
EN 60079-11 : 2007, EN 60079-15 : 2005, EN 60079-26 : 2007
ATEX certificate: KEMA 07ATEX0149 X
Bemyndiget organ:
KEMA Quality B.V. (0344)
Utrechtseweg 310, 6812 AR Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands
Rønde, 15. januar 2010 Kim Rasmussen
Producentens underskrift
9116 - Product Version 9116-001 5
UNIVERSALKONVERTER
9116
• Indgang for RTD, TC, Ohm, potentiometer, mA og V
• Forsyning for 2-trådstransmittere
• Aktiv / passiv mA-udgang og relæudgang
• Kan forsynes separat eller installeres på power rail,
PR type 9400
• SIL 2-certificeret via Full Assessment
Avancerede features
• Konfiguration og monitorering via aftagelig displayfront (PR 4501); proceskalibrering, signal- og relæsimulering.
• Avanceret relæ-opsætning; f.eks. setpunkt, vindue, forsinkelse, følerfejlsindikrering og forsyningsovervågning.
• Kopiering af opsætningen fra et modul til andre af samme type via displayfronten.
• Reducerede Uo Ex-data < 8,3 V for aktive indgangssignaler.
• TC-indgange med intern eller ekstern CJC for højere nøjagtighed.
• 9116 detekterer automatisk, om modulet skal levere et aktivt eller et passivt
strømsignal.
Anvendelse
• 9116 kan monteres i sikkert område samt i zone 2 / division 2 og modtage
signaler fra zone 0, 1, 2, 20, 21 og 22 / Class I/II/III, Div. 1, Gr. A-G.
• Konvertering og skalering af temperatur-, spændings-, potentiometer- og
lineære modstandssignaler.
• Spændingsforsyning og signalisolator for 2-trådstransmittere.
• Overvågning af fejlsituationer og kabelbrud via det individuelle statusrelæ og/
eller kollektivt elektronisk signal via power rail.
• 9116 er konstrueret, udviklet og certificeret til brug i SIL 2-installationer iht.
kravene i IEC 61508.
Teknisk karakteristik
• 1 grøn og 1 rød LED i front indikerer normal drift og funktionsfejl. 1 gul LED
indikerer relæstatus.
gr. A-GZone 2 / Cl. 1, div. 2, gr. A-D eller sikkert område
9116 - Product Version 9116-001 7
PR 4501 DISPLAY- / PROGRAMMERINGSFRONT
Funktionalitet
Den enkle menustruktur og de forklarende hjælpe tekster leder
dig automatisk gennem opsætningen, og gør produktet meget
enkelt at anvende. Se beskrivelse af funktioner og opsætningsmuligheder under afsnittet ”Progammering / betjening af trykknapper”.
Anvendelse
• Kommunikationsinterface til ændring af driftsparametre i 9116.
• Kan flyttes fra en 9116 til en anden 9116 og downloade opsætningen fra det
første module til andre af samme type.
• Som fastmonteret display til visualisering af procesdata og status.
Teknisk karakteristik
• Fire liniers LCD-display, linie 1 (5,57 mm høj) viser indgangsstatus, linie 2
(3,33 mm høj) skifter mellem indgangsværdi og TAG-nr., linie 3 (3,33 mm høj)
viser udgangsværdi og enheder - UNIT, og linie 4 viser status for relæ og
kommunikation samt om modulet er SIL-låst. Statisk prik = SIL-låst og blinkende prik = ikke SIL-låst.
• Programmeringsadgang kan forhindres ved indkodning af et password.
Passwordet gemmes i 9116, så sikkerheden mod uønskede ændringer er så
høj som muligt.
Fejl på indgang - kontroller indgangsforbindelser og
genstart enheden
Fejl på udgang - kontroller udgangsforbindelser og
genstart enheden
Ingen kommunikationNO.CO
Fejl i FLASH - kontroller konfiguration
Ugyldig konfiguration eller ugyldig versionTY.ER
HardwarefejlRA.ERFejl i RAM*
HardwarefejlIF.ERFejl i intern Flash*
HardwarefejlSW.ERFejl i SW monitor*
HardwarefejlAD.ERFejl i A/D-konverter*
HardwarefejlAO.SUFejl i analog udgangsforsyning*
HardwarefejlCA.ERFejl i fabrikskalibrering*
HardwarefejlCM.ERFejl i primær CPU*
HardwarefejlRE.ERFejl i readback fra relæ*
HardwarefejlII.ERFejl i initialiseringscheck*
HardwarefejlRS.ERReset-fejl*
HardwarefejlIC.ERFejl i kommunikation på indg.*
HardwarefejlM1.ERFejl fra primær CPU til kanal 1*
HardwarefejlMC.ERKonfig.-fejl i primær CPU*
HardwarefejlMF.ERFlash-fejl i primær CPU*
HardwarefejlMR.ERRAM-fejl i primær CPU*
HardwarefejlMS.ERFejl i forsyning til primær CPU*
HardwarefejlMP.ERProgFlow-fejl i primær CPU*
HardwarefejlMI.ER
HardwarefejlDE.ERModulfejl*
HardwarefejlFC.ER
Visning ved hardwarefejl
IN.ER
AO.ER
FL.ER
CO.ER
Intern CJC-føler defekt eller
CJC-temperatur uden for
område**
Defekt (eller manglende) CJCklemme eller temperatur uden
for gyldigt område
Signalniveauer på indgang uden
for grænser eller for bundet til
forkerte terminaler*
Fejl i analog udgangsstrøm
(kun for SIL-mode)*
Ingen kommunikation med
(4501)
Fejl i FLASH (ugyldig
konfiguration)***
Konfiguration hentet fra
EEprom har ugyldigt type- eller
revisionsnummer
Fejl i primær initialiserings-
selvtest*
Ugyldig kode-checksum
i 4501
9116 - Product Version 9116-001 15
! Alle fejlvisninger i display blinker 1 gang pr. sekund (1 Hz)samt suppleres med tilhørende
hjælpetekst. Hvis fejlen er en følerfejl, blinker baggrundsbelysningen også - dette kan
tilsidesættes (stoppes) ved at trykke på 3.
* Fejlen kan resettes ved at slukke og tænde for modulet.
** Fejlen kan tilsidesættes ved at vælge en anden indgangstype end TC.
*** Fejlen kan resettes ved at steppe igennem menuerne.
16 9116 - Product Version 9116-001
Power Rail
forbindelser
91 92 93 94 95
TILSLUTNINGER
Forsyning og
statusrelæ
31 32 33 34
NCNC
Gnd.
+24 V
Fejl-signal
NC = ingen forbindelse
Indgange:
RTD, 3- / 4-lederRTD, 2-leder
41 42 43 4441 42 43 44
Modstand, 2-leder
41 42 43 4441 42 43 44
51 52 53 54
+
-
Tx
Modstand,
3- / 4-leder
41 42 43 44
StrømSpænding2-trådstransmitter
51 52 53 54
-
Gnd.
41 42 43 44
Potentiometer
51 52 53 54
+
Udgange:
Strøm
(Aktiv udgang)
11 12 13 14
2-trådstransmitter
(Passiv udgang)
11 12 13 14
11 12 13 14
N.C.
+24 V
TC, intern
CJC-føler
+
-
13
2
+
-
Relæ
*TC,
CJC-klemme
41 42
+
-
* Bestilles særskilt:
CJC-klemme
5910Ex.
+
-
mA
+
mA
N.O.
9116 - Product Version 9116-001 17
BLOKDIAGRAM
1
I
o20 mA
800.0
I
51
9116
* NC = ingen forbindelse
-
Tx
Strøm
+
-
+
-
53
52
Spæn-
+
ding
41
54
*
-
43
42
4
3
2
44
Potentiometer
RTD, forbind.
ledere
TC
Kanalstatus, Rød
Relæstatus, Gul
Modulstatus,
Grøn
Indgang
CPU
13
Relæ N.O.
udgang
Relæ-
Relæ N.O.
Gnd.
11
udgang
mA-
mA
Forsyning
12
I+
Statusrelæ N.C.
Statusrelæ N.C.
FLASH
Forsyning +24 VDC
Power rail forbindelser
+24V
NC*NC*
3114323433
Gnd.
+
mA
18 9116 - Product Version 9116-001
Visning af signal- og kabelfejl uden displayfront
Lukket
Power rail
signalstatus
N.C.
Statusrelæ,
Fejl:
Rød LED
Relæ:
Gul LED
Liste over LED- og fejlsignalvisninger
Lukket
BlinkerONBlinkerSluppet
(hvis aktiveret)
(hvis aktiveret)
BlinkerOFFBlinkerSluppet
kabelbrud/-kortslutning
Udgangsrelæ sluppetBlinkerOFFOFFTrukketÅben
kabelbrud/-kortslutning
TilstandGrøn LED
Ingen forsyningOFFOFFOFFSluppetLukket
Modul defektOFFONSluppetLukket
Modul OKBlinkerTrukketÅben
Signal OKBlinkerOFFTrukketÅben
Udgangsrelæ trukketBlinkerONOFFTrukketÅben
Udgangsrelæ sluppet pga.
Udgangsrelæ trukket pga.
9116 - Product Version 9116-001 19
PROGRAMMERING /
BETJENING AF TRYKKNAPPER
Dokumentation til rutediagram
Generelt
Når du skal konfigurere 9116, bliver du guidet igennem samtlige parametre og
kan vælge netop de indstillinger, der passer til applikationen. Til hver menu
findes en rullende hjælpetekst, som vises i displaylinie 3.
Konfigurationen udføres ved hjælp af de 3 taster:
1 forøger talværdien eller vælger næste parameter
2formindsker talværdien eller vælger forrige parameter
3accepterer valget og går til næste menu
Når konfigurationen er gennemført, returneres til normaltilstand 1.0.
Tryk og hold
uden at gemme de ændrede tal eller parametre.
Hvis ingen taster har været aktiveret i 1 minut, returnerer displayet til normaltil-
stand (1.0) uden at gemme de ændrede tal eller parametre.
Uddybende forklaringer
Passwordbeskyttelse: Programmeringsadgang kan forhindres ved indkodning
af et password. Passwordet gemmes i konverteren, så sikkerheden mod uønskede ændringer er så høj som muligt. Default password 2008 giver adgang
til alle programmeringsmenuer. Passwordbeskyttelse er obligatorisk i SILapplikationer.
Valg af units
Efter valg af indgangstype kan man vælge, hvilke procesenheder der skal vises
i displayet (se skema). Ved valg af temperaturindgang vises pocesværdien
altid i Celsius eller Fahrenheit. Vælges i menupunktet efter valg af temperaturindgang.
CJC
Det er via menuen CJC muligt at vælge mellem ekstern CJC-klemme, og intern
3 tasten nede for at gå til forrige menu eller normaltilstand (1.0)
20 9116 - Product Version 9116-001
Signal- og følerfejlsinformation via displayfront 4501
Følerfejl (se grænser i skema) vises i display med SE.BR (sensor break) eller
SE.SH (sensor short). Signaler uden for det valgte område (ikke følerfejl, se
skema for grænser) vises i display som IN.LO (lavt indgangssignal) eller IN.HI
(højt indgangssignal). Fejlindikeringen vises i tekst i 1. linie, samtidig med at
baggrundsbelysningen blinker. 4. linie i displayet er en statuslinie, der viser,
om modulet er SIL-låst (statisk prik = SIL-låst og blinkende prik = ikke SILlåst) samt status for relæ og kommunikation (prik med løbende cirkel) som
indikerer, om 4501 fungerer korrekt.
Signal- og følerfejlsindikering uden displayfront:
Status på enheden kan aflæses på de 3 LED’s i fronten af modulet.
Grøn blinkende LED indikerer normal drift.
Ingen lys i grøn LED indikerer manglende forsyningsspænding eller modulfejl.
Konstant rød LED indikerer fatal fejl.
Rød blinkende LED indikerer følerfejl.
Relæfunktioner
Der kan vælges mellem 5 forskellige relæfunktions-opsætninger.
Setpunkt: Enheden fungerer som enkel grænsekontakt.
Window: Relæet har et vindue, der defineres med et lavt og et højt
setpunkt. På begge sider af vinduet har relæet samme status.
Fejlfunktion: Relæet aktiveres ved følerfejl.
Power: Relæet er trukket, så længe der er forsyning på enheden.
Off: Relæet er deaktiveret.
Stigende/faldende: Relæerne kan sættes til at blive aktive for et stigende eller
faldende indgangssignal.
Forsinkelse: Der kan sættes både en ON- og en OFF-forsinkelse i området
0...3600 sekunder.
Hysterese: Der kan sættes en hysterese på 0,1...25% af span eller mellem 1 og
25% af displayområdet.
Vindue: Funktionen vindue opnås ved at vælge setpunkt ”vindue” i menuen og
sætte øvre og nedre setpunkter.
Se den grafiske afbildning af relæfunktionen vindue på side 30.
9116 - Product Version 9116-001 21
Setpunkt: Funktionen setpunkt opnås ved at vælge setpunkt i menuen og
indtaste den ønskede grænse. Enheden fungerer derved som en enkelt grænsekontakt.
Se den grafiske afbildning af relæfunktionen setpunkt på side 31.
At relæet er aktiveret betyder, at kontakten er lukket, hvis ”normalt åben” kon-
taktfunktionen er valgt, og kontakten er åben, hvis ”normalt lukket” kontaktfunktionen er valgt.
Forsinkelsestid for ind- og udkobling kan stilles uafhængig af hinanden hen-
holdsvis i menuerne ON.DEL og OFF DEL.
Avancerede funktioner
Enheden giver adgang til en række avancerede funktioner, der nås ved at svare
”YES” til punktet ”ADV.SET”.
Display setup: Her kan man justere kontrast og baggrundsbelysning.
Opsætning af TAG-nummer med 5 alfanumeriske karakterer. Indgangsværdi
vises altid i linie 2 på displayet. Valg af funktionsvisning i linie 3 på displayet der vælges mellem visning af analog udgang og TAG-nummer eller vekslende
displayvisning.
2-punkts proceskalibrering: Enheden kan proceskalibreres til et aktuelt ind-
gangssignal i 2 punkter. Der påtrykkes et lavt indgangssignal (ikke nødvendigvis 0%), og den aktuelle værdi angives på 4501. Herefter påtrykkes et
højt signal (ikke nødvendigvis 100%), og den aktuelle værdi angives på 4501.
Såfremt man siger ja til at bruge kalibreringen, vil enheden herefter arbejde i
henhold til denne nye justering. Siger man senere nej i dette punkt eller vælger en anden indgangssignaltype, går enheden tilbage til fabrikskalibreringen.
Processimulerings-funktion: Vælger man ja til punktet ”EN.SIM”, er det muligt
med piltasterne at simulere et indgangssignal og dermed styre udgangssignalet op og ned, eller relætilstanden OFF eller ON. SIM-menuen skal forlades
ved at trykke 3 (ingen time-out). Hvis 4501 fjernes, afbrydes processimuleringen.
Password: Her kan vælges et password mellem 0000 og 9999 til beskyttelse
mod uautoriserede ændringer. Enheden leveres default uden password.
22 9116 - Product Version 9116-001
Memory
I memory menuen er det muligt at gemme opsætningen fra enheden i 4501, for
derefter at flytte 4501 over på en anden enhed og uploade opsætningen til
denne.
Sprog: Der kan i menuen ”LANG” vælges mellem 7 forskellige sprogvarianter
af hjælpetekster, der fremkommer i menuen. Der kan vælges mellem UK, DE,
FR, IT, ES, SE og DK.
Power rail: I menuen ”RAIL” vælges om følerfejl skal overføres til en central
overvågning i PR 9410 power control unit.
Safety Integrity Level: Se Safety Manual for yderligere
information.
9116 - Product Version 9116-001 23
Power up
1.2
1
3
I
30.00
I
Io12.00mA
1.0
1.1
Eksempel på fejlvisning
Rød tekst viser safety
parametre i en SILkonfiguration. Se Safety
Manual for yderligere
information.
SE.BR
o3.50mA
direkte til [EN.SIL]
0000
9999
1 2
0000
PASSW.
Txt 1
Hurtig setpunktsindstilling
1 2
50.0
SETP.
Txt 57
1 Forøgelse af setpunkt
3
2 Formindskelse af setpunkt
3 Gem og forlad menuen
Hvis ingen taster har været aktiveret i 1 minut, returnerer displayet til normaltilstanden 1.0 uden at gemme eventuelle konfigurationsændringer.
1 Forøgelse af værdi / vælg næste parameter
2 Formindskelse af værdi / vælg forrige parameter
3 Accepter valget og gå til næste menuHolde 3 går til forrige menu / returnerer til 1.0 uden at gemme
3
3
3
3
999.9
-199.9
1 2
100.0
DISP.HI
Txt 14
3
DISP
PERC
1 2
DISP
REL.UNI
Txt 15
@C
@F
1 2
@C
UNIT
Txt 9
3
Fortsættes næste side
1.0 = Normaltilstand. Linie 1
viser indgangsstatus.
Linie 2 viser indgangsværdi
og TAG nr. Linie 3 viser
udgangsværdi og enheder.
Linie 4 viser relæ- og kom munikationsstatus samt om
modulet er SIL-låst. Statisk
prik = SIL-låst og blinkende
prik = ikke SIL-låst.
1.1 = Kun hvis beskyttet med
password.
1.2 = Kun hvis FastSet er aktive ret, og relæfunktionen
er setpunkt.
Valgbare
UNIT:
@C
@F
K
%
m
3
cm
mm
um
ft
in
mils
yd
m3
l
s
min
m/s
mm/s
m/min
m/h
in/s
ips
ft/s
in/min
ft/min
in/h
ft/h
m/s2
1.3 = Kun hvis indgangstyper
understøtter følerfejls check.
Gælder ikke for følgende
indgangssignaler:
0...20 mA og spænding.
1.4 = Kun hvis indgangssignalet
er temperatur.
1.5 = Kun hvis opsætning ikke er
beskyttet med password.
rpm
Hz
t
kg
g
N
Pa
MPa
kPa
hPa
bar
mbar
kj
Wh
MWh
kWh
W
GW
MW
kW
hp
A
kA
mA
uA
V
kV
mV
ohm
S
uS
m3/min
m3/h
l/s
l/min
l/h
gal/min
gal/h
t/h
mol
pH
[blank]
9116 - Product Version 9116-001 25
SETP
WIND
ERR
POW
OFF
1 2
SETP
REL.FUN
Txt 19
WIND
REL.FUN
Txt 19
1.3
ERR
REL.FUN
Txt 19
POW
REL.FUN
Txt 19
OFF
REL.FUN
Txt 19
3
3
3
3
3
N.O.
N.C.
1 2
N.O.
CONTAC
Txt 20
O.I.W
C.I.W
1 2
O.I.W
CONTAC
Txt 27
CLOS
OPEN
1 2
OPEN
ERR.ACT
Txt 34
20-4
20-0
4-20
0-20
1 2
4-20
O.RANGE
Txt 37
3
3
3
3
850
-200
1 2
50.0
SETP.
Txt 21
849.9
-200
1 2
50.0
SETP.LO
Txt 28
23mA
0/3.5mA
NONE
1 2
23mA
OUT.ERR
Txt 38
1.3
INCR
DECR
1 2
3
INCR
ACT.DIR
Txt 22
850.0
-199.9
1 2
3
60.0
SETP.HI
Txt 28
849
-200
1 2
3
0.0
OUT.LO
Txt 41
1.4 1.4
3
3
3
262.5
0.1
1 2
1.0
HYST.
Txt 23
262.5
0.1
1 2
1.0
HYST.
Txt 30
850.0
-199.0
1 2
150.0
OUT.HI
Txt 42
HOLD
3
3
CLOS
OPEN
NONE
1 2
NONE
ERR.ACT
Txt 24
1.3
HOLD
CLOS
OPEN
NONE
1 2
NONE
ERR.ACT
Txt 24
3600
0000
3
ON.DEL
Txt 25
3600
0000
3
ON.DEL
Txt 25
1.3
0.0
60
1 2
3
0.0
RESP.
Txt 39
3
Til normaltilstand 1.0
1 2
1 2
3600
0000
1 2
3
0
0
3
0
OFF.DEL
Txt 26
3600
0000
1 2
0
OFF.DEL
Txt 26
3
26 9116 - Product Version 9116-001
MEM, DISP,
PASS, LANG,
CAL, RAIL,
SIM, SIL
1 2
MEM
SETUP
Txt 43
DISP
SETUP
Txt 43
3
3
SAVE
LOAD
1 2
SAVE
MEMORY
Txt 44
9
0
1 2
3
CONTRA
Txt 45
RUTEDIAGRAM
AVANCEREDE INDSTILLINGER (ADV.SET)
3
3
TAG
ALT
A.OUT
1 2
A.OUT
DISP
Txt 48
3
9
0
1 2
3
9
LIGHT
Txt 46
3
9
A
1 2
TAG.1
TAGNO
Txt 47
PASS
SETUP
Txt 43
LANG
SETUP
Txt 43
CAL
SETUP
Txt 43
RAIL
SETUP
Txt 43
SIM
SETUP
Txt 43
SIL
SETUP
Txt 43
YES
NO
1 2
33
YES
EN.PASS
Txt 54
DE, DK, ES, FR,
IT, SE, UK
1 2
3
UK
LANGUA
Txt 59
YES
NO
1 2
3
YES
CAL.LO
Txt 49
YES
NO
1 2
3
YES
RAIL.ER
Txt 63
YES
NO
1 2
3
YES
EN.SIM
Txt 51
2.0
YES
NO
1 2
3
YES
EN.SIL
Txt 64
3
0000
NEW.PAS
Txt 55
NO
9999
0000
1 2
3
YES
NO
1 2
YES
EN.FAST
Txt 56
3
3
850.0
-200.0
1 2
3
2.0
@C
Txt 61
NO
3
2.0 I undermenuen simulering (SIM) skal 3
trykkes for at returnere til normaltilstand 1.0
Vælg 0.0-1 V indgangsområde
Vælg 0.2-1 V indgangsområde
Vælg 0-5 V indgangsområde
Vælg 1-5 V indgangsområde
Vælg 0-10 V indgangsområde
Vælg 2-10 V indgangsområde
[05]
Vælg 0-20 mA indgangsområde
Vælg 4-20 mA indgangsområde
Indstil relæ-setpunkt i % af indgangsområde
Indstil relæ-setpunkt i displayenheder
[16]
Vælg Pt10 som følertype
Vælg Pt20 som følertype
Vælg Pt50 som følertype
Vælg Pt100 som følertype
Vælg Pt200 som følertype
Vælg Pt250 som følertype
Vælg Pt300 som følertype
Vælg Pt400 som følertype
Vælg Pt500 som følertype
Vælg Pt1000 som følertype
[17]
Vælg Ni50 som følertype
Vælg Ni100 som følertype
Vælg Ni120 som følertype
Vælg Ni1000 som følertype
[18]
Vælg TC-B som følertype
Vælg TC-E som følertype
Vælg TC-J som følertype
Vælg TC-K som følertype
Vælg TC-L som følertype
Vælg TC-N som følertype
Vælg TC-R som følertype
Vælg TC-S som følertype
Vælg TC-T som følertype
Vælg TC-U som følertype
Vælg TC-W3 som følertype
Vælg TC-W5 som følertype
Vælg TC-LR som følertype
[19]
Vælg OFF-funktion - relæ er permanent OFF
Vælg POWER-funktion - relæ viser power-status OK
Vælg FEJL-funktion - relæ viser kun følerfejl
Vælg VINDUE-funktion - relæet styres af 2 setpunkter
Vælg SETPUNKT-funktion - relæet styres af 1 setpunkt
[20]
Vælg kontakt normalt lukket
Vælg kontakt normalt åben
[21]
Indstil relæ-setpunkt
[22]
Vælg aktiver relæ ved faldende signal
Vælg aktiver relæ ved stigende signal
[23]
Indstil relæ-hysterese
[24]
Vælg Ingen følerfejlsaktion - udefineret status ved fejl
Vælg relækontakt bryder ved fejl
Vælg relækontakt slutter ved fejl
Vælg hold relæstatus ved fejl
[25]
Indstil relæ ON-forsinkelse i sekunder
[26]
Indstil relæ OFF-forsinkelse i sekunder
[27]
Vælg relækontakt er åben inden for vinduet
Vælg relækontakt er lukket inden for vinduet
Vælg relækontakt bryder ved fejl
Vælg relækontakt slutter ved fejl
[37]
Vælg 0-20 mA udgangsområde
Vælg 4-20 mA udgangsområde
Vælg 20-0 mA udgangsområde
Vælg 20-4 mA udgangsområde
[38]
Vælg Ingen fejlaktion - udgang udefineret ved fejl
Vælg downscale ved fejl
Vælg NAMUR NE43 downscale ved fejl
Vælg NAMUR NE43 upscale ved fejl
[39]
Vælg responstid for analog udgang i sekunder
[41]
Indstil temperatur for analog udgang lav
[42]
Indstil temperatur for analog udgang høj
[43]
Gå til valg af SIL låsning
Gå til simuleringstilstand
Gå til valg af fejl til RAIL
Udfør proceskalibrering
Gå til valg af sprog
Gå til password-indstilling
Gå til displayopsætning
Udfør memory-operationer
[44]
Overfør gemt opsætning til 9116
Gem 9116-opsætning i 4501
[45]
Juster LCD-kontrast
[46]
Juster LCD-baggrundsbelysning
[47]
Angiv TAG-nr. - udfyld alle pladser
[48]
Vis analog udgangsværdi i display
Vis TAG-nr. i display
værdier vises i display
Kalibrer indgang lav til procesværdi?
Kalibrer indgang høj til procesværdi?
Aktiver indgangssimulering
Indstil simuleringsværdi for indgang
Relæsimulering - brug 1 til at skifte relætilstand
Vælg passwordbeskyttelse?
Angiv nyt password
Aktiver Fastset-funktionalitet?
Relæ-setpunkt - tryk 3 for at gemme
Relæ-setpunkt - Read only
Vælg sprog
Brug proceskalibreringsværdier?
Indstil værdi for lavt kalibreringspunkt
Indstil værdi for højt kalibreringspunkt
Vælg om statussignal skal overføres til power rail
28 9116 - Product Version 9116-001
[64]
Vælg at SIL-låse konfigurationen
0-20 mA er ikke gyldigt udgangsområde for drift i
SIL-låst tilstand
The following operations should only be carried out on a
WARNING
disconnected device and under ESD-safe conditions:
General mounting, connection and disconnection of wires.
Troubleshooting the device.
Repair of the device and replacement of circuit breakers
must be done by PR electronics A/S only.
Do not open the front plate of the device as this will cause
damage to the connector for the display / programming front
PR 4501. This device contains no DIP-switches or jumpers.
SYMBOL IDENTIFICATION
Triangle with an exclamation mark: Read the manual before installation
and commissioning of the device in order to avoid incidents that could
lead to personal injury or mechanical damage.
The CE mark proves the compliance of the device with the essential
requirements of the directives.
The double insulation symbol shows that the device is protected by
double or reinforced insulation.
Ex devices have been approved according to the ATEX directive for
use in connection with installations in explosive areas. See installation
drawings in appendix.
SAFETY INSTRUCTIONS
DEFINITIONS
Hazardous voltages have been defined as the ranges: 75...1500 Volt DC, and
50...1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and
also troubleshoot technically correct and in accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate
the knobs or potentiometers during normal operation.
34 9116 - Product Version 9116-001
WARNING
RECEIPT AND UNPACKING
Unpack the device without damaging it and check whether the device type
corresponds to the one ordered. The packing should always follow the device
until this has been permanently mounted.
ENVIRONMENT
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock,
as well as rain and heavy moisture. If necessary, heating in excess of the stated
limits for ambient temperatures should be avoided by way of ventilation.
The device must be installed in pollution degree 2 or better.
The device is designed to be safe at least under an altitude up to 2 000 m.
MOUNTING
Only technicians who are familiar with the technical terms, warnings, and
in struc tions in the manual and who are able to follow these should connect the
device.
Should there be any doubt as to the correct handling of the device, please
contact your local distributor or, alternatively,
The use of stranded wires is not permitted for mains wiring except when wires
are fitted with cable ends.
Descriptions of input / output and supply connections are shown in the block
diagram and on the side label.
The device is provided with field wiring terminals and shall be supplied from a
Power Supply having double / reinforced insulation. A power switch shall be
easily accessible and close to the device. The power switch shall be marked as
the disconnecting unit for the device.
For installation on Power Rail 9400 the power is supplied by Power Control Unit
9410.
Year of manufacture can be taken from the first two digits in the serial number.
CALIBRATION AND ADJUSTMENT
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.
9116 - Product Version 9116-001 35
NORMAL OPERATION
Operators are only allowed to adjust and operate devices that are safely fixed
in panels, etc., thus avoiding the danger of personal injury and damage. This
means there is no electrical shock hazard, and the device is easily accessible.
CLEANING
When disconnected, the device may be cleaned with a cloth moistened with
distilled water.
LIABILITY
To the extent the instructions in this manual are not strictly observed, the
customer cannot advance a demand against PR electronics A/S that would
otherwise exist according to the concluded sales agreement.
HOW TO DEMOUNT SYSTEM 9000
Picture 1:
By lifting the bottom lock, the device
is detached from the power rail.
36 9116 - Product Version 9116-001
EC DECLARATION OF CONFORMITY
As manufacturer
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
hereby declares that the following product:
Type: 9116
Name: Universal converter
is in conformity with the following directives and standards:
The EMC Directive 2004/108/EC and later amendments
EN 61326-1 : 2006
For specification of the acceptable EMC performance level, refer to the
electrical specifications for the device.
The Low Voltage Directive 2006/95/EC and later amendments
EN 61010-1 : 2001
The ATEX Directive 94/9/EC and later amendments
EN 61241-0 : 2006, EN 61241-11 : 2006, EN 60079-0 : 2006,
EN 60079-11 : 2007, EN 60079-15 : 2005, EN 60079-26 : 2007
ATEX certificate: KEMA 07ATEX0149 X
Notified body
KEMA Quality B.V. (0344)
Utrechtseweg 310, 6812 AR Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands
Rønde, 15 January 2010 Kim Rasmussen
Manufacturer’s signature
9116 - Product Version 9116-001 37
UNIVERSAL CONVERTER
9116
• Input for RTD, TC, Ohm, potentiometer, mA and V
• Supply for 2-wire transmitters
• Active / passive mA output and relay output
• Can be supplied separately or installed on power rail, PR 9400
• SIL 2-certified via Full Assessment
Advanced features
• Configuration and monitoring by way of detachable display front (PR 4501);
process calibration, signal and relay simulation.
• Advanced relay configuration, e.g. setpoint, window, delay, sensor error
indication and power monitoring.
• Copying of the configuration from one device to others of the same type via
PR4501.
• Reduced Uo Ex data < 8.3 V for active input signals.
• TC inputs with internal or external CJC for higher accuracy.
• The device automatically detects whether it must supply an active or a
passive current signal.
Application
• Can be mounted in the safe area and in zone 2 / div. 2 and receive signals
from zone 0, 1, 2, 20, 21 and 22 / Class I/II/III, Div. 1, Gr. A-G.
• Conversion and scaling of temperature, voltage, potentiometer and linear
resistance signals.
• Power supply and signal isolator for 2-wire transmitters.
• Monitoring of error events and cable breakage via the individual status relay
and/or a collective electronic signal via the power rail.
• The 9116 has been designed, developed and certified for use in SIL 2
applications according to the requirements of IEC 61508.
Technical characteristics
• 1 green and 1 red front LED indicate operation status and malfunction. 1
yellow LED indicates relay status.
• 2.6 kVAC galvanic isolation between input, output and supply.
38 9116 - Product Version 9116-001
Input signals:
RTD and lin. R
Poten-
tiometer
Connection, wires
* Order separately:
CJC connector 5910Ex
APPLICATIONS
TC
44
43
*
42
41
Power rail
Output signals:
Analogue, 0/4...20 mA and relay
12
11
14
13
Status relay signal
Rail, +24 VDC
Rail, Gnd.
No connection
No connection
mA
Relay
Relay
mA
+
-
+
N.O.
Power connection:
Gnd.
31
Supply +19.2...31.2 VDC
32
Device status
33
N.C.
34
Device status
Current
+
Tx
-
+
Zone 0, 1, 2,
20, 21, 22 /
Cl. I/II/III, div. 1
gr. A-G
Volt-
age
54
53
+
52
51
Supply via
power rail
Zone 2 / Cl. 1, div. 2, gr. A-D or safe area
9116 - Product Version 9116-001 39
PR 4501 DISPLAY / PROGRAMMING FRONT
Functionality
The simple and easily understandable menu structure
and the explanatory help texts guide you effortless ly and
automatically through the configuration steps, thus making
the product very easy to use. Functions and configuration
options are described in the section ”Configuration /
operating the function keys”.
Application
• Communications interface for modification of operational parameters in 9116.
• Can be moved from one 9116 device to another and download the
configuration of the first unit to subsequent units.
• Fixed display for visualisation of process data and status.
Technical characteristics
• LCD display with 4 lines; Line 1 (H=5.57 mm) shows input status, line 2
(H=3.33) mm toggels between input value and tag. no. Line 3 (H=3.33
mm) shows output value and UNIT. Line 4 shows status for relay and
communication and whether the device is SIL-locked. Static dot = SIL-locked
and flashing dot = not SIL-locked.
• Programming access can be blocked by assigning a password. The
password is saved in the device in order to ensure a high degree of
protection against unauthorised modifications to the configuration.
Hardware errorCA.ERFactory calibration error*
Hardware errorCM.ERMain CPU error*
Hardware errorRE.ERRelay readback error*
Hardware errorII.ERInitialization check error*
Hardware errorRS.ERReset error*
Hardware errorIC.ERInput communication error*
Hardware errorM1.ERMain CPU to Ch.1 error*
Hardware errorMC.ERMain CPU config. error*
Hardware errorMF.ERMain CPU Flash error*
Hardware errorMR.ERMain CPU Ram error*
Hardware errorMS.ERMain CPU supply error*
Hardware errorMP.ERMain CPU ProgFlow error*
Hardware errorMI.ER
Hardware errorDE.ERDevice error*
Hardware errorFC.ERInvalid code checksum in 4501
Readout at hardware error
AO.ER
FL.ER
CO.ER
Defect internal CJC sensor or
CJC temperature out of allowed
range **
Defect (or missing) CJC
connector or temperature out of
allowed range **
Signal levels on input beyond
limits or connected to wrong
terminals*
Error in analogue output current
(SIL mode only)*
No communication
with (4501)
FLASH error
(configuration invalid)***
Configuration read from
EEprom has invalid type or
rev. no.
Analogue output
supply error*
Main CPU initialization
check error*
9116 - Product Version 9116-001 47
! All error indications in the display flash once per second (1 Hz), and the corresponding help
text is shown. If the error is a sensor error, the display backlight flashes as well - this is
acknowledged (stopped) by pushing the OK button.
* Error is acknowledged by resetting the device power
** Error can be disregarded by selecting input type different than TC.
*** Error is acknowledged by stepping through the basic setup.
48 9116 - Product Version 9116-001
Power Rail
connections
91 92 93 94 95
CONNECTIONS
Supply and
status relay
31 32 33 34
Error signal
+24 V
NC = no connection
RTD, 3- / 4-wireRTD, 2-wire
NCNC
Gnd.
41 42 43 4441 42 43 44
Resistance, 2-wire
41 42 43 4441 42 43 44
51 52 53 54
+
-
Tx
Resistance,
3- / 4-wire
41 42 43 44
CurrentVoltage2-wire transmitter
51 52 53 54
-
Gnd.
Inputs:
TC, internal CJC
41 42 43 44
51 52 53 54
+
Outputs:
Current
(Active output)
11 12 13 14
2-wire transmitter
(Passive output)
11 12 13 14
11 12 13 14
N.C.
+24 V
sensor
+
-
Potentiometer
13
2
+
-
Relay
*TC,
CJC connector
CJC
41 42
* Order separately:
CJC connector
5910Ex.
44
+
-
+
-
mA
+
mA
N.O.
9116 - Product Version 9116-001 49
BLOCK DIAGRAM
1
I
o20 mA
800.0
I
51
9116
* NC = no connection
-
Tx
Current
+
-
+
-
53
52
+
Volt-
age
41
54
*
-
43
42
4
3
2
44
Potentiometer
RTD, conn.
wires
TC
Relay status, Yellow
Ch. status, Red
Device status,
Green
Input
CPU
13
Relay N.O.
output
Relay
Relay N.O.
Gnd.
Supply
FLASH
output
mA
11
12
I+
mA
Status relay N.C.
Status relay N.C.
Supply +24 VDC
Power Rail connections
+24V
NC*NC*
3114323433
Gnd.
+
mA
50 9116 - Product Version 9116-001
Signal error and cable fault indications without display front
Output relay de-energized w. wire short/breakFlashingOFFFlashingDe-energizedClosed (if enabled)
Output relay energizedFlashingONOFFEnergizedOpen
Output relay energized w. wire short/breakFlashingONFlashingDe-energizedClosed (if enabled)
Device OKFlashingEnergizedOpen
Signal OKFlashingOFFEnergizedOpen
Device failureOFFONDe-energizedClosed
No supplyOFFOFFOFFDe-energizedClosed
ConditionGreen LED
9116 - Product Version 9116-001 51
CONFIGURATION /
OPERATING THE FUNCTION KEYS
Documentation for routing diagram.
In general
When configuring the 9116, you will be guided through all parameters and you
can choose the settings which fit the application. For each menu there is a
scrolling help text which is automatically shown in line 3 on the display.
Configuration is carried out by use of the 3 function keys:
1 will increase the numerical value or choose the next parameter
2will decrease the numerical value or choose the previous parameter
3will accept the chosen value and proceed to the next menu
When configuration is completed, the display will return to the default state 1.0.
Pressing and holding
state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state
(1.0) without saving the changed values or parameters.
Further explanations
Password protection: Programming access can be blocked by assigning a
password. The password is saved in the converter in order to ensure a high
degree of protection against unauthorised modifications to the configuration.
Default password 2008 allows access to all configuration menus. Password
protection is mandatory in SIL applications.
Selection of units
After choosing the input signal type you can choose which process units should
be shown in the display (see table). By selection of temperature input the
process value is always displayed in Celsius or Fahrenheit. This is selected in
the menu point after selection of temperature input.
CJC
In the CJC menu you can choose between CJC connector and internal cold
junction compensation. The CJC connecter (PR 5910Ex) must be ordered
separately.
3 will return to the previous menu or return to the default
52 9116 - Product Version 9116-001
Signal and sensor error information via display front 4501
Sensor error (see limits in the table) is displayed as SE.BR (sensor break) or
SE.SH (sensor short). Signals outside the selected range (not sensor error,
see table for limits) are displayed as IN.LO indicating low input signal or IN.HI
indicating high input signal. The error indication is displayed as text in line 1
and at the same time the backlight flashes. Line 4 of the display is a status
line which shows whether the device is SIL-locked (static dot = SIL-locked
and flashing dot = not SIL-locked) as well as relay status and COM (running
circle) indicating correct functioning of 4501.
Signal and sensor error indication without display front
Status of the unit can also be read from the 3 LEDs in the front of the device.
Green flashing LED indicates normal operation.
No light in the green LED indicates lack of supply voltage or error in the device.
Steady red LED indicates fatal error.
Flashing red LED indicates sensor error.
Relay functions
5 different settings of relay function can be selected.
Setpoint: The unit works as a single trip amplifier
Window: The relay has a window that is defined by a low and a high set -
point. On both sides of the window the relay has the same status.
Error function: The relay is activated by sensor error.
Power: The relay is activated as long as the power is on.
Off: The relay is deactivated.
Increasing/decreasing: The relays can be set to activate at increasing or
decreasing input signal.
Delay: An ON and an OFF delay can be set in the range 0...3600 s.
Hysteresis: A hysteresis can be set at 0.1...25% of the span or between 1 and
25% of display range.
Window: The window function is selected by choosing ”window” in the menu
and defining a high and a low setpoint.
See the graphic depiction of the window functions on page 62.
Setpoint: The setpoint function is selected by choosing ”setpoint” in the menu
and entering the desired limit. The device then works as a single limit switch.
See the graphic depiction of the window functions on page 63.
9116 - Product Version 9116-001 53
An activated relay means that the contact is closed if the contact function
”normally open” is selected, and the contact is open if the contact function
”normally closed” is selected.
The delay time for activation and deactivation can be set independently of each
other in the menus ON.DEL and OFF DEL respectively.
Advanced functions
The unit gives access to a number of advanced functions which can be reached
by answering “Yes” to the point “adv.set”.
Display setup: Here you can adjust the brightness contrast and the backlight.
Setup of TAG numbers with 5 alphanumerics. Input value is always shown in
line 2. Selection of functional readout in line 3 of the display - choose between
readout of analogue output or tag no or alternating display.
Two-point process calibration: The device can be process-calibrated in 2
points to fit a given input signal . A low input signal (not necessarily 0%)
is applied and the actual value is entered via 4501. Then a high signal (not
necessarily 100%) is applied and the actual value is entered via 4501. If you
accept to use the calibration, the device will work according to this new
adjustment. If you later reject this menu point or choose another type of input
signal the device will return to factory calibration.
Process simulation function: In the menu point “EN.SIM” it is possible to
simulate an input signal by means of the arrow keys and thus control the
output signal up or down, or the relay state OFF and ON . You must exit the
menu by pressing 3 (no time-out). The simulation function exits automatically,
if the 4501 is detached.
Password: Here you can choose a pass word between 0000 and 9999 in order
to protect the device against unauthorised modifications to the configuration.
The device is delivered default without password.
Memory: In the memory menu you can save the configuration of the device in
the 4501, and then move the 4501 onto another device of the same type and
download the configuration in the new device.
54 9116 - Product Version 9116-001
Language: In the menu ”lang.setup” you can choose between 7 different
language versions of help texts that will appear in the menu. You can choose
between UK, DE, FR, IT, ES, SE and DK.
Power rail: In the menu ”RAIL” you can choose if sensor errors are transmitted
to the central surveillance in the PR 9410 power control unit.
Safety integrity level: See Safety Manual for details
9116 - Product Version 9116-001 55
Power up
1.2
1
3
I
30.00
I
Io12.00mA
1.0
1.1
Error indication, example
Red text signifies safety
parameters in a SIL
configuration. See safety
manual for details
SE.BR
o3.50mA
directly to EN.SIL]
0000
9999
1 2
0000
PASSW.
Txt 1
Fast setpoint adjustment
and relay test
1 2
50.0
SETP.
Txt 57
1 Increase setpoint
3
2 Decrease setpoint
3 Save and exit the menu
1 and 2 simultaneously = change relay state
If no key is activated for 1 minute, the display will return to the default state 1.0
without saving configuration changes.
1 Increase value / choose next parameter
2 Decrease value / choose previous parameter
3 Accept the chosen value and proceed to the next menuHold 3 Back to previous menu / return to menu 1.0 without saving
3
3
3
3
999.9
-199.9
1 2
100.0
DISP.HI
Txt 14
3
DISP
PERC
1 2
DISP
REL.UNI
Txt 15
@C
@F
1 2
@C
UNIT
Txt 9
3
Continued on the next page
1.0 = Default state. Line 1 shows
input status. Line 2 shows
input value and TAG NO.
Line 3 shows output value
and units. Line 4 shows
status for relay and commu nication and whether the
device is SIL-locked. Static
dot = SIL-locked and
flashing dot = not SIL locked.
1.1 = Only if password-protected.
1.2 = Only if FastSet is activated
and the relay function is
setpoint.
Selectable
3
mils
@C
@F
K
%
m
cm
mm
um
ft
in
yd
m3
l
UNITS:
s
min
m/s
mm/s
m/min
m/h
in/s
ips
ft/s
in/min
ft/min
in/h
ft/h
m/s2
1.3 = Only if input types support
sensor error check.
Not valid for these input
signals: 0...20 mA and
voltage.
1.4 = Only if input signal is
temperaure.
1.5 = Only if the configuration is
not protected by a pass word.
rpm
Hz
t
kg
g
N
Pa
MPa
kPa
hPa
bar
mbar
kj
Wh
MWh
kWh
W
GW
MW
kW
hp
A
kA
mA
uA
V
kV
mV
ohm
S
uS
m3/min
m3/h
l/s
l/min
l/h
gal/min
gal/h
t/h
mol
pH
[blank]
9116 - Product Version 9116-001 57
SETP
WIND
ERR
POW
OFF
1 2
SETP
REL.FUN
Txt 19
WIND
REL.FUN
Txt 19
1.3
ERR
REL.FUN
Txt 19
POW
REL.FUN
Txt 19
OFF
REL.FUN
Txt 19
3
3
3
3
3
N.O.
N.C.
1 2
N.O.
CONTAC
Txt 20
O.I.W
C.I.W
1 2
O.I.W
CONTAC
Txt 27
CLOS
OPEN
1 2
OPEN
ERR.ACT
Txt 34
20-4
20-0
4-20
0-20
1 2
4-20
O.RANGE
Txt 37
3
3
3
3
850
-200
1 2
50.0
SETP.
Txt 21
849.9
-200
1 2
50.0
SETP.LO
Txt 28
23mA
0/3.5mA
NONE
1 2
23mA
OUT.ERR
Txt 38
1.3
INCR
DECR
1 2
3
INCR
ACT.DIR
Txt 22
850.0
-199.9
1 2
3
60.0
SETP.HI
Txt 28
849
-200
1 2
3
0.0
OUT.LO
Txt 41
1.4 1.4
3
3
3
262.5
0.1
1 2
1.0
HYST.
Txt 23
262.5
0.1
1 2
1.0
HYST.
Txt 30
850.0
-199.0
1 2
150.0
OUT.HI
Txt 42
HOLD
CLOS
OPEN
NONE
1 2
3
3
NONE
ERR.ACT
Txt 24
1.3
HOLD
CLOS
OPEN
NONE
1 2
NONE
ERR.ACT
Txt 24
3
3
1.3
0.0
60
1 2
3
0.0
RESP.
Txt 39
3
To default state 1.0
3600
0000
1 2
0
ON.DEL
Txt 25
3600
0000
1 2
0
ON.DEL
Txt 25
3600
0000
1 2
3
0
OFF.DEL
Txt 26
3600
0000
1 2
3
0
OFF.DEL
Txt 26
3
58 9116 - Product Version 9116-001
MEM, DISP,
PASS, LANG,
CAL, RAIL,
SIM, SIL
1 2
MEM
SETUP
Txt 43
DISP
SETUP
Txt 43
3
3
SAVE
LOAD
1 2
SAVE
MEMORY
Txt 44
9
0
1 2
3
CONTRA
Txt 45
ROUTING DIAGRAM
ADVANCED SETTINGS (ADV.SET)
3
3
TAG
ALT
A.OUT
1 2
A.OUT
DISP
Txt 48
3
9
0
1 2
3
9
LIGHT
Txt 46
3
9
A
1 2
TAG.1
TAGNO
Txt 47
PASS
SETUP
Txt 43
LANG
SETUP
Txt 43
CAL
SETUP
Txt 43
RAIL
SETUP
Txt 43
SIM
SETUP
Txt 43
SIL
SETUP
Txt 43
YES
NO
1 2
33
YES
EN.PASS
Txt 54
DE, DK, ES, FR,
IT, SE, UK
1 2
3
UK
LANGUA
Txt 59
YES
NO
1 2
3
YES
CAL.LO
Txt 49
YES
NO
1 2
3
YES
RAIL.ER
Txt 63
YES
NO
1 2
3
YES
EN.SIM
Txt 51
2.0
YES
NO
1 2
3
YES
EN.SIL
Txt 64
3
0000
NEW.PAS
Txt 55
NO
9999
0000
1 2
3
YES
NO
1 2
YES
EN.FAST
Txt 56
3
3
850.0
-200.0
1 2
3
2.0
@C
Txt 61
NO
3
2.0 In the submenu simulation (SIM) you must
press 3 to return to the default state 1.0.
850.0
-200.0
1 2
3
23.0
%
Txt 52
NO
0000
9999
1 2
3
2008
NEW.PAS
Txt 55
NO
1.4
3
3
3
YES
NO
1 2
YES
CAL.HI
Txt 50
REL.SIM
Txt 53
OPEN
LOCK
1 2
LOCK
CONFIG
Txt 66
850.0
-200.0
1 2
3
147.8
Txt 62
NO
3
@C
3
Verify SIL configuration
33333
. . . . . . . . . . . . . .
YES
YES
USE.CAL
Txt 60
To default state 1.0
NO
1 2
3
SIL.OK
9116 - Product Version 9116-001 59
SCROLLING HELP TEXTS IN DISPLAY LINE 3
[01]
Set correct password
[02]
Enter Advanced setup menu?
[03]
Select Temperature input
Select Potentiometer input
Select Linear resistance input
Select Current input
Select Voltage input
[04]
Select 0.0-1 V input range
Select 0.2-1 V input range
Select 0-5 V input range
Select 1-5 V input range
Select 0-10 V input range
Select 2-10 V input range
[05]
Select 0-20 mA input range
Select 4-20 mA input range
Select Celsius as temperature unit
Select Fahrenheit as temperature unit
[10]
Select TC sensor type
Select Ni sensor type
Select Pt sensor type
[11]
Select Display unit
[12]
Select Decimal point position
[13]
Set Display range low
[14]
Set Display range high
[15]
Select Relay setpoint in % of input range
Select Relay setpoint in display units
[16]
Select Pt10 sensor type
Select Pt20 sensor type
Select Pt50 sensor type
Select Pt100 sensor type
Select Pt200 sensor type
Select Pt250 sensor type
Select Pt300 sensor type
Select Pt400 sensor type
Select Pt500 sensor type
Select Pt1000 sensor type
[17]
Select Ni50 sensor type
Select Ni100 sensor type
Select Ni120 sensor type
Select Ni1000 sensor type
[18]
Select TC-B sensor type
Select TC-E sensor type
Select TC-J sensor type
Select TC-K sensor type
Select TC-L sensor type
Select TC-N sensor type
Select TC-R sensor type
Select TC-S sensor type
Select TC-T sensor type
Select TC-U sensor type
Select TC-W3 sensor type
Select TC-W5 sensor type
Select TC-Lr sensor type
[19]
Select OFF function - relay is permanently off
Select POWER function - relay indicates power status OK
Select ERROR function - relay indicates sensor error only
Select WINDOW function - relay is controlled by 2 setpoints
Select SETPOINT function - relay is controlled by 1 setpoint
[20]
Select Normally Closed contact
Select Normally Open contact
[21]
Set Relay setpoint
[22]
Select Action on decreasing signal
Select Action on increasing signal
[23]
Set Relay hysteresis
[24]
Select No error action - undefined status at error
Select Open relay contact at error
Select Close relay contact at error
Select Hold relay status at error
[25]
Set Relay ON delay in seconds
[26]
Set Relay OFF delay in seconds
[27]
Select Contact is Closed Inside Window
Select Contact is Open Inside Window
[28]
Set Relay window setpoint low
[29]
Set Relay window setpoint high
[30]
Set Relay window hysteresis
[31]
Select Internal temperature sensor
Select CJC connector (Accessory)
[34]
Select Open relay contact at error
Select Close relay contact at error
[37]
Select 0-20 mA outout range
Select 4-20 mA output range
Select 20-0 mA output range
Select 20-4 mA output range
[38]
Select No error action - output undefined at error
Select Downscale at error
Select Namur NE43 downscale at error
Select Namur NE43 upscale at error
[39]
Select Analogue output response time in seconds.
[41]
Set Temperature for analogue output low
[42]
Set Temperature for analogue output high
[43]
Enter SIL setup
Enter Simulation mode
Enter Rail setup
Perform Process Calibration
Enter Language setup
Enter Password setup
Enter Display setup
Perform Memory operations
[44]
Load saved configuration into module
Save configuration in display front
[45]
Adjust LCD contrast
[46]
Adjust LCD backlight
[47]
Write a 5-character channel TAG
[48]
Show Analog output value in display
Show TAG on display
Alternate shown information in display
[49]
Calibrate Input low to process value?
[50]
Calibrate Input high to process value?
[51]
Enable input simulation?
[52]
Set the input simulation value
[53]
Relay simulation - use 1 to toggle relay
[54]
Enable Password protection?
[55]
Set New password
[56]
Enable Fastset functionality?
[57]
Relay setpoint - press 3 to save
[58]
Relay setpoint - Read only
[59]
Select Language
[60]
Use process calibration values?
[61]
Set value for low calibration point
[62]
Set value for high calibration point
[63]
Enable Rail status signal output?
[64]
Enable SIL configuration lock?
0...20 mA is not a valid output range for SIL
operation
60 9116 - Product Version 9116-001
[65]
is channel using process-compensated calibration
data?
[66]
Configuration SIL status (Open / Locked)
[80]
Sensor short circuit
[81]
Sensor wire breakage
[82]
Display underrange
[83]
Display overrange
[84]
Input underrange
[85]
Input overrange
[86]
Input error - check input connections and reset
power
[87]
Output error - check connentions and reset power
Flash memory error - chek configuration
Les opérations suivantes doivent être effectuées avec le module
AVERTISSEMENT
débranché et dans un environnement exempt de décharges
électrostatiques (ESD) :
Montage général, raccordement et débranchement de fils.
Recherche de pannes sur le module.
Seule PR electronics SARL est autorisée à réparer le module
et à remplacer les fusibles.
Ne pas ouvrir la plaque avant du module au risque d’endommager
le connecteur de l’indicateur / la façade de programmation PR
4501. Ce module ne contient ni de commutateurs DIP ni de
cavaliers.
SIGNIFICATION DES SYMBOLES
Triangle avec point d’exclamation : Attention ! Lire ce manuel avant
l’installation et la mise en service de ce module afin d’éviter des incidents
pouvant causer des dommages corporels ou des dégâts mécaniques.
Le signe CE indique que le module est conforme aux exigences des
directives.
Ce symbole indique que le module est protégé par une isolation double
ou renforcée.
L’utilisation des modules de type Ex avec des installations situées dans
des zones à risques d’explosions a été autorisée suivant la directive ATEX.
Voir le schéma d’installation dans les annexes.
CONSIGNES DE SECURITE
DEFINITIONS
Les gammes de tensions dangereuses sont les suivantes : de 75 à 1500 Vcc
et de 50 à 1000 Vca.
Les techniciens sont des personnes qualifiées qui sont capables de monter et
de faire fonctionner un appareil, et d’y rechercher les pannes, tout en respectant
les règles de sécurité.
66 9116 - Product Version 9116-001
AVERTISSEMENT
Les opérateurs, connaissant le contenu de ce guide, règlent et actionnent les
boutons ou les potentiomètres au cours des manipulations ordinaires.
RECEPTION ET DEBALLAGE
Déballez le module sans l’endommager. Il est recommandé de conserver
l’emballage du module tant que ce dernier n’est pas définitivement monté. A la
réception du module, vérifiez que le type de module reçu correspond à celui que
vous avez commandé.
ENVIRONNEMENT
N’exposez pas votre module aux rayons directs du soleil et choisissez un endroit
à l’humidité modérée et à l’abri de la poussière, des températures élevées, des
chocs et des vibrations mécaniques et de la pluie. Le cas échéant, des systèmes
de ventilation permettent d’éviter qu’une pièce soit chauffée au-delà des limites
prescrites pour les températures ambiantes.
Ce module doit être installé en degré de pollution 2 ou meilleur.
Ce module est conçu pour fonctionner en toute sécurité sous une altitude
inférieure à 2000 m.
MONTAGE
Il est conseillé de réserver le raccordement du module aux techniciens qui
connaissent les termes techniques, les avertissements et les instructions de ce
guide et qui sont capables d’appliquer ces dernières.
Si vous avez un doute quelconque quant à la manipulation du module, veuillez
contacter votre distributeur local. Vous pouvez également vous adresser à
PR electronics SARL, Zac du Chêne, Activillage, 4, allée des Sorbiers,
Pour le raccordement électrique de l’alimentation générale, il est possible
d’utiliser des fils multibrins seulement s’ils possèdent des embouts de câblage.
Les connexions des alimentations et des entrées / sorties sont décrites dans le
schéma de principe et sur l’étiquette de la face latérale du module.
Les appareils sont équipés de borniers à vis et doivent être raccordés à une
alimentation qui a une isolation double ou renforcée. L’interrupteur doit être
à proximité du module et facile d’accès. Ce bouton doit être étiqueté avec la
mention : peut couper la tension du module.
Pour une installation sur le rail d’alimentation 9400, le module sera alimenté par
le contrôleur d’alimentation 9410.
F-69673 Bron Cedex (tél. : (0) 472 140 607) ou à
9116 - Product Version 9116-001 67
L’année de production est définie par les deux premiers chiffres du numéro de
série.
ETALONNAGE ET REGLAGE
Lors des opérations d’étalonnage et de réglage, il convient d’effectuer les
mesures et les connexions des tensions externes en respectant les spécifications
mentionnées dans ce guide. Les techniciens doivent utiliser des outils et des
instruments pouvant être manipulés en toute sécurité.
MANIPULATIONS ORDINAIRES
Les opérateurs sont uniquement autorisés à régler et faire fonctionner des
modules qui sont solidement fixés sur des platines des tableaux, ect., afin
d’écarter les risques de dommages corporels. Autrement dit, il ne doit exister
aucun danger d’électrocution et le module doit être facilement accessible.
MAINTENANCE ET ENTRETIEN
Une fois le module hors tension, prenez un chiffon imbibé d’eau distillée pour
le nettoyer.
LIMITATION DE RESPONSABILITE
Dans la mesure où les instructions de ce guide ne sont pas strictement
respectées par le client, ce dernier n’est pas en droit de faire une réclamation
auprès de PR electronics SARL, même si cette dernière figure dans l’accord de
vente conclu.
DEMONTAGE DU SYSTEME 9000
Figure 1 :
Débloquez le verrou inférieur
pour dégager le module du rail
d’alimentation.
68 9116 - Product Version 9116-001
DECLARATION DE CONFORMITE CE
En tant que fabricant
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
déclare que le produit suivant :
Type : 9116
Nom : Convertisseur programmable à seuils, [Ex ia]
correspond aux directives et normes suivantes :
La directive CEM (EMC) 2004/108/CE et les modifications subséquentes
EN 61326-1 : 2006
Pour une spécification du niveau de rendement acceptable CEM (EMC)
se référer aux spécifications électriques du module.
La directive basse tension 2006/95/CE et les modifications subséquentes
EN 61010-1 : 2001
La directive ATEX 94/9/CE et les modifications subséquentes
EN 61241-0 : 2006, EN 61241-11 : 2006, EN 60079-0 : 2006,
EN 60079-11 : 2007, EN 60079-15 : 2005, EN 60079-26 : 2007
Certificat ATEX : KEMA 07ATEX0149 X
Organisme notifié :
KEMA Quality B.V. (0344)
Utrechtseweg 310, 6812 AR Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands
Rønde, le 15 janvier 2010 Kim Rasmussen
Signature du fabricant
9116 - Product Version 9116-001 69
CONVERTISSEUR PROGRAMMABLE À SEUILS, [Ex ia]
9116
• Entrées : Pt100, TC, Ohm, potentiomètre, mA et V
• Alimentation pour transmetteurs 2-fils
• Sortie mA active / passive et sortie relais
• Alimenté séparément ou par le rail d’alimentation, type 9400
• Certifié SIL 2 en « Evaluation Complète »
Options avancées
• Programmation et contrôle à l’aide de la façade de programmation (4501);
calibration de process et simulation de signaux et de relais.
• Configuration avancée du relais, p.ex. consigne, fenêtre, délai, détection
erreur capteur et surveillance de l’alimentation.
• Recopie de la configuration d’un module à d’autres du même type à l’aide de
la façade de programmation.
• Caractéristiques S.I. d’Uo réduites à < 8,3 V pour des signaux d’entrée actives.
• Les entrées TC peuvent utiliser soit la CSF interne soit le bornier avec
capteur Pt100 incorporé (PR 5910Ex, voie 1 / PR 5913Ex, voie 2) pour une
précision améliorée.
• Le 9116 détecte automatiquement s’il doit fournir un signal de courant actif
ou passif.
Fonctions
• Le module peut être installé dans la zone non-dangereuse et en zone 2/div. 2 et
recevoir des signaux de la zone 0, 1, 2, 20, 21 et 22 / Class I/II/III, Div. 1, Gr. A-G.
• Conversion et mise à l’échelle de signaux en température, en tension,
potentiométriques et de résistance linéaire.
• Alimentation et isolateur de signaux pour transmetteurs 2-fils.
• Surveillance de cas d’erreurs internes rupture câble par le relais d’état
individuel et / ou un signal électronique collectif par le rail d’alimentation.
• Le 9116 a été conçu, développé et certifié pour utilisation dans les
applications SIL 2 en conformité avec les exigences de la CEI 61508.
Caractéristiques techniques
• 1 LED verte et 2 LED rouges en face avant indiquent un fonctionnement
normal ou incorrect du module. 1 LED jaune indique l’état du relais.
• Isolation galvanique de 2,6 kVca entre l’entrée, la sortie et l’alimentation.
70 9116 - Product Version 9116-001
Signaux d’entrée :
Pt100 et R lin.
Poten-
tiomètre
Connexion, fils
*Commander separément :
Connecteur CSF 5910Ex
APPLICATIONS
TC
44
43
*
42
41
Rail
d’alimentation
Signaux de sortie :
Analogique, 0/4...20 mA et relais
12
11
14
13
Signal du relais d’état
Rail, +24 Vcc
Rail, masse
Pas de connexion
Pas de connexion
mA
Relais
Relais
mA
+
-
+
N.O.
Connexion d’alimentation :
31
32
33
34
Alimentation
par rail
Masse
Alimentation +19,2...31,2 Vcc
Etat du module
N.F.
Etat du module
Courant
+
Tx
-
+
Zone 0, 1, 2,
20, 21, 22 /
Cl. I/II/III, div. 1
gr. A-G
Tension
54
53
+
52
51
Zone 2 / Cl. 1, div. 2, gr. A-D ou zone non-da ngereuse
9116 - Product Version 9116-001 71
PR 4501 INDICATEUR /
FAÇADE DE PROGRAMMATION
Fonctionnalité
Le menu simple, structuré à l’aide de questions, guide
automatiquement l’utilisateur par un menu déroulant et
rend ainsi aisé l’utilisation du produit. Voir la description
des fonctions et options de configuration dans la section
« Configuration / utilisation des touches de fonction ».
Application
• Interface de communication pour la modification des paramètres de
fonctionnement du 9116.
• Peut être transféré d’un module à d’autres du même type et charger la
configuration du premier module vers les modules suivants.
• Quand le 4501 est monté sur le module, il affiche les valeurs du process et
l’état du module.
Caractéristiques techniques
• Affichage LCD en quatre lignes; Ligne 1 (5,57 mm de haut) affiche l’état
d’entrée, ligne 2 (3,33 mm de haut) alterne entre la valeur d’entrée et le
numéro de répère. Ligne 3 (3,33 mm de haut) affiche la valeur de sortie et
UNIT. Ligne 4 affiche l’etat du relais et de communication ainsi que l’état
SIL (ouvert / verrouillé). Point statique = verrouillage SIL, point clignotante =
aucun verrouillage SIL.
• L’accès à la programmation peut être bloqué par un mot de passe. Ce mot
de passe est sauvegardé dans le module afin d’assurer un haut niveau de
protection contre les modifications non autorisées.
Montage / installation
• Cliquer le 4501 sur la face avant du 9116.
72 9116 - Product Version 9116-001
Références de commande
9116B1 = Convertisseur programmable -
Dimensions, sans façade 4501 (HxLxP) ..... 109 x 23,5 x 104 mm
Dimensions, avec façade 4501 (HxLxP) ..... 109 x 23,5 x 116 mm
Degré de protection .................................... IP20
Poids ........................................................... 185 g / 200 g avec 4501
2
74 9116 - Product Version 9116-001
Isolation :
Entrée aux autres ........................................ 300 Vca double / renforcée
Relais de sortie à la sortie analogique ........ 150 Vca double / renforcée ou
300 Vca isolation de base
Sortie analogique à l’alimentation ............... 300 Vca double/reinforced isolation
Relais d’état à l’alimentation ....................... 150 Vca double / renforcée ou
300 Vca isolation de base
Entrée Pt100, résistance linéaire et potentiométrique :
Type
d’entrée
Pt100
Ni100
Résist. linéaire
Potentiomètre
Entrée pour types Pt100 :
Pt10*, Pt20*, Pt50*, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000
Ni50, Ni100, Ni120, Ni1000
Effet de la résistance de ligne
UL, Standard for Safety .............................. UL 61010-1
SIL ............................................................... IEC 61508
EC = Echelle configurée
Configuration du contrôle d’erreur de câble
Module:ConfigurationDétection erreur capteur :
9116
ERR.ACT=NONE - OUT.ERR=NONE.OFF
Sensor error check:
Autre :ON
9116 - Product Version 9116-001 77
Indication dans le 4501 de :
Signal d’entrée hors d’échelle
En dépassement de l’echelle définie du convertisseur A/D ou des standards températures
EntréePlageAffichageLimite
VOLT
CURR0...20 mA / 4...20 mA
LIN.R
POTM0 - 100%
TEMPTC / Pt100
Entrée PlageAffichageLimite
ToutesTous
Détection erreur capteur
EntréePlageAffichageCondition
CURRRupture de boucle (4...20 mA)SE.BR<= 3,6 mA; > = 21 mA
POTMTous, SE.BR sur toutes connexions 3-fils
LIN.R
TEMP
Indication de dépassement d’échelle (IN.LO, IN.HI) :
0...1 V / 0,2...1 V
0...10 V / 2...10 V
0...800
Ω
0...10 kΩ
Affichage en dessous du mini. / au-dessus du maxi (-1999, 9999) :
Détection erreur capteur (SE.BR, SE.SH):
TousSE.BR
Pour R lin._0%≥env. 18 ΩSE.SHCourt circuit capteur
TousSE.BR
Pt100 à Pt1000 et Ni50 à Ni1000SE.SHCourt circuit capteur
IN.LO< -25 mV
IN.HI> 1,2 V
IN.LO< -25 mV
IN.HI> 12 V
IN.LO< -1,05 mA
IN.HI> 25,05 mA
IN.LO< -10 Ω
IN.HI> 900 Ω
IN.LO<-10 Ω
IN.HI> 11 kΩ
IN.LO< -0.5 %
IN.HI> 100.5 %
IN.LO< plage température -2°C
IN.HI> plage température +2°C
-1999Indication <-1999
9999Indication >9999
SE.BRRupture capteur
SE.SHCourt circuit capteur
Rupture capteur ou
resistance de ligne trop haute
Rupture capteur ou
resistance de ligne trop haute
78 9116 - Product Version 9116-001
Indications erreur matériel
Erreur capteur CSF - contrôler la température
du module
Erreur connecteur CSF - contrôler le bornier CSFCJ.CE
Erreur d’entrée - contrôler les connexions et
redémarrer le module
Erreur de la sortie analogique - contrôler
connexions et redémarrer le module
Pas de communicationNO.COPas de communication avec (4501)
Erreur dans la mémoire FLASH - contrôler la
configuration
Configuration ou version invalideTY.ER
Erreur matérielRA.ERErreur RAM*
Erreur matérielIF.ERErreur de Flash interne*
Erreur matérielSW.ERErreur contrôleur SW*
Erreur matérielAD.ERErreur du convertisseur A/D*
Erreur matérielAO.SUErreur d’alim. de sortie analog.*
Erreur matérielCA.ERErreur d’étalonnage usine
Erreur matérielCM.ERErreur du CPU principal*
Erreur matérielRE.ERErreur de relecture du relais*
Erreur matérielII.ERErreur contrôle d’initialisation*
Erreur matérielRS.ERErreur de redémarrage*
Erreur matérielIC.ERErreur communication d’entrée*
Erreur matérielM1.ERErreur CPU prin. à voie 1*
Erreur matérielMC.ERErreur config. du CPU prin.*
Erreur matérielMF.ERErreur Flash du CPU prin.*
Erreur matérielMR.ERErreur RAM du CPU prin.*
Erreur matérielMS.ERErreur aliment. du CPU prin.*
Erreur matérielMP.ERErreur ProgFlow du CPU prin.*
Erreur matérielMI.ER
Erreur matérielDE.ERErreur du module*
Erreur matérielFC.ER
Recherche erreursAffichageCause d’erreur
Indication erreur matériel
CJ.ER
IN.ER
AO.ER
FL.ER
CO.ER
Défaut capteur CSF interne ou temp.
CSF dépasse l’échelle **
Bornier CSF en défaut ou manquant,
température dépasse l’échelle
valable **
Niveaux de signal en entrée dépasse
limites ou connecté aux faux bornes*
Erreur de courant de la sortie
analogique (seul. en mode SIL)*
Erreur FLASH (configuration
Configuration lu de l’EEprom porte
invalide)***
un numéro de type ou de révision
Erreur de l’autotest d’initialisation
Somme de contrôle de code non
invalide
principale
valable en 4501
9116 - Product Version 9116-001 79
! Les indications d’erreurs clignotent toutes les secondes. (1 Hz). Un texte d’aide explique l’erreur.
Si l’erreur est un erreur capteur, le rétroéclairage de l’afficheur clignote - ceci est corrigé (arrêté)
en appuyant sur la touche OK.
* L’erreur est corrigée en déconnectant et puis reconnectant l’alimentation du module.
** L’erreur peut être négligée en sélectionnant un type d’entrée autre que TC.
*** L’erreur est corrigée en parcourant les menus.
80 9116 - Product Version 9116-001
Connexions au rail
d’alimentation
91 92 93 94 95
CONNEXIONS
Alimentation et
relais d’état
31 32 33 34
Signal d’erreur
NC = pas de connexion
+24 V
Masse
NCNC
Entrées :
Pt100, 3- / 4-filsPt100, 2-fils
41 42 43 4441 42 43 44
Résistance, 2-fils
41 42 43 4441 42 43 44
51 52 53 54
+
-
Tx
Résistance,
3- / 4-fils
41 42 43 44
CourantTensionTransmetteur 2-fils
51 52 53 54
-
+
Sortie :
Courant
(sortie active)
11 12 13 14
Transmetteur 2-fils
(sortie passive)
11 12 13 14
Masse
+24 V
TC, capteur
CSF interne
41 42 43 44
+
Potentiomètre
13
2
51 52 53 54
-
Relais
11 12 13 14
N.F.
-
+
*TC,
Connecteur CSF
CJC
41 42
+
-
* Commander
separément :
Connecteur CSF
5910Ex
44
+
-
mA
+
mA
N.O.
9116 - Product Version 9116-001 81
SCHEMA DE PRINCIPE
1
I
o20 mA
800.0
I
51
9116
* NC = pas de connexion
-
Tx
Courant
+
-
+
-
53
52
+
Ten-
sion
41
54
*
-
43
42
4
3
2
44
Potentiomètre
Pt100, conn.
fils
TC
Etat de relais, jaune
Etat de voie, rouge
Etat de module,
verte
Entrée
CPU
Connexions au rail d’alimentation
+24V
NC*NC*
3114323433
Masse
13
Relais N.O.
relais
Sortie
Relais N.O.
Masse
Alimentation
FLASH
Sortie
mA
11
12
I+
mA
Alimentation +24 Vcc
Relais d’état N.F.
Relais d’état N.F.
+
mA
82 9116 - Product Version 9116-001
Indications d’erreur signal et câble sans la façade 4501
pour le rail
Etat de signal
Relais
d’état, N.F.
Erreur:
LED rouge
Relais:
LED jaune
Liste d’indications des LED et signaux d’erreur
EtatLED verte
Pas d’alimentationOFFOFFOFFDésexcitéFermé
Défaut moduleOFFONDésexcitéFermé
Module OKClignotanteExcitéOuvert
Signal OKClignotanteOFFExcitéOuvert
Relais de sortie exitéClignotanteONOFFExcitéOuvert
Relais de sortie exité par court circuit / ruptureClignotanteONClignotanteDésexcitéFermé (si activé)
Relais de sortie désexité par court circuit / rupture ClignotanteOFFClignotanteDésexcitéFermé (si activé)
Relais de sortie désexitéClignotanteOFFOFFExcitéOuvert
9116 - Product Version 9116-001 83
PROGRAMMATION /
OPERATION DES TOUCHES DE FONCTION
Documentation pour le diagramme de programmation.
Généralités
Lors de la configuration du 9116 vous êtes guidés tout au long des paramètres
du menu ; ainsi vous pouvez choisir le réglage qui correspond à votre
application. Pour chaque menu il y a un texte d’aide qui défile en ligne 3 de
l’indicateur.
La configuration se fait à l’aide des 3 touches de fonction :
1 Incrémenter la valeur numérique ou choisir le paramètre suivant
2Décrémenter la valeur numérique ou choisir le paramètre précédent
3Valider les valeurs choisies et fin du menu
Une fois la configuration terminée, l’indicateur retournera sur l’état défaut 1.0.
En appuyant et maintenant la touche 3 l’indicateur retourne au menu précédent
ou sur l’état défaut (1.0) sans sauvegarde des modifications éventuelles
apportées à la configuration.
Si aucune touche n’est activée pendant 1 minute, l’indicateur retournera sur
l’état défaut sans sauvegarde des modifications éventuelles apportées à la
configuration.
Informations complémentaires
Protection par mot de passe : L’accès à la programmation peut être bloqué
par un mot de passe. Ce mot de passe est sauvegardé dans le module
afin d’assurer un haut niveau de protection contre les modifications non
autorisées. Le mot de passe usine 2008 permet l’accès à tous les menus
de configuration. Protection par mot de passe est obligatoire dans les
applications SIL.
Sélection des unités
Après sélection du type de signal d’entrée vous pouvez choisir l’unité de valeur
du process pour l’affichage en texte (voir tableau). En sélectionnant une entrée
température, l’unité de mesure sur l’afficheur est en Celsius ou Fahrenheit. Ce
choix se fait dans le point de menu après sélection d’entrée température.
84 9116 - Product Version 9116-001
CSF (CJC)
Dans le menu CJC vous pouvez choisir entre connecteur CSF ou compensation
de soudure froide interne. Le connecteur CSF (PR 5910Ex) est à commander
séparemment.
Informations relatives à l’erreur de câble sur la façade 4501
Erreur de câble (voir limites dans tableau) est affiché par CA.BR (rupture câble)
ou CA.SH (court circuit câble). Signal hors limites (voir tableau des limites)
est affiché par IN.LO (limite basse) ou IN.HI (limite haute). L’affichage de
l’erreur se fait en format texte sur la ligne 1 avec le rétro-éclairage lumineux
clignotant. La ligne 4 de l’affichage indique l’état SIL (point statique =
verrouillage SIL, point clignotante = aucun verrouillage SIL) ainsi que l’état
du relais et de la communication (point avec cercle) qui indique l’état de
fonctionnement du 4501.
Indication du signal et erreur capteur sans la façade
L’état du module peut être lu sur la façade à l’aide des 3 voyants.
Voyant vert clignotant indique l’état normal de fonctionnement.
Si le voyant vert n’est pas illuminé, cela indique un défaut d’alimentation ou
une erreur dans le module.
Voyant rouge fixe indique une erreur fatale.
Voyant rouge clignotant indique une erreur capteur.
Fonctions des relais
5 différentes fonctions peuvent être sélectionnées :
Consigne : Fonctionnement en relais à seuils.
Fenêtre : Le relais a une fenêtre définie par le seuil bas et haut.
Des deux cotés de la fenêtre le relais a le même état.
Fonction erreur : Le relais est activé en cas d’erreur capteur.
Alimentation : Le relais est actif en présence de l’alimentation.
OFF : Le relais est désactivé.
Croissant / Décroissant : Le relais peut être actif en mode croissant ou
décroissant.
Délais : Fonctions Délai “ON” ou “OFF” peuvent être choisies pour le relais
entre 0...3600 s.
Hystérésis : L’hystérésis peut être configuré entre 0,1 et 25% de l’échelle ou
entre 1 et 25 % de la gamme d’affichage.
9116 - Product Version 9116-001 85
Fenêtre : La fonction Fenêtre « Window » est choisie dans le menu en
définissant le point haut ou bas du seuil.
Voir le graphique déscriptif de la fonction fenêtre à la page 94.
Consigne : La fonction consigne « Setpoint » est choisie dans le menu en
indiquant les limites souhaitées. Le module alors fonctionne comme un
simple relais à seuils.
Voir le graphique déscriptif de la fonction consigne à la page 95.
Un relais actif signifie que le contact est fermé et défini en « Normalement
ouvert » et le contact est ouvert lorsque il est en « normalement fermé ».
Il est possible d’activer ou désactiver la fonction temporisation « délai » sur le
menu ON.DEL et OFF DEL.
Fonctions avancées
L’unité donne accès à un certain nombre de fonctions avancées qui sont
accessibles en répondant « YES » à « ADV.SET ».
Configuration de l’affichage : Il est possible de régler la luminosité et le
rétro-éclairage. Enregistrement d’un numéro de repère à 5 caractères
alphanumériques. La valeur d’entrée est toujours affichée en ligne 2.
Sélection de l’affichage en ligne 3 de l’indicateur - choix entre : sortie
analogique et numéro répère. En sélectionnant ”ALT” l’affichage alterne les
informations affichées.
Calibration du process en 2 points
en 2 points. Le point mini du signal d’entrée (pas nécessairement 0%)
est appliquée et la valeur actuelle est entrée sur l’unité 4501. Ensuite le
point maxi du signal (pas nécessairement 100%) est appliquée et la valeur
actuelle est entrée sur l’unité 4501. Si vous validez ces points, l’appareil va
fonctionner selon cet ajustement. Si plus tard vous souhaitez modifier ou
changer de type d’entrée l’unité reviendra à la calibration usine.
Fonction simulation : Si vous validez le point « EN.SIM » il est possible de
simuler un signal d’entrée à l’aide des flèches et ainsi contrôler le signal de
sortie haut et bas ou l’état du relais OFF et ON. Vous devez sortir du menu
en pressant 3 (pas de time-out). La simulation sera terminée, si le 4501 est
enlevé.
: L’unité peut procéder à une calibration
86 9116 - Product Version 9116-001
Mot de passe : Ici vous pouvez choisir un mot de passe allant de 0000 à 9999
afin de protéger la programmation. L’unité est livrée sans mot de passe.
Mémoire : Dans le menu mémoire (memory) vous pouvez sauvegarder la
configuration du module dans le 4501, et puis transférer le 4501 sur un
autre module du même type et charger la configuration sauvegardée vers ce
module.
Langue : Dans le menu « LANG », vous pouvez sélectionner 7 différentes
langues pour le texte d’aide. Choix entre : Anglais, allemand, français, italien,
espagnol, suédois et danois.
Rail d’alimentation
: Dans le menu ”RAIL” vous pouvez choirsir si des erreurs
capteur doivent être transmis à l’unité de surveillance du module PR 9410
Contrôleur d’alimentation.
Safety Integrity Level (SIL): Voir le ”Safety Manual” (en Anglais)
pour information supplémentaire.
9116 - Product Version 9116-001 87
Power up
1.2
1
3
I
30.00
I
Io12.00mA
1.0
Indication d’erreur, exemple
Texte rouge signifie des
paramètres de sécurité
dans une configuration SIL.
Voir le ”Safety Manual” (en
Anglais) pour information
supplémentaire.
1.1
SE.BR
o3.50mA
0000
9999
0000
PASSW.
Txt 1
Si le verrouillage SIL est activé
directement en [EN.SIL]
1 2
Réglage rapide des consignes et
test des relais
1 2
50.0
SETP.
Txt 57
1 Incrémentation de la consigne
3
2 Décrémentation de la consigne
3 Sauvegarde des valeurs et sorti du menu
1 et 2 simultanément = le relais change d’état
Continué à la page
Diagramme de
programmation
ADV.SET
3
YES
ADV.SET
Txt 2Txt 10Txt 18Txt 31
3
3
3
3
3
3
999.9
-199.9
1 2
0.0
DISP.LO
Txt 13
4W
3W
2W
1 2
3W
CONNEC.
Txt 6
4W
4W
3W
3W
2W
2W
1 2
1 2
3W
3W
CONNEC.
CONNEC.
Txt 6
Txt 6
INT
CONN
1 231 2
INT
CJC
88 9116 - Product Version 9116-001
DIAGRAMME DE PROGRAMMATION
Si aucune touche n’est actionnée pendant 1 minute, l’indicateur retournera
sur l’état défaut sans sauvegarde des modifications éventuelles apportées à la
configuration.
1Incrémenter la valeur / choisir paramètre suivant
2 Décrémenter la valeur / choisir paramètre précédent
3Valider les valeurs choisies et fin du menuMaintien 3 Retour au menu précédent / retour au menu 1.0 sans sauvegarde
3
999.9
-199.9
1 2
100.0
DISP.HI
Txt 14
3
DISP
PERC
1 2
DISP
REL.UNI
Txt 15
3
Continué à la page suivante
1.0 = Etat défaut. Ligne 1
affiche l’état d’entrée,
ligne 2 affiche l’entrée et
numéro répère, ligne 3
affiche la sortie et les
unités et ligne 4 affiche
l’etat de relais et de
communication ainsi que
l’état SIL (ouvert / verrouillé).
Point statique = verrouillage
SIL, point clignotante =
aucun verrouillage SIL.
1.1 = Seulement si l’indicateur
est protégé par un mot de
passe.
1.2 = Seulement si le Réglage
Rapide est activé et le
relais a la fonction consigne.
1.3 = Seulement si le type
d’entrée supporte le
contrôle d’erreur de câble
Ne vaut pas pour les
signaux d’entrée :
0...20 mA et tension.
1.4 = Seulement si le signal
d’entrée est température.
1.5 = Seulement si la configu ration n’est pas protégé
par un mot de passe
3
Choix de l’
@C
@F
1 2
3
@C
UNIT
Txt 9
3
mils
3
9116 - Product Version 9116-001 89
@C
@F
K
%
m
cm
mm
um
ft
in
yd
m3
l
UNITES :
s
min
m/s
mm/s
m/min
m/h
in/s
ips
ft/s
in/min
ft/min
in/h
ft/h
m/s2
rpm
Hz
t
kg
g
N
Pa
MPa
kPa
hPa
bar
mbar
kj
Wh
MWh
kWh
W
GW
MW
kW
hp
A
kA
mA
uA
V
kV
mV
m3/min
gal/min
[blank]
ohm
S
uS
m3/h
l/s
l/min
l/h
gal/h
t/h
mol
pH
SETP
WIND
ERR
POW
OFF
1 2
SETP
REL.FUN
Txt 19
WIND
REL.FUN
Txt 19
1.3
ERR
REL.FUN
Txt 19
POW
REL.FUN
Txt 19
OFF
REL.FUN
Txt 19
3
3
3
3
3
N.O.
N.C.
1 2
N.O.
CONTAC
Txt 20
O.I.W
C.I.W
1 2
O.I.W
CONTAC
Txt 27
CLOS
OPEN
1 2
OPEN
ERR.ACT
Txt 34
20-4
20-0
4-20
0-20
1 2
4-20
O.RANGE
Txt 37
3
3
3
3
850
-200
1 2
50.0
SETP.
Txt 21
849.9
-200
1 2
50.0
SETP.LO
Txt 28
23mA
0/3.5mA
NONE
1 2
23mA
OUT.ERR
Txt 38
1.3
INCR
DECR
1 2
3
INCR
ACT.DIR
Txt 22
850.0
-199.9
1 2
3
60.0
SETP.HI
Txt 28
849
-200
1 2
3
0.0
OUT.LO
Txt 41
1.4 1.4
3
3
3
262.5
0.1
1 2
1.0
HYST.
Txt 23
262.5
0.1
1 2
1.0
HYST.
Txt 30
850.0
-199.0
1 2
150.0
OUT.HI
Txt 42
3
3
3
HOLD
CLOS
OPEN
NONE
1 2
NONE
ERR.ACT
Txt 24
1.3
HOLD
CLOS
OPEN
NONE
1 2
NONE
ERR.ACT
Txt 24
1.3
0.0
60
1 2
0.0
RESP.
Txt 39
3600
0000
1 2
3
0
ON.DEL
Txt 25
3600
0000
1 2
3
0
ON.DEL
Txt 25
3
3
3600
0000
1 2
0
OFF.DEL
Txt 26
3600
0000
1 2
0
OFF.DEL
Txt 26
3
3
Retour au menu 1.0
90 9116 - Product Version 9116-001
MEM, DISP,
PASS, LANG,
CAL, RAIL,
SIM, SIL
1 2
MEM
SETUP
Txt 43
DISP
SETUP
Txt 43
3
3
DIAGRAMME DE PROGRAMMATION,
SAVE
LOAD
1 2
SAVE
MEMORY
Txt 44
9
0
1 2
3
CONTRA
Txt 45
REGLAGE AVANCE (ADV.SET)
3
3
TAG
ALT
A.OUT
1 2
A.OUT
DISP
Txt 48
9
0
1 2
3
9
LIGHT
Txt 46
3
9
A
1 2
TAG.1
TAGNO
Txt 47
3
PASS
SETUP
Txt 43
LANG
SETUP
Txt 43
CAL
SETUP
Txt 43
RAIL
SETUP
Txt 43
SIM
SETUP
Txt 43
SIL
SETUP
Txt 43
YES
NO
1 2
33
YES
EN.PASS
Txt 54
DE, DK, ES, FR,
IT, SE, UK
1 2
3
UK
LANGUA
Txt 59
YES
NO
1 2
3
YES
CAL.LO
Txt 49
YES
NO
1 2
3
YES
RAIL.ER
Txt 63
YES
NO
1 2
3
YES
EN.SIM
Txt 51
2.0
YES
NO
1 2
3
YES
EN.SIL
Txt 64
3
0000
NEW.PAS
Txt 55
NO
9999
0000
1 2
3
YES
NO
1 2
YES
EN.FAST
Txt 56
3
3
850.0
-200.0
1 2
3
2.0
@C
Txt 61
NO
3
2.0 Dans le sous-menu simulation (SIM) il faut
actionner 3 pour retourner sur l’état defaut 1.0
Sélectionner gamme d’entrée 0.0-1 V
Sélectionner gamme d’entrée 0.2-1 V
Sélectionner gamme d’entrée 0-5 V
Sélectionner gamme d’entrée 1-5 V
Sélectionner gamme d’entrée 0-10 V
Sélectionner gamme d’entrée 2-10 V
[05]
Sélectionner gamme d’entrée 0-20 mA
Sélectionner gamme d’entrée 4-20 mA
Sélectionner Celsius comme unité de température
Sélectionner Fahrenheit comme unité de
température
[10]
Sélectionner type de capteur TC
Sélectionner type de capteur Ni
Sélectionner type de capteur Pt
[11]
Sélectionner unités d’affichage
[12]
Sélectionner position du point décimale
[13]
Régler gamme d’affichage basse
[14]
Régler gamme d’affichage haute
[15]
Régler consigne relais en pourcentages de la
gamme d’entrée
Régler Consigne relais en unités d’affichage
[16]
Sélectionner Pt10 comme type de capteur
Sélectionner Pt20 comme type de capteur
Sélectionner Pt50 comme type de capteur
Sélectionner Pt100 comme type de capteur
Sélectionner Pt200 comme type de capteur
Sélectionner Pt250 comme type de capteur
Sélectionner Pt300 comme type de capteur
Sélectionner Pt400 comme type de capteur
Sélectionner Pt500 comme type de capteur
Sélectionner Pt1000 comme type de capteur
[17]
Sélectionner Ni50 comme type de capteur
Sélectionner Ni100 comme type de capteur
Sélectionner Ni120 comme type de capteur
Sélectionner Ni1000 comme type de capteur
[18]
Sélectionner TC-B comme type de capteur
Sélectionner TC-E comme type de capteur
Sélectionner TC-J comme type de capteur
Sélectionner TC-K comme type de capteur
Sélectionner TC-L comme type de capteur
Sélectionner TC-N comme type de capteur
Sélectionner TC-R comme type de capteur
Sélectionner TC-S comme type de capteur
Sélectionner TC-T comme type de capteur
Sélectionner TC-U comme type de capteur
Sélectionner TC-W3 comme type de capteur
Sélectionner TC-W5 comme type de capteur
Sélectionner TC-Lr comme type de capteur
[19]
Sélectionner Fonction OFF - le relais est en
permanence OFF
Sélectionner Fonction POWER - le relais indique état
d’alimentation OK
Sélectionner Fonction ERREUR - le relais indique
uniquement erreur capteur
Sélectionner Fonction FENETRE - le relais est
contrôlé par 2 consignes
Sélectionner Fonction CONSIGNE - le relais est
contrôlé par 1 consigne
Sélectionner activation du relais pour un signal
descendant
Sélectionner activation du relais pour un signal montant
[23]
Régler hystérésis du relais
[24]
Sélectionner aucune action d’erreur - état non-défini
en cas d’erreur
Sélectionner ouvrir contact du relais en cas d’erreur
Sélectionner fermer contact du relais en cas d’erreur
Sélectionner Maintenir état du relais en cas d’erreur
[25]
Régler délai ON du relais en secondes
[26]
Régler délai OFF du relais en secondes
[27]
Sélectionner contact du relais est fermé dans la fenêtre
Sélectionner contact du relais est ouvert dans la fenêtre
[28]
Régler consigne basse de la fenêtre relais
[29]
Régler consigne haute de la fenêtre relais
[30]
Régler hystérésis de la fenêtre relais
[31]
Sélectionner capteur de température interne
Sélectionner bornier CSF (accessoire)
[34]
Sélectionner ouvrir contact du relais en cas d’erreur
Sélectionner fermer contact du relais en cas d’erreur
[37]
Sélectionner gamme de sortie 0-20 mA
Sélectionner gamme de sortie 4-20 mA
Sélectionner gamme de sortie 20-0 mA
Sélectionner gamme de sortie 20-4 mA
[38]
Sélectionner aucune action d’erreur - sortie pas définie
en cas d’erreur
Sélectionner bas d’échelle en cas d’erreur
Sélectionner NAMUR NE43 bas d’échelle en cas
d’erreur
Sélectionner NAMUR NE43 haut d’échelle en cas
d’erreur
[39]
Régler Temps de réponse de la sortie analogique en
secondes
[41]
Régler température de la sortie analogique basse
[42]
Régler température de la sortie analogique haute
[43]
Aller dans la configuration SIL
Aller dans le mode simulation
Aller dans la configuration du rail d’alimentation
Exécuter calibration de process
Aller dans la configuration langue
Aller dans la configuration du mot de passe
Aller dans la configuration d’affichage
Exécuter opérations de mémoire
[44]
Charger la configuration sauvegardée au module
Sauvegarder la configuration dans la 4501
[45]
Ajuster le contraste LCD
[46]
Ajuster le rétro-éclairage LCD
[47]
Entrer numéro repère de 5 caractères
[48]
Valeur de la sortie analogique affichée en ligne 3
Numéro repère affiché en ligne 3
Alterner les informations affichées
[49]
Calibrer l’entrée basse à la valeur de process ?
[50]
Calibrer l’entrée haute à la valeur de process ?
[51]
Permettre simulation de l’entrée ?
[52]
Régler la valeur de simulation en entrée
[53]
Simulation relais - utiliser 1 pour alterner l’état du relais
[54]
Permettre protection par mot de passe ?
[55]
Entrer Nouveau mot de passe
[56]
Permettre la fonctionalité Réglage rapide ?
92 9116 - Product Version 9116-001
[57]
Consigne relais - appuyer sur 3 pour sauvegarder
[58]
Consigne relais - Lecture
[59]
Sélectionner langue
[60]
Utiliser valeurs de calibration process ?
[61]
Régler valeur de la position basse de la calibration
[62]
Régler valeur de la position haute de la calibration
[63]
Activer signal d’état du rail d’alimentation
[64]
Permettre verrouillage de la configuration SIL ?
0-20 mA n’est pas une gamme de sortie valable en
opération SIL
[65]
... Est-ce que la voie utilise des données de
calibration compensées au process ?
[66]
Etat de la configuration SIL ( Ouverte / Verrouillée)
[80]
Court circuit du capteur
[81]
Rupture du câble capteur
[82]
Affichage en dessous du mini.
[83]
Affichage en dessus du maxi.
[84]
Entrée dépasse l’échelle basse
[85]
Entrée dépasse l’échelle haute
[86]
Erreur d’entrée - contrôler les connexions et
redémarrer le module
[87]
Erreur de sortie - contrôler connexions et
redémarrer le module
[88]
Erreur dans la mémoire FLASH - contrôler la
configuration
[89]
Configuration ou version invalide
[90]
Erreur matériel
[91]
Erreur du capteur CSF - contrôler la température
du module
Die folgende Maßnahmen sollten nur in spannungslosem
WARNUNG
Zustand des Gerätes und unter ESD-sicheren Verhältnisse
durchgeführt werden:
Installation, Montage und Demontage von Leitungen.
Fehlersuche im Gerät.
Reparaturen des Gerätes und Austausch von Sicherungen
dürfen nur von PR electronics A/S vorgenommen werden.
Die Frontplatte des Gerätes darf nicht geöffnet werden, weil
hier durch die Kontakte zur Kontaktierung des Frontdisplays
4501 beschädigt werden können. Das Gerät enthält keine internen DIP-Schalter oder Programmierbrücken.
ZEICHENERKLÄRUNGEN
WARNUNG
Dreieck mit Ausrufungszeichen: Das Handbuch ist sorgfältig
durchzulesen vor Montage und Inbetriebnahme des Gerätes, um
schweren Verletzungen oder mechanischer Zerstörung zu vermeiden.
Die CE-Marke ist das sichtbare Zeichen dafür, dass das Gerät die Vorschriften erfüllt.
Doppelte Isolierung ist das Symbol dafür, dass das Gerät besondere
Anforderungen an die Isolierung erfüllt.
Ex-Geräte sind entsprechend der ATEX Direktive für die Verwendung in
Ver bindung mit Installationen in explosionsgefährdeter Umgebung zugelassen. Siehe Installationszeichnung im Appendix.
SICHERHEITSREGELN
DEFINITIONEN
Gefährliche Spannungen sind definitionsgemäß die Bereiche: 75...1500 Volt
Gleichspannung und 50...1000 Volt Wechselspannung.
Techniker sind qualifizierte Personen, die dazu ausgebildet oder angelernt sind,
eine Installation, Bedienung oder evtl. Fehlersuche auszuführen, die sowohl
technisch als auch sicherheitsmäßig vertretbar ist.
Bedienungspersonal sind Personen, die im Normalbetrieb mit dem Produkt die
Drucktasten oder Potentiometer des Produktes einstellen bzw. bedienen und
die mit dem Inhalt dieses Handbuches vertraut gemacht wurden.
98 9116 - Product Version 9116-001
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.