PR Elecronics 5715 User Manual

5715
SIGNALS THE BEST
Programmable LED Indicator
No. 5715V102-UK From serial number: 121496001 (B) 131077001 (D)
1318
PR electronics A/S tilbyder et bredt program af analoge og digitale signalbehandlingsmoduler til industriel automation. Programmet består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere, Universaltransmittere m. Vi har modulerne, du kan stole på i selv barske miljøer med elektrisk støj, vibrationer og temperaturud­sving, og alle produkter opfylder de strengeste internationale stan­darder. Vores motto »Signals the Best« er indbegrebet af denne loso – og din garanti for kvalitet.
PR electronics A/S offers a wide range of analogue and digital signal conditioning devices for industrial automation. The product range includes Isolators, Displays, Ex Interfaces, Temperature Transmitters, and Universal Devices. You can trust our products in the most extreme environments with electrical noise, vibrations and temperature uctuations, and all products comply with the most exacting international standards. »Signals the Best« is the epitome of our philosophy – and your guarantee for quality.
PR electronics A/S offre une large gamme de produits pour le traite ment des signaux analogiques et numériques dans tous les domaines industriels. La gamme de produits s’étend des transmetteurs de température aux afcheurs, des isolateurs aux interfaces SI, jusqu’aux modules universels. Vous pouvez compter sur nos produits même dans les conditions d’utilisation sévères, p.ex. bruit électrique, vibrations et uctuations de température. Tous nos produits sont conformes aux normes internationales les plus strictes. Notre devise »SIGNALS the BEST« c’est notre ligne de conduite - et pour vous l’assurance de la meilleure qualité.
PR electronics A/S verfügt über ein breites Produktprogramm an analogen und digitalen Signalverarbeitungsgeräte für die in­dustrielle Automatisierung. Dieses Programm umfasst Displays, Temperaturtransmitter, Ex- und galvanische Signaltrenner, und Universalgeräte. Sie können unsere Geräte auch unter extremen Einsatzbedingungen wie elektrisches Rauschen, Erschütterungen und Temperaturschwingungen vertrauen, und alle Produkte von PR electronics werden in Überein stimmung mit den strengsten internationalen Normen produziert. »Signals the Best« ist Ihre Garantie für Qualität!
DK
UK
FR
DE
5715V102-UK 1
PROGRAMMABLE LED INDICATOR
5715
CONTENTS
Warning .............................................................................. 2
Symbol identification .......................................................... 2
Safety instructions .............................................................. 3
Declaration of conformity ................................................... 5
Front and back layout ........................................................ 6
Application ......................................................................... 7
Technical characteristics .................................................... 7
Mounting / installation ........................................................ 7
Applications ........................................................................ 8
Order: 5715 ........................................................................ 9
Electrical specifications ...................................................... 9
Sensor error detection inside and outside range............... 13
Connections ....................................................................... 14
Block diagram .................................................................... 15
Routing diagram ................................................................. 17
Scrolling help texts ............................................................. 18
Configuration / operating the function keys ...................... 20
Programming via PC .......................................................... 21
Graphic depiction of the relay function setpoint................ 21
2 5715V102-UK
SYMBOL IDENTIFICATION
Triangle with an exclamation mark: Warning / demand. Potentially
lethal situations.
The CE mark proves the compliance of the module with the essential requirements of the directives.
WARNING
This module is designed for connection to hazardous electric voltages. Ignoring this warning can result in severe personal injury or mechanical damage. To avoid the risk of electric shock and fire, the safety instructions of this manual must be observed and the guidelines followed. The specifications must not be exceeded, and the module must only be applied as described in the following. Prior to the commissioning of the module, this manual must be examined carefully. Only qualified personnel (technicians) should install this module. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
WARNING
Until the module is fixed, do not connect hazardous voltages to the module. The following operations should only be carried out on a disconnected module and under ESD safe conditions: Troubleshooting the module.
Repair of the module must be done by PR electronics A/S only.
HAZARD-
OUS
VOLTAGE
GENERAL
5715V102-UK 3
SAFETY INSTRUCTIONS
DEFINITIONS
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and 50 to 1000 Volt AC. Technicians are qualified persons educated or trained to mount, operate, and also troubleshoot technically correct and in accordance with safety regulations. Operators, being familiar with the contents of this manual, adjust and operate the knobs or potentiometers during normal operation.
RECEIPT AND UNPACKING
Unpack the device without damaging it. The packing should always follow the device until this has been permanently mounted. Check at the receipt of the device whether the type corresponds to the one ordered.
ENVIRONMENT
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock, as well as rain and heavy moisture. If necessary, heating in excess of the stated limits for ambient temperatures should be avoided by way of ventilation. All modules fall under Installation Category II, Pollution Degree 1, and Insulation Class II.
MOUNTING
Only technicians who are familiar with the technical terms, warnings, and instructions in the manual and who are able to follow these should connect the module. Should there be any doubt as to the correct handling of the module, please contact your local distributor or, alternatively,
PR electronics A/S
www.prelectronics.com
Mounting and connection of the module should comply with national legislation for mounting of electric materials, i.e. wire cross section, protective fuse, and location. Descriptions of Input / Output and supply connections are shown in the block diagram and side label.
4 5715V102-UK
The following apply to fixed hazardous voltages-connected modules:
The max. size of the protective fuse is 10 A and, together with a power switch, it should be easily accessible and close to the module. The power switch should be marked with a label telling it will switch off the voltage to the module.
UL INSTALLATION REQUIREMENTS
For use on a flat surface of a type 1 enclosure Use 60/75°C copper conducters only
Enclosure rating (face only) .................... Type 4X, UL50E
Max. ambient temperature ..................... 60°C
Max. wire size, pins 41...46 .................... AWG 30-16
Max. wire size, others ............................ AWG 30-12
UL file number ........................................ E248256
CALIBRATION AND ADJUSTMENT
During calibration and adjustment, the measuring and connection of external voltages must be carried out according to the specifications of this manual. The technician must use tools and instruments that are safe to use.
NORMAL OPERATION
Operators are only allowed to adjust and operate modules that are safely fixed in panels, etc., thus avoiding the danger of personal injury and damage. This means there is no electrical shock hazard, and the module is easily accessible.
CLEANING
When disconnected, the module may be cleaned with a cloth moistened with distilled water.
LIABILITY
To the extent the instructions in this manual are not strictly observed, the custom er cannot advance a demand against PR electronics A/S that would otherwise exist according to the concluded sales agreement.
5715V102-UK 5
DECLARATION OF CONFORMITY
As manufacturer
PR electronics A/S Lerbakken 10 DK-8410 Rønde
hereby declares that the following product:
Type: 5715 Name: Programmable LED indicator
is in conformity with the following directives and standards:
The EMC Directive 2004/108/EC and later amendments
EN 61326-1
For specification of the acceptable EMC performance level, refer to the
electrical specifications for the module.
The Low Voltage Directive 2006/95/EC and later amendments
EN 61010-1
Rønde, 17 December 2009 Kim Rasmussen Manufacturer’s signature
6 5715V102-UK
FRONT AND BACK LAYOUT
Picure 1: Front of PReview 5715.
Picture 2: Back of PReview 5715.
5715V102-UK 7
PROGRAMMABLE LED INDICATOR
PREVIEW 5715
• 4-digit 14-segment LED display
• Input for mA, V, potentiometer, Ohm, RTD and TC
• 4 relays and analogue output
• Universal supply
• Programmable via front keys and PC
Application
• Displayfordigitalreadoutofcurrent/voltage/resistance/temperatureor
3-wire potentiometer signals.
• Processcontrolwith4pairsofpotential-freechange-overrelaysand
analogue output.
• Fortanklevelcontrol,withthepossibilityofcustomerlinearisationensuring
correct level measurement and control in non-linear tanks.
Technical characteristics
• 4-digitLEDindicatorwith13.8mm14-segmentcharacters.Max.display
read out -1999...9999 with programmable decimal point and relay ON / OFF indication.
• Allstandardoperationalparameterscanbeadjustedtoanyapplicationby
way of the front function keys. When programming is carried out by way of a PC and the configuration program PReset, additional configuration options are available, such as customer-defined linearisation and special input signals.
• Helptextsineightlanguagescanbeselectedviaamenuitem.
• Amenuitemallowstheusertominimisetheinstallationtesttimefortherelay
outputs by activating / deactivating each relay independently of the input signal.
Mounting / installation
• Tobemountedinpanelfront.Theincludedrubberpackingmustbemounted
between the panel cutout hole and the display front to obtain a protection degree of IP65 (type 4X). For extra protection in extreme environments, PReview 5715 can be delivered with a specially designed splash-proof cover as accessory.
46
45
44
43
42
41
4 3 2
1 2 3 4
1 2 3 4
12
11
26
25
24
23
22
21
66
65
64
63
62
61
32
31
1 2 3 4
-
+
-
+
-
+
-
+
-
+
8 5715V102-UK
APPLICATIONS
Input signals:
Current
Potentio-
meter
Output signals:
4 change-over relays
Analogue, 0/4...20 mA
Supply:
21.6...253 VAC or
19.2...300 VDC
Voltage
RTD & Lin R -
Connection, wires
2-twire transmitter
TC
5715V102-UK 9
Electrical specifications
Specifications range:
-20°C to +60°C
Common specifications:
Supply voltage, universal ............................ 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC Consumption:
Isolation voltage, test / operation ............... 2.3 kVAC / 250 VAC
Signal / noise ratio ...................................... Min. 60 dB (0...100 kHz)
Communications interface .......................... USB Loop Link
Response time (0...90%, 100...10%):
Temperature input .................................... < 1 s
Current / voltage input ............................. < 400 ms
Calibration temperature............................... 20...28°C
Accuracy, the greater of general and basic values:
General values
Input type
Absolute
accucary
Temperature
coefficient
All ±0.1% of reading ±0.01% of reading / °C
Type Internal consumption Max. consumption 5715B 3.0 W 3.3 W 5715D 3.5 W 3.8 W
Type Version
5715 4 relays....................: B
Analogue output and 4 relays ..: D
Order: 5715
10 5715V102-UK
Auxiliary supply:
2-wire supply (pin 46...45) ....................... 25...15 VDC / 0...20 mA
Wire size, pin 41...46 (max.) ........................ 1 x 1.5 mm
2
stranded wire
Wire size, others (max.) ............................... 1 x 2.5 mm
2
stranded wire
Relative humidity ......................................... < 95% RH (non cond.)
Dimensions (HxBxD) ................................... 48 x 96 x 120 mm
Cutout dimensions ...................................... 44.5 x 91.5 mm
Protection degree (mounted in panel) ......... IP65 / Type 4X, UL50E
Weight ......................................................... 260 g
RTD, linear resistance and potentiometer input:
Input for RTD types: Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000 Ni50, Ni100, Ni120, Ni1000, Cu10, Cu20, Cu50, Cu100
EMC immunity influence ..................................... < ±0,5% of reading
Basic values
Input
type
Basic
accuracy
Temperature
coefficient
mA ±4 µA ±0.4 µA / °C
Volt ±20 µV ±2 µV / °C
Pt100 ±0.2°C ±0.01°C / °C
Linear resistance ±0.1 Ω ±0.01 Ω / °C
Potentiometer ±0.1 Ω ±0.01 Ω / °C
TC type:
E, J, K, L, N, T, U
±1°C
±0.05°C / °C
TC type: R, S, W3,
W5, LR
±2°C
±0.2°C / °C
TC type: B
160...400°C
±4.5°C
±0.45°C / °C
TC type: B
400...1820°C
±2°C
±0.2°C / °C
Input
type
Min.
value
Max.
value
Standard
Pt10...Pt1000 Ni50...Ni1000
Cu10...Cu100
Lin. R
Potentiometer
-200°C
-60°C
-200°C 0 Ω
10 Ω
+850°C +250°C +260°C
10000 Ω
100 kΩ
IEC 60751
DIN 43760
α = 0.00427
-
-
5715V102-UK 11
Cable resistance per wire, RTD (max.) ........ 50 Ω
Sensor current, RTD .................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3- / 4-wire), RTD ......................................... < 0.002 Ω / Ω
Sensor error detection, RTD ....................... Yes
Short circuit detection, RTD ........................ < 15 Ω
TC input:
Cold junction compensation (CJC)
via internal sensor ................................... ±(2.0°C + 0.4°C * Δt)
Δt = internal temperature - ambient temperature
Sensor error detection, all TC types ........... Ye s
Sensor error current:
when detecting ....................................... Nom. 2 μA
else .......................................................... 0 μA
Current input:
Measurement range .................................... 0...20 mA
Programmable measurement ranges .......... 0...20 and 4...20 mA
Input resistance ........................................... Nom. 20 Ω + PTC 25 Ω
Sensor error detection:
loop break 4...20 mA ............................... Ye s
Voltage input:
Measurement range .................................... 0...12 VDC
Programmable measurement ranges .......... 0...1, 0.2...1,
0...10 and 2...10 VDC
Input resistance ........................................... Nom. 10 MΩ
Type
Min.
value
Max.
value
Standard
B E
J K L N R S T U
W3 W5
LR
+0°C
-100°C
-100°C
-180°C
-200°C
-180°C
-50°C
-50°C
-200°C
-200°C 0°C 0°C
-200°C
+1820°C +1000°C +1200°C +1372°C
+900°C +1300°C +1760°C +1760°C
+400°C
+600°C +2300°C +2300°C
+800°C
IEC 60584-1 IEC 60584-1 IEC 60584-1 IEC 60584-1
DIN 43710 IEC 60584-1 IEC 60584-1 IEC 60584-1 IEC 60584-1
DIN 43710
ASTM E988-90 ASTM E988-90 GOST 3044-84
12 5715V102-UK
Outputs:
Display:
Display readout ........................................... -1999...9999 (4 digits)
Decimal point .............................................. Programmable
Digit height .................................................. 13.8 mm
Display updating ......................................... 2.2 times / s
Input outside input range is
indicated by ................................................. Explanatory text
Current output:
Signal range (span) ...................................... 0...20 mA
Programmable signal ranges ...................... 0...20, 4...20,
20...0 and 20...4 mA
Load (max.) .................................................. 20 mA / 800 Ω / 16 VDC
Load stability ............................................... 0.01% of span / 100 Ω
Sensor error detection ................................ 23 / 0 / 3.5 mA / none
NAMUR NE 43 Up- / Downscale ................ 23 mA / 3.5 mA
Output limitation:
on 4...20 and 20...4 mA signals ............... 3,8...20.5 mA
on 0...20 and 20...0 mA signals ............... 0...20.5 mA
Current limit ................................................. 28 mA
Relay outputs:
Relay function.............................................. Setpoint
Hysteresis .................................................... 0...100%
On and Off delay ......................................... 0...3600 s
Sensor error detection ................................ Make / Break / Hold
Max. voltage ................................................ 250 VRMS
Max. current ................................................ 2 A / AC
Max. AC power ........................................... 500 VA
Max. current at 24 VDC............................... 1 A
Marine approval:
Det Norske Veritas, Ships & Offshore ......... Standard for Certification No. 2.4
GOST R approval:
VNIIM, Cert. no. ........................................... See www.prelectronics.com
Observed authority requirements: Standard:
EMC 2004/108/EC ...................................... EN 61326-1
LVD 2006/95/EC .......................................... EN 61010-1
UL, Standard for Safety .............................. UL 508
5715V102-UK 13
Sensor error detection inside and outside range
Sensor error check in 5715 variants:
Variant: Configuration Sensor error detection:
5715B
ERR1, ERR2, ERR3 and ERR4 = NONE OFF
Else: ON
5715D
ERR1, ERR2, ERR3 and ERR4=NONE, O.ERR=NONE.
OFF
Else: ON
Readout at hardware error
! Error indications in the display blink once a second. The help text explains the error
Error search Readout Error cause Test of internal communication uC / ADC HW.ER Permanent error in ADC Test of internal CJC sensor CJ.ER CJC sensor defect Check-sum test of the configuration in RAM RA.ER Error in RAM Check-sum test of the configuration in EEprom EE.ER Error in EEPROM
Outside range readout (IN.LO, IN.HI):
If the valid range of the A/D converter or the polynomial is exceeded
Input Range Readout Limit
VOLT
0...1 V / 0,2...1 V
IN.LO < -25 mV
IN.HI > 1,2 V
0...10 V / 2...10 V
IN.LO < -25 mV
IN.HI > 12 V
CURR 0...20 mA / 4...20 mA
IN.LO < -1,05 mA
IN.HI > 25,05 mA
POTM -
IN.LO < -0,5%
IN.HI > 100,5%
TEMP TC / RTD
IN.LO < temperature range -2°C
IN.HI > temperature range +2°C
LIN R
0...800 ohm
IN.LO < 0 ohm
IN.HI > 1 kohm
0...10 kohm
IN.LO < 0 ohm
IN.HI > 15 kohm
Sensor error detection (SE.BR, SE.SH):
Input Range Readout Limit
CURR Loop break (4..20mA) SE.BR <= 3,6 mA; > = 21 mA
TEMP
TC SE.BR > ca. 750 kohm / (1,25 V)
RTD, 2-, 3- & 4-wire
No SE.SH for Cuxx, Pt10, Pt20 & Pt50
SE.BR > 12 kohm SE.SH < 15 ohm
LIN R
0...800 ohm SE.BR > 875 ohm
0...10 kohm SE.BR > 12 kohm
Display readout below min. / above max. (-1.9.9.9, 9.9.9.9):
Input Range Readout Limit
CURR /
VOLT / Lin R
All
-1.9.9.9 Display readout <-1999
9.9.9.9 Display readout >9999
POTM -
-1.9.9.9 Display readout <-1999
9.9.9.9 Display readout >9999
Tx
31 32
41 42 43 44 45 4641 42 43 44 45 4641 42 43 44 45 46
41 42 43 44 45 46 41 42 43 44 45 46 41 42 43 44 45 46
41 42 43 44 45 46 41 42 43 44 45 46
mA
11 12
R2
R1
21 22 23 24 25 26
R3 R4
41 42 43 44 45 4661 62 63 64 65 66
- +
- +
- + - + - +
14 5715V102-UK
CONNECTIONS
RTD & Lin R, 2-wire RTD & Lin R, 3-wire RTD & Lin R, 4-wire
PotentiometerVoltage
TC 2-wire transmitter Current
Current Relays
Inputs:
Output:
Supply:
Relays
I+
212223
11
12
31
32
2425266162
636465
66
CPU
AD
EEPROM
PTC
20 Ω
5715
1 2 3 4
46
45
44
43
42
41
TC+V
4 3 2
R1
R2
R3
R4
1
3
2
Tx
+
+
+
mA
5715V102-UK 15
BLOCK DIAGRAM
I
Output
Common
Relay 1 N.O.
Relay 1 N.C.
Common
Relay 2 N.O.
Relay 2 N.C.
Common
Relay 3 N.O.
Relay 3 N.C.
Common
Relay 4 N.O.
Relay 4 N.C.
Supply
Supply
21.6...253 VACor19.2...300 VDC
Version D
0.2 mA
Int.
CJC
2-wire supply
> 15 VDC
Input +,
mA
Input gnd.
RTD & Lin R
wires
Potm.
PC communication
Gnd.
Power up
50.0
3
F.SET
REL1 REL2 REL3 REL4
3
1.0
1.2
1 2
1 2
SETP
-1999 9999
/OFF
3
1 2
DI.LO PERC
DI.HI
1.1
0000 9999
1 2
3
CURR
3
RANG
0-20 4-20
1 2
VOLT
3
RANG
1 2
0-1 0.2-1
0-10 2-10
IN
1 2
1111
1.1.1.1
1 2
POTM
TEMP
TYPE
PT.TY
TC
CONN
TC.TY
PT
3
1 2 1 2
NI
NI.TY CONN
50-1000
1 2
2W 3W 4W
1 2
1 2
3
3
3
PASS
3
a999 9999
1 2
3
a999 9999
1 2
3
PERC DISP
1 2
3
1.3
DEC.P
TC.B TC.E TC.J TC.K TC.L TC.N TC.R TC.S TC.T TC.U TC.W3 TC.W5 TC.LR
1111
111.1
1 2
UNIT
'C 'F
1 2
ADV
NO
YES
1 2
3
10-1000
2W 3W 4W
3
LIN.R
3
LR.LO
0-9998
1 2
LR.HI
1-9999
1 2
CONN
1 2
2W 3W 4W
3
3
3
CU.TY CONN
CU
3
1 2 1 2
10-100
2W 3W 4W
3
3
3
1 2
3
3
3
3
3
3
3
3
ADV.SET
YES
3
C.LIN
1.4
DEC.P
16 5715V102-UK
1.0 = Default state
1.1 = Only if password-protected
1.2 = Only is FastSet is enabled
1.3 = Setpoint adjustment and relay test disabled at pass­word 5000...9999.
1.4 = Only for special configura­tion via PC
1.5 = Not valid for these input signals: Potentiometer,
0...20 mA and voltage
1.6 = Only if input signal is tem­perature
1.7 = No analogue output
1.8 = In default state press and hold
1 or 2 to change
display intensity between damped and full (7 = full intensity)
Fast setpoint adjustment and relay test
1Increase setpoint 2Decrease setpoint 3Save and exit the menu 1and 2 simultaneously =
relay changes state
REL.1
SET
SKIP
OFF
1 2
3
SETP
0.0
100.0
1 2
3
ACT1
INCR DECR
1 2
3
HYS1
0.0
100.0
1 2
3
ERR1
HOLD ACTI DEAC NONE
1 2
3
ON.DE
0000 3600
1 2
3
OF.DE
0000 3600
1 2
3
3
1.5
REL.X
SET
SKIP
OFF
1 2
3
SETP
0.0
100.0
1 2
3
ACTX
INCR DECR
1 2
3
HYSX
0.0
100.0
1 2
3
ERRX
HOLD ACTI DEAC NONE
1 2
3
ON.DE
0000 3600
1 2
3
OF.DE
0000 3600
1 2
3
3
1.5
A.OUT
4-20 0-20 20-4 20-0
1 2
3
O.LO
a999 9999
1 2
3
O.HI
a999 9999
1 2
3
O.ERR
0/3.5mA
23mA NONE
1 2
3
RESP
0.0
60.0
1 2
3
E.PAS
YES
NO
1 2
3
N.PAS
0000 9999
1 2
3
NO
----
1.51.6 1.6
1.7
1.7
DE DK ES FR IT SE UK CZ
X = 2...4
ADV.SET
LANG
DISP
CAL
1.8
7
LIGH
3
1...7
1 2
LANG
DISP CAL
1 2
3
3
UK
HLP.T
1 2
3
YES
CA.LO
3
YES NO
1 2
2.0
VAL.L
3
100.0
0.0
1 2
NO
3
YES
CA.HI
3
1 2
90.0
VAL.H
3
100.0
0.0
1 2
NO
YES
USE.C
3
1 2
YES NO
YES NO
3
5715V102-UK 17
ROUTING DIAGRAM
If no key is activated for 2 minutes, the display returns to default state
1.0 without saving configuration changes.
1 Increase value / choose next parameter 2 Decrease value / choose previous parameter 3 Accept the chosen parameter and go to the next menu
Hold 3 Back to previous menu / return to default state 1.0 without saving
To default state 1.0
18 5715V102-UK
SCROLLING HELP TEXTS
Display in default state xxxx, hardware error: SE.BR --> SENSOR WIRE BREAKAGE SE.SH --> SENSOR SHORT CIRCUIT IN.HI --> INPUT OVERRANGE IN.LO --> INPUT UNDERRANGE
9.9.9.9 --> DISPLAY OVERRANGE
-1.9.9.9 --> DISPLAY UNDERRANGE HW.ER --> HARDWARE ERROR EE.ER --> EEPROM ERROR -
CHECK CONFIGURATION
RA.ER --> RAM MEMORY ERROR CJ.ER --> CJC SENSOR ERROR
Fastset (Enabled): F.SET REL1 --> FAST SET MENU - REL2 --> SELECT RELAY REL3 REL4
SETP
xxxx --> RELAY SETPOINT - PRESS OK TO SAVE
Fastset (Disabled): SETP
xxxx --> RELAY SETPOINT - READ ONLY
Configuration menus: ADV
YES --> ENTER ADVANCED SETUP MENU? NO
PASS xxxx --> SET CORRECT PASSWORD
IN C.LIN* --> TEXT ENTERED BY USER IN PRESET CURR --> CURRENT INPUT VOLT --> VOLTAGE INPUT POTM --> POTENTIOMETER INPUT LIN.R --> LINEAR RESISTANCE INPUT TEMP --> TEMPERATURE SENSOR INPUT
RANG When current selected:
0-20 --> INPUT RANGE IN mA 4-20 --> INPUT RANGE IN mA
RANG When voltage selected:
0-10 --> INPUT RANGE IN VOLT 2-10 --> INPUT RANGE IN VOLT
0.0-1 --> INPUT RANGE IN VOLT
0.2-1 --> INPUT RANGE IN VOLT
DEC.P 1111 --> DECIMAL POINT POSITION
111.1 --> DECIMAL POINT POSITION
11.11 --> DECIMAL POINT POSITION
1.111 --> DECIMAL POINT POSITION
LR.LO xxxx --> SET RESISTANCE VALUE LOW
LR.HI xxxx --> SET RESISTANCE VALUE HIGH
DI.LO xxxx --> DISPLAY READOUT LOW
DI.HI xxxx --> DISPLAY READOUT HIGH
REL.U PERC --> SET RELAY IN PERCENTAGE DISP --> SET RELAY IN DISPLAY UNITS
TYPE CU --> SELECT CU SENSOR TYPE PT --> SELECT PT SENSOR TYPE NI --> SELECT NI SENSOR TYPE TC --> SELECT TC SENSOR TYPE
CU.TY 10 --> SELECT CU SENSOR TYPE 20 --> SELECT CU SENSOR TYPE 50 --> SELECT CU SENSOR TYPE 100 --> SELECT CU SENSOR TYPE
PT.TY 10 --> SELECT PT SENSOR TYPE 20 --> SELECT PT SENSOR TYPE 50 --> SELECT PT SENSOR TYPE 100 --> SELECT PT SENSOR TYPE 200 --> SELECT PT SENSOR TYPE 250 --> SELECT PT SENSOR TYPE 300 --> SELECT PT SENSOR TYPE 400 --> SELECT PT SENSOR TYPE 500 --> SELECT PT SENSOR TYPE 1000 --> SELECT PT SENSOR TYPE
NI.TY 50 --> SELECT NI SENSOR TYPE 100 --> SELECT NI SENSOR TYPE 120 --> SELECT NI SENSOR TYPE 1000 --> SELECT NI SENSOR TYPE
CONN When Cu, Pt and Ni sensor is selected 2W --> SELECT 2-WIRE SENSOR CONNECTION 3W --> SELECT 3-WIRE SENSOR CONNECTION 4W --> SELECT 4-WIRE SENSOR CONNECTION
TC.TY TC. B --> SELECT TC SENSOR TYPE TC. E --> SELECT TC SENSOR TYPE TC. J --> SELECT TC SENSOR TYPE TC. K --> SELECT TC SENSOR TYPE TC. L --> SELECT TC SENSOR TYPE TC. N --> SELECT TC SENSOR TYPE TC. R --> SELECT TC SENSOR TYPE TC. S --> SELECT TC SENSOR TYPE TC. T --> SELECT TC SENSOR TYPE TC. U --> SELECT TC SENSOR TYPE TC.W3 --> SELECT TC SENSOR TYPE TC.W5 --> SELECT TC SENSOR TYPE TC.LR --> SELECT TC SENSOR TYPE
DEC.P When temperature selected 1111 --> DECIMAL POINT POSITION
111.1 --> DECIMAL POINT POSITION
UNIT °C --> DISPLAY AND RELAY SETUP IN CELSIUS °F --> DISPLAY AND RELAY SETUP IN FAHRENHEIT
5715V102-UK 19
REL1 SET --> ENTER RELAY 1 SETUP SKIP --> SKIP RELAY 1 SETUP OFF --> RELAY 1 DISABLED
SETP xxxx --> RELAY SETPOINT
ACT1 INCR --> ACTIVATE AT INCREASING SIGNAL DECR --> ACTIVATE AT DECREASING SIGNALL
HYS1 xxxx --> RELAY HYSTERESIS
ERR1 HOLD --> HOLD RELAY AT ERROR ACTI --> ACTIVATE RELAY AT ERROR DEAC --> DEACTIVATE RELAY AT ERROR NONE --> UNDEFINED STATUS AT ERROR
ON.DE xxxx --> RELAY ON-DELAY IN SECONDS
OF.DE xxxx --> RELAY OFF-DELAY IN SECONDS
RELX (X = 2...4) SET --> ENTER RELAY 2 SETUP SKIP --> SKIP RELAY 2 SETUP OFF --> RELAY 2 DISABLED
SETP xxxx --> RELAY SETPOINT
ACTX (X = 2...4) INCR --> ACTIVATE AT INCREASING SIGNAL DECR --> ACTIVATE AT DECREASING SIGNAL
HYSX (X = 2...4) xxxx --> RELAY HYSTERESIS
ERRX (X = 2...4) HOLD --> HOLD RELAY AT ERROR ACTI --> ACTIVATE RELAY AT ERROR DEAC --> DEACTIVATE RELAY AT ERROR NONE --> UNDEFINED STATUS AT ERROR
ON.DE xxxx --> RELAY ON-DELAY IN SECONDS
OF.DE xxxx --> RELAY OFF-DELAY IN SECONDS
A.OUT 0-20 --> OUTPUT RANGE IN mA 4-20 --> OUTPUT RANGE IN mA 20-0 --> OUTPUT RANGE IN mA 20-4 --> OUTPUT RANGE IN mA
O.LO xxxx --> DISPLAY VALUE FOR OUTPUT LOW
O.HI xxxx --> DISPLAY VALUE FOR OUTPUT HIGH
O.ERR 23 mA --> NAMUR NE43 UPSCALE AT ERROR 3,5 mA --> NAMUR NE43 DOWNSCALE AT ERROR 0mA --> DOWNSCALE AT ERROR NONE --> UNDEFINED OUTPUT AT ERROR
RESP xxx.x --> ANALOGUE OUTPUT RESPONSE TIME IN SECONDS
E.PAS NO --> ENABLE PASSWORD PROTECTION YES
N.PAS xxxx --> SELECT NEW PASSWORD
ADV MENU: LANG --> ENTER LANGUAGE SETUP DISP --> ENTER DISPLAY SETUP CAL --> PERFORM PROCESS CALIBRATION
HLP.T DE --> DE - WAEHLE DEUTSCHEN HILFETEXT DK --> DK - VAELG DANSK HJAELPETEKST ES --> ES - SELECCIONAR TEXTO DE AYUDA EN ESPANOL FR --> FR - SELECTION TEXTE D’AIDE EN FRANCAIS IT --> IT - SELEZIONARE TESTI DI AIUTO ITALIANI SE --> SE - VALJ SVENSK HJALPTEXT UK --> UK - SELECT ENGLISH HELPTEXT CZ --> CZ - VYBER CESKOU NAPOVEDU
LIGH
xxxx --> ADJUST DISPLAY LIGHT INTENSITY
CA.LO YES --> CALIBRATE INPUT LOW TO PROCESS VALUE? NO
CA.HI YES --> CALIBRATE INPUT HIGH TO PROCESS VALUE? NO
VAL.L xxxx --> SET VALUE FOR LOW CALIBRATION POINT
VAL.H xxxx --> SET VALUE FOR HIGH CALIBRATION POINT
USE.C YES --> USE PROCESS CALIBRATED VALUES? NO
20 5715V102-UK
CONFIGURATION / OPERATING
THE FUNCTION KEYS
Documentation for the routing diagram
In general:
When configuring the display you are guided through all parameters, allowing
you to choose the settings which fit the application. For each menu there is a scrolling help text which is automatically shown in the display if no key has been activated for appr. 5 seconds.
Configuration is carried out by way of the 3 function keys
1 2 and 3.
1 will increase the numerical value or choose the next parameter. 2 will
decrease the numerical value or choose the previous parameter.
3 will
accept the chosen value and go to the next menu. If a function does not exist in the hardware, all parametres belonging to that function will be skipped in order to make configuration as simple as possible. The configuration will not be saved until the end of the menu structure when the display shows - - - -.
Pressing and holding
3 will return to the previous menu or go back to the
default state (1.0) without saving the changed values or parameters.
If no key is activated for 2 minutes, the display will return to the default state
(1.0) without saving the changed values or parameters.
Furhter explanations: Fast setpoint adjustment and relay test: These menus are interactive and
allow you to adjust the setpoints while the display is measuring the input sig­nal. The diodes will then indicate when the relays change state, thus easing the setpoint adjustment in many situations. By activating
1 and 2 simulta-
neously, a relay test will be initiated and the relay will change state. The set­point adjustment will be saved by a quick press of
3 . Holding down 3 for
more that 0.5 seconds wil return the display to the default state (1.0) without changing the setpoint.
Password protection: Using a password will block access to the menu and
parameters. There are two levels of password protection. Passwords be tween 0000 and 4999 allow access to the fast setpoint adjustment and relay test menus (using this password blocks access to all other parts of the menu). Passwords between 5000 and 9999 block access to all parts of the menu, fast setpoint and relay test (current setpoint is still shown). Default password 2008 allows access to all configuration menus.
100
90
80
70
60
50
40
30
20
10
0 10 20 30 40 50 60 70 80 90 100
t
Off N.O. Off N.O.On N.O.
On N.C. On N.C.
Off N.C.
100
90
80
70
60
50
40
30
20
10
0 10 20 30 40 50 60 70 80 90 100
t
Off N.O. Off N.O.On N.O.
On N.C. On N.C.
Off N.C.
5715V102-UK 21
PROGRAMMING VIA PC
By way of PReset, a simple yet sophisticated PC program, all operational
parameters in the 5715 can be quickly configured to suit any application. Furthermore, the PC configuration allows you to set up a customer-defined input type for the input signals current, voltage, resistance and potentiometer. This input type can be defined with special input spans, e.g. 5...12 mA, and customer-defined linearisation with or without offset. The customer-defined input type is saved in the 5715 in the input menu C.LIN. If the display is later configured by way of the front keys for e.g. temperature input, the input type C.LIN containing all the original parameters can be subsequently selected. The PC configuration is sent to the display by way of the communications interface USB Loop Link.
Graphic depiction of the relay function setpoint
Relay unitsRelay units
Setpoint = 50
Hysteresis = 10
Hysteresis = 10
Setpoint = 50
Relay action: Increasing Relay action: Decreasing
Programmable displays with a wide selection of inputs and outputs for display of temperature, volume and weight, etc. Feature linearisation, scaling, and difference measurement functions for programming via PReset software.
Displays
A wide selection of transmitters for DIN form B mounting and DIN rail devices with analogue and digital bus communication ranging from application­specic to universal transmitters.
Temperature
Galvanic isolators for analogue and
digital signals as well as HART
®
signals. A wide product range with both loop-powered and universal isolators featuring linearisation, inversion, and scaling of output signals.
Isolation
Interfaces for analogue and digital signals
as well as HART
®
signals between sensors / I/P converters / frequency signals and control systems in Ex zone 0, 1 & 2 and for some devices in zone 20, 21 & 22.
Ex interfaces
PC or front programmable devices with universal options for input, output and supply. This range offers a number of advanced features such as process calibration, linearisation and auto-diagnosis.
Universal
Head ofce
Denmark www.prelectronics.com
PR electronics A/S sales@prelectronics.dk Lerbakken 10 tel. +45 86 37 26 77
DK-8410 Rønde fax +45 86 37 30 85
www.prelectronics.fr sales@prelectronics.fr
www.prelectronics.de sales@prelectronics.de
www.prelectronics.es sales@prelectronics.es
www.prelectronics.it sales@prelectronics.it
www.prelectronics.se sales@prelectronics.se
www.prelectronics.co.uk sales@prelectronics.co.uk
www.prelectronics.com sales@prelectronics.com
www.prelectronics.cn sales@prelectronics.cn
Loading...