Prefect Control PRE9200, PRE9220, PRE9250, PRE9280 Installation Instructions Manual

Prefect Instructions
1
Prefect Control Ltd Unit 2, Church Field Business Park, Church Field Road, Sudbury, Suffolk, CO10 2YF Tel: 01787 320 604 Fax: 0845 450 3020 Email: mail@prefectcontrols.com Website: www.prefectcontrols.com
Due to our policy of continuous improvement, we reserve the right to change specifications without notice
V1.1
PRE9200, 9220, 9250, 9280UNI Run Back Timers
The PRE9200 series of time delay switches are designed to provide timed control of lighting, heating or ventilation loads. Using push button, touch (light press required), pull cord or remote activation, the user can switch on a load for a preset time period and have the load turn off automatically after the time period has elapsed.
Multiple timing ranges come as standard to allow the time out period to be set accurately. Time setting is achieved using switches and a thumbwheel at the rear of the unit.
Several modes of operation are selectable using the switches:
• ON/OFF mode: Activating the timer will turn on the load and start the timing. Activating the timer again during a timer run will immediately turn off the load and stop the time run.when
a 230v trigger voltage is applied to the TRIG terminal the timer will start. Disconnecting then reconnecting the trigger voltage will then stop the timer.
• Resetting mode: activating the timer will turn on the load and start the time run. Activating the timer again during an exsisting time run will re-start the time run period from scratch. When using an external trigger in this mode, the timer will not start until the trigger is removed making it ideal for pump or fan overrun applications.
• Non-resetting: Activating the timer will turn on the load and start the time run. Triggering the timer again during a time run will have no effect. Applying a 230v trigger to the TRIG terminal will start the time run. whether the voltage remains or is disconected the time run will complete.
Operation:
Wire the PRE9200 timers as in diagram 1. Connection to the TRIG terminal is optional on all units except the PRE9220 remote timer. Applying a live to the trigger terminal will start the timer running. A momentary switch can be used, for example, in corridor lighting applications. A permanent input can be used, for example, in pump overrun applications.
To switch from more than one position simply wire two or more units in parallel to achieve two way and intermediate switching, or use the trigger terminal with a slave switch.
For lighting applications that call for the replacement of a three wire switching system follow diagram 2. When installing touch switches do not fix to a vibrating or uneven surface.
Installation Instructions:
Prefect Instructions
2
Prefect Control Ltd Unit 2, Church Field Business Park, Church Field Road, Sudbury, Suffolk, CO10 2YF Tel: 01787 320 604 Fax: 0845 450 3020 Email: mail@prefectcontrols.com Website: www.prefectcontrols.com
Due to our policy of continuous improvement, we reserve the right to change specifications without notice
V1.1
Installation Instructions Continued...
WARNING. This device works at mains potential. Be sure to take care when working with electricity. Ensure all work complies with relevant regulations in force at time of installation.
1. Perform safe ilsoation procedure of the appropriate cicuits
2. Connect the timer to the conductors
Live supply to the L terminal Neutral to the N terminal Load to the LIVE OUT terminal Where required connect the external trigger to the TRIG terminal.
3. Set the timing range according to the diagram opposite. For example; if a timmming range of 100 minutes is required set the switches to; 1 to 2 hours.
4. Set the thumb wheel to the precise time setting. the thumbwheel adjusts between the time settings set by the switches. Following the example above the wheel would need to be set to a 2 o’clock position.
5. Double check all connections are correct & firmly fitted.
6. Ensuring the cabaling is not in a position to become damaged fit the unit to the box
7. When safe to do so, switch the mains supply back on at the distribution board.
Installation & Settings:
Diagram 1 Diagram 2
LOAD: 16 Amp resistive load 10 Amp incandescent lighting 6 Amp fluorescent lighting 3 Amp compact fluorescent lighting 3 Amp low energy lighting. 3 Amp low voltage lighting (switch primary of transformer) Fluorescent lighting (max 6 fittings recommended). For fluorescent lighting total power factor correction capacitance must not exceed 40μF. 3 Amp fans and ventilation equipment . Switch SON lighting loads via a contactor
SUPPLY VOLTAGE: 220-240 Volts AC 50 Hz TIMING PERIOD: Adjustable 1 second to 2 hours in ranges
FIXING METHOD: Surface fixing 25mm deep plastic surface mount
moulded box. Flush fixing 25mm steel wall box or 32mm deep cavity wall box.NOTE: When using a metal box ensure the top and bottom lugs are removed from the box.
TERMINAL CAPACITY: 4.0mm2 MATERIAL: Flame retardant ABS TYPE: Class 2 TEMPERATURE: -10°C to 35°C CONFORMITY EMC-89/336/EEC
TIMING
ADJUSTMENT
LIVE IN
NEUTRAL
LOAD
CIRCUIT PROTECTION
(IF REQUIRED)
SLAVE TRIGGER
LINK
43
ON
TIME
21
L
N
LIVE OUT
TRIG
TIMING
ADJUSTMENT
LIVE IN
NEUTRAL
LOAD
CIRCUIT PROTECTION
(IF REQUIRED)
SLAVE TRIGGER
43
ON
TIME
21
L
N
LIVE OUT
TRIG
1hour­2hours
1sec­5mins
15mins­1hour
5mins­15mins
Resetting mode
non-resetting mode
on/off mode
The timming wheel selects the run time. Clockwise turn increases time, anti-clockwise decreases time.
Loading...