Preen AFV-11008, AFV-11010, AFV-11015, AFV-11020, AFV-11030 User Manual

...
AC POWER SOURCE
AFV Series
Product Manual
If you meet any problems, you should seek immediate assistance from branches of AC Power that the equipment was purchased or customer service & support department of AC Power Corp.
AC Power pursues policy of continual product development and reserves the right to
change the equipment design without prior notice.
Copyright by AC Power Corp.
All rights reserved.
AFV variable frequency power supply User Manual
Safety instructions
Danger
Dangerous high voltages exist inside this machine. Do not open any covers of this machine unless authorized
and done by trained technicians. Otherwise, electrical shock to persons may happen.
In case the machine needs to be moved or re-wired, all electricity to the machine must be disconnected and removed. After electricity is removed, please wait for at least 20 minutes before touching any live parts of this machine or electrical shock may occur: the electrical charges on the bulky capacitors inside the machine need some time to be fully discharged.
For optimal safety protection to the users, this machine must have solid connections to the earth. Do not use this machine if it is not grounded.
In case of fire, use an extinguisher with powder chemicals instead of liquid agents. Electrical shock may occur if liquid extinguishing products are used.
Any foreign objects and/or liquid are strictly prohibited from entering to the inside of this machine.
Caution
Storage and operating environment have a certain degree of influence on the life and reliability of this product. Therefore, avoid placing and/or operating this machine in environments with the following:
(i). Having extreme ambient temperature or humidity that exceeds the allowable limit stated in the specification, temperature: 0℃~45, humidity: 090%.
(ii). Having direct sunlight exposure, or being near a heat source.
(iii). Places that tend to be vibrated or hit by other objects.
(iv). Having heavy dust, heavy salt, corrosive chemicals or inflammable chemicals in the air.
Please keep air ventilation inlets and outlets clear and clean. Obstruction on the inlet or outlet will have significant negative impact on the machine’s quality and reliability.
If the machine will not be used for a long time, please store it in a dry and clean environment with temperature in the range of -40℃~+70.
Caution
i
This machine is composed of many delicate and precision devices. Please do not open any covers of this machine unless authorized and done by trained technicians. Warranty is voided if the quality seal is broken.
AFV variable frequency power supply User Manual
Contents
Chapter I Product Introduction .................................................................................................... 1
Chapter II Working Principle ....................................................................................................... 2
2.1 Functional block diagram of complete machine ................................................................ 2
2.2 Description of functional block diagram ............................................................................ 3
2.3 Constitution of main control circuit .................................................................................... 3
Chapter III Transportation and Installation ............................................................................... 4
3.1 Transportation precautions ................................................................................................. 4
3.2 Unpacking inspection ............................................................................................................ 4
3.3 Installation environment requirements .............................................................................. 5
3.4 Description of cable connection ........................................................................................... 6
3.4.1 Single-phase input and single-phase output connection terminal .......................................................... 6
3.4.2 Three-phase input and single-phase output connection terminal ........................................................... 6
3.4.3 Three-phase input and three-phase output connection terminal ............................................................. 7
3.5 Cable wiring........................................................................................................................... 8
Chapter IV Product Specifications .............................................................................................. 11
4.1 Technical specifications ...................................................................................................... 11
4.2 Shape structure ................................................................................................................... 16
Chapter V Operation ....................................................................................................................... 19
5.1 Initial power-up of system .................................................................................................. 19
5.2 Menu description................................................................................................................. 19
5.3 Parameter setting ................................................................................................................ 20
5.3.1 Start-up ............................................................................................................................................... 20
5.3.2 User mode ........................................................................................................................................... 21
5.4 Application interface ........................................................................................................... 22
5.4.1 General mode ..................................................................................................................................... 22
5.4.2 Step mode ............................................................................................................................................ 23
5.4.3 Gradual mode ..................................................................................................................................... 24
5.4.4 Measurement mode ............................................................................................................................ 25
5.4.5 System maintemance interface ......................................................................................................... 26
5.4.6 System log ........................................................................................................................................... 27
6.1 Communication interface ................................................................................................... 29
6.2 Operations of remote control on PC ................................................................................. 30
Chapter VII Maintenance ............................................................................................................ 44
7.1 Routine maintenance ....................................................................................................... 44
AFV variable frequency power supply User Manual
7.2 Periodic maintenance ....................................................................................................... 45
Chapter VIII Troubleshooting and Solutions ............................................................................ 46
Appendix Guarantee Card ............................................................................................................. 48
AFV variable frequency power supply User Manual
Chapter I Product Introduction 1
Chapter I Product Introduction
AFV series power supply is a programmable power supply for grid simulation. By virtue of advanced SPWM technology and direct digital frequency synthesis (DDS) waveform technology, the power supply has stable output frequency and good continuity. AFV series power supply not only can provide continuous, pure and stable sinusoidal voltage, but also can achieve local control and remote control by the user’s PC for the power supply system through internal control and communication modules. At the same time, the internal electronic circuit can quickly detect over current, overload, overvoltage and output short circuit, automatically protect and cut off the output, and send out an alarm. The integrative laminated busbar technology and modular configuration are applied in the power supply inverter unit to improve reliability and stability. The touch screen display and control are utilized for easier operation.
The main performance characteristics of AFV series variable frequency power supply are as
follows:
By virtue of advanced SPWM technology and direct digital frequency synthesis (DDS)
waveform technology are used, the power supply has stable output frequency and good continuity;
The patented inner loop energy-saving test design is used to save the energy consumption; High precision settings and output; Comprehensive and stable protection, perfect self-diagnostic maintenance function and
higher system reliability;
The laminated busbar structure is used to effectively reduce the inductance of the inverter
circuit and improve the reliability of the inverter;
Intelligent fan speed regulation control is used with built-in dust filter to achieve efficient
heat dissipation and effective protection function under harsh environment;
Communication interface: Communication way RS485 (standard configuration) and
Ethernet (optional configuration);
Running event recording function is provided, and the number of records may be up to 255.
AFV variable frequency power supply User Manual
Chapter II Working Principle 2
Chapter II Working Principle
2.1 Functional block diagram of complete machine
All functional units of AFV series variable frequency power supply control system from input
to output according to the functional sequence are shown in Fig. 2-1.
Fig. 2-1 Functional block diagram of complete machine
AFV variable frequency power supply User Manual
Chapter II Working Principle 3
2.2 Description of functional block diagram
1) input: Connect from power supply endpoint to the input terminal disk of the equipment.
2) Input air switch: Control the commercial power input equipment.
3) Input filter: Input inductor and capacitor filter.
4) Rectifier filter: Convert the input alternating current into direct current.
5) Soft start: DC capacitor is charged slowly to reduce the impulse current.
6) Inverter circuit: Convert the direct current into PWM waveform.
7) Transformer filter: Boost the output voltage of IGBT and output the voltage after LC filter.
8) Output: The output voltage is transferred to the output terminal disk (or output copper bar) through the contactor.
9) Lightning protection device: Overvoltage protection, lightning protection, restraining surge
current, absorbing spike pulse, etc.
10) Voltage sampling: Input voltage sampling conditioning circuit.
11) SCR drive: Drive control circuit of soft start SCR.
12) IGBT drive: Amplify PWM signals to drive IGBT power components.
13) Voltage feedback: Steadily output voltage amplitude.
14) Voltage/current sampling circuit: Sampling conditioning circuit of output voltage and
current.
15) Power supply: Power supply of all PCB.
16) Main control circuit: The processing of all input and output signals.
17) Display: Touch screen display.
18) EPO: Emergency stop signal.
19) FUSE detection: Transmit the FUSE power-off signal to the control circuit for trip
protection.
20) Over-temperature detection: Transmit the over-temperature signal to the control circuit for
trip protection.
2.3 Constitution of main control circuit
The main control circuit is mainly divided into the three parts, namely protection sampling module, main control module and display control module. The relationships between these three parts are shown in Fig. 2-2.
Protection sampling
module
Main control module
Fig. 2-2 Block diagram of control parts
AFV variable frequency power supply User Manual
Display control
module
Chapter III Transportation and Installation
3.1 Transportation precautions
Chapter III Transportation and Installation 4
Fig. 3-1 Schematic diagram of transportation
Because the equipment is heavy, the lifting operations need to be slow during the transportation of the forklift, so as to prevent damaging the equipment itself or the surroundings. During the transportation that the equipment needs to be fixed firmly to prevent the equipment from sliding or dumping due to vehicle bumps. Although the shockproof packaging was design in, it is recommended that more cautious should be taken in consideration in case of driving on bumpy roads.
3.2 Unpacking inspection
When open the wooden boxes which contain the equipment, pay extra attention on handling
it due to heavy weight consideration. Avoid dropping or dumping occurs.
Before turn on the equipment check the equipment condition if any damage was found. You
should inform service staff of our company to take proper treatment.
Check the accessories according to the delivery accessory list. If any accessories are missed,
please contact the customer service.
AFV variable frequency power supply User Manual
Chapter III Transportation and Installation 5
3.3 Installation environment requirements
When selecting the installation environment, the following matters should be followed:
1) Install the equipments in indoor and keep the environment air flow. Try to keep the equipment air inlet/outlet free of dust;
2) The ground on which the equipment is installed should have sufficient strength and flatness, and the equipment shall not shake after the installation is in place;
3) The equipment adopts incoming line and outgoing line. Therefore, it is recommended to arrange these lines and cables connected to the external from the cable trenches, so as to facilitate the installation and maintenance;
4) Where the equipment placed should give sufficient space to allow the heat which produced by the equipment to radiate. (see Fig. 3-2) At the same time, do not cover the air inlet of the front panel, for allowing heat to radiate;
5) Do not use the equipment in the environment with dust, volatile gases, too high saline matter or corrosive substances, because this may affect the product life;
6) Do not place the equipment in the environment with too high temperature or humidity; and away from water, flammable gases, corrosive or heat sources and avoid direct sunlight;
7) Use correct power distribution way to guarantee the safety of the equipment and users
equipment.
Fig. 3-2 Schematic diagram of bottom of fixing device
AFV variable frequency power supply User Manual
Chapter III Transportation and Installation 6
3.4 Description of cable connection
The cable connection of the main circuit is as follows:
3.4.1 Single-phase input and single-phase output connection terminal Input connection terminal is Copper bar as shown 3-3(b),while the machine capacity is greater
than 20k;
Fig. 3-3-(a)
Fig. 3-3-(b)
Fig. 3-3 Single phase input and single phase output connection terminal
3.4.2 Three-phase input and single-phase output connection terminal Output connection terminal is Copper bar as shown 3-5(b),while the machine capacity is greater
than 15k; Input and Output connection terminal are Copper bar as shown 3-5(c),while the machine capacity is greater than 60k;
Fig. 3-4-(a)
AFV variable frequency power supply User Manual
Fig. 3-4-(b)
Chapter III Transportation and Installation 7
Fig. 3-4-(c)
3.4.3 Three-phase input and three-phase output connection terminal Input and Output connection terminal are Copper bar as shown 3-5(b),while the machine
capacity is greater than 60k;
Fig. 3-5-(a)
Fig. 3-5-(b)
Fig. 3-5 Schematic diagram of wiring terminal
AFV variable frequency power supply User Manual
Chapter III Transportation and Installation 8
Before installing the equipment, all the switches need to be disconnected. The circuit cables
should be connected properly according to the above diagram.
3.5 Cable wiring
1) Use the voltmeter to confirm whether there is no voltage output in the distribution lines;
2) Confirm whether all the switches of the variable frequency power supply are in the “OFF”
position;
3) The input and output cables can be selected according to the cables recommended in Tables
3-1 ;
Table 3-1 Input table of distribution cables
(a) Input high voltage
Input:△ 380V,400V,415V,480V
model Input current (A)
AFV-11008 AFV-11010 AFV-11015 AFV-11020 AFV-11030 AFV-31010 AFV-31015 AFV-31030 AFV-31045 AFV-31060 AFV-31080 AFV-31100 AFV-31120 AFV-33010 AFV-33015 AFV-33030 AFV-33045 AFV-33060 AFV-33080 AFV-33100 AFV-33120 AFV-33160
55.9
64.6
96.9
129.1
193.8 22 33
66A
99
132 197 246 296
22 33 66 99
132 197 246 296
394.7
Input live wire (mm2)
A B C
ground wire (mm2)
10mm2 10mm2 16mm2 16mm2 25mm2 16mm2 35mm2 16mm2 70mm2 35mm2
2
2.5mm
2.5mm2 2.5mm2 2.5mm2 4 mm2 4 mm2 4 mm2 4 mm2 16mm2 16mm2 16mm2 16mm2 25mm2 25mm2 25mm2 16mm2 35mm2 35mm2 35mm2 16mm2 70mm2 70mm2 70mm2 35mm8 95mm2 95mm2 95mm2 50mm9
2
120mm
2.5mm
120mm2 120mm2 70mm10
2
2.5mm2 2.5mm2 2.5mm2 4 mm2 4 mm2 4 mm2 4 mm2 16mm2 16mm2 16mm2 16mm2 25mm2 25mm2 25mm2 16mm2 35mm2 35mm2 35mm2 16mm2 70mm2 70mm2 70mm2 35mm16 95mm2 95mm2 95mm2 50mm17
2
120mm
70mm2*2 70mm2*2 70mm2*2
120mm2 120mm2 70mm18
70mm19
AFV variable frequency power supply User Manual
(b) Input low voltage
Input:△ 200V,208V
Chapter III Transportation and Installation 9
model Input current (A)
AFV-11008 AFV-11010 AFV-11015 AFV-11020 AFV-11030 AFV-31010 AFV-31015 AFV-31030 AFV-33010 AFV-33015 AFV-33030
101.0
126.3
189.4
252.6
378.9
42.1
63.1
126.3
42.1
63.1
126.3
Table 3-2 Output table of distribution cables
model
Output
current (A)
Input live wire (mm2)
A B C
ground wire (mm2)
25mm2 16mm2 35mm2 16mm2 70mm2 35mm2 95mm2 50mm2
70mm2*2
70mm2
6mm2 6mm2 6mm2 6mm2 16mm2 16mm2 16mm2 16mm2 35mm2 35mm2 35mm2 16mm2
6mm2 6mm2 6mm2 6mm2 16mm2 16mm2 16mm2 16mm2 35mm2 35mm2 35mm2 16mm2
Output live wire (mm2)
U V W
zero line
(mm2)
ground wire
(mm2)
AFV-11008
AFV-11010
AFV-11015
AFV-11020
AFV-11030
AFV-31010
AFV-31015
AFV-31030
AFV-31045
AFV-31060
AFV-31080
AFV-31100
AFV-31120
HI:33.3A LO:66.7A HI:41.7A LO:83.3A HI:62.5A
LO:125A
HI:83.3A
LO:166.7A
HI:125A
LO:250A HI:41.7A LO:83.3A HI:62.5A
LO:125A
HI:125A
LO:250A
HI:187.5A
LO:375A
HI:250A
LO:500A
HI:333.3A LO:666.7A HI:416.7A LO:833.3A
HI:500A LO:1000A
16mm2 16mm2 16mm2
16mm2 16mm2 16mm2
35mm2 35mm2 16mm2
50mm2 50mm2 25mm2
95mm2 95mm2 50mm2
16mm2 16mm2 16mm2
35mm2 35mm2 16mm2
95mm2 95mm2 50mm2
70mm2*2
95mm2*2
70mm2*3
70mm2*4
95mm2*4
70mm2*2 70mm2
95mm2*2 95mm2
70mm2*3 70mm2*2
70mm2*4 70mm2*2
95mm2*4 95mm2*2
AFV variable frequency power supply User Manual
Chapter III Transportation and Installation 10
AFV-33010
AFV-33015
AFV-33030
AFV-33045
AFV-33060
AFV-33080
AFV-33100
AFV-33120
AFV-33160
HI:13.9A LO:27.8A HI:20.8A LO:41.7A HI:41.7A LO:83.3A HI:62.5A
LO:125A HI:83.3A
LO:166.7A HI:111.1A LO:222.2A HI:138.9A LO:277.8A HI:166.7A LO:333.3A HI:222.2A LO:444.4A
4mm2 4mm2 4mm2 4mm2 4mm2
10mm2 10mm2 10mm2 10mm2 10mm2
16mm2 16mm2 16mm2 16mm2 16mm2
35mm2 35mm2 35mm2 35mm2 16mm2
50mm2 50mm2 50mm2 50mm2 25mm2
70mm2 70mm2 70mm2 70mm2 35mm2
120mm2 120mm
150mm2 150mm
70mm2*2 70mm2*2 70mm2*2
2
120mm2 120mm2 60mm2
2
150mm2 150mm2 75mm2
70mm2*2 70mm2
The reference cables recommended in the above-mentioned tables are multi-core flexible copper cables, and the user can select different cables according to the input and output current conditions by themselves. When the length of the input or output lines exceed 20 meters, it is recommended that the wire diameter of the cable should be doubled.
4) Properly connect the input distribution lines to the corresponding wiring terminals at the input
terminal of the equipment successively, and connect the output load lines to the corresponding wiring terminals at the output terminal of the equipment.
AFV variable frequency power supply User Manual
Chapter IV Product Specifications
4.1 Technical specifications
1Single–phase input/Single-phase output specification
Chapter IV Product Specifications 11
Model
Output capacity (kVA)
Phase number Voltage Voltage Range
AC input
AC output
Complete
machine
performance
Display
Environment
Frequency range
Power factor (resistive)
Phase number Waveform Standard sinusoidal wave
Voltage
Frequency Frequency
stability rate Power voltage regulation Load regulation Waveform distortion (THD)
Efficiency Reaction time ≤2ms
Protection device
Display interface
Voltage Current Frequency Real power Apparent
power Power factor Insulation
reactance Withstand voltage insulation Cooling device
Working temperature Relative humidity
Altitude Below 1,500m
Low High
AFV-11008 AFV-11010 AFV-11015 AFV-11020 AFV-11030
8 10 15 20 30
Single phase
115V/200V,120V/208V,220V/380V,230V/400V,240V/415V,277V/480V
±15﹪
47Hz-63Hz
0.9
Single phase
0V-150.0V(L-N) 0V-300.0V(L-N)
45Hz-65Hz(option45-500Hz)
≤0.01%
≤1%
±1% (linear load)
≤2% (linear load)
≥90%
Input no-fuse switch, output over/under voltage, over current, overload,
input over/under voltage, reverse current protection, over temperature &
short circuit, conduct fast protection and lock fault, display fault;
Touch screen
0.2V+0.1%FS resolution:0.1V
0.2A+0.1%FS resolution:0.1A
0.01Hz+0.01%FS resolution:0.01Hz
0.2kW+0.1%F, Resolution:0.1kW
0.2kVA+0.1%FS, Resolution:0.1kVA
±0.01 resolution:0.01 Hz
≥DC500V 10MΩ
AC 1800V 10mA/ 1 minute
Fan cooling
0°C-45°C
0-90% (non-condensing state)
AFV variable frequency power supply User Manual
2Three –phase input/Single-phase output specification
Chapter IV Product Specifications 12
Model
Output capacity (kVA)
Phase number
Voltage
AC input
AC output
Voltage range
Frequency range
Power factor (resistive)
Phase number
Waveform Standard sinusoidal wave
Voltage
Frequency
Low
High
AFV­31010
10 15 30 45 60 80 100 120
AFV­31015
AFV­31030
AFV­31045
3φ3W+G
AFV­31060
AFV­31080
AFV­31100
115V/200V,120V/208V,
220V/380V,230V/400V,
240V/415V,277V/480V
0.9 0.85
0V-150.0V(L-N)
0V-300.0V(L-N)
45Hz-65Hz(option 45-500Hz)
230V/400V,240V/415V,277V/480V
±15﹪
47Hz-63Hz
3φ4W+G
AFV­31120
Complete
machine
performance
Display
Frequency stability rate
Power voltage regulation
Load regulation
Waveform distortion (THD)
Efficiency
Reaction time ≤2ms
Protection device
Display interface
Voltage
Current
Frequency
Real power
For input no-fuse switch, output over/under voltage, over current, overload,
input over/under voltage, reverse current protection, over temperature & short
circuit, conduct fast protection and lock fault, display fault;
≥90% ≥85%
0.2V+0.1%FS resolution:0.1V
0.2A+0.1%FS resolution:0.1A
0.01Hz+0.01%FS resolution:0.01Hz
0.2kW+0.1%F, Resolution:0.1kW
≤0.01%
≤1%
±1% (linear load)
≤2% (linear load)
Touch screen
Apparent power
Power factor
AFV variable frequency power supply User Manual
0.2kVA+0.1%FS, Resolution:0.1kVA
±0.01 resolution:0.01 Hz
Environment
Chapter IV Product Specifications 13
Insulation reactance
≥DC500V 10MΩ
Withstand voltage
AC 1800V 10mA/ 1 minute
insulation Cooling device Fan cooling
Working temperature
Relative humidity
0-90% (non-condensing state)
0°C-45°C
Altitude Below 1,500m
AFV variable frequency power supply User Manual
3Three –phase input/Three-phase output specification
Chapter IV Product Specifications 14
Model
Output capacity (kVA)
Phase number
Voltage
Voltage range
AC input
Frequency range
Power factor (resistive)
Phase number
Waveform Standard sinusoidal wave
AC output
Voltage
Frequency
Low
High
AFV­33010
AFV­33015
AFV­33030
AFV­33045
AFV­33060
AFV­33080
AFV­33100
AFV­33120
AFV­33160
10 15 30 45 60 80 100 120 160
3φ3W+G
115V/200V,120V/208V,
220V/380V,230V/400V, 240V/415V,277V/480V
230V/400V,240V/415V,277V/480V
±15﹪
47Hz-63Hz
0.9 0.85
3φ4W+G
0V-150.0V(L-N)
0V-300.0V(L-N)
45Hz-65Hz(option45-500Hz)
Complete
machine
performan
ce
Display
Frequency stability rate
Power voltage regulation
Load regulation
Waveform distortion (THD)
Efficiency
≥90% ≥85%
≤0.01%
≤1%
±1% (linear load)
≤2% (linear load)
Reaction time ≤2ms
Protection device
Display interface
Voltage
Current
Frequency
Real power
For input no-fuse switch, output over/under voltage, over current, overload, input over/under
voltage, reverse current protection, over temperature & short circuit, conduct fast protection
and lock fault, display fault;
Touch screen
0.2V+0.1%FS resolution:0.1V
0.2A+0.1%FS resolution:0.1A
0.01Hz+0.01%FS resolution:0.01Hz
0.2kW+0.1%F, Resolution:0.1kW
Apparent power
Power factor
Remote interface
Environm
ent
Insulation reactance
AFV variable frequency power supply User Manual
0.2kVA+0.1%FS, Resolution:0.1kVA
±0.01 resolution:0.01 Hz
RS-485(standard);RS-232/GPIB(optional)
≥DC500V 10MΩ
Chapter IV Product Specifications 15
Withstand voltage
AC 1800V 10mA/ 1 minute
insulation Cooling device Fan cooling
Working temperature
Relative humidity
0-90% (non-condensing state)
0°C-45°C
Altitude Below 1,500m
AFV variable frequency power supply User Manual
Chapter IV Product Specifications 16
4.2 Shape structure
AFV series products correspond to the corresponding size according to the capacity.
Table 4-1 Equipment size
Model
AFV-11008,AFV-11010,AFV-11015, AFV-31010 AFV-11020,AFV-11030 AFV-31015, AFV-31030 AFV-33010,AFV-33015,AFV-33030
AFV-31045,AFV-31060, AFV-33045, AFV-33060
AFV-31080 AFV-33080,AFV-33100 AFV-31100, AFV-31120
AFV-33120,AFV-33160
Corresponding size
W (mm) D (mm) H (mm) Wheeled
600 850 945
600 850 1340
800 860 1545
1050 970 1800
1150
1240 1900
Fig. 4-1 Axonometric view of complete machine appearance
AFV variable frequency power supply User Manual
③ ②
Chapter V Operation 17
AFV variable frequency power supply User Manual
Chapter V Operation 18
Fig. 4-2 Description of complete equipment appearance
Touch screen.
Emergency stop button.
Input switch.
Input terminal;
Output terminal.
AFV variable frequency power supply User Manual
Chapter V Operation 19
Chapter V Operation
5.1 Initial power-up of system
The input and output wirings should be properly connected according to the input and output connection way in Section 3.3. If the system is started, the main engine fan will start to operate, the panel display screen is on and the main interface is entered, indicating that the start-up is normal and the parameter setting can be conducted for the machine.
Note: If there is an external load, the load switch should be disconnected first, and the input
switch should be connected (it needs to confirm whether the electric power of the input terminal
row is normal before the input switch is connected).
Users can enter the application interface by clicking “Application”. Users can set the output voltage and frequency value, press the [Operation] key after the setting is completed, and then click “Meas.” to display the actual output each phase voltage, current, frequency, etc.
5.2 Menu description
Application
The application interface displays each phase voltage, current and frequency of output terminal of the AFV(equipment).
System
In the application interface, time setting and system maintenance can be setting by requirement.
Event
Record the historical work information of the equipment.
AFV variable frequency power supply User Manual
Chapter V Operation 20
5.3 Parameter setting
Parameters set up correctly is basic requirement for running the AFV(equipment) smoothly. Detailed user modes are described as follow.
5.3.1 Start-up
When the AFV(equipment) power on, the screen will show company LOGO as shown in Fig. 5-1.
Fig. 5-1 Start-up interface
The initialization interface is shown in Fig. 5-2.
Fig. 5-2 Initialization interface
AFV variable frequency power supply User Manual
Chapter V Operation 21
5.3.2 User mode
Enter the main menu of the user mode. The interface display is shown in Fig. 5-3.
Fig. 5-3 Main menu of user mode
APP--Application: Enter the operation setting interface;
SYSTEM: Enter the time setting and system maintenance interface;
EVENT: Enter the equipment work record information table interface.
AFV variable frequency power supply User Manual
Chapter V Operation 22
5.4 Application interface
In the application interface, users can conduct the operations of the general mode, Step mode, Gradual mode and Measurement mode of the equipment.
Note: All the product information in the operation interface of the equipment should comply
with the model specifications of the actual equipment.
5.4.1 General mode
(a) Three-phase output setting interface
(b) Single-phase output setting interface
Fig. 5-4 Setting interface of general mode
Limit Curr.:Setting different current protection value. Individually Adjust:Individual Adjust Volt. When this option is chosen, each phase can
be set up independently.
【Phase Setting:When this option is chosen, the phase angle can be set up.
AFV variable frequency power supply User Manual
Chapter V Operation 23
Note:Above function is optional.
【U Volt./V Volt./W Volt.-- U-phase voltage/ V-phase voltage/ W-phase voltage:
The following three ways can be used for setting voltage at all phases:
a) Directly input the voltage value in . Click the box to pop up the keyboard, and
then input the voltage value;
b) In the box of touch left and right for adjustment; c) Click & to conduct the setting. The variation unit is 0.1.
Note:If the【Individual Adjust Volt.】 is not picked,setting up a value on a specific single
phase, the value on the same field for the other two phases will be changed to the same value as the one you just entered simultaneously.
Freq:Frequency: The setting way is same as that of voltage;
LOW: The equipment starts to output the low voltage after clicking it;
HIGH: The equipment starts to output the high voltage after clicking it;
RUN: The equipment starts the output according to the set value after clicking it;
STOP: The equipment stops the output after clicking it;
RESET: The equipment restores the initial state after clicking it;
: AC indicator light displays the operational state of the AC output of the equipment:
Red represents that the mode of the equipment is in the stop state, while green represents that the mode of the equipment is running.
5.4.2 Step mode
(a) Step mode setting interface
AFV variable frequency power supply User Manual
Chapter V Operation 24
(b) Step mode effect interface
SETTING: Download the set parameters;
RUN: The equipment starts to run the step mode after clicking it;
RESET: The equipment restores the initial state after clicking it;
STOP: The equipment stops running the step mode after clicking it;
& : Switch over step setting interface and step effect interface.
5.4.3 Gradual mode
(a) Gradual mode setting interface
AFV variable frequency power supply User Manual
(b) Gradual mode effect interface
【SETTING: Download the set parameters;
Chapter V Operation 25
RUN: The equipment starts to run the gradual mode after clicking it;
RESET: The equipment restores the initial state after clicking it;
STOP: The equipment stops running the gradual mode after clicking it;
& : Switch over gradual change setting interface and gradual change effect interface.
5.4.4 Measurement mode
(a) Three-phase output setting interface
AFV variable frequency power supply User Manual
(b) Single -phase output setting interface
Fig. 5-7 Real-time acquisition interface
MEAS.--Measurement: Real-time acquisition;
Chapter V Operation 26
STOP: The equipment stops the output after clicking it;
RESET: The equipment restores the initial state after clicking it;
Fig. 5-8 Fault alarm interface
RESET: Fault reset;
OK: Click it to return to the real-time acquisition interface.
5.4.5 System maintemance interface
AFV variable frequency power supply User Manual
【Date: Setting the date;
Chapter V Operation 27
Fig. 5-9 System maintemance interface
Time: Setting the time
System Setting: The system configuration is only for the users to view, and it cannot be
modified. If it needs to modify the system configuration, please contact the manufacturer and customer service personnel;
Addr】:Setting the communication address, default value is 2;
COMM Type: Select the communication interface (or protocol), default is RS485;
Phase Setting:Option function ,Click it to Enter the Phase setting interface.
Fig. 5-10 Phase setting interface
5.4.6 System log
System log interface is shown in Fig. 5-11.
AFV variable frequency power supply User Manual
Chapter V Operation 28
Fig. 5-11 System log setting interface
Previous/Next: Browse the historical event contents; Clear: Empty the system log table; Back: Return to the previous menu.
AFV variable frequency power supply User Manual
Chapter VI Operation 29
Chapter VI Remote Control
6.1 Communication interface
RS-485 and RS-232 are standard communication interfaces for this series of machine. RS-232
supports SCPI command and RS-485 supports MODBUS RTU command. The RS-232 and RS-485 belong to the same interface with different pins and need to be configured in factory. LAN, USB, GPIB options apply different converters and connect to the RS-232/485 port.
6.1.1 Interface of RS-232/485
Open the front cover, RS-232/RS-485 interface is located in the back of touch screen shown as
below figure:
a) Back of the touch screen computer
RS-485 interface is female connector, and has nine pins
Pin
1 Rx-(B) RS 485 B 5 GND Signal Gnd 6 Rx+(A) RS 485 A
b) Pin definition of this RS-485interface
RS-232 interface is female connector, and has nine pins
Pin
2 RXD TXD 3 TXD RXD 5 GND Signal Gnd
c) Pin definition of this RS-232 interface
Fig. 6-1 Pictures of RS485 connection
6.1.2 Indication of remote control on touch screen
Signal PC
Signal PC
While the communication interface of this machine is successfully linked with other computing equipment, there will be an indication text (“under remote control …”) shown on the
AFV variable frequency power supply User Manual
screen, as below figure:
Chapter VI Operation 30
(a) Three-phase output setting interface
(b) Single-phase output setting interface
Fig. 6-2 “Under remote control”… shown on screen
6.2 Operations of remote control on PC
6.2.1 Software installation
Open the software CD package, install the software by executing the setup.exe in the CD, as shown in the below picture.
AFV variable frequency power supply User Manual
Fig. 6-3 Software installatin kit on the CD
Chapter VI Operation 31
Operating system supported: Windows XPWIN7WIN8.
Fig. 6-4 Procedures of the installation: 1st step.
AFV variable frequency power supply User Manual
Fig. 6-5 Procedures of the installation: 2nd step.
Chapter VI Operation 32
Choose the installation folder, recommend installing on D:\ disk (do not install on system disk).
Fig. 6-6 Procedures of the installation: 3rd step.
AFV variable frequency power supply User Manual
Chapter VI Operation 33
Fig. 6-7 Shortcut on the PC desktop after successful installation
6.2.2 Operations on PC
Double click the shortcut (as shown in fig. 6-7) on the desktop, then enter the communication
setting UI (as shown in fig. 6-8). Before communication interface are successfully linked, the operation button Read Dev. Info.is grayed (and can not operate).
6-8 Communication UI
Dev AddrAddress of this machine while in communicationfor this series (AFV) of
machines, default value is 2
Comm mode: Select the communication interface (or protocol), default is RS485
Comm Serial number of the com port to be selected
LinkClick on this button after setting up all the required parameters for that specific
communication mode, physical link is created. Status of this action will be shown on the blank area below this button.
Other communication parameter is fixed: 9600bpsdatabit8 stopbit1checkNone
After a successful connection, button Read Dev. Info.lift ashing, clickRead Dev. Info.
(communication right) enter such as 6-9 shown in the device information display interface:
AFV variable frequency power supply User Manual
Chapter VI Operation 34
6-9 System Config UI
Users can view the system configuration information read from the power supply equipment is consistent with the parameters of the actual product, if it does not meet, please contact customer service staff to resolve.
After system configuration parameters confirm, click Enter button to enter the main
interface of the software function, as shown in figure 6-10.
6.2.3 Main interface
AFV variable frequency power supply User Manual
Chapter VI Operation 35
(a) Three-phase output setting interface
(b) Single-phase output setting interface
Fig. 6-10 Main interface of upper computer
AFV variable frequency power supply User Manual
Chapter VI Operation 36
In the above menu
New】:Create a new file for system data storage
Open】:Open an existing system data file
(1) Save】:Store all the data that users have created into the current system data file;In the
menu of “Basic App”, click onStep】,and get into all the options and actions in “step”
mode.
(a) Menu of “step change” – Parameters settings
AFV variable frequency power supply User Manual
Chapter VI Operation 37
(b) Menu of “step” – Results preview
Fig. 6-11 Menu of “step” mode in remote control
【Cycle parameter】:The machine will start the output from the first procedure set in “Start
No.” to the last procedure set in “End No.”, and execute the whole procedures continuously for the number of iteration of the parameter set in this field. The maximum number of procedures that can be stored is 24. The maximum number of iteration is 255.
Click onPreviewcan preview the procedures (once executed) in time domain
Setting】:Save all the parameters in the touch screen into the control unit . User has to
execute this action before running the whole “Step” procedures
All the data the users enter in this menu will be saved, once any of the action buttons of
Preview, Setting or Runis clicked.
indicator Red light indicates that the machine is in idle state (output stopped),
while green light indicates the machine is in normal working state (output activated).
Note:If none of the above 3 action buttons has been clicked, all the data the user has entered
in this session will be lost once this menu is exited.
【RunOnce clicked, the machine will start the output immediately as above procedures
setup
Stop Once clickedthe machine will stop the output immediately
ResetOnce clicked, the machine will release itself from the “alarm” state.
AFV variable frequency power supply User Manual
Chapter VI Operation 38
(2) In the menu of “Basic App”, click on 【Gradual】will bring you to the menu of “Gradual” mode.
(a) Menu of “Gradual” – Parameters settings
(b) Menu of “Gradual” – Results preview
Fig. 6-12 Menu of “Gradual” mode under remote control
【Cycle parameter】:The machine will start the output from the first procedure set in “Start
AFV variable frequency power supply User Manual
Chapter VI Operation 39
No.” to the last procedure set in “End No.”, and execute the whole procedures continuously for the number of iteration of the parameter set in this field. The maximum number of procedures that can be stored is 12. The maximum number of iteration is 255.
Click onPreviewcan preview the procedures (once executed) in time domain.
Setting】:Save all the parameters in the touch screen into the control unit inside the
machine, the user have to execute this action before running the whole “Gradual” procedures.
All the data the users enter in this menu will be saved, once any of the action buttons of
Preview, Setting or Runis clicked.
indicator Red light indicates that the machine is in idle state (output stopped),
while green light indicates the machine is in normal working state (output activated).
Note:If none of the above 3 action buttons has been clicked, all the data the user has entered
in this session will be lost once this menu is exited.
【RunOnce this button is clicked, the machine will start the output immediately as above
procedures setup
Stop Once clickedthe machine will stop the output immediately
ResetOnce clicked, the machine will release itself from the “alarm” state
(3) Click onMeasurewill enter the menu of “Measure”.
(a) Three-phase output setting interface
AFV variable frequency power supply User Manual
(b) Single-phase setting interface
Chapter VI Operation 40
Fig. 6-13 General Mode
(a) Three-phase output setting interface
AFV variable frequency power supply User Manual
(b) Single-phase setting interface
Fig. 6-13 Menu of “Measure” under remote control
Chapter VI Operation 41
“Interval” : The time interval fixed the default value:1000ms. “Record Logs”: Save all the data measured in this mode into a log file.The file
path:C://ACPower.
“Measure” collection and “Stop” collection can be clicked and executed any time. Input measure data:R/S/T phase data is measure on anytime. Output measure data:U/V/W phase data is measure when the device running.
Note: these items can be selected only under the collection is ongoing.
(4) Click on the sub-menu ofLanguage Setting, there are 3 kinds of languages can be chosen.
Click on the language you want, and all the user-interface in this software will be changed to that language.
AFV variable frequency power supply User Manual
Chapter VI Operation 42
(a) Three-phase output setting interface
(b) Single-phase setting interface
Fig. 6-14 Language selection under rermote control
(5) Click on Apply Setting will enter the menu of “Phase Angle and Max Curr.
AFV variable frequency power supply User Manual
Setting”.(Optional function)
Chapter VI Operation 43
(a) Phase Angle and Max Current optioning interface
(b) Phase Angle setting interface
(c) Max Current setting interface
Fig. 6-15 Phase Angle and Max Current setting interface
AFV variable frequency power supply User Manual
Chapter VII Maintenance 44
Chapter VII Maintenance
Extreme temperature, high humidity, heavy dust, chemicals pollution and physical vibration all could impose negative impacts on the life and reliability of this machine. Nevertheless, the nature aging of all the electrical and mechanical components would further cause it to be more vulnerable to all kinds of faults. Therefore, routine and periodic maintenance are necessary and key to the reliability of this machine in the long run.
Only authorized and trained technical professionals are allowed to carry out the
maintenance on this machine.
7.1 Routine maintenance
First, the daily operating environment must comply with the requirements stated in this user manual. Routine inspection on the environment and the machine should be checked on a regular basis. All the environment data, the operating status and the parameters set in the machine should be recorded as well. It is best to have a detailed and accurate “machine usage log file” for all time reference and maintenance.
Abnormal phenomenon on the machine can be detected by the routine inspection and maintenance. Once observed, the users should try to identify the root cause first and remove the problem immediately. Call our customer service if you are not able to identify the cause, or not able to remove the problem. The earlier the problem can be removed, the longer the life of the machine. Checking items in the routine maintenance are listed in Table 7-1.
Table 7-1 List of checking items on routine maintenance
Inspection details
Object
to
check
Checking items
When
to
Methods to check
Criteria
check
(1). Temperature and humidity
Environ
-ment
(2). Dust, moisture and
water leakage (drop on
the machine). (3). Abnormal Chemical vapor
AFV variable frequency power supply User Manual
Anytime
(1).Thermometer, Hygrometer (2). Visual inspection (3). Visual inspection and smell
(1). Ambient temperature must < 45˚C, or maximum load need to be de-rated. Humidity should be comply with the spec requirements. (2). Little dust, no condensing, no water drop on the machine. (3). No abnormal smell, no abnormal color in the air.
Visual inspection, sense of moving.
Thermometer Sense of hearing
Voltmeter Voltmeter Ammeter
Thermometer
This
machine
Input /
Output
status
Shock, vibration Heat dissipation Acoustic noise
Input voltage Output voltage Output current
Temperature inside the machine
Anytime
Anytime
7.2 Periodic maintenance
Depending on the usage of this machine and the environment where it worksa periodic
maintenance can be carried out once every 3~6 months.
Chapter VII Maintenance 45
No shock, no vibration。 ⑵Fan operating: check to see if speed
and air flow volume OK or not. Measure the temperature on the surface of the enclosure; they should not have more than 30˚C temperature rise.
No abnormal acoustic noise.。
within the spec limit within the spec limit within the spec limit
Temperature rise < 45˚C
Maintenance task
Screen filter for the air inlet should be detached and washed clean.
Note:Open the front door of the enclosure to detach and re-install the screen filter, there is a
cover in front of the screen filter, it needs to be removed before the filter can be accessed.
AFV variable frequency power supply User Manual
Chapter VIII Troubleshooting and Solutions 46
Chapter VIII Troubleshooting and Solutions
Before seeking services, users can first do self-inspection and record fault phenomena in
details according to tips in this section. When you need to seek services, please contact the dealer.
Table 8-1 Alarm contents and solutions
Fault code
Err-01 U-phase IGBT1 overcurrent fault
Err-02 U-phase IGBT2 overcurrent fault
Err-03 U-phase IGBT3 overcurrent fault
Err-04 U-phase IGBT4 overcurrent fault
Err-05 V-phase IGBT1 overcurrent fault
Err-06 V-phase IGBT2 overcurrent fault
Err-07 V-phase IGBT3 overcurrent fault
Err-08 V-phase IGBT4 overcurrent fault
Err-09 W-phase IGBT1 overcurrent fault
Err-10 W-phase IGBT2 overcurrent fault
Err-11 W-phase IGBT3 overcurrent fault
Err-12 W-phase IGBT4 overcurrent fault
Err-13
Radiator over-temperature The fan works abnormally Check the fan
Fault type Possible causes of faults Solutions
U-phase IGBT is damaged Check and replace IGBT
U-phase IGBT is damaged Check and replace IGBT
U-phase IGBT is damaged Check and replace IGBT
U-phase IGBT is damaged Check and replace IGBT
V-phase IGBT is damaged Check and replace IGBT
V-phase IGBT is damaged Check and replace IGBT
V-phase IGBT is damaged Check and replace IGBT
V-phase IGBT is damaged Check and replace IGBT
W-phase IGBT is damaged Check and replace IGBT
W-phase IGBT is damaged Check and replace IGBT
W-phase IGBT is damaged Check and replace IGBT
W-phase IGBT is damaged Check and replace IGBT
Err-14
Err-15
Err-16
Err-19
Err-20
Err-21
Err-22
Err-23
Err-24
Err-25
Err-26
Err-27
Err-28
Err-29
Transformer over-temperature The fan works abnormally Check the fan
Emergency stop button
The emergency stop button is presses
Fuse 1 is broken The fuse blows out Check and replace the fuse
IGBT over-temperature 1 The fan works abnormally Check the fan
IGBT over-temperature 2 The fan works abnormally Check the fan
Input undervoltage fault The input voltage is too low
Input overvoltage fault The output voltage is too high Check the input voltage
DC voltage is too low The input voltage is too low Check the input voltage
DC voltage is too high The output voltage is too high
U overload U-phase overload Check the load
V overload V-phase overload Check the load
W overload W-phase overload Check the load
Output undervoltage fault The output voltage is too low Check the output voltage
Output overvoltage fault The output voltage is too high Check the output voltage
Check the emergency stop
button
Check the input voltage
Check the input voltage
AFV variable frequency power supply User Manual
Chapter Customer Service 47
Chapter Customer Service
Preen provides all kinds of technical service to its customers. Please first contact the sales representative from whom you acquire this machine for any questions or problems. If you not able to reach that sales representative, then you are welcome to contact the nearest branch office or our Suzhou central office for solid support. Our contact information are listed as follows
Telephone(+1) 949-988-7799
Support on the webwww.PreenPower.com
Customers may browse our website to seek technical information or on-line support.
Our website
http//www.PreenPower.com
Our Email for customers
E-mailsupport@acpower.net
Please refer to the provisions in the warranty contract for details of the maintenance tasks. We do provide our customers with various kinds of packages for paid service in which there are different levels of customization. These paid services includes “fast response on issues encountered”, “preventive maintenance” and “continuation of warranty after original warranty expires”. Contact the sales representative or the branch office for more detail
AFV variable frequency power supply User Manual
Appendix Guarantee Card 48
Appendix Guarantee Card
Quality
Service
Innovation
Warranty
For customer, _______________________________________________
Model: __________________________________ Serial Number: _____
Should this machine malfunction or fail due to material or manufacturing flaws within one year, AC Power Corp. (APC) will take full responsibility for the repairs. This warranty only holds if the machine has been operating for normal use and in the normal environment specified in the manual. APC reserves the right to charge the customer for the repairs if the defects are due to any cause other than material or manufacturing flaws, and/or if the defects are due to any cause resulting from operating in a severe environment (factors beyond the allowable limits).
The warranty begins on the date when this machine is installed and our sales representative signs this document; it is only valid when the machine has been installed correctly and while operated properly. No modifications on the structure or circuitry and no replacement of any components by unauthorized personnel are allowed under this warranty.
In case of machine malfunction or failure, please call our customer service for help first. Under some situations and directed by our company staffs, you may need to uninstall it, pack and wrap it up securely, and then send it back to us with a description of the problems encountered. We shall resolve your problems as soon as possible.
Please keep this warranty paper all the time even after it expires. We will only take a minimum charge for the repairs after the warranty’s expiration if you still hold this paper.
Thank you for choosing AC Power Corp.
AFV variable frequency power supply User Manual
Appendix Guarantee Card 49