Precision Digital Corporation Survivor PD662 Instruction Manual

PRECISION DIGITAL CORPORATION
233 South Street • Hopkinton MA 01748 USA Tel (800) 343-1001 • Fax (508) 655-8990
www.predig.com
Process Meter
NEMA 4X, IP66 Loop-Powered Field-Mount Process Meter
4-20 mA Input
0.6" (15.2 mm) 3½+ Digits LCD Display; -1999 to 2999
1.7 Volt Drop (3.7 Volt Drop with Backlight)
HART® Protocol Transparent
Loop-Powered Backlight Option
CSA Certified for -40 to 75°C (-40 to 167°F) Operation
Four Internal Buttons for Easy Field Scaling
Max/Min Display
Programmable noise filter
32-Point and Square Root Linearization Functions
Plastic NEMA 4X, IP66 Enclosure
Conformal Coated PCBs for Dust and Humidity Protection
One ½" Conduit Hole in Rear of Enclosure
Pipe & Panel Mounting Kits
Stainless Steel Tag Available
C US
PD662 General Purpose NEMA 4X, IP66 Loop-Powered Meter Instruction Manual
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Meter Instruction Manual
2
Disclaimer
The information contained in this document is subject to change without notice. Precision Digital makes no representations or warranties with respect to the contents hereof; and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose.
CAUTION: Read complete instructions prior to installation and operation of the meter.
WARNING: Risk of electric shock or personal injury
Warnings
This product is not recommended for life support applications or applications where malfunctioning could result in personal injury or property loss. Anyone using this product for such applications does so at his/her own risk. Precision Digital Corporation shall not be held liable for damages resulting from such improper use.
Cancer and Reproductive Harm www.P65Warnings.ca.gov. For California Proposition 65 details please visit our website www.predig.com
Limited Warranty
Precision Digital Corporation warrants this product against defects in material or workmanship for the specified period under “Specifications” from the date of shipment from the factory. Precision Digital’s liability under this limited warranty shall not exceed the purchase value, repair, or replacement of the defective unit.
Registered Trademarks
All trademarks mentioned in this document are the property of their respective owners.
© 2018 Precision Digital Corporation. All rights reserved.
www.predig.com
Introduction
The PD662 NEMA 4X, CSA Certified loop-powered meter is perfect for applications where a simple, inexpensive display is required and AC power is not available. The PD662 derives all its power from the 4-20 mA loop, including its optional backlight feature. It can be easily scaled in the field using four push buttons; with or without applying an actual calibration signal. The PD662’s display will read up to 2999; we call this 3½+ digits! The PD662 is housed in a rugged NEMA 4X enclosure and is provided with one ½" NPT pipe conduit hole.
Ordering information
Model
Options Installed
PD662-0L0-00*
None
PD662-0K0-00
Loop-Powered Backlight
* Quick Shipment Program product typically shipped within 2 working days
Accessories
Model
Description
PDA1024-01
24 VDC Power Supply for DIN Rail
PDA6624
Panel Mounting Kit
PDA6845
2" Pipe Mounting Kit
PDA-SSTAG
Stainless Steel Tag
!
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Instruction Manual
3
Table of Contents
INTRODUCTION ---------------------------- 2! ORDERING INFORMATION ------------- 2! SPECIFICATIONS -------------------------- 4!
General ------------------------------------------------------- 4! Input ----------------------------------------------------------- 4!
COMPLIANCE INFORMATION --------- 4!
Safety --------------------------------------------------------- 4! Electromagnetic Compatibility ----------------------- 5!
SAFETY INFORMATION ------------------ 5! INSTALLATION ----------------------------- 5!
Unpacking --------------------------------------------------- 5! Mounting ---------------------------------------------------- 5! PD662 Connections -------------------------------------- 6!
Connection & Wiring Diagrams --------------------- 6!
SETUP AND PROGRAMMING ---------- 6!
Front Panel Buttons ------------------------------------- 6! Setting Numeric Values -------------------------------- 7! Programming the Meter -------------------------------- 7! Main Menu -------------------------------------------------- 7!
Main Menu Display Functions & Messages ------ 8! Setting the Decimal Point (dP) ---------------------- 8! Scaling the Meter (SCL) ------------------------------- 8! Calibrating the Meter (Cal) --------------------------- 9! Recalibrating the Internal Calibration Reference (Ical) ------------------------------------------------------ 9!
Advanced Features Menu ------------------------------ 9!
Advanced Features Menu & Display Messages 9! Signal Input Conditioning Function (Fnc) ------- 10! Information Menu (info) --------------------------- 10! Input Signal Filter (FIL) ----------------------------- 10! Internal Calibration (ICal) -------------------------- 11!
OPERATION -------------------------------- 11!
Front Panel Buttons Operation -------------------- 11! Maximum & Minimum Readings (HI & LO) ----- 12! Reset Meter to Factory Defaults ------------------- 12! Factory Defaults & User Settings ----------------- 13!
MOUNTING DIMENSIONS ------------- 13! TROUBLESHOOTING ------------------- 14!
Troubleshooting Tips --------------------------------- 14!
QUICK USER INTERFACE REFERENCE GUIDE --------------------- 15! EU DECLARATION OF CONFORMITY ----------------------------- 17!
Table of Figures
Figure 1. PD662 Mounting Board Rear View .......... 6!
Figure 2. PD662 Input Connections without
Backlight ........................................................... 6!
Figure 3. PD662 Input Connections with
Backlight ........................................................... 6!
Figure 4. Case Dimensions – Front View ............. 13!
Figure 5. Case Dimensions – Side View ............... 13!
Figure 6. Case Dimensions – Bottom View .......... 13!
Figure 7. PDA6845 Pipe Mounting Kit .................. 14!
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Meter Instruction Manual
4
Specifications
Except where noted all specifications apply to operation at +25
General
DISPLAY
0.6" (15.2 mm) LCD, 3½+ digits;
-1999 to 2999
DISPLAY UPDATE RATE
2 Updates/Second
OVERRANGE
Display flashes 2999
UNDERRANGE
Display flashes -1999
PROGRAMMING METHOD
Four internal pushbuttons
NOISE FILTER
Programmable HI, LO, or
OFF
RECALIBRATION
Recalibration is recommended at least every 12 months.
MAX/MIN DISPLAY
Max/Min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
NON-VOLATILE MEMORY
All programmed settings are stored in non­volatile memory for a minimum of ten years if power is lost.
NORMAL MODE REJECTION
64 dB at 50/60 Hz
ENVIRONMENTAL
Operating temperature for CSA certification:
-40 to 75°C Functional temperature range: -40 to 85°C Storage temperature range: -40 to 85°C Relative humidity: 0 to 90% non­condensing
CONNECTIONS
Removable screw terminals accept 12 to 22 AWG wire
ENCLOSURE
Impact resistant polyester plastic, body gray, cover clear with blue faceplate; NEMA 4X, IP66; ½" conduit hole provided at base.
MOUNTING
½" NPT pipe (0.865 in, 12.7 mm) conduit hole on bottom of enclosure. 0.166 in (4.2 mm) wall mounting holes located behind front cover screws.
TIGHTENING TORQUE
Screw terminal connectors: 4.5 lb-in (0.5 Nm)
OVERALL DIMENSIONS
4.33" x 3.15" x 2.76" (110 mm x 80 mm x 70 mm)
WEIGHT
10.4 oz (295 g)
WARRANTY
3 years parts and labor
Input
ACCURACY
±1 count
FUNCTION
Linear (2 to 32 points) or square root
TEMPERATURE DRIFT
50 PPM/°C from -40 to 85°C ambient
DECIMAL POINT
User selectable decimal point
MINIMUM SPAN
Input 1 & Input 2: 0.40 mA
CALIBRATION RANGE
An Error message will appear if input 1 and input 2 signals are too close together.
Input Range
Minimum Span Input 1 & Input 2
4-20 mA
0.40 mA
MAXIMUM VOLTAGE DROP
Without Backlight
With Backlight
1.7 VDC @ 20 mA
3.7 VDC @ 20 mA
EQUIVALENT RESISTANCE
85 Ω @ 20 mA
185 Ω @ 20 mA
INPUT OVERLOAD
Over current protection to 2 A max.
Compliance Information
Safety
CSA Certified
U.S. & Canada 2252 05 – Process Control Equipment 2252 85 – Process Control Equipment, U.S. Standards
CSA File Number
157123
CSA Applicable Requirements
CAN/CSA C22.2 No. 61010­1-04 Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use – Part 1: General Requirements UL 61010-1:2004, 2nd Edition Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use – Part 1: General Requirements
Low Voltage Directive
EN 61010-1:2010 Safety requirements for measurement, control, and laboratory use IEC 61010-1:2010 Safety requirements for measurement, control, and laboratory use
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Instruction Manual
5
Electromagnetic Compatibility
EMC Emissions & Immunity
EN 61326-1:2013 EMC requirements for Electrical equipment for measurement, control and laboratory use – Industrial
Safety Information
CAUTION:
Read complete instructions prior to
installation and operation of the meter.
The equipment shall be installed by qualified personnel in accordance with applicable local and national regulations (e.g. CEC, NEC, FCC, SCC, etc). Follow all safety and operation guidelines in this manual. If the meter is used in a manner not rec­ommended by the manufacturer, the overall safety will be impaired. Installation and service should be performed only by trained service personnel. This unit is not suitable for hazardous locations such as potentially explosive zones or locations.
No user replaceable part inside. All service shall be performed at the factory. Do not disconnect and reconnect cables during a lightning storm. Suitable surge suppressor (e.g. lightning protec­tion) shall be provided in end application installa­tion.
Installation
All pushbuttons and wiring connectors are accessed by opening the NEMA 4X enclo­sure by removing the 4 captive screws that secure the cover.
Unpacking
Remove the meter from box. Inspect the packaging and contents for damage. Report damages, if any, to the carrier. If any part is missing or the meter malfunc­tions, please contact your supplier or the factory for assistance.
Mounting
The PD662 can be wall mounted using the mounting holes beneath the cover screws. A ½” NPT pipe conduit hole is provided. It can be panel mounted with the addition of the PDA6624 panel mount kit. It can also be pipe mounted by using the PDA6845 pipe mount kit. Refer to Mounting Dimensions, page 13 for details on wall or panel space requirements.
The unit shall be installed in a way that will prevent any accidental contact of the internal meter circuits and power supply lines.
Cable suitable for outdoor use and a CSA Approved gland rated 4X, or a suitable conduit and a CSA Approved connector rated 4X, is intended to be used in final installation.
Metallic conduit shall be reliably bonded to protective earth/ground without creating any ground loop.
!
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Meter Instruction Manual
6
Connections
Disconnect power before opening the unit.
To access the connectors, remove the enclosure cover and unscrew the two captive stainless­steel screws on the rear mounting board. Re­move the meter assembly from the enclosure. Signal connections are made to a three-terminal removable connector. The signal wiring terminal block is on the rear of the meter assembly.
S+
4-20 mA signal input positive terminal connection
S-
4-20 mA signal return/negative terminal connection
X
Not connected (no backlight option)
B-
4-20 mA signal return/negative terminal when using the installed loop powered backlight option
Refer to Figure 1 for terminal positions on the rear of the mounting board inside the meter enclosure.
P+
24 VDC power positive terminal connection
P-
24 VDC power negative terminal connection
WIRING INSTRUCTIONS
Connect signal positive to terminal S+.
Connect signal negative to terminal S-.
If backlight installed, connect
signal negative to terminal B-, not S-.
S+ S- B-
S+ S- B-
Figure 1. PD662 Mounting Board Rear View
Connection & Wiring Diagrams
Signal input connections are made to a three­terminal connector labeled S+|S-|X for models without a backlight and S+|S-|B- for models with a backlight. The 4-20 mA input with no backlight has a maximum voltage drop of 1.7 V and is wired as shown in Figure 2. The loop-powered backlight configura­tion requires a total maximum voltage drop of
3.7 V. The backlight is recommended for dim lighting conditions and is enabled when wired as shown in Figure 3.
Figure 2. PD662 Input Connections without
Backlight
Figure 3. PD662 Input Connections with
Backlight
Setup and Programming
There is no need to recalibrate the meter for milliamps when first received from the factory.
The meter is factory calibrated for milliamps prior to shipment. The calibration equipment is certified to NIST standards.
Overview
There are no jumpers involved in the setup process of the meter. Setup and programming is done through the front panel buttons. After all connections have been completed and verified, apply power to the loop.
For a Quick User Interface Reference Guide go to page 15
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Instruction Manual
7
Front Panel Buttons
2662
MENU
ENTER
u p
Button/ Symbol
Description
MENU
Menu button to enter program­ming mode. Press and hold for 5 seconds to access the Ad- vanced features of the meter.
ENTER
Enter button to access a menu or accept a setting.
u
Right arrow to scroll through the menus or move to the next digit or decimal position during programming. Displays the Max then Min dis­play values when pressed dur­ing normal run mode.
p
Up arrow to scroll through the menus, decimal point, or to in­crement the value of a digit. Resets the Max and Min dis­play value when pressed dur­ing normal run mode.
Setting Numeric Values
The numeric values are set using the Right and Up arrow buttons. Press Right arrow to select
next digit and Up arrow to increment digit. The two left-most digits on the display are set as a single digit, able to display -19 to 29.
The digit being changed blinks. Press the Enter button, at any time, to accept a
setting or Menu button to exit without saving changes.
The decimal point is set using the Right or Up arrow button in the Setup-decimal point menu.
Programming the Meter
It is very important to read the following information, before proceeding to program the meter:
There is no need to recalibrate the meter for milliamps when first received from the factory.
The meter is factory calibrated for milliamps prior to shipment. The calibration equipment is certified to NIST standards.
Use the Scale (SCL) menu to enter scale parameters without applying a live signal.
Alternatively, use the Calibrate (CAL) menu to apply a signal from a calibrator or a 4-20 mA transmitter to calibrate the meter.
Inputs may be calibrated or scaled to any display within the range of the meter.
Additional parameters, not needed for most applications, are viewed and programmed with the Advanced Features menu, see Advanced Features Menu on page 9.
Main Menu
The main menu consists of the most commonly used functions: Decimal Point Location, Scale, and Calibration.
26.62
MENU
dP SCl CAL
Run
Mode
MENU
Press Menu button to enter Programming Mode then press the Up arrow button to scroll main menu.
Press Menu, at any time, to exit and return to Run Mode. Changes made to settings prior to pressing Enter are not saved.
Changes to the settings are saved to memory only after pressing Enter.
The display moves to the next menu every time a setting is accepted by pressing Enter.
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Meter Instruction Manual
8
Main Menu Display Functions & Messages
The meter displays various functions and messages during setup, programming, and operation. The following table shows the main menu functions and messages in the order they appear in the menu.
Display
Parameter
Action/Setting
dp
Decimal point
Set decimal point
SCL
Scale
Enter the Scale menu
Npt
Number of Points
Set number of linearization points
in1
Scale Input 1
Input signal 1 value (mA)
D1
Scale Display 1
Scaled value for input 1
in2
Scale Input 2
Input signal 2 value (mA)
D2
Scale Display 2
Scaled value for input 2
CAL
Calibrate
Enter the Calibrate menu
Npt
Number of Points
Set number of linearization points
in1
Calibrate Input 1
Read input signal 1
D1
Calibrate Display 1
Enter value for input 1
in2
Calibrate Input 2
Read input signal 2
D2
Calibrate Display 2
Enter value for input 2
Setting the Decimal Point (dP)
Decimal point may be set with up to three decimal places or with no decimal point at all.
Pressing the Right or Up arrow moves the decimal point one place to the right until no decimal point is displayed, then it moves to the left most position.
ENTER
dP dd.dd
or
Select Decimal Point
Next
Scaling the Meter (
SCL
)
The 4-20 mA input can be scaled to display the process in engineering units.
A signal source is not needed to scale the meter; simply program the inputs and corresponding display values.
If using linear signal input conditioning, enter the number of scale points (2-32), followed by the input values and display values. If using square root signal input conditioning, the number of points input menu will not be present.
Number of Points (
npt
)
Set the number of linearization points used in the Scale menu. 2 to 32 points may be used. The Scale menu is entered after entering the number of points
d1
Press Enter to Accept Setting
in2
Scale
Input 2
in1
Set Input 1
Value
SCL
ENTER
04.00
Set Display 1
Value
Press Up to Set Digit Value
Press Right to Select Next Digit
Press Menu to Exit at any Time
000.0
MENU
npt
002
Number of Points menu not displayed for square root input conditioning.
Set Number of Scale Points
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Instruction Manual
9
Minimum Input Span
The minimum input span is the minimum difference between input 1 and input 2 signals required to complete the calibration or scaling of the meter. The minimum span is 0.40 mA.
If the minimum span is not maintained, the meter reverts to input 2, allowing the appropriate input signals to be applied.
Calibrating the Meter (
Cal
)
To scale the meter without a signal source,
refer to Scaling the Meter (SCL), page 8.
The meter can be calibrated to display the process in engineering units by applying the appropriate input signal. The use of a calibrated signal source is strongly recommended.
1. Press the Up arrow button to scroll to the
Calibration menu (CAL) and press Enter.
2. If using linear signal input conditioning, enter the number of calibration points (2-32).
3. The meter displays in1. Apply a known signal and press Enter. The display will flash while accepting the signal.
4. When the meter displays d1, press Enter. Enter a corresponding display value for the signal input, and press Enter to accept.
5. The meter displays in2. Apply a known signal and press Enter. The display will flash while accepting the signal.
6. When the meter displays d2, press Enter. Enter a corresponding display value for the signal input, and press Enter to accept.
Recalibrating the Internal Calibration Reference (
Ical
)
The Internal Calibration (ICAL) menu, located in the Advanced Features menu, is used to recalibrate the internal calibration reference. Recalibration is recommended at least every twelve months. Refer to Internal Calibration (ICal), page 11 for instructions.
Advanced Features Menu
To simplify the setup process, functions not needed for most applications are located in the Advanced Features menu. Press and hold the MENU button for five seconds to access the Advanced Features menu
d1
Press Enter to Accept Setting
in2
Calibrate
Input 2
in1
ENTER
Set Display 1
Value
Press Up to Set Digit Value
Press Right to Select Next Digit
Press Menu to Exit at any Time
000.0
MENU
npt
002
Number of Points menu not displayed for square root input conditioni ng.
Set Number of Scale Points
Cal
Display Flashes
Accepting Input
Press Enter to Access Menu or to Accept Setting
ICAL
FIL
ENTER
MENU
Press Up to Scroll Menu and to Increment Digit Value
Press Menu to Exit at any Time
inFo
MENU
Press and hold for five seconds
26.62
Run Mode
fnc
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Meter Instruction Manual
10
Advanced Features Menu & Display Messages
The following table shows the Advanced features menu functions and messages in the order they appear in the menu.
Display
Parameter
Action/Setting
Fnc
Input Function
Set linear or square root input conditioning function
Lnr
Linear
Set linear scal­ing
Sqr
Square Root
Set square root input condition­ing function
info
Information
Enter the Information menu
Sft
Software Information
Software release number
ver
Version
Meter firmware version
*C
Calibration Temp (°C)
Temperature at time of I­calibration (°C)
*F
Calibration Temp (°F)
Temperature at time of I­calibration (°F)
FIL
Filter
Set filter function level
ICAL
I-Calibration
Internal master factory calibration
rst
Reset Defaults
Restore factory default parameter settings
Signal Input Conditioning Function (
Fnc
)
The PD662 provides linear and square root signal input conditioning functions for inputs from linear and non-linear transmitters.
Linear (
Lnr
)
Meters are set up at the factory for linear func­tion using two-point linearization. Multi-point line­arization with up to 32 points may be used. The linear function provides a display that is linear with respect to the input signal between each set of input points.
Square Root (
sqr
)
The square root function is used to linearize the signal from a differential pressure transmitter and display flow rate in engineering units.
Information Menu (
info
)
The Information menu is located in the Advanced Features menu, to access Information menu see Advanced Features Menu on page 9.
It shows software identification number, version number, and calibration temperatures. To determine the software version of a meter:
1. Go to the Information menu (info) and
press Enter button.
2. The meter will automatically scroll through the software release number and software version. The meter temperatures at the time of last internal calibration in °C and °F are displayed for calibration troubleshooting. Pressing the ENTER, RIGHT, or UP buttons will progress the information display.
3. Following the information display, the meter will exit the Advanced Features menu and return to run mode.
Input Signal Filter (
FIL
)
The noise filter is available for unusually noisy signals that cause an unstable process variable display. The noise filter averages the input signal over a certain period. The filter level can be set to low (LO), high (HI), or off (OFF). The higher the filter setting, the longer the averaging time and so the longer the display may take to find its final value.
The filter contains a noise filter bypass feature so that while small variations in the signal will be filtered out, large, abrupt changes to the input signal are displayed immediately.
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Instruction Manual
11
Internal Calibration (
ICal
)
There is no need to recalibrate the meter for milliamps when first received from the factory.
The meter is factory calibrated for milliamps prior to shipment. The calibration equipment is certified to NIST standards.
The internal calibration allows the user to scale the meter without applying a signal. The use of a calibrated signal source is necessary to perform the internal calibration of the meter. Check calibration of the meter at least every 12 months.
Notes:
The signal source must have a full- scale accuracy of 0.01% or better between 4 and 20 mA in order to maintain the specified accuracy of the meter.
Allow the meter to warm up for at least 15 minutes before performing the internal calibration procedure.
The Internal calibration menu is part of the Advanced Features menu.
1. Press and hold the MENU button for 5 seconds to enter the Advanced Features menu.
2. Press the Up arrow button to scroll to the Internal Calibration menu (ICAL) and press Enter.
3. The meter displays 4.00 mA. Apply a 4.00 mA signal and press Enter. The display flashes for a moment while the meter is accepting the signal.
4. After the signal is accepted, the meter displays 20.00 mA. Apply a 20.00 mA signal and press Enter. The display flashes for a moment while the meter is accepting the signal.
Error Message (
Err
)
An error message indicates that the calibration process was not successful. After the error message is displayed, the meter will revert to input 2 calibration settings. The error message might be caused by inadvertently leaving the signal at the previous level or not maintaining a
0.40 mA minimum span. Press the Menu button
to cancel the current calibration process if necessary.
Operation
Front Panel Buttons Operation
Button Symbol
Description
MENU
Press to enter or exit Programming Mode or exit Max/Min readings
u
Press to reset Max/Min readings
p
Press to display Max/Min readings alternately
ENTER
Press to display Max or Min reading indefinitely while displaying Max or
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Meter Instruction Manual
12
Maximum & Minimum Readings (HI & LO)
The maximum and minimum (peak & valley) readings reached by the process are stored in the meter since the last reset or power-up. The meter flashes HI or LO to differentiate between run mode and max/min display.
Press Up to Display and to Toggle Between Max & Min
10 Sec Time Out
16.62
Run Mode
HI <LO
ENTER
MENU
Press Enter to hold Max/Min
Press Right to Reset Max/Min
Press Menu to Exit Max/Min
19.45 5.34
1. Press Up arrow button to display maximum reading since the last reset/power-up.
2. Press Up arrow again to display the minimum reading since the last reset/power­up.
3. Press Enter to continue to display the Max or Min display reading by disabling the Max/Min timeout. The meter will continue to track new Max/Min readings. Press MENU to exit the Max/Min reading.
4. If Enter is not pressed, the Max/Min display reading will continue to flash and time out after ten seconds. The meter will return to display the actual reading.
5. Press Right arrow button while in Max/Min Mode to reset both Max and Min. Max/Min display readings are reset to the current reading.
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to determine what’s happening, it might be better to start the setup process from the factory defaults.
Instructions to load factory defaults:
1. Enter the Advanced features menu. See Advanced Features Menu, page 9.
2. Press Up arrow button to display info menu.
3. Press RIGHT arrow button when info is shown.
4. Press ENTER button when rSt is shown. Press Enter again when display flashes rSt. Note: If Enter is not pressed a second time within three seconds, rSt will stop flashing and the last ENTER press cancelled.
5. The meter goes through an initialization sequence (same as on power-up), and loads the factory default settings.
rSt
info
Press and Hold for 5 Sec
Meter Re-
Initializes
Flashing Display
rSt
FNc
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Instruction Manual
13
Factory Defaults & User Settings
The following table shows the factory setting for most of the programmable parameters on the meter. Next to the factory setting, the user may record the new setting for the particular application.
Model: ___________________ S/N: ___________________ Date: ___________________
Parameter
Display
Default Setting
User Setting
Decimal point
Dd.dd
2 places
Scale
SCL
Number of Points
NPT
2
Input 1
in1
4.00 mA Display 1
D1
4.00
Input 2
in2
20.00 mA
Display 2
D2
20.00
Advanced Features
Input Conditioning Function
Fnc
Linear
Filter
FIL
Off
Mounting Dimensions
Figure 4. Case Dimensions – Front View
Figure 5. Case Dimensions – Side View
A: 3.15 in (80 mm)
B: 4.33 in (110 mm)
C: 2.44 in (62 mm)
D: 3.62 in (92 mm)
E: 2.76 in (70 mm)
F: 0.79 in (20 mm)
G
H
I
Figure 6. Case Dimensions – Bottom View
G: 0.87 in (22 mm)
H: 0.80 in (20 mm)
I: 2.17 in (55 mm)
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Meter Instruction Manual
14
Figure 7. PDA6845 Pipe Mounting Kit
The PDA6845 pipe mounting kit may be used to mount a PD662 to a 2" pipe. The kit includes an
8.20 in (208 mm) x 4.10 in (104 mm) mounting panel with a 2" U-bolt and all necessary mounting hardware.
Troubleshooting
Due to the many features and functions of the meter, it’s possible that the setup of the meter does not agree with what an operator expects to see. If the meter is not working as expected, refer to the recommendations described below.
Troubleshooting Tips
Symptom
Check/Action
No display or faint display
1. Check connections.
2. Perform hard reset by temporarily shorting S+ and S- terminals for a few seconds.
Rate display unsteady
Increase filter setting in Advanced menu.
Meter displays error message during calibration (err)
Check:
1. Signal connections
2. Minimum input span requirements
Meter flashes
2999
-1999
Check:
1. Input signal within scaled range of 2999 and -1999.
Display stuck flashing a number and HI or
LO
Press Menu to exit Max/Min display readings.
Display response is too slow
Check filter setting to see if it can be lowered to LO or OFF.
If the display locks up or the meter does not respond at all
Perform hard reset by temporarily shorting S+ and S- terminals for a few seconds and then removing short.
Backlight does not appear.
Check:
1. Meter has a backlight installed.
2. Signal connections are as shown in Figure 3 on page
6.
Other symptoms not described above
Call Technical Support for assistance.
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Meter Instruction Manual
15
Quick User Interface Reference Guide
Scale
Run Mode
Calibrate
Display
Max/Min
dd.dd
in2
d1
in1
ddd.d
dddd
d.ddd
Pushbutton Function Menu Go to Programming Mode, leave Programming Mode, and Max/Min
Mode. Hold for 5 seconds to access Advanced Features.
Right Arrow Move to next digit or decimal point position. Reset Min/Max. Up Arrow Move to next selection or increment digit. Go to Max/Min Mode. Enter Accept selection/value and move to next selection.
Max/Min Mode
While in Run Mode, pressing Up Arrow will initiate Max/Min Mode. Up Arrow toggles between Max & Min displays, and Right Arrow resets the Max/Min to the current value. Press Menu or wait 10 seconds to return to Run Mode. Pressing Enter will disable the 10 second timeout and continuously flash Max or Min.
Decimal
d2
Program
Run
Max &
Min
Advanced
Features
Up Arrow
Menu
Menu
Menu
Menu
Operational Modes
in2
d1
in1
d2
*Access by pressing Right arrow twice
Press & hold Menu for 5 seconds to access Advanced Features Menu
Filter
Initial
Calibrate
Information
*Factory Defaults
Hold
Menu
Function
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Meter Instruction Manual
16
This page intentionally left blank
EU Declaration of Conformity
Issued in accordance with ISO/IEC 17050-1:2004.
We,
Precision Digital Corporation 233 South Street Hopkinton, MA 01748 USA
as the manufacturer, declare under our sole responsibility that the product(s),
Model PD662 Survivor Series Loop Powered Meter
to which this declaration relates, is in conformity with the European Union Directives shown below:
2014/35/EU Low Voltage Directive 2014/30/EU EMC Directive 2011/65/EU RoHS Directive
This conformity is based on compliance with the application of harmonized or applicable technical standards and, when applicable or required, a European Union notified body certification.
Standards:
EN 61010-1:2001 EN 61326:2006
The standards EN 61010-1:2001, and EN 61326:2006 are no longer harmonized. The requirements of these standards have been checked against the harmonized standards EN 61010-1:2010, and EN 61326:2013 and there were no major technical changes affecting the latest technical knowledge for the products listed above.
Product Markings:
Signed for and on behalf of Precision Digital Corporation:
Name: Jeffrey Peters Company: Precision Digital Corporation Title: President Date: 04/20/2016
Document No: DoC PD662 {042016}
PD662 General Purpose NEMA 4X, IP68 Loop-Powered Meter Instruction Manual
PRECISION DIGITAL CORPORATION
233 South Street • Hopkinton MA 01748 USA Tel (800) 343-1001 • Fax (508) 655-8990
www.predig.com
LIM662_I
SFT054 Ver 1.800 & up
12/18
How to Contact Precision Digital
For Technical Support please
Call: (800) 610-5239 or (508) 655-7300
Fax: (508) 655-8990
Email: support@predig.com
For Sales Support or to place an order please contact your local distributor or
Call: (800) 343-1001 or (508) 655-7300
Fax: (508) 655-8990
Email: sales@predig.com
For the latest version of this manual please visit
www.predig.com