PRECISION DIGITAL DART PD602, DART 85-265 VAC, DART 12-36 VDC, DART PD602-6R0-0, DART PD602-7R0-0 User Manual

...
Page 1
DART MODEL PD602
3.622" (92mm)
1.772"
(45mm)
Panel Cutout to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances: A: +0.032 (+0.8mm)
-0.000 (-0.0mm) B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
1.76"
(45mm)
0.59"
(15mm)
3.2"
(81mm)
2.45"
(62mm)
3.61"
(92mm)
2.50"
(64mm)
4.68"
(119mm)
LOW-COST PROCESS METER
Features & Benefits
4-20 mA, 0-5 V, 1-5 V, 0-10 V inputs
NEMA 4X front panel with protective overlay
Calibrate from the front panel
Easy to set up and calibrate
Universal power supply
12-36 VDC power option
24 VDC @ 200 mA supply option
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
High input (e.g. 20 mA): 20 to 2000 above low input display.
Decimal Point: Jumper selectable up to three decimal places Front Panel: NEMA 4X, IP65; panel gasket provided Input Impedance: Voltage ranges: greater than 200 kΩ; Current range: 10-60 Ω, varies with resettable fuse impedance Input Overload: Protected by automatically resettable fuse Display Update Rate: 2.5/second Overrange: Displays 1 Underrange: Displays -1 Temperature Drift:
100 PPM/°C
Recalibration: Recommended at least every 12 months Power Options:
85-265 VAC, 50/60 Hz, 90-265 VDC, 8 W max or 12-
36 VDC, 12-24 VAC, 6 W max.
Transmitter Supply: Required Fuse: UL Recognized, 5 A max, slow-blow; up to 6
Isolated 24 VDC ±10% @ 200 mA max
meters
may share one fuse.
Normal Mode Rejection: 62 dB at 50/60 Hz Common Mode Rejection: 120 dB at 50/60 Hz Isolation: 4 kV input-to-power line; 500 V input-to-24 VDC supply Operating Temperature: Storage Temperature:
0 to 65°C
-40 to 85°C
Relative Humidity: 0 to 90% non-condensing Connections: Removable screw terminals accept 12 to 26 AWG Enclosure: Weight: Warranty: Extended Warranty:
1/8 DIN, high impact plastic, UL 94V-0, color: gray
5.0 oz (142 g) 1 year parts & labor
1 or 2 years, refer to Price List for details.
MOUNTING DIMENSIONS
Panel Mounting Instructions
1. Remove the two mounting brackets provided with the meter (back-off the two screws so that there is ¼″ (6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
2. Insert meter into the panel cutout.
3. Install mounting brackets and tighten the screws against the panel. To achieve a proper seal, tighten the mounting bracket screws evenly until meter is snug to the panel along its short side.
DO NOT OVER TIGHTEN.
ORDERING INFORMATION
Dart Model PD602
85-265 VAC** Model
PD602-6R0-0* PD602-7R0-0 None
PD602-6R0-1* 24 VDC Transmitter Supply
*Quick Shipment Program product, shipped within 2 working days. **Meters may be powered from AC or DC, see Specifications for details.
Model Description
12-36 VDC** Model
Options Installed
Setup, Calibration & Labels
PRECISION DIGITAL CORPORATION
PDN-CAL
PDN-CERTCAL Certificate of Calibration
PDN-CERTCAL2 Certificate of Calibration with Data
PDLXXXX Engraved Plastic Labels
2-Point Input Calibration
www.predig.com
Page 2
DART MODEL PD602
2 1
POWERSIGNAL
AC
or DC
POWE
R
+ -
Loop Power
Supply
S+ S-
1 2
-
+
4-20 mA
Transmitte
r
External Fuse
S+ S-
SIGNAL
-
-
+
+
2-Wire
4-20 mA
Transmitter
24V OUT
P+ P-
POWER
2 1
1 22 1
AC or DC
POWER
External Fuse
S+ S-
SIGNAL
-Pwr+ Signal+
3-Wire
Voltage or Curren
t
Transmitte
r
External or
Internal
Power Supply
P+ P-
1 2
+
Voltage or
Current
Source
S+ S-
SIGNAL
1 2
-
1602
LO HI
LO & HI Calibration
Controls
Access-Hole
Overla
y
A B C D E F
JUM PER AR RAY
Spare Jumper
Def ault Configuration
4-2 0 mA & 199.9 DP
De cimal
Po in
t
Se lection
Input Signal Selection
A B C A B C
D E F D E F D E F
A B C A B C
4-20 mA 1-5 V
1.999 19.99 199.9
0-5 V 0-10 V
SAFETY INFORMATION
LOW-COST PROCESS METER
CAUTION: Read complete instructions
prior to installation and operation of the meter.
WARNING: Risk of electric shock. Observe all safety regulations. Electrical wiring should be performed in accordance with all applicable national, state, and local codes to prevent damage to the meter and ensure personnel safety.
SETUP
All operations are performed with the meter in the case.
Input Signal & Decimal Point Selection
The input signal and the decimal point are selected by the jumper array located at the rear of the meter, next to the signal connector. The label affixed to the case shows the jumper location and configuration for the selected input signal.
Connections
All connections are made to removable screw terminal connectors located at the rear of the meter. The label affixed to the case shows the location of all connectors available with requested configuration.
WARNING: Hazardous voltages exist within enclosure. Only trained service personnel should perform installation and service.
Three-wire transmitter & voltage
or current source connections
Front Panel Calibration Controls
The LO and HI calibration controls are located behind the faceplate. The calibration controls may be reached through an access-hole on the faceplate. After the calibration has been completed, use the overlay provided to cover the access-hole to maintain NEMA 4X protection.
Meter powered from universal supply
Transmitter powered by external power supply
1. Apply low input signal (e.g. 4 mA) and adjust the LO calibration control for desired display reading.
2. Apply high input signal (e.g. 20 mA) and adjust the HI calibration control for desired display reading.
3. Complete the calibration by making any minor adjustments to the LO and HI displays.
4. Remove adhesive backing from the overlay provided and apply to the faceplate to cover the access-hole for the calibration controls.
Transmitter powered by internal power supply (optional)
PRECISION DIGITAL CORPORATION
19 Strathmore Road • Natick MA • 01760 • USA • Tel: (800) 343-1001 • Fax: (508) 655-8990
Meter powered from universal supply
Th re e access-hole overl ay s ar e pr ov id ed with each meter. Wh en recalibrating the me te r, use a new ove rl ay t o ma in ta in NE MA 4X protection .
LIM602_C 06/05
www.predig.com