PPI Zenex Plus User Manual

Zenex Plus User Manual
Zenex Plus
Multi-Purpose Temperature Controller
with Graphic Display
User Manual
Zenex Plus User Manual
CONTENTS
1. FRONT PANEL LAYOUT 1
2. BASIC OPERATION 2
4. SUPERVISORY PARAMETERS 7
5. FACTORY PARAMETER 12
6. PANEL MOUNTING AND ELECTRICAL CONNECTIONS 21
Zenex Plus User Manual
Section 1
FRONT PANEL LAYOUT
The Controller front panel comprises of Graphic Readout and Membrane Keys as shown in Figure 1.1 below.
Figure 1.1
PPI
Graphic
Readout
Zenex Plus
GRAPHIC READOUT
The Graphic Readout is a X Pixel Monochrome LCD Display. In Normal operation mode the Readout shows 128 64 measured Temperature Value, Set Temperature Value, Alarm / Process Status & Balance Time (if enabled & running). The Process Status Information can be viewed using screen scroll feature.
In Mode, the Readout displays parameter names and values that can be edited using front keys.Set-up
KEYS
There are six tactile keys provided on the front panel for configuring the and setting-up the parameter values. controller
The Table 1. below lists each key (identified by the front panel symbol) and the associated function. 1
Symbol
Key
25.8
TEMP HIGH
0:10:00
Table 1.1
SP
°C
Keys
25.0
Function
Scroll
Alarm
Acknowledge
DOWN
UP
SET-UP
ENTER
Press to scroll through various Process Information Screens in Normal Operation Mode.
Press to acknowledge and mute (if active) alarm output.
Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.
Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change.
Press to enter or exit set-up mode.
Press to store the set parameter value and to scroll to the next parameter.
1
Zenex Plus User Manual
Section 2
BASIC OPERATIONS
Figure 2.1
POWER-UP DISPLAY
Upon power-up the controller displays model name, Hardware Version and Software Version for 2 seconds as shown in figure 2.1.
H/W Version
S/W Version
RUN MODE
After the Power-up display the controller enters into RUN Mode. This is the normal operation mode wherein the controller starts PV measurements, Alarm monitoring and Control Loop execution.
Main Screen
This is the default screen and its appearance depends upon whether a timer function is enabled or disabled as shown in the figures 2.2 (a) & 2.2 (b) respectively.
Figure 2.2(a) : Timer Disabled
Measured Temperature
Alarm / Process
Status
25.0
TEMP HIGH
SP
°C
25.0
Set Temperature
02
07
Figure 2.2(b) : Timer Enabled
Note : The Balance Time is shown in either HHH:MM or H:MM:SS
depending upon the remaining time counts as under : HHH:MM for 249:59 to 10:00 H:MM:SS for 9:59:59 to 0:00:00
Balance Time
In case of measured value errors, the messages listed in Table 2.1 flash in place of process value as illustrated in Figure 2.3.
Table 2.1
Message Error Type
OPEN
OVR
UNR
Sensor Open
Over-range
Under-range
RTD Pt100 / Thermocouple is Broken / Open
Temperature above Max. Specified Range
Temperature below Min. Specified Range
Cause
0:10:00
25.0
TEMP HIGH
SP
25.0
TEMP HIGH
°C
Figure 2.3
OPEN
Measured Temperature
Alarm / Process Status
Set Temperature
°C
SP
25.0
2
Zenex Plus User Manual
The Alarm / Process Status space on the screen may show one or more of the several messages listed in Table 2.2 depending upon the existence of active alarms or process events. In case of co-existence of multiple active alarms or process events, the messages are scrolled one after the other with an approximate time interval of 3 seconds. Also if there is no active alarm or process event, the message space is blank.
Table 2.2
Message String Alarm / Process Status
Temp High
Temp Low
Tuning
Door Open
Timer Hold
Process Status Screen
The Process Status Screen is shown upon pressing (Scroll) key from Main Screen or upon acknowledging a new Alarm by pressing (Acknowledge) key. As depicted in Figure 2.4(a) for Old Version & 2.4(b) for New Version; the screen shows Temperature Alarm Status, Door Open / Close Status, the Heater Output Status (ON / OFF or % Power) & Compressor ON / OFF Status.
The measured temperature is in Process High Alarm State.
The measured temperature is in Process Low Alarm State.
The Controller is Self Tuning.
The Equipment / Chamber door is open for a time longer than the set ‘DOOR ALRM DLY’ time.
The Countdown Timer is paused since the PV is outside Hold Band.
Figure 2.4(a) :
Old Version
Temperature Alarm Status
Heating Control
Output Power
Temperature Alarm Status
Heating Control
Output Power
PROCESS STATUS
°C
High
Heating
0.0%
Figure 2.4(b) :
New Version
Process Status
Temp
High
Heater
0.0%
Compressor
Door
Close
Compressor
OFF
Door
Close
OFF
Door Status
Compressor
Output Status
Door Status
Compressor
Output Status
3
Zenex Plus User Manual
Figure 2.5 (a)
Temperature Alarm Status
Temp
Normal
Temp
Low
Temp
High
Within
Limits
Below
Low Limit
Above
High Limit
Figure 2.5 (b)
Door Status
Door
Close
Door
Open
The Controller provides programmable Low & High deviation limits around the temperature control setpoint to monitor Alarm conditions. The screen shows either Normal or Low or High Status, as shown in Figure 2.5 (a) depending upon the deviation of measured temperature value from the control setpoint and set limits.
The Controller provides a Digital Input for interfacing Door switch that senses the door position, Open or Close. The screen indicates the door status as shown in Figure 2.5 (b).
4
Zenex Plus User Manual
Section 3
OPERATOR PARAMETERS
The Operator Parameters are accessible under PASSWORD 0. The list includes parameters for adjusting Control Setpoint, Alarm Setpoints & Zero-offset. If Timer is enabled then Time Interval value & Timer Start / Abort commands are also available.
The Figure 3.1 shows how to access Operator Parameters. The Example illustrates changing the Low Deviation alarm value from 2.0 to 5.0. (The Example is shown with Timer disabled).
Figure 3.1
ENTER PASSWORD >>
2.0
°C
SP
25.0
Press SET-UP Key for Password Entry
or
Press UP/DOWN Keys
to adjust Parameter Value
0
Default Password
for Operator Parameters
Press ENTER Key
To open Operator
LO DEVIATION >>
5.0
Desired Value
Press ENTER Key
to store the New Value
25.0
TEMP HIGH
RUN Mode
Main Screen
LO DEVIATION >>
Desired Parameter
& to move to Next Parameter
The Table 3.1 below described the Operator Parameters in detail.
Table 3.1
Parameter Description
Parameter List
CTRL SET VALUE >>
25.0
First Parameter
Press & Release
ENTER Key until Desired
Parameter appears
HI DEVIATION >>
2.0
Next Parameter
Settings
(Default Value)
TIME START COMMAND >> TIME ABORT COMMAND >>
(Available only if Timer is Enabled)
These two commands are mutually exclusive.
Set to Yes to start Timer, if not already started.
Set to Yes to abort a running timer.
TIME INTERVAL (H:M) >>
(Available only if Timer is Enabled)
The set time value for the timer in Hours : Minutes.
Yes
No
(Default : No)
0.01 to 249.59 (HH:MM)
(Default : 0.10)
5
Zenex Plus User Manual
Parameter Description
CTRL SET VALUE >>
This parameter sets the value at which the controller atte to mpts maintain the measured temperature value.
LO DEVIATION >>
This Parameter sets a negative deviation (offset) limit with respect to the ‘ ’. The Alarm is activated if the measured Control Set-point temperature value falls below this limit.
HI DEVIATION >>
This Parameter sets a negative deviation (offset) limit with respect to the ‘Control Set-point’. The Alarm is activated if the measured temperature value exceeds this limit.
CHANGE PASSWORD >>
The Controller is shipped from the factory with a default password (0) for accessing the parameters reserved for Operator. However, if required the password can be changed by setting the new value for this parameter.
(The new password replaces the old password. That is, the old password is no longer valid. it is user’s responsibility to memorize the password.)
Settings
(Default Value)
Setpoint LO limit to
Setpoint HI limit
(Default : 25.0)
0.2 to 99.9
(Default : 2.0)
0.2 to 99.9
(Default : 2.0)
1 to 100
(Default : 0)
6
Zenex Plus User Manual
Section 4
SUPERVISORY PARAMETERS
The various parameters have been assembled in different groups under the default factory password 123.
Refer Table 4.1 below for a quick summary of parameters under different groups. Each parameter has been described in subsequent sections.
Table 4.1
Group
Serial Parameter
Sensor Input
Device ID, Baud Rate, Parity, Serial Write
Zero Offset
Parameters
Tune, Setpoint Low Limit, Setpoint High Limit, Compressor Set-point, Compressor Hysteresis,
Control
Heat Control Action, Heat Hysteresis, CZ Proportional Band, CZ Integral Time, CZ Derivative Time, HZ Proportional Band, HZ Integral Time, HZ Derivative Time, Cycle Time, Overshoot Inhibit, Cutoff Factor
Password
Exit
Change Password
Exit Setup Mode
Accessing Group & Parameters
The Figure 4.1 below illustrates how to access the group and parameters. The example shows changing the value for the parameter ‘Setpoint High Limit’ from 600.0 to 100.0 that is located under group ‘Control’.
Figure 4.1
TEMP HIGH
25.0
ENTER PASSWORD >>
°C
SP
25.0
0
or
ENTER PASSWORD >>
123
RUN Mode
Main Screen
SELECT GROUP>>
SERIAL
First Group
SETPOINT HI LIMIT >>
600.0
Desired Parameter
for Operator Parameters
Press SET-UP Key for Password Entry
SELECT GROUP>>
or
Press UP/DOWN Keys
to Select Desired Group
SETPOINT HI LIMIT >>
or
Press UP/DOWN Keys
to adjust Parameter Value
Default Password
CONTROL
Desired Group
100.0
Desired Parameter
Value
Supervisory Parameters
Press UP/DOWN Keys
To adjust Password Value
Press ENTER Key
to Access Parameters
Press ENTER Key to
store the Value
and move to Next
Parameter
Password for
TUNE >>
NO
First Parameter in
selected Group
HEAT CTRL ACTION >>
PID
Next Parameter
Press & Release
ENTER Key for the
First (Desired) Group
or
Press UP/DOWN Keys
to Select Desired Parameter
7
Zenex Plus User Manual
Notes
The Last Parameter in the selected Group rolls back to the ‘SELECT GROUP’ screen again to avoid re-entering the password in case parameters under multiple groups need to be set.
Parameter Descriptions
The various Supervisory Parameters have been described with their respective group & sub-group.
SUPERVISORY SENSOR INPUT
Parameter Description
ZERO OFFSET >>
This value is algebraically added to the measured Temperature Value at control channel to derive the final value that is displayed and compared for alarm / control. Use this value to nullify any known constant error.
Final Value = Measured Value + Offset
SUPERVISORY SERIAL PARAMETERS
Parameter Description
DEVICE ID >>
Unique numeric code assigned to the for identification by indicator the host. Set the value as required by the host.
Settings
(Default Value)
-50.0 to 50.0
(Default : 0.0)
Settings
(Default Value)
1 to 127
(Default : 1)
BAUD RATE >>
Communication speed in ‘Bits per Second’. Set the value to match with the host baud rate.
PARITY >>
One of the communication error trapping features. Select the data packet parity as implemented by the host protocol.
SERIAL WRITE PERMISSION >>
Setting to ‘No’ disallows the host to set / modify any parameter value. The host, however, can read the value.
8
2400 4800
9600 19200 38400 57600
(Default : )9600
None Even
Odd
(Default : Even)
No
Yes
(Default : No)
Zenex Plus User Manual
SUPERVISORY CONTROL
Parameter Description
TUNE >>
(Available for Heat Only / Heat+Cool Control Strategy)
Set ‘Yes’ to activate and ‘No’ to abort the Tuning operation.
SETPOINT LO LIMIT >>
This parameter sets the minimum limit on the Control Setpoint value.
SETPOINT HI LIMIT >>
This parameter sets the maximum limit on the Control Setpoint value.
COMPRESSOR SETPOINT >>
(Available for ‘Heat + Cool’ Control Compressor PV with based Strategy)
This Setpoint Value is compared with the process value to switch the compressor On/Off with the set compressor hysteresis.
Settings
(Default Value)
Yes
No
(Default : No)
For Thermocouple Input :
-200 to Setpoint HI Limit For RTD Input :
-99.9 to Setpoint HI Limit (Default : 0.0)
For Thermocouple Input : Setpoint LO Limit to 9999
For RTD Input :
Setpoint LO Limit to 600.0
(Default : 600.0)
0.0 to 100.0
(Default : 45.0)
COMPRESSOR HYST >>
(Available for ‘Cool Only’ ‘Heat + Cool’ Control & with Compressor PV based Strategy)
Differential (dead) band between the compressor ON and OFF states.
HEAT CTRL ACTION >>
(Available for ‘Heat Only’ & ‘Heat+Cool’ Control Strategy)
On-Off
The control algorithm tends to maintain the PV at SP by either switching the output (say, Heater) fully OFF or fully ON. The On and Off switching is differentiated by the user settable ‘Hysteresis Band’.
PID
The control algorithm uses a 2nd order equation to compute the ‘% Output Power’ required to maintain the PV at SP. The constants P, I, D are automatically set by the controller.
HEAT HYST >>
(Available for ‘ON-OFF’ Heat Control Action)
Sets a differential (dead) band between the ON and OFF states. Keep it large enough to avoid frequent switching of the load without losing the desired control accuracy.
0.1 to 99.9
(Default : 2.0)
ON-OFF
PID
(Default : PID)
0.1 to 99.9
(Default : 0.2)
9
Zenex Plus User Manual
Heat Only Control
PROPORTIONAL BAND >>
0.1 to 999.9
(Default : 50.0)
INTEGRAL TIME >>
0 to 3600 sec
(Default : 100 sec)
DERIVATIVE TIME >>
0 to 600 sec
(Default : 16 sec)
CYCLE TIME >>
0.5 to 100.0 sec
(Default : 10.0 sec)
Heat + Cool
Control Zone : Single
PROPORTIONAL BAND >>
0.1 to 999.9
(Default : 50.0)
INTEGRAL TIME >>
0 to 3600 sec
(Default : 100 sec)
DERIVATIVE TIME >>
0 to 600 sec
(Default : 16 sec)
CYCLE TIME >>
0.5 to 100.0 sec
(Default : 10.0 sec)
Heat + Cool
Control Zone : Dual
CZ PROP BAND >>
Proportional Band for
Cool Pre-dominant zone
0.1 to 999.9
(Default : 50.0)
CZ INTEGRAL TIME >>
Integral Time for
Cool Pre-dominant zone
0 to 3600 sec
(Default : 100 sec)
CZ DERIVATIVE TIME >>
Derivative Time for
Cool Pre-dominant zone
0 to 600 sec
(Default : 16 sec)
HZ PROP BAND >>
Proportional Band for
Heat Pre-dominant zone
0.1 to 999.9
(Default : 50.0)
OVERSHOOT INHIBIT >>
Enable
Disable
(Default : Disable)
CUTOFF FACTOR >>
1.0 to 2.0 sec
(Default : 1.2 sec)
OVERSHOOT INHIBIT >>
Enable
Disable
(Default : Disable)
CUTOFF FACTOR >>
1.0 to 2.0 sec
(Default : 1.2 sec)
HZ INTEGRAL TIME >>
Integral Time for
Heat Pre-dominant zone
0 to 3600 sec
(Default : 100 sec)
HZ DERIVATIVE TIME >>
Derivative Time for
Heat Pre-dominant zone
0 to 600 sec
(Default : 16 sec)
CYCLE TIME >>
0.5 to 100.0 sec
(Default : 10.0 sec)
OVERSHOOT INHIBIT >>
Enable
Disable
(Default : Disable)
CUTOFF FACTOR >>
10
1.0 to 2.0 sec
(Default : 1.2 sec)
Zenex Plus User Manual
PROPORTIONAL BAND
Sets proportional gain (% power per unit error). Defined in same units and resolution as that for PV.
INTEGRAL TIME
Sets integral time constant in Seconds. Setting the value to 0, cuts-off the integral action.
DERIVATIVE TIME
Sets derivative time constant in seconds. Setting the value to 0, cuts-off the derivative action.
CYCLE TIME
Sets the total ‘On + Off’ time in seconds for time proportional power output through Relay / SSR for OP1.
OVERSHOOT INHIBIT Set this parameter to ‘Enable’ if the process exhibits unacceptable overshoot upon start-up or a step change in SP. If enabled, the controller controls the rate of change of PV to minimize overshoot while approaching the target SP.
CUTOFF FACTOR
This parameter adjusts the effectiveness of the Overshoot Inhibit feature. Increase the value if the overshoot is curbed but the PV takes longer to reach the SP. Decreases the value if the overshoot persists.
SUPERVISORY PASSWORD
Parameter Description
CHANGE PASSWORD >>
The Controller is shipped from the factory with a default password ( ) for accessing the parameters reserved for the 123 equipment manufacturer. owever, if required the password can be changed H by setting the new value for this parameter.
(The new password replaces the old password. hat is, the old T password is no longer valid. it is user’s responsibility to memorize the password.)
SUPERVISORY EXIT
Parameter Description
Settings
(Default Value)
1000 to 1999
(Default : 123)
EXIT SETUP MODE >>
Select to quit Setup mode and return to Main Display mode.
11
Zenex Plus User Manual
Section 5
FACTORY PARAMETERS
The various parameters have been assembled in various group under the default factory password 321.
Refer Table 5.1 below for a quick summary of parameters under different groups. Each parameter has been described in subsequent sections.
Table 5.1
Group
Sensor Input
Alarm
Input Type, Filter Constant
Hysteresis, Inhibit
Parameters
Control Strategy, Compressor Strategy, Boundary Set Value,
Heat Cool Select
Control Zones, Time Delay (Sec)
Enable, Start Band, Holdback Strategy, Hold Band,
Timer
Door Open
Factory Default
Password
Exit
Heat Off, Cool Off, Power Recovery
Enable/Disable, Switch Logic, Door Alarm Delay
Set to Default Yes/No
Change Password
Exit Setup Mode
Accessing Group & Parameters
The Figure 5.1 below illustrates how to access the group and parameters. The example shows changing the value for the parameter ‘Hysteresis’ that is located under group ‘Alarm’ from 0.2°C to 0.5°C.
Figure 5.1
SELECT GROUP>>
CTRL SENSOR INPUT
or
TEMP HIGH
25.0
°C
SP
25.0
ENTER PASSWORD >>
0
or
ENTER PASSWORD >>
321
RUN Mode
Main Screen
SELECT GROUP>>
ALARM
Desired Group
for Operator Parameters
Press SET-UP Key for Password Entry
Press ENTER Key
to Access
Desired Parameters
Default Password
Press UP/DOWN Keys
HYSTERESIS >>
0.2
First Parameter in
selected group
To adjust Password
Value
or
Press UP/DOWN
Keys to Adjust
parameter Value
Desired Password
ENTER Key for the
HYSTERESIS >>
0.5
Desired Parameter
Value
Press ENTER Key
to Store the New Value
& Move to Next Parameters
Press & Release
First Group
First Group
Press UP/DOWN
Keys to Select Desired Group
INHIBIT >>
YES
Next Parameter in
selected group
Notes
The Last Parameter in the selected Group rolls back to the ‘SELECT GROUP’ screen again to avoid re-entering the password in case parameters under multiple groups need to be set.
12
Zenex Plus User Manual
Parameter Descriptions
The various Factory Parameters have been described with their respective group & sub-group.
FACTORY CONTROL SENSOR INPUT
Parameter Description
INPUT TYPE >>
Select Input type in accordance with the type of Temperature sensor (Thermocouple / RTD) connected for measurement.
FILTER CONSTANT >>
Sets the time constant, in Seconds, for the low-pass digital filter applied to the measured PV. The filter helps smoothing / averaging the signal input and removing the undesired noise. The higher the filter value the lower the indication response to the PV changes and vice-a-versa.
Table 5.2
Option
Type J (Fe-K)
Type K (Cr-Al)
Range (Min. to Max.)
0 to +960°C
-200 to +1376°C
Settings
(Default Value)
Refer Table 5.2
(Default : RTD Pt100)
0.5 to 60.0
(Default : 0.5)
Resolution & Unit
Type T (Cu-Con)
Type R (Rh-13%)
Type S (Rh-10%)
Type B
Type N
Reserved for customer specific Thermocouple type not listed above. The type shall be specified in accordance with the ordered (optional on request) Thermocouple type.
RTD Pt100
-200 to +387°C
0 to +1771°C
0 to +1768°C
0 to +1826°C
0 to +1314°C
-99.9 to +600.0°C
1 °C
0.1 °C
13
Zenex Plus User Manual
FACTORY ALARM PARAMETERS
Parameter Description
HYSTERESIS >>
This parameter sets a differential (dead) band between the ON and OFF Alarm status change. Keep it large enough to avoid frequent switching of the Alarm Status/Relay.
INHIBIT >>
Yes
The Alarm activation is suppressed until the Temperature value is within Alarm limits from the time the controller is switched ON. This allows suppressing the Alarm during the start-up Alarm conditions.
No
The Alarm is not suppressed during the start-up Alarm conditions.
Settings
(Default Value)
0.1 to 99.9
(Default : 0.2)
YES
NO
(Default : YES)
FACTORY
The PPI “Multi-Purpuse Temperature Controller” provides control outputs for driving, both, heating & cooling sources. The user can enable any one or both outputs depending upon the test equipment type and application. If both outputs are enabled (by setting the parameter ‘Control Strategy’ to Heat + Cool) and if the cooling source is compressor then the controller offers various strategies for switching the compressor as described below.
HEAT COOL SELECT
Compressor Switching Strategies
1. Compressor Off
The compressor is kept Off. This strategy is usually selected for temperature values significantly above the ambient
temperature.
2. Compressor On
The compressor is kept On regardless of the measured or set temperature value. This strategy is usually selected for
temperature values significantly below the ambient temperature.
3. SP Based Strategy
In this strategy, the chamber temperature range is split in two zones by setting the parameter 'Boundary Set-point' (BSP).
Refer Figure 5.2.
14
Zenex Plus User Manual
Figure 5.2
70°C
Temp. Control SP in
Heat Pre-dominant Zone
50°C
Boundary Set-point
Compressor Status
45°C
30°C
0°C
ON
OFF
Temp. Control SP in
Cool Pre-dominant Zone
The zone at and above the boundary SP ( ) is referred as Heat Pre-dominant zone and that below the boundary SP ) ( is referred as Cool Pre-dominant zone. The controller automatically switches between the two zones depending upon the Temperature SP. If the Temperature SP is below boundary SP, Cool Pre-dominant zone is active and the compressor is kept ON. If the Temperature SP is at or above boundary SP, Heat Pre-dominant zone is active and the compressor is kept OFF. This strategy eliminates the need for the user to manually switch the compressor ON or OFF.
I Control Zones “Dual”; separate tuning can be performed in the Cool and Heat Pre-dominant zones for f the parameter is set to accurate control in each zone. The controller maintains separate sets of Proportional Band, Integral Time & Derivative Time constants for each zone that are automatically selected and used by the controller depending upon the active zone.
However, if the parameter Control Zones is set to “Single”; the controller uses a single set of Proportional Band, Integral Time & Derivative Time constants for both zones.
4. PV Based Strategy
In this strategy, the compressor is switched to cool down the air temperature. The controller switches the compressor ON
or OFF based on the comparison between the et emperature values. Refer Figure below.Measured & S T 5.3
Figure 5.3
Measured Temperature Temperature SP
Compressor Switch-ON Level Compressor Switch-OFF Level
Temperature SP = 20.0°C Compressor Set-point = 1.0°C Compressor Hysteresis = 1.2°C
Compressor Switch-ON Level = 20.0 + 1.0 = 21.0°C Compressor Switch-OFF Level = 21.0 - 1.2 = 19.8°C
21.0
20.0
19.8
ON
°C
Compressor Status
OFF
The compressor is turned ON if the chamber air temperature value is above the Temperature SP by an amount set by the parameter 'Compressor Set-point'. That is;
Compressor Switch - ON Level = (Temperature SP) + (Compressor Set-point)
15
Zenex Plus User Manual
Once the air temperature falls below Compressor Switch-ON Level by an amount set by the parameter 'Compressor Hysteresis', the compressor is turned OFF. That is;
Compressor Switch - OFF Level = (Compressor Switch-ON Level) – (Compressor Hysteresis)
The hysteresis inserts a dead band between the Compressor Switch-ON Level and Compressor Switch-OFF Level to avoid frequent switching of the compressor.
Compressor Time Delay
Once the compressor is switched off, a time delay is desired before it is turned ON again. The time delay prevents the possible damage due to short cycling. When the compressor switches off, it spins backward as pressure equalizes. If compressor is energized while it is still spinning backward, it continues to run backward until it trips on internal overloads. This may cause damage to the compressor.
The time delay cycle is executed every time the compressor is turned off. The compressor turning off may be a result of power failure or the on-off control algorithm executed by the controller. The controller in “Auto Mode” monitors the Process Value (PV) against the Set-Point (SP) and attempts to switch the compressor ON or OFF depending upon whether the PV is above or below the SP.
The time delay starts counting down from the instance the compressor is switched off. The compressor is inhibited from switching-on until the delay elapses regardless of the difference between the PV and SP. Once the time delay is elapsed, the control algorithm switches the compressor ON as and when the PV is above SP.
Figure 5.4
°C
PV (Temperature) SP
Compressor Switch-ON Level Compressor Switch-OFF Level
Temperature SP = 20.0°C Compressor Set-point = 1.0°C Compressor Hysteresis = 1.2°C
Compressor Switch-ON Level = 20.0 + 1.0 = 21.0°C Compressor Switch-OFF Level = 21.0 - 1.2 = 19.8°C
Compressor Status
21.0
20.0
19.8
ON
OFF
Case 2 Case 3Case 1
The figure 5.4 above illustrates 3 cases. Case (1) illustrates power-up delay. In case (2); the time elapses before PV rises above the SP. The compressor is thus switched ON as soon as the PV rises above the SP. In case (3); the PV rises above the SP while the time delay is still in progress. The compressor is switched ON as soon as the delay time elapses.
Table 5.2 lists various parameters required for setting-up appropriate compressor switching strategy and associated parameters.
For parameter description the user is requested to read the preceding section.
16
Zenex Plus User Manual
Table 5.2
Parameter Description
CONTROL STRATEGY >>
Heat Only
Used in applications like Heating Oven, Vacuum Oven, Muffle Furnace, etc.; that require raising the temperature above ambient. The (Heater) control output switches ‘heating source’ for HTR maintaining the temperature at desired setpoint. The CMP (Compressor) control output is inactive (kept off).
Cool Only
Used in applications like Deep Freezer, Cold Cabinet, Lab Refrigerator, etc.; that require lowering the temperature below ambient. The (Compressor) control output switches ‘cooling CMP source’ for maintaining the temperature at desired setpoint. The HTR (Heater) control output is inactive (kept off).
Heat + Cool Used in applications like Environment Chamber, BOD Incubator,
etc.; that require either lowering the temperature below or rasing the temperature above ambient. Both, the (Compressor) CMP and (Heater) control outputs switch ‘cooling source’ & HTR ‘heating source’, respectively, for maintaining the temperature at desired setpoint.
Settings
(Default Value)
Heat Only Cool Only
Heat + Cool
(Default : Heat + Cool)
TIME DELAY (SEC) >>
COMPRESSOR >>STRATEGY
CONT. ON SP BASED PV BASED
TIME DELAY (SEC) >>
0 to 1000 Sec
(Default : 200 Sec)
Control Strategy : Cool Only
Control Strategy : Heat + Cool
BOUNDARY SET VALUE >>
0.0 to 100.0
(Default : 45.0)
CONTROL ZONES >>
SINGLE
DUAL
(Default : SINGLE)
0 to 1000 Sec
(Default : 200 Sec)
CONT. OFF
CONT. ON SP BASED
PV BASED
(Default : SP BASED)
TIME DELAY (SEC) >>
0 to 1000 Sec
(Default : 200 Sec)
TIME DELAY (SEC) >>
0 to 1000 Sec
(Default : 200 Sec)
17
Zenex Plus User Manual
FACTORY TIMER PARAMETERS
Parameter Description
ENABLE >>
Yes
Timer function and Start / Abort commands are enabled.
No
Timer function and Start / Abort commands are disabled.
START BAND >>
After issuance of start command, the timer starts counting down once the PV enters the process band around SP defined by this parameter value.
HOLDBACK STRATEGY >>
None
PV based timer pause is not required.
Up Timer is paused if PV is outside holdband SP.above
Down Timer is paused if PV is outside holdband SP.below
Settings
(Default Value)
No
Yes
(Default : No)
0 to 999.9
(Default : 0.5)
None
Up
Down
Both
(Default : None)
Both
Timer is paused if PV is outside holdband either above or below SP.
HOLD BAND >>
Sets the temperature limit(s) with respect to the SP for the timer to pause. The timer holds on counting should the PV cross the limit(s).
HEAT OFF >>
Heater is turned off, once Timer operation is over.
COOL OFF >>
Compressor is turned off, once Timer operation is over.
POWER RECOVERY >>
Abort
The timer operation is suspended until a new start command is issued.
Re-Start
The timer re-runs the complete time.
0.1 to 999.9
(Default : 0.5)
No
Yes
(Default : No)
No
Yes
(Default : No)
Abort
Restart
Continuous
(Default : Restart)
Continue
The Timer resumes operation for the balance time.
18
Zenex Plus User Manual
FACTORY DOOR OPEN
Parameter Description
ENABLE >>
Set to ‘Yes’ if is mounted for detecting Switch door Open / Close position.
SWITCH LOGIC >>
Close : Door Open The Door position is considered if the switch is CLOSE.Open
Open : Door Open The Door position is considered if the switch is OPEN.Open
DOOR ALRM DLY (SEC) >>
This parameter sets a timer. From the time the door is opened, the timer begins counting down. If the door is not closed before the timer reaches 0, the Door Open alarm is activated.
FACTORY FACTORY DEFAULT
Settings
(Default Value)
YES
NO
(Default : NO)
CLOSE : DOOR OPEN
OPEN : DOOR OPEN
(Default : CLOSE : DOOR OPEN)
0 to 1000 Sec
(Default : 60 Sec)
Parameter Description
SET TO DEFAULT >>
Set to ‘Yes’ to set all the parameter values to their Default alues.V
FACTORY PASSWORD
Parameter Description
CHANGE PASSWORD >>
The Controller is shipped from the factory with a default password (321) for accessing the parameters reserved for the equipment manufacturer. owever, if required the password can be changed H by setting the new value for this parameter.
(The new password replaces the old password. hat is, the old T password is no longer valid. it is user’s responsibility to memorize the password.)
Settings
(Default Value)
YES
NO
(Default : NO)
Settings
(Default Value)
2000 to 2999
(Default : 321)
19
Zenex Plus User Manual
FACTORY
EXIT SETUP MODE >>
Select to quit mode and return to mode.Setup Main Display
EXIT
Parameter Description
20
Zenex Plus User Manual
Section 6
PANEL MOUNTING AND ELECTRICAL CONNECTIONS
WARNING MISH A N D L I N G / NE G L I G E N C E CAN RESULT IN PERSONAL DEATH OR SERIOUS INJURY.
PANEL CUTOUT
Figure 6.1(a) : Old Version
Figure 6.1(b) : New Version
Panel Cutout
75 X 152 mm
-0, +1.0 mm
Panel Cutout
75 X 150 mm
-0, +1.0 mm
PANEL MOUNTING
Follow the steps below for mounting the instrument on panel :
1. Prepare a cutout to the size shown in Figure 6.1.
2. Remove the Panel Mounting Clamp from the instrument Enclosure.
3. Insert the rear of the enclosure through the panel cutout from the front of the mounting panel.
4. Fix the mounting clamp pair such that it ensures secured mounting of the enclosure against the panel wall.
ELECTRICAL CONNECTIONS
1. The user must rigidly observe the Local Electrical Regulations.
2. Do not make any connections to the unused terminals for making a tie-point for other wires (or for any other reasons) as they may have some internal connections. Failing to observe this may result in permanent damage to the controller.
3. Run power supply cables separated from the Sensor cables (Thermocouple / RTD). If the cables are run through conduits, use separate conduits for power supply cable and low-level signal cables.
4. Use appropriate fuses and switches, wherever necessary, for driving the high voltage loads to protect the controller from any possible damage due to high voltage surges of extended duration or short-circuits on loads.
5. Take care not to over-tighten the terminal screws while making connections.
6. Make sure that the controller supply is switched-off while making/removing any connections or removing the controller from its enclosure.
CONNECTION DIAGRAM
The Electrical Connection Diagram is shown on the Top (Old Version) or Back (New Version) side of the controller enclosure. The diagram shows the terminals viewed from the REAR SIDE with the controller Front Label upright. Refer figure 6.2(a) for Old Version & 6.2(b) for New Version.
21
Zenex Plus User Manual
Figure 6.2(a) :
Old Version
1 2
Pt100
TC
Heater Control
-
+
14
15
23 3227
25 31302928
24
-
+
EXT.
VOLTAGE
DO-1 DO-2 DO-3
+-+-+
2 3
1
3
Control
+
-
- -
+
Compressor
16 17
26
AI-1 AI-2
DO-4
-
4
+
4
Process
Alarm
+ +
18
DO-5
-
-
+
9 106 7 85
5
6
Event
Alarm
19 20 21
Figure 6.2(b) :
New Version
AI-1 : Process Sensor
Connections
2625
Zenex Plus B124-V2
+
DI-1
DI-2
DO-6
+
11
DI-3
-
12
15 16
14
13
7
-
27
28
Pt100
TC
-
DI-4
DI-5
DI-6
17
19 20
18
8 9 10
Door Open
Timer Start
Alarm ACK
22 23
Digital Output
DO-1 : Heater Control DO-2 : Compressor Control DO-3 : Process Alarm DO-4 : Event Alarm DO-5 : Unused DO-6 : Unused
Digital Input
DI-1 : Door Open DI-2 : Timer Start DI-3 : Alarm ACK DI-4 : Unused DI-5 : Unused DI-6 : Unused
24
11 12
B+ B-
RS485
Serial
85 ~ 264
26 27
25
SERIAL COMM
85~265VAC
Supply
VAC
L
33 34
B+ B-
RS485
L N
22
21
13
B124
Zenex Plus
N
TEMPERATURE SENSOR INPUT
Connect Thermocouple or 3-wire RTD Pt100 sensor as shown below.
RTD Pt100, 3-wire
Connect single leaded end of RTD bulb to terminal T2 and the double leaded ends to terminals T3 and T4 (interchangeable) as shown in Figure 6.3. Use low resistance copper conductor leads of the same gauge and length. Avoid joints in the cable.
Thermocouple
Connect Thermocouple Positive (+) to terminal T2 and Negative (-) to terminal T3 as shown in Figure 6.3. Use correct type of extension lead wires or compensating cable. Avoid joints in the cable.
22
Old Version
New Version
SUPPLY
Figure 6.3
T1
1
25
Pt100
TC
T2
2
26
+
T3
3
27
T4
4
28
-
Zenex Plus User Manual
DIGITAL OUTPUTS
Heater Control Output Compressor Control Output Process Alarm Output Event Alarm Output
All the above Control & Alarm outputs are Voltage pulses (12VDC @ 40mA) for driving external SSR or Relay. The ‘+’ and ‘-’ terminals are for voltage ‘Source’ and ‘Return’ paths, respectively. Refer Figure 6.4 below.
Figure 6.4
Heater
Control
+
New Version
Old Version
DIGITAL INPUTS
Door Open Timer Start Alarm Acknowledge
Potential-free contact closure input terminals are provided as digital inputs. An ‘Open’ or ‘Close’ switch position is detected as input. Refer Figure 6.5.
PC COMMUNICATION PORT
1
14
-
2
15
Compressor
Control
+
3
16
-
4
17
Process
Alarm
+
5
-
6
19
DI-1:Door Open DI-2:Timer Start DI-3:Alarm ACK
New Version
Old Version
Event Alarm
+
7
20
-
8
2118
Figure 6.5
DI-1
13
14
23
DI-2
DI-3
15
24
16
2522
Figure 6.6
B+
Terminating Resistor
(100 to 150 Ohms)
Twisted Wire Pair
New
Version
34
Version
B-
Old
12
PC
33 B+
B-
The controller Communication Port is RS485 and requires a similar port at the host (master) end. If, however, the host port is different (say, RS232 or USB), use appropriate protocol converter (say, RS485-RS232 or USB to RS485) for interface.
For reliable noise free communication, use a pair of twisted wires inside screened cable as shown in Figure . The wire 6.6 should have less than 100 ohms / km nominal DC resistance (Typically 24 AWG or thicker). Connect the terminating resistor (Typically 100 to 150 ohm) at one end to improve noise immunity.
Screened Cable
Serial Comm.
23
11
Terminals
Zenex Plus User Manual
POWER SUPPLY
As standard, the is supplied with power connections suited for 8 to 264 VAC line supply. Use well-insulated module 5 copper conductor wire of the size not smaller than 0.5mm² for power supply connections ensuring proper polarity as shown in Figure 6.7. module The is not provided with fuse and power switch. If necessary, mount them separately. Use a time lag fuse rated 1A @ 240 VAC.
Figure 6.7
Line
Neutral
Fuse
2 Pole
Isolating Switch
New
Version
Old
Version
21 L
22 N2627
Power Supply Terminals
24
Zenex Plus User Manual
Process Precision Instruments
101, Diamond Industrial Estate, Navghar, Vasai Road (E),
Dist. Palghar - 401 210.Maharashtra, India
0250 - 2391722/33/37/42 07498799226, 09321985369
support@ppiindia.net sales@ppiindia.net,
25
w w w . p p i i n d i a . n e t
Apr 2019
Loading...