The Controller front panel comprises of Graphic Readout and Membrane Keys as shown in Figure 1.1 below.
Figure 1.1
PPI
Graphic
Readout
Zenex Plus
GRAPHIC READOUT
The Graphic Readout is a X Pixel Monochrome LCD Display. In Normal operation mode the Readout shows 12864measured
Temperature Value, Set Temperature Value, Alarm / Process Status & Balance Time (if enabled & running). The Process
Status Information can be viewed using screen scroll feature.
In Mode, the Readout displays parameter names and values that can be edited using front keys.Set-up
KEYS
There are six tactile keys provided on the front panel for configuring the and setting-up the parameter values. controller
The Table 1. below lists each key (identified by the front panel symbol) and the associated function. 1
Symbol
Key
25.8
TEMP HIGH
0:10:00
Table 1.1
SP
°C
Keys
25.0
Function
Scroll
Alarm
Acknowledge
DOWN
UP
SET-UP
ENTER
Press to scroll through various Process Information Screens in
Normal Operation Mode.
Press to acknowledge and mute (if active) alarm output.
Press to decrease the parameter value. Pressing once
decreases the value by one count; keeping pressed speeds up
the change.
Press to increase the parameter value. Pressing once
increases the value by one count; keeping pressed speeds up
the change.
Press to enter or exit set-up mode.
Press to store the set parameter value and to scroll to the next
parameter.
1
Zenex PlusUser Manual
Section 2
BASIC OPERATIONS
Figure 2.1
POWER-UP DISPLAY
Upon power-up the controller displays model name, Hardware Version
and Software Version for 2 seconds as shown in figure 2.1.
H/W Version
S/W Version
RUN MODE
After the Power-up display the controller enters into RUN Mode. This is the normal operation mode wherein the controller
starts PV measurements, Alarm monitoring and Control Loop execution.
Main Screen
This is the default screen and its appearance depends upon whether a timer function is enabled or disabled as shown in the
figures 2.2 (a) & 2.2 (b) respectively.
Figure 2.2(a) : Timer Disabled
Measured Temperature
Alarm / Process
Status
25.0
TEMP HIGH
SP
°C
25.0
Set Temperature
02
07
Figure 2.2(b) : Timer Enabled
Note :
The Balance Time is shown in either HHH:MM or H:MM:SS
depending upon the remaining time counts as under :
HHH:MM for 249:59 to 10:00
H:MM:SS for 9:59:59 to 0:00:00
Balance Time
In case of measured value errors, the messages listed in Table 2.1 flash in place of process value as illustrated in Figure 2.3.
Table 2.1
Message Error Type
OPEN
OVR
UNR
Sensor Open
Over-range
Under-range
RTD Pt100 / Thermocouple is Broken / Open
Temperature above Max. Specified Range
Temperature below Min. Specified Range
Cause
0:10:00
25.0
TEMP HIGH
SP
25.0
TEMP HIGH
°C
Figure 2.3
OPEN
Measured
Temperature
Alarm / Process
Status
Set Temperature
°C
SP
25.0
2
Zenex PlusUser Manual
The Alarm / Process Status space on the screen may show one or more of the several messages listed in Table 2.2 depending
upon the existence of active alarms or process events. In case of co-existence of multiple active alarms or process events, the
messages are scrolled one after the other with an approximate time interval of 3 seconds. Also if there is no active alarm or
process event, the message space is blank.
Table 2.2
Message StringAlarm / Process Status
Temp High
Temp Low
Tuning
Door Open
Timer Hold
Process Status Screen
The Process Status Screen is shown upon pressing (Scroll) key from Main Screen or upon acknowledging a new Alarm by
pressing (Acknowledge) key. As depicted in Figure 2.4(a) for Old Version & 2.4(b) for New Version; the screen shows
Temperature Alarm Status, Door Open / Close Status, the Heater Output Status (ON / OFF or % Power) & Compressor ON /
OFF Status.
The measured temperature is in Process High
Alarm State.
The measured temperature is in Process Low
Alarm State.
The Controller is Self Tuning.
The Equipment / Chamber door is open for a time
longer than the set ‘DOOR ALRM DLY’ time.
The Countdown Timer is paused since the PV is
outside Hold Band.
Figure 2.4(a) :
Old Version
Temperature
Alarm Status
Heating Control
Output Power
Temperature
Alarm Status
Heating Control
Output Power
PROCESS STATUS
°C
High
Heating
0.0%
Figure 2.4(b) :
New Version
Process Status
Temp
High
Heater
0.0%
Compressor
Door
Close
Compressor
OFF
Door
Close
OFF
Door Status
Compressor
Output Status
Door Status
Compressor
Output Status
3
Zenex PlusUser Manual
Figure 2.5 (a)
Temperature Alarm Status
Temp
Normal
Temp
Low
Temp
High
Within
Limits
Below
Low Limit
Above
High Limit
Figure 2.5 (b)
Door Status
Door
Close
Door
Open
The Controller provides programmable Low & High deviation
limits around the temperature control setpoint to monitor Alarm
conditions. The screen shows either Normal or Low or High
Status, as shown in Figure 2.5 (a) depending upon the
deviation of measured temperature value from the control
setpoint and set limits.
The Controller provides a Digital Input for interfacing Door
switch that senses the door position, Open or Close. The
screen indicates the door status as shown in Figure 2.5 (b).
4
Zenex PlusUser Manual
Section 3
OPERATOR PARAMETERS
The Operator Parameters are accessible under PASSWORD 0. The list includes parameters for adjusting Control Setpoint,
Alarm Setpoints & Zero-offset. If Timer is enabled then Time Interval value & Timer Start / Abort commands are also available.
The Figure 3.1 shows how to access Operator Parameters. The Example illustrates changing the Low Deviation alarm value
from 2.0 to 5.0. (The Example is shown with Timer disabled).
Figure 3.1
ENTER PASSWORD >>
2.0
°C
SP
25.0
Press SET-UP Key
for Password Entry
or
Press UP/DOWN Keys
to adjust Parameter Value
0
Default Password
for Operator Parameters
Press ENTER Key
To open Operator
LO DEVIATION >>
5.0
Desired Value
Press ENTER Key
to store the New Value
25.0
TEMP HIGH
RUN Mode
Main Screen
LO DEVIATION >>
Desired Parameter
& to move to Next Parameter
The Table 3.1 below described the Operator Parameters in detail.
Table 3.1
Parameter Description
Parameter List
CTRL SET VALUE >>
25.0
First Parameter
Press & Release
ENTER Key until Desired
Parameter appears
HI DEVIATION >>
2.0
Next Parameter
Settings
(Default Value)
TIME START COMMAND >>
TIME ABORT COMMAND >>
(Available only if Timer is Enabled)
These two commands are mutually exclusive.
Set to Yes to start Timer, if not already started.
Set to Yes to abort a running timer.
TIME INTERVAL (H:M) >>
(Available only if Timer is Enabled)
The set time value for the timer in Hours : Minutes.
Yes
No
(Default : No)
0.01 to 249.59
(HH:MM)
(Default : 0.10)
5
Zenex PlusUser Manual
Parameter Description
CTRL SET VALUE >>
This parameter sets the value at which the controller atte to mpts
maintain the measured temperature value.
LO DEVIATION >>
This Parameter sets a negative deviation (offset) limit with respect
to the ‘’. The Alarm is activated if the measured Control Set-point
temperature value falls below this limit.
HI DEVIATION >>
This Parameter sets a negative deviation (offset) limit with respect
to the ‘Control Set-point’. The Alarm is activated if the measured
temperature value exceeds this limit.
CHANGE PASSWORD >>
The Controller is shipped from the factory with a default password
(0) for accessing the parameters reserved for Operator. However,
if required the password can be changed by setting the new value
for this parameter.
(The new password replaces the old password. That is, the old
password is no longer valid. it is user’s responsibility to memorize
the password.)
Settings
(Default Value)
Setpoint LO limit to
Setpoint HI limit
(Default : 25.0)
0.2 to 99.9
(Default : 2.0)
0.2 to 99.9
(Default : 2.0)
1 to 100
(Default : 0)
6
Zenex PlusUser Manual
Section 4
SUPERVISORY PARAMETERS
The various parameters have been assembled in different groups under the default factory password 123.
Refer Table 4.1 below for a quick summary of parameters under different groups. Each parameter has been described in
subsequent sections.
Heat Control Action, Heat Hysteresis,
CZ Proportional Band, CZ Integral Time, CZ Derivative Time,
HZ Proportional Band, HZ Integral Time, HZ Derivative Time,
Cycle Time, Overshoot Inhibit, Cutoff Factor
Password
Exit
Change Password
Exit Setup Mode
Accessing Group & Parameters
The Figure 4.1 below illustrates how to access the group and parameters. The example shows changing the value for the
parameter ‘Setpoint High Limit’ from 600.0 to 100.0 that is located under group ‘Control’.
Figure 4.1
TEMP HIGH
25.0
ENTER PASSWORD >>
°C
SP
25.0
0
or
ENTER PASSWORD >>
123
RUN Mode
Main Screen
SELECT GROUP>>
SERIAL
First Group
SETPOINT HI LIMIT >>
600.0
Desired Parameter
for Operator Parameters
Press SET-UP Key
for Password Entry
SELECT GROUP>>
or
Press UP/DOWN Keys
to Select Desired Group
SETPOINT HI LIMIT >>
or
Press UP/DOWN Keys
to adjust Parameter Value
Default Password
CONTROL
Desired Group
100.0
Desired Parameter
Value
Supervisory Parameters
Press UP/DOWN Keys
To adjust Password Value
Press ENTER Key
to Access Parameters
Press ENTER Key to
store the Value
and move to Next
Parameter
Password for
TUNE >>
NO
First Parameter in
selected Group
HEAT CTRL ACTION >>
PID
Next Parameter
Press & Release
ENTER Key for the
First (Desired) Group
or
Press UP/DOWN Keys
to Select Desired Parameter
7
Zenex PlusUser Manual
Notes
The Last Parameter in the selected Group rolls back to the ‘SELECT GROUP’ screen again to avoid re-entering the password in case
parameters under multiple groups need to be set.
Parameter Descriptions
The various Supervisory Parameters have been described with their respective group & sub-group.
SUPERVISORYSENSOR INPUT
Parameter Description
ZERO OFFSET >>
This value is algebraically added to the measured Temperature
Value at control channel to derive the final value that is displayed
and compared for alarm / control. Use this value to nullify any
known constant error.
Final Value = Measured Value + Offset
SUPERVISORYSERIAL PARAMETERS
Parameter Description
DEVICE ID >>
Unique numeric code assigned to the for identification by indicator
the host. Set the value as required by the host.
Settings
(Default Value)
-50.0 to 50.0
(Default : 0.0)
Settings
(Default Value)
1 to 127
(Default : 1)
BAUD RATE >>
Communication speed in ‘Bits per Second’. Set the value to match
with the host baud rate.
PARITY >>
One of the communication error trapping features. Select the data
packet parity as implemented by the host protocol.
SERIAL WRITE PERMISSION >>
Setting to ‘No’ disallows the host to set / modify any parameter
value. The host, however, can read the value.
8
2400
4800
9600
19200
38400
57600
(Default : )9600
None
Even
Odd
(Default : Even)
No
Yes
(Default : No)
Zenex PlusUser Manual
SUPERVISORYCONTROL
Parameter Description
TUNE >>
(Available for Heat Only / Heat+Cool Control Strategy)
Set ‘Yes’ to activate and ‘No’ to abort the Tuning operation.
SETPOINT LO LIMIT >>
This parameter sets the minimum limit on the Control Setpoint
value.
SETPOINT HI LIMIT >>
This parameter sets the maximum limit on the Control Setpoint
value.
COMPRESSOR SETPOINT >>
(Available for ‘Heat + Cool’ Control Compressor PV with
based Strategy)
This Setpoint Value is compared with the process value to switch
the compressor On/Off with the set compressor hysteresis.
Settings
(Default Value)
Yes
No
(Default : No)
For Thermocouple Input :
-200 to Setpoint HI Limit
For RTD Input :
-99.9 to Setpoint HI Limit
(Default : 0.0)
For Thermocouple Input :
Setpoint LO Limit to 9999
For RTD Input :
Setpoint LO Limit to 600.0
(Default : 600.0)
0.0 to 100.0
(Default : 45.0)
COMPRESSOR HYST >>
(Available for ‘Cool Only’ ‘Heat + Cool’ Control &with
Compressor PV based Strategy)
Differential (dead) band between the compressor ON and OFF
states.
HEAT CTRL ACTION >>
(Available for ‘Heat Only’ & ‘Heat+Cool’ Control Strategy)
On-Off
The control algorithm tends to maintain the PV at SP by either
switching the output (say, Heater) fully OFF or fully ON. The On
and Off switching is differentiated by the user settable ‘Hysteresis
Band’.
PID
The control algorithm uses a 2nd order equation to compute the
‘% Output Power’ required to maintain the PV at SP. The constants
P, I, D are automatically set by the controller.
HEAT HYST >>
(Available for ‘ON-OFF’ Heat Control Action)
Sets a differential (dead) band between the ON and OFF states.
Keep it large enough to avoid frequent switching of the load
without losing the desired control accuracy.
0.1 to 99.9
(Default : 2.0)
ON-OFF
PID
(Default : PID)
0.1 to 99.9
(Default : 0.2)
9
Zenex PlusUser Manual
Heat Only Control
PROPORTIONAL BAND >>
0.1 to 999.9
(Default : 50.0)
INTEGRAL TIME >>
0 to 3600 sec
(Default : 100 sec)
DERIVATIVE TIME >>
0 to 600 sec
(Default : 16 sec)
CYCLE TIME >>
0.5 to 100.0 sec
(Default : 10.0 sec)
Heat + Cool
Control Zone : Single
PROPORTIONAL BAND >>
0.1 to 999.9
(Default : 50.0)
INTEGRAL TIME >>
0 to 3600 sec
(Default : 100 sec)
DERIVATIVE TIME >>
0 to 600 sec
(Default : 16 sec)
CYCLE TIME >>
0.5 to 100.0 sec
(Default : 10.0 sec)
Heat + Cool
Control Zone : Dual
CZ PROP BAND >>
Proportional Band for
Cool Pre-dominant zone
0.1 to 999.9
(Default : 50.0)
CZ INTEGRAL TIME >>
Integral Time for
Cool Pre-dominant zone
0 to 3600 sec
(Default : 100 sec)
CZ DERIVATIVE TIME >>
Derivative Time for
Cool Pre-dominant zone
0 to 600 sec
(Default : 16 sec)
HZ PROP BAND >>
Proportional Band for
Heat Pre-dominant zone
0.1 to 999.9
(Default : 50.0)
OVERSHOOT INHIBIT >>
Enable
Disable
(Default : Disable)
CUTOFF FACTOR >>
1.0 to 2.0 sec
(Default : 1.2 sec)
OVERSHOOT INHIBIT >>
Enable
Disable
(Default : Disable)
CUTOFF FACTOR >>
1.0 to 2.0 sec
(Default : 1.2 sec)
HZ INTEGRAL TIME >>
Integral Time for
Heat Pre-dominant zone
0 to 3600 sec
(Default : 100 sec)
HZ DERIVATIVE TIME >>
Derivative Time for
Heat Pre-dominant zone
0 to 600 sec
(Default : 16 sec)
CYCLE TIME >>
0.5 to 100.0 sec
(Default : 10.0 sec)
OVERSHOOT INHIBIT >>
Enable
Disable
(Default : Disable)
CUTOFF FACTOR >>
10
1.0 to 2.0 sec
(Default : 1.2 sec)
Zenex PlusUser Manual
PROPORTIONAL BAND
Sets proportional gain (% power per unit error). Defined in same units and resolution as that for PV.
INTEGRAL TIME
Sets integral time constant in Seconds. Setting the value to 0, cuts-off the integral action.
DERIVATIVE TIME
Sets derivative time constant in seconds. Setting the value to 0, cuts-off the derivative action.
CYCLE TIME
Sets the total ‘On + Off’ time in seconds for time proportional power output through Relay / SSR for OP1.
OVERSHOOT INHIBIT
Set this parameter to ‘Enable’ if the process exhibits unacceptable overshoot upon start-up or a step change in SP. If enabled,
the controller controls the rate of change of PV to minimize overshoot while approaching the target SP.
CUTOFF FACTOR
This parameter adjusts the effectiveness of the Overshoot Inhibit feature. Increase the value if the overshoot is curbed but the
PV takes longer to reach the SP. Decreases the value if the overshoot persists.
SUPERVISORYPASSWORD
Parameter Description
CHANGE PASSWORD >>
The Controller is shipped from the factory with a default password
() for accessing the parameters reserved for the 123equipment
manufacturer. owever, if required the password can be changed H
by setting the new value for this parameter.
(The new password replaces the old password. hat is, the old T
password is no longer valid. it is user’s responsibility to memorize
the password.)
SUPERVISORYEXIT
Parameter Description
Settings
(Default Value)
1000 to 1999
(Default : 123)
EXIT SETUP MODE >>
Select to quit Setup mode and return to Main Display mode.
11
Zenex PlusUser Manual
Section 5
FACTORY PARAMETERS
The various parameters have been assembled in various group under the default factory password 321.
Refer Table 5.1 below for a quick summary of parameters under different groups. Each parameter has been described in
subsequent sections.
Table 5.1
Group
Sensor Input
Alarm
Input Type, Filter Constant
Hysteresis, Inhibit
Parameters
Control Strategy, Compressor Strategy, Boundary Set Value,
Heat Cool Select
Control Zones, Time Delay (Sec)
Enable, Start Band, Holdback Strategy, Hold Band,
Timer
Door Open
Factory Default
Password
Exit
Heat Off, Cool Off, Power Recovery
Enable/Disable, Switch Logic, Door Alarm Delay
Set to Default Yes/No
Change Password
Exit Setup Mode
Accessing Group & Parameters
The Figure 5.1 below illustrates how to access the group and parameters. The example shows changing the value for the
parameter ‘Hysteresis’ that is located under group ‘Alarm’ from 0.2°C to 0.5°C.
Figure 5.1
SELECT GROUP>>
CTRL SENSOR INPUT
or
TEMP HIGH
25.0
°C
SP
25.0
ENTER PASSWORD >>
0
or
ENTER PASSWORD >>
321
RUN Mode
Main Screen
SELECT GROUP>>
ALARM
Desired Group
for Operator Parameters
Press SET-UP Key
for Password Entry
Press ENTER Key
to Access
Desired Parameters
Default Password
Press UP/DOWN Keys
HYSTERESIS >>
0.2
First Parameter in
selected group
To adjust Password
Value
or
Press UP/DOWN
Keys to Adjust
parameter Value
Desired Password
ENTER Key for the
HYSTERESIS >>
0.5
Desired Parameter
Value
Press ENTER Key
to Store the New Value
& Move to Next Parameters
Press & Release
First Group
First Group
Press UP/DOWN
Keys to Select
Desired Group
INHIBIT >>
YES
Next Parameter in
selected group
Notes
The Last Parameter in the selected Group rolls back to the ‘SELECT GROUP’ screen again to avoid re-entering the password in case
parameters under multiple groups need to be set.
12
Zenex PlusUser Manual
Parameter Descriptions
The various Factory Parameters have been described with their respective group & sub-group.
FACTORYCONTROL SENSOR INPUT
Parameter Description
INPUT TYPE >>
Select Input type in accordance with the type of Temperature
sensor (Thermocouple / RTD) connected for measurement.
FILTER CONSTANT >>
Sets the time constant, in Seconds, for the low-pass digital filter
applied to the measured PV. The filter helps smoothing /
averaging the signal input and removing the undesired noise. The
higher the filter value the lower the indication response to the PV
changes and vice-a-versa.
Table 5.2
Option
Type J (Fe-K)
Type K (Cr-Al)
Range (Min. to Max.)
0 to +960°C
-200 to +1376°C
Settings
(Default Value)
Refer Table 5.2
(Default : RTD Pt100)
0.5 to 60.0
(Default : 0.5)
Resolution & Unit
Type T (Cu-Con)
Type R (Rh-13%)
Type S (Rh-10%)
Type B
Type N
Reserved for customer specific Thermocouple
type not listed above. The type shall be specified
in accordance with the ordered (optional on
request) Thermocouple type.
RTD Pt100
-200 to +387°C
0 to +1771°C
0 to +1768°C
0 to +1826°C
0 to +1314°C
-99.9 to +600.0°C
1 °C
0.1 °C
13
Zenex PlusUser Manual
FACTORYALARM PARAMETERS
Parameter Description
HYSTERESIS >>
This parameter sets a differential (dead) band between the ON
and OFF Alarm status change. Keep it large enough to avoid
frequent switching of the Alarm Status/Relay.
INHIBIT >>
Yes
The Alarm activation is suppressed until the Temperature value is
within Alarm limits from the time the controller is switched ON. This
allows suppressing the Alarm during the start-up Alarm
conditions.
No
The Alarm is not suppressed during the start-up Alarm conditions.
Settings
(Default Value)
0.1 to 99.9
(Default : 0.2)
YES
NO
(Default : YES)
FACTORY
The PPI “Multi-Purpuse Temperature Controller” provides control outputs for driving, both, heating & cooling sources. The
user can enable any one or both outputs depending upon the test equipment type and application. If both outputs are enabled
(by setting the parameter ‘Control Strategy’ to Heat + Cool) and if the cooling source is compressor then the controller offers
various strategies for switching the compressor as described below.
HEAT COOL SELECT
Compressor Switching Strategies
1. Compressor Off
The compressor is kept Off. This strategy is usually selected for temperature values significantly above the ambient
temperature.
2. Compressor On
The compressor is kept On regardless of the measured or set temperature value. This strategy is usually selected for
temperature values significantly below the ambient temperature.
3. SP Based Strategy
In this strategy, the chamber temperature range is split in two zones by setting the parameter 'Boundary Set-point' (BSP).
Refer Figure 5.2.
14
Zenex PlusUser Manual
Figure 5.2
70°C
Temp. Control SP in
Heat Pre-dominant Zone
50°C
Boundary Set-point
Compressor Status
45°C
30°C
0°C
ON
OFF
Temp. Control SP in
Cool Pre-dominant Zone
The zone at and above the boundary SP () is referred as Heat Pre-dominant zone and that below the boundary SP ) (
is referred as Cool Pre-dominant zone. The controller automatically switches between the two zones depending upon the
Temperature SP. If the Temperature SP is below boundary SP, Cool Pre-dominant zone is active and the compressor is kept
ON. If the Temperature SP is at or above boundary SP, Heat Pre-dominant zone is active and the compressor is kept OFF. This
strategy eliminates the need for the user to manually switch the compressor ON or OFF.
IControl Zones“Dual”; separate tuning can be performed in the Cool and Heat Pre-dominant zones for f the parameter is set to
accurate control in each zone. The controller maintains separate sets of Proportional Band, Integral Time & Derivative Time
constants for each zone that are automatically selected and used by the controller depending upon the active zone.
However, if the parameter Control Zones is set to “Single”; the controller uses a single set of Proportional Band, Integral Time
& Derivative Time constants for both zones.
4. PV Based Strategy
In this strategy, the compressor is switched to cool down the air temperature. The controller switches the compressor ON
or OFF based on the comparison between the et emperature values. Refer Figure below.Measured & S T5.3
The compressor is turned ON if the chamber air temperature value is above the Temperature SP by an amount set by the
parameter 'Compressor Set-point'. That is;
Once the air temperature falls below Compressor Switch-ON Level by an amount set by the parameter 'Compressor
Hysteresis', the compressor is turned OFF. That is;
The hysteresis inserts a dead band between the Compressor Switch-ON Level and Compressor Switch-OFF Level to avoid
frequent switching of the compressor.
Compressor Time Delay
Once the compressor is switched off, a time delay is desired before it is turned ON again. The time delay prevents the possible
damage due to short cycling. When the compressor switches off, it spins backward as pressure equalizes. If compressor is
energized while it is still spinning backward, it continues to run backward until it trips on internal overloads. This may cause
damage to the compressor.
The time delay cycle is executed every time the compressor is turned off. The compressor turning off may be a result of power
failure or the on-off control algorithm executed by the controller. The controller in “Auto Mode” monitors the Process Value (PV)
against the Set-Point (SP) and attempts to switch the compressor ON or OFF depending upon whether the PV is above or
below the SP.
The time delay starts counting down from the instance the compressor is switched off. The compressor is inhibited from
switching-on until the delay elapses regardless of the difference between the PV and SP. Once the time delay is elapsed, the
control algorithm switches the compressor ON as and when the PV is above SP.
The figure 5.4 above illustrates 3 cases. Case (1) illustrates power-up delay. In case (2); the time elapses before PV rises
above the SP. The compressor is thus switched ON as soon as the PV rises above the SP. In case (3); the PV rises above the
SP while the time delay is still in progress. The compressor is switched ON as soon as the delay time elapses.
Table 5.2 lists various parameters required for setting-up appropriate compressor switching strategy and associated
parameters.
For parameter description the user is requested to read the preceding section.
16
Zenex PlusUser Manual
Table 5.2
Parameter Description
CONTROL STRATEGY >>
Heat Only
Used in applications like Heating Oven, Vacuum Oven, Muffle
Furnace, etc.; that require raising the temperature above ambient.
The (Heater) control output switches ‘heating source’ for HTR
maintaining the temperature at desired setpoint. The CMP
(Compressor) control output is inactive (kept off).
Cool Only
Used in applications like Deep Freezer, Cold Cabinet, Lab
Refrigerator, etc.; that require lowering the temperature below
ambient. The (Compressor) control output switches ‘cooling CMP
source’ for maintaining the temperature at desired setpoint. The
HTR (Heater) control output is inactive (kept off).
Heat + Cool
Used in applications like Environment Chamber, BOD Incubator,
etc.; that require either lowering the temperature below or rasing
the temperature above ambient. Both, the (Compressor) CMP
and (Heater) control outputs switch ‘cooling source’ & HTR
‘heating source’, respectively, for maintaining the temperature at
desired setpoint.
Settings
(Default Value)
Heat Only
Cool Only
Heat + Cool
(Default : Heat + Cool)
TIME DELAY (SEC) >>
COMPRESSOR >>STRATEGY
CONT. ONSP BASEDPV BASED
TIME DELAY (SEC) >>
0 to 1000 Sec
(Default : 200 Sec)
Control Strategy : Cool Only
Control Strategy : Heat + Cool
BOUNDARY SET VALUE >>
0.0 to 100.0
(Default : 45.0)
CONTROL ZONES >>
SINGLE
DUAL
(Default : SINGLE)
0 to 1000 Sec
(Default : 200 Sec)
CONT. OFF
CONT. ON
SP BASED
PV BASED
(Default : SP BASED)
TIME DELAY (SEC) >>
0 to 1000 Sec
(Default : 200 Sec)
TIME DELAY (SEC) >>
0 to 1000 Sec
(Default : 200 Sec)
17
Zenex PlusUser Manual
FACTORYTIMER PARAMETERS
Parameter Description
ENABLE >>
Yes
Timer function and Start / Abort commands are enabled.
No
Timer function and Start / Abort commands are disabled.
START BAND >>
After issuance of start command, the timer starts counting down
once the PV enters the process band around SP defined by this
parameter value.
HOLDBACK STRATEGY >>
None
PV based timer pause is not required.
Up
Timer is paused if PV is outside holdband SP.above
Down
Timer is paused if PV is outside holdband SP.below
Settings
(Default Value)
No
Yes
(Default : No)
0 to 999.9
(Default : 0.5)
None
Up
Down
Both
(Default : None)
Both
Timer is paused if PV is outside holdband either above or below
SP.
HOLD BAND >>
Sets the temperature limit(s) with respect to the SP for the timer to
pause. The timer holds on counting should the PV cross the
limit(s).
HEAT OFF >>
Heater is turned off, once Timer operation is over.
COOL OFF >>
Compressor is turned off, once Timer operation is over.
POWER RECOVERY >>
Abort
The timer operation is suspended until a new start command is
issued.
Re-Start
The timer re-runs the complete time.
0.1 to 999.9
(Default : 0.5)
No
Yes
(Default : No)
No
Yes
(Default : No)
Abort
Restart
Continuous
(Default : Restart)
Continue
The Timer resumes operation for the balance time.
18
Zenex PlusUser Manual
FACTORYDOOR OPEN
Parameter Description
ENABLE >>
Set to ‘Yes’ if is mounted for detecting Switchdoor Open / Close
position.
SWITCH LOGIC >>
Close : Door Open
The Door position is considered if the switch is CLOSE.Open
Open : Door Open
The Door position is considered if the switch is OPEN.Open
DOOR ALRM DLY (SEC) >>
This parameter sets a timer. From the time the door is opened, the
timer begins counting down. If the door is not closed before the
timer reaches 0, the Door Open alarm is activated.
FACTORYFACTORY DEFAULT
Settings
(Default Value)
YES
NO
(Default : NO)
CLOSE : DOOR OPEN
OPEN : DOOR OPEN
(Default : CLOSE : DOOR OPEN)
0 to 1000 Sec
(Default : 60 Sec)
Parameter Description
SET TO DEFAULT >>
Set to ‘Yes’ to set all the parameter values to their Default alues.V
FACTORYPASSWORD
Parameter Description
CHANGE PASSWORD >>
The Controller is shipped from the factory with a default password
(321) for accessing the parameters reserved for the equipment
manufacturer. owever, if required the password can be changed H
by setting the new value for this parameter.
(The new password replaces the old password. hat is, the old T
password is no longer valid. it is user’s responsibility to memorize
the password.)
Settings
(Default Value)
YES
NO
(Default : NO)
Settings
(Default Value)
2000 to 2999
(Default : 321)
19
Zenex PlusUser Manual
FACTORY
EXIT SETUP MODE >>
Select to quit mode and return to mode.SetupMain Display
EXIT
Parameter Description
20
Zenex PlusUser Manual
Section 6
PANEL MOUNTING AND ELECTRICAL CONNECTIONS
WARNING
MISH A N D L I N G / NE G L I G E N C E
CAN RESULT IN PERSONAL DEATH
OR SERIOUS INJURY.
PANEL CUTOUT
Figure 6.1(a) : Old Version
Figure 6.1(b) : New Version
Panel Cutout
75 X 152 mm
-0, +1.0 mm
Panel Cutout
75 X 150 mm
-0, +1.0 mm
PANEL MOUNTING
Follow the steps below for mounting the instrument on panel :
1. Prepare a cutout to the size shown in Figure 6.1.
2. Remove the Panel Mounting Clamp from the instrument Enclosure.
3. Insert the rear of the enclosure through the panel cutout from the front of the mounting panel.
4. Fix the mounting clamp pair such that it ensures secured mounting of the enclosure against the panel wall.
ELECTRICAL CONNECTIONS
1. The user must rigidly observe the Local Electrical Regulations.
2. Do not make any connections to the unused terminals for making a tie-point for other wires (or for any other reasons) as
they may have some internal connections. Failing to observe this may result in permanent damage to the controller.
3. Run power supply cables separated from the Sensor cables (Thermocouple / RTD). If the cables are run through conduits,
use separate conduits for power supply cable and low-level signal cables.
4. Use appropriate fuses and switches, wherever necessary, for driving the high voltage loads to protect the controller from
any possible damage due to high voltage surges of extended duration or short-circuits on loads.
5. Take care not to over-tighten the terminal screws while making connections.
6. Make sure that the controller supply is switched-off while making/removing any connections or removing the controller
from its enclosure.
CONNECTION DIAGRAM
The Electrical Connection Diagram is shown on the Top (Old Version) or Back (New Version) side of the controller enclosure.
The diagram shows the terminals viewed from the REAR SIDE with the controller Front Label upright. Refer figure 6.2(a) for
Old Version & 6.2(b) for New Version.
21
Zenex PlusUser Manual
Figure 6.2(a) :
Old Version
12
Pt100
TC
Heater
Control
-
+
14
15
233227
2531302928
24
-
+
EXT.
VOLTAGE
DO-1 DO-2 DO-3
+-+-+
2 3
1
3
Control
+
-
--
+
Compressor
1617
26
AI-1AI-2
DO-4
-
4
+
4
Process
Alarm
++
18
DO-5
-
-
+
9 106 7 85
5
6
Event
Alarm
192021
Figure 6.2(b) :
New Version
AI-1 : Process Sensor
Connections
2625
Zenex Plus B124-V2
+
DI-1
DI-2
DO-6
+
11
DI-3
-
12
15 16
14
13
7
-
27
28
Pt100
TC
-
DI-4
DI-5
DI-6
17
19 20
18
8910
Door Open
Timer Start
Alarm ACK
2223
Digital Output
DO-1 : Heater Control
DO-2 : Compressor
Control
DO-3 : Process Alarm
DO-4 : Event Alarm
DO-5 : Unused
DO-6 : Unused
Connect Thermocouple or 3-wire RTD Pt100 sensor as shown below.
RTD Pt100, 3-wire
Connect single leaded end of RTD bulb to terminal T2 and the double leaded
ends to terminals T3 and T4 (interchangeable) as shown in Figure 6.3. Use
low resistance copper conductor leads of the same gauge and length. Avoid
joints in the cable.
Thermocouple
Connect Thermocouple Positive (+) to terminal T2 and Negative (-) to
terminal T3 as shown in Figure 6.3. Use correct type of extension lead wires
or compensating cable. Avoid joints in the cable.
22
Old Version
New Version
SUPPLY
Figure 6.3
T1
1
25
Pt100
TC
T2
2
26
+
T3
3
27
T4
4
28
-
Zenex PlusUser Manual
DIGITAL OUTPUTS
Heater Control Output
Compressor Control Output
Process Alarm Output
Event Alarm Output
All the above Control & Alarm outputs are Voltage pulses (12VDC @ 40mA) for driving external SSR or Relay. The ‘+’ and ‘-’
terminals are for voltage ‘Source’ and ‘Return’ paths, respectively. Refer Figure 6.4 below.
Figure 6.4
Heater
Control
+
New Version
Old Version
DIGITAL INPUTS
Door Open
Timer Start
Alarm Acknowledge
Potential-free contact closure input terminals are provided as digital
inputs. An ‘Open’ or ‘Close’ switch position is detected as input. Refer
Figure 6.5.
PC COMMUNICATION PORT
1
14
-
2
15
Compressor
Control
+
3
16
-
4
17
Process
Alarm
+
5
-
6
19
DI-1:Door Open
DI-2:Timer Start
DI-3:Alarm ACK
New Version
Old Version
Event
Alarm
+
7
20
-
8
2118
Figure 6.5
DI-1
13
14
23
DI-2
DI-3
15
24
16
2522
Figure 6.6
B+
Terminating Resistor
(100 to 150 Ohms)
Twisted
Wire Pair
New
Version
34
Version
B-
Old
12
PC
33 B+
B-
The controller Communication Port is RS485 and requires a similar port at the host (master) end. If, however, the host port is
different (say, RS232 or USB), use appropriate protocol converter (say, RS485-RS232 or USB to RS485) for interface.
For reliable noise free communication, use a pair of twisted wires inside screened cable as shown in Figure . The wire 6.6
should have less than 100 ohms / km nominal DC resistance (Typically 24 AWG or thicker). Connect the terminating resistor
(Typically 100 to 150 ohm) at one end to improve noise immunity.
Screened Cable
Serial Comm.
23
11
Terminals
Zenex PlusUser Manual
POWER SUPPLY
As standard, the is supplied with power connections suited for 8 to 264 VAC line supply. Use well-insulated module5
copper conductor wire of the size not smaller than 0.5mm² for power supply connections ensuring proper polarity as
shown in Figure 6.7.module The is not provided with fuse and power switch. If necessary, mount them separately. Use a
time lag fuse rated 1A @ 240 VAC.