PPI ScaneXPlus User Manual

Page 1
Multi-Channel Universal Process Value Scanner with Common High / Low Alarms
User Manual
Scane
Plus
Page 2
2. FRONT PANEL LAYOUT 4
3. BASIC OPERATION 6
4. SET UP MODE : ACCESS AND OPERATION 9
5. CONFIGURATION PARAMETERS 11
6. ALARM CONFIGURATION PARAMETERS 18
7. ALARM SETTING PARAMETERS 19
APPENDIX-A : DC LINEAR SIGNAL INTERFACE 21
APPENDIX-B : BOTTOM / TOP CLIPPING 23
CONTENTS
User Manual
SCANEX PLUS
Page 3
1
WARNING MISHANDLING / N E G L I G E N C E CAN RESULT IN PERSONAL DEATH OR SERIOUS INJURY.
PANEL MOUNTING AND ELECTRICAL CONNECTIONS
PANEL CUTOUT
PANEL MOUNTING
Follow the steps below for mounting the instrument on panel :
1. Prepare a cutout to the size shown in Figure 1.1.
2. Remove the Panel Mounting Clamp from the instrument Enclosure.
3. Insert the rear of the enclosure through the panel cutout from the front of the mounting panel.
4. Fix the mounting clamp pair such that it ensures secured mounting of the enclosure against the panel wall.
ELECTRICAL CONNECTIONS
Observe the followings while making electrical connections.
1. Run power supply cables separated from sensor (Thermocouple/RTD/mA/mV/V) cables. If the cables are run through conduits, use separate conduits for power supply cable and sensor cables.
2. Use appropriate fuses and switches, wherever necessary, for driving the high voltage loads to protect the instrument from any possible damage due to high voltage surges of extended duration or short-circuits on loads.
3. Switch-off the power supply while making / removing any connections.
The Figure 1.2(a) & Figure 1.2(b) show the terminals viewed from the rear side, with the scanner label upright, for 8 Channel & 16 Channel versions, respectively.
Panel Cutout
92 X 184 mm
-0, +0.5 mm
Figure 1.1
Figure 1.2(a) : 8 Channel
User Manual
SCANEX PLUS
Section 1
71 72 73 74 75 76 77 78
C NO C NO C NO C NO
RLY-1 RLY-2 RLY-3 RLY-4
Alarm Outputs
AI-1
AI-3
AI-5 AI-7
AI-4 AI-6 AI-8
1 2 3 4 5 6 7 8 91011 12 13 14 15 16
AI-2
35 36 37 38 39 40 41 42 434445 46 47 48 49 50
67 68
+
-
RS485
OUT
69 70
L N
Supply
85~264VAC
33 34
+
-
RS485
IN
AI - X
RTD
TC
V/mV
mA
Page 4
2
User Manual
SCANEX PLUS
AI - X
mV / V
T1 T2 T3 T4
T1 T2 T3 T4
INPUT CHANNELS
All input channels are identical from wiring connection viewpoint. For explanation purpose, the 4 terminals pertaining to each channel have been marked as T1, T2 ,T3 & T4 in the following pages. The descriptions below apply to all the channels with no deviations.
Thermocouple
Connect Thermocouple Positive (+) to terminal T2 and Negative (-) to terminal T3 as shown in Figure 1.3. Use the correct type of Thermocouple extension lead wires or compensating cable for the entire distance ensuring the correct polarity throughout. Avoid joints in the cable.
AI - X
TC
T1 T2 T3 T4
T1 T2 T3 T4
AI - X
RTD
T1 T2 T3 T4
T1 T2 T3 T4
DC Linear Voltage (mV / V)
Use a shielded twisted pair with the shield grounded at the signal source for connecting mV / V source. Connect common (-) to terminal T3 and the signal (+) to terminal T2, as shown in Figure
1.5.
RTD Pt100 (3-wire or 2-wire)
For 3-wire configuration, connect single leaded end of RTD bulb to terminal T2 and the double leaded ends to terminals T3 and T4 (interchangeable) as shown in Figure 1.4. Use copper conductor leads of very low resistance ensuring that all 3 leads are of the same gauge and length. Avoid joints in the cable.
For 2-wire configuration, connect the 2 sensor wires to terminal T2 and T3 (interchangeable). Also short terminals T3 & T4.
Figure 1.3
Figure 1.4
Figure 1.5
AI - X
mA
T1 T2 T3 T4
T1 T2 T3 T4
DC Linear Current (mA)
Use a shielded twisted pair with the shield grounded at the signal source for connecting mA source. Connect common (-) to terminal T3 and the signal (+) to terminal T2. Also short terminals T1 & T2. Refer Figure 1.6.
Figure 1.6
71 72 73 74 75 76 77 78
C NO C NO C NO C NO
RLY-1 RLY-2 RLY-3 RLY-4
Alarm Outputs
AI-1
AI-3
AI-5 AI-7 AI-9 AI-11 AI-13 AI-15
AI-4 AI-6 AI-8 AI-10 AI-12 AI-14 AI-16
1 2 3 4 5 6 7 8 91011 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
AI-2
35 36 37 38 39 40 41 42 434445 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66
67 68
+
-
RS485
OUT
69 70
L N
Supply
85~264VAC
33 34
+
-
RS485
IN
AI - X
RTD
TC
V/mV
mA
Figure 1.2(b) : 16 Channel
Page 5
3
User Manual
SCANEX PLUS
Figure 1.8
Line
Neutral
2 Pole
Isolating Switch
Fuse
Power Supply Terminals
6970L
N
As standard, the module is supplied with power connections suited for 85 to 264 VAC line supply. Use well-insulated copper conductor wire of the size not smaller than 0.5mm² for power supply connections ensuring proper polarity as shown in Figure
1.8. The module is not provided with fuse and power switch. If necessary, mount them separately. Use a time lag fuse rated 1A @ 240 VAC.
POWER SUPPLY
RELAY OUTPUTS
There are 4 Relay Outputs provided for common alarms. The relay connections are shown in Figure 1.7 below.
Figure 1.7
Potential-free Relay changeover contacts NO (Normally Open) and C (Common) rated 10A/240VAC (resistive load) are provided as Relay output.
AC
LOAD
Relay Output Terminals
NO
C
DC
Page 6
4
Indicator Function
MANUAL
ALARMS
(1 to 16)
Glows ON when the Scanner is put in Manual Scan Mode.
Flashes if the corresponding channel is in Alarm condition.
Table 2.1
FRONT PANEL LAYOUT
The front panel comprises of digital readouts, LED indicators and membrane keys as shown in Figure 2.1 below.
READOUTS
The PV Readout is a 5 digit, 7-segment bright red LED display that displays the PV (Process Value). In Set-up Mode, the PV Readout displays parameter values/options.
The Channel No. Readout is a 2 digit, 7-segment bright red LED display that shows the Channel No. for which the PV Readout shows the PV. In Set-up Mode, the Channel No. Readout remains blank.
The Unit Readout is a 4 digit, 7-segment bright green LED display and usually displays the ‘Unit’ pertaining to the PV Readout. In Set-up Mode, the Unit Readout displays parameter name (prompts).
INDICATORS
There is a single 3 mm red LED indicator that shows the Auto/Manual Scan Mode Status. A group of 16 red LEDs show the Alarm Status for each of 16 channels. Refer table 2.1 below.
User Manual
SCANEX PLUS
Figure 2.1
Alarm Status
Indicators
ALARMS
Auto / Manual Key
Alarm Ack/View Key
ENTER Key
UP Key
DOWN Key
PAGE Key
Auto/Manual Scan
Mode Indicator
Channel No. Readout
Unit Readout
Scane
Plus
MANUAL
PV Readout
Section 2
Page 7
5
Press to enter / exit Set-up Mode
Press to decrease the parameter value. Pressing once decreases the value by one count; holding the key pressed speeds up the change.
PAGE
DOWN
Symbol
Function
Press to store the set parameter value and to scroll to the next parameter.
Press to Acknowledge any pending Alarm(s) and to View details of the channels under Alarm.
Press to toggle between Auto and Manual Scan Mode. In Manual Scan Mode, Use UP / DOWN keys to the desired channel.
Key
Press to increase the parameter value. Pressing once increases the value by one count; holding the key pressed speeds up the change.
UP
ENTER
Alarm
Ack/View
Auto /
Manual
User Manual
SCANEX PLUS
Table 2.2
KEYS
There are six tactile keys provided on the front panel for setting-up the parameter values and for other functions & commands.
The Table 2.2 below lists each key and the associated function.
Page 8
6
POWER-UP
Upon switching on the power to the unit, all displays and indicators are lit on for approximately 3 seconds during which time the Scanner runs a self initialization sequence.
MAIN DISPLAY MODE
After the self initialization sequence, the Scanner enters MAIN Display Mode. The PV Readout starts showing the measured PV (Process value) with the corresponding channel number being shown on the Channel No. Readout. The MAIN Display Mode is one that shall be used most often.
The Scanner may be configured to operate in either Auto or Manual Scan Mode. The Power-on default mode is ‘Auto Scan Mode’. Use front panel key ‘A/M’ to toggle between the Auto and Manual Scan Mode.
Auto Scan Mode
In this mode, the Scanner shows the Process Value for each channel sequentially at a periodic interval, called ‘Scan Rate’. The Scan Rate is user settable from 1 to 99 seconds. The channels are displayed in ascending (increasing) order with the last channel automatically rolling over to the first channel. In Auto Scan Mode, the front indicator marked ‘MANUAL’ remains OFF.
Manual Scan Mode
In this mode, the Scanner keeps displaying the Process Value for the selected channel indefinitely. The user can switch to and hold any desired channel by using UP/DOWN keys. In Manual Scan Mode, the front indicator marked ‘MANUAL’ is lit ON.
ALARM SYSTEM
There are up to 4 soft Alarms (AL-1 to AL-4) available for each channel.
Status Indication
There are 16 front panel Alarm Status LEDs, one for each channel. If any one or more set Alarm for a channel is active, the corresponding front panel indicator flashes.
Relay Activation & Acknowledge
The 4 Relay Outputs (RLY-1 to RLY-4) are mapped with the 4 Alarms (AL-1 to AL-4) as explained below in Table 3.1.
User Manual
SCANEX PLUS
Section 3
BASIC OPERATION
Output
Relay Activation
RLY-1
If Alarm-1 for any one or more channels is ON
If Alarm-2 for any one or more channels is ON
If Alarm-3 for any one or more channels is ON
If Alarm-4 for any one or more channels is ON
Associated Alarm
AL-1
RLY-2 AL-2
RLY-3 AL-3
RLY-4 AL-4
Table 3.1
The front panel Alarm Ack/View key is used to mute the Audio Alarm or to bring the system out of Trip Condition. The effect of acknowledge function depends both on the Relay Logic (Direct / Reverse) and Latched / Un-Latched operation. Note that Acknowledging the alarm only de-activates the relay output and does not remove the Alarm condition. Refer Table 3.2 for effect of Acknowledge Key.
Page 9
7
Relay Logic
Effect of Acknowledge Key
Direct
(Alarm)
Switches OFF the Alarm output
No effect
Switches OFF the Alarm output provided no Alarm condition is pending
Switches ON the Trip relay (brings out of tripping) provided no Alarm condition is pending
Latched
No
Reverse
(Trip)
No
Yes
Yes
Direct
(Alarm)
Reverse
(Trip)
Table 3.2
PV ERROR INDICATION
In case the PV falls below the Minimum Range or rises above the Maximum Range specified for the selected ‘Input Type’ or in case the input sensor is open / broken; the PV Readout flashes the error messages listed in Table 3.3 below. The Figure 3.2 illustrates an open sensor condition for channel-14, for example.
Message PV Error Type
Over-range (PV above Max. Range)
Under-range (PV below Min. Range)
Open (Sensor open / broken)
Table 3.3
Figure 3.2
ALARMS
Scane
Plus
Manual
User Manual
SCANEX PLUS
Detail Alarm View
Pressing the Alarm Ack/View key also provides complete Alarm status information for the channels under alarm condition. The information available is for view only. The Unit Readout indicates the ‘Channel Number’ under Alarm and the corresponding ‘Alarm Number(s)’ are indicated on the PV Readout. The UP/DOWN keys can be used to scroll through all the channels under Alarm.
The example Figure 3.1 below illustrates the following case :
Channel-2 and Channel-12 are currently under Alarm condition. The active Alarms for Channel-2 are Alarm-1 and Alarm-4 while for Channel-12 it is only Alarm1.
MAIN Display
Mode
Figure 3.1
Press UP / DOWN key
to view next / previous channel
in alarm condition
MAIN Display
Mode
Press ALARM
ACK/VIEW key
Press PAGE or ENTER
key to return to
Main Display Mode
Alarm View
Mode
Alarm View
Mode
Page 10
8
User Manual
SCANEX PLUS
Table 3.4
Parameter Description
Settings
(Default Value)
OPERATOR PAGE & PARAMETERS
The Operator page contains the parameters that are used most frequently and the commands that are required for day-to-day operation. This page is not locked for editing by Master Lock. The Figure 3.2 below illustrates how to access Operator Page (Page 0).
RESET COMMAND
This feature clears the current Min/Max values of all Channels and starts afresh monitoring the channels for new highest and lowest values.
For resetting, set the reset command to ‘Yes’.
View Only
(Default : NA)
MINIMUM PV
The minimum PV attained by the selected channel.
View Only
(Default : NA)
MAXIMUM PV
The maximum PV attained by the selected channel.
No
Yes
(Default : No)
1 to Actual no. of
Channels to Scan
(Default : 1)
CHANNEL NUMBER
Select the channel No. whose Min/Max PV is to be viewed.
This Parameter reappears cyclically after viewing Max/Min Values for each selected channel number.
1 Sec. to 99 Sec.
(Default : 3 Sec.)
SCAN RATE
Applicable for Auto Scan Mode only. This parameter value sets the time interval for which each channel is displayed. In other words, the rate at which the channels are sequentially updated for indication.
The Operator Page parameters are listed in Table 3.4 below.
Figure 3.2
Operator Page
First Parameter
on Operator
Page
Press PAGE
key to enter
Set-up mode
Press ENTER
key to open
Operator Page
MAIN Display
Mode
Page 11
9
SET UP MODE : ACCESS AND OPERATION
There are many user settings that determine how the instrument will function or operate. These setting are called Parameters.
For the convenience and ease of operation, the various parameters have been grouped separately depending upon the functions they define. Each such group is called a PAGE. Each PAGE is assigned a unique number, called PAGE NUMBER, for its access. The parameters contained in a PAGE are presented in a fixed sequence to the user for setting. The user can access a desired PAGE by entering its PAGE NUMBER and can select and set the desired parameter values.
PARAMETER PROMPTS
Each parameter has an identifying tag, called the Parameter Prompt. While setting parameter values in a PAGE, the parameter prompt is always displayed on the Unit Readout and its current value is displayed on the PV Readout.
ACCESSING A PAGE
Each PAGE is accessible only from the MAIN Display Mode. That is, from the current PAGE, the user must return to the MAIN Display Mode before the other PAGE can be accessed.
Figure 4.1 illustrates access to the desired PAGE from MAIN Display Mode.
User Manual
SCANEX PLUS
Section 4
ADJUSTING PARAMETER VALUES
For accessing and adjusting the parameter, one must first open the PAGE containing the parameter.
Figure 4.2 illustrates how to access the desired parameter(s) and adjust the corresponding value(s). The illustration shows accessing the parameter ‘Alarm Type’ for Alarm-1 of Channel-1 and changing its value from ‘None’ to ‘Process High’. Press PAGE key to revert to MAIN Mode.
Figure 4.1
Default Page
Page Number
Press PAGE
key to enter
Set-up mode
Use UP/DOWN
key to set
Page Number
Press ENTER
key to open
the Page
MAIN Display
Mode
Figure 4.2
Previous set
Alarm Type
Default Alarm
Number
Press & Release
ENTER Key
to select Channel-1
Use UP/DOWN
keys to set the
desired Value
First Parameter
on PAGE-10
Press & Release
ENTER Key
to select Alarm-1
First Parameter
on PAGE-10
Page 12
10
PARAMETER LOCKING
For protecting the parameter values from unauthorized / accidental alterations, the parameter adjustments can be Locked. The Operator Page is not affected by locking. The Figure 4.3 illustrates the steps for Locking.
For Un-Locking, repeat the sequence of steps shown in Figure 4.3 twice.
SETTING DEFAULT VALUES
The instrument is shipped from the factory with all the parameters set to their default values. Refer Figure 4.4 below for
regaining the factory default values.
User Manual
SCANEX PLUS
Figure 4.4
Default Page
Press PAGE
key to enter
Set-up Mode
Default Code
Use UP/DOWN
keys to set the
‘Default’ Code
Press ENTER key.
Scanner resets and restarts
with default parameter values
MAIN Display
Mode
MAIN Display
Mode
Figure 4.3
Default Page Locking Code
Press PAGE
key to enter
Set-up mode
Use UP/DOWN
keys to set the ‘Locking’ Code
Press ENTER key
to Lock & Return to
MAIN Mode
MAIN Display
Mode
MAIN Display
Mode
Desired Alarm
Type
Next Parameter
Press ENTER key
to store the value &
move to next Parameter
Page 13
11
RESOLUTION
Set the process value indication resolution (decimal point). All the resolution based parameters (Alarm setpoint, hysteresis etc.) then follow this resolution setting.
Refer Table 5.2
(Default : 0.1)
Refer Table 5.2
(Default : Type K)
INPUT TYPE
Refer Table 5.2. Select the Input Type in accordance with the type of sensor connected to the selected channel.
1 to Actual no. of
channels to scan
(Default : 1)
SELECT CHANNEL FOR CONFIGURATION
Refer Figure 5.1 (a) and 5.1 (b).
COMMON INPUT CONFIGURATIONS
In most applications the Scanner is used to monitor the process value at different points within a closed space (Chamber, Cold Room, etc). Thus the type of sensors and also the measurement resolution and units used are Identical (Common) for all channels. This parameter facilitates eliminating repetitive settings for multiple channels in such cases.
Yes : The parameter values for Input type, Resolution and PV
Units are applied to all the channels.
No : The parameter values for Input type, Resolution and PV
Units need to be set independently for each channel.
SENSOR-BREAK PV STATUS
This parameter setting allows user to define the alarm behavior under Sensor open condition.
UP : Any Alarm set as ‘Process High’ gets activated.
DOWN : Any Alarm set as ‘Process Low’ gets activated.
ACTUAL NUMBERS OF CHANNELS TO SCAN
The numbers of channels actually connected/used for monitoring. This allows skipping unused channels for scanning. Note that only consecutive channels, starting from channel-1, must be used.
PAGE 12 : CONFIGURATION PARAMETERS
The configuration parameters are listed in Table 5.1 below and are generally required to be set only at the time of installation. Set these parameters appropriately based on the types of Thermocouple / Sensor connected and other application needs.
Parameter Description
Settings
(Default Value)
Table 5.1
Up Scale
Down Scale
(Default : Up Scale)
1 to Max. Available
(Default : 8 or 16)
No
Yes
(Default : Yes)
User Manual
SCANEX PLUS
Section 5
Page 14
12
Parameter Description
Settings
(Default Value)
PV UNITS
Select Temperature units in °C or °F for Thermocouple or Pt100 sensor.
For DC Linear input (mA/mV/V), Select appropriate Units from the list in Table 5.3. Note however that the selected Units are for the purpose of indication on Lower Readout only.
-1999.9 to 3000.0 (Default : 100.0)
DC RANGE LOW
(Applicable only for DC Linear Inputs)
The process value corresponding to the Signal Low value from the transmitter. For more Description Refer Appendix-A.
-1999.9 to 3000.0 (Default : 0.0)
Refer Table 5.3
(Default : ºC)
User Manual
SCANEX PLUS
(Default : Disable)
Enable
Disable
BOTTOM CLIPPING ENABLE
(Applicable only for DC Linear Inputs)
Refer Appendix-B.
-1999.9 to Top Clipping
Default: 0.0
BOTTOM CLIPPING
(Applicable only for DC Linear Inputs)
Refer Appendix-B.
SIGNAL HIGH
(Applicable only for DC Linear Inputs)
The transmitter output signal value corresponding to Range High process value. For more Description Refer Appendix-A.
SIGNAL LOW
(Applicable only for DC Linear Inputs)
The transmitter output signal value corresponding to Range Low process value. For more Description Refer Appendix-A.
Input Type
Settings
Default
0 to 20 mA
0.00 to Signal High
0.00
4 to 20 mA
0 to 80 mV
0 to 1.25 V
0 to 5 V
0 to 10 V
1 to 5 V
4.00 to Signal High
0.00 to Signal High
0.000 to Signal High
0.000 to Signal High
0.00 to Signal High
1.000 to Signal High
4.00
0.00
0.000
0.000
0.00
1.000
Input Type
Settings
Default
0 to 20 mA
4 to 20 mA
0 to 80 mV
0 to 1.25 V
0 to 5 V
0 to 10 V
1 to 5 V
Signal Low to 20.00
20.00
20.00
80.00
1.250
5.000
10.00
5.000
Signal Low to 20.00
Signal Low to 80.00
Signal Low to 1.250
Signal Low to 5.000
Signal Low to 10.00
Signal Low to 5.000
DC RANGE HIGH
(Applicable only for DC Linear Inputs)
The process value corresponding to the Signal High value from the transmitter. For more Description Refer Appendix-A.
Page 15
13
User Manual
SCANEX PLUS
Bottom Clipping to 3000.0
(Default : 100.0)
(Default : Disable)
Enable
Disable
TOP CLIPPING ENABLE
(Applicable only for DC Linear Inputs)
Refer Appendix-B.
TOP CLIPPING
(Applicable only for DC Linear Inputs)
Refer Appendix-B.
Parameter Description
Settings
(Default Value)
Table 5.2
Resolution
Option
What it means
Range (Min. to Max. )
Type J Thermocouple
Type K Thermocouple
Type T Thermocouple
0.0 to +960.0°C / +32.0 to +1760.0°F
-200.0 to +1376.0°C / -328.0 to +2508.0°F
-200.0 to +387.0°C / -328.0 to +728.0°F
Type R Thermocouple
Type S Thermocouple
Type B Thermocouple
Type N Thermocouple
0.0 to +1771.0°C / +32.0 to +3219.0°F
1 °C/°F
or
0.1 °C/°F
3-wire, RTD Pt100
-199 to +600°C / -328 to +1112°F
-199.9 to +600.0°C / -328.0 to +1112.0°F
or
1 °C/°F
or
0.1 °C/°F
0.0 to +1314.0°C / +32.0 to +2397.0°F
0.0 to +1826.0°C / +32.0 to +3218.0°F
0.0 to +1768.0°C / +32.0 to +3214.0°F
Reserved for customer specific Thermocouple type not listed
above. The type shall be specified in accordance with the ordered (optional on request) Thermocouple type.
-1999.9 to 3000.0 (Default : 0.0)
OFFSET
In many application, the measured PV at the input requires a constant value to be added or subtracted to obtain a final process value for removing sensor zero error or to compensate known thermal gradient. This parameter is used to remove such errors.
Actual (Displayed) PV = Measured PV + Offset for PV.
Page 16
14
User Manual
SCANEX PLUS
0 to 20mA DC current
4 to 20mA DC current
0 to 80mV DC voltage
Reserved
0 to 1.25V DC voltage
0 to 5.0V DC voltage
0 to 10.0V DC voltage
1 to 5.0V DC voltage
-19999 to 30000 units
1
0.1
0.01
0.001
units
Resolution
Option
What it means
Range (Min. to Max. )
°C
°F
Kelvin
Engineering Units
Percentage
Pascals
Mpascals
Kpascals
Bar
Milli bar
PSI
kg/sq cm
mm water gauge
Inches water gauge
mm mercury
Torr
Unit Readout
Units
Table 5.3
Page 17
15
User Manual
SCANEX PLUS
Liters per hour
Liters per minute
% Relative Humidity
% O
2
% CO
2
% Carbon Potential
volts
Amps
Milli amps
Milli Volts
Ohms
Parts per million
Revolutions per pinute
Milli seconds
Seconds
Unit Readout
Units
Miles per hour
Milli grams
Grams
Kilo grams
Minutes
Hours
PH
%PH
Page 18
16
Note : Press PAGE Key to Revert to Main Display Mode.
User Manual
SCANEX PLUS
Set Resolution common to all
Channels
Set Unit common to all
Channels
Select Channel for which
Offset value is to be set
Set Offset value for the
selected Channel
Figure 5.1(a)
Set Resolution common to all
Channels
Set Unit common to all
Channels
Set Signal Low
common to all Channels
Set Signal High
common to all Channels
Set DC Range Low
common to all channels
Set DC Range High
common to all channels
Choose
whether Bottom Clipping
to be enabled for
all Channel
Set the Bottom Clipping Value
common to all Channels
Select Channel for which
Offset value is to be set
Set Offset value for the
selected Channel
Select Input Type
All Channel Common = “YES”
For DC Input Type
For Thermocouple/RTD
Input Type
No
Choose
whether Top Clipping
to be enabled for
all Channel
Set the Top Clipping Value
common to all Channels
Yes
Yes
A
A
B
B
No
B
Page 19
17
Figure 5.1(b)
Set Resolution for the
Selected Channel
Set Unit for the Selected
Channel
Set Signal Low
for the Selected Channel
Set Signal High
for the Selected Channel
Set DC Range Low
for the Selected Channel
Set DC Range High
for the Selected Channel
Choose
whether Bottom Clipping
to be enabled for
Selected Channel
Set the Bottom Clipping Value
for the Selected Channel
Select Channel for which
Offset value is to be set
Set Offset value for the
selected Channel
Select Input Type
All Channel Common = “NO”
For DC Input Type
For Thermocouple/RTD
Input Type
Set the Top Clipping Value for
the Selected Channel
Yes
Yes
User Manual
SCANEX PLUS
Choose
whether Top Clipping
to be enabled for
Selected Channel
Select Channel
D
D
Set Resolution for the
Selected Channel
Set Unit for the Selected
Channel
Select Channel for which
Offset value is to be set
Set Offset value for the
selected Channel
D
No
A
A
B
B
No
C
C
Page 20
18
RELAY LATCH
No : The Relay switches ON or OFF with Alarm activation or de-
activation.
Yes : The Relay Output switches (ON for Normal Logic / Off for
Reverse logic) upon Alarm activation. However, Alarm de­activation does not affect the Relay status. The Relay status can only be regained by pressing acknowledge key provided the Alarm has de-activated.
RELAY LOGIC
Normal : The Relay remains ON under Alarm condition; OFF
otherwise. Useful for activating Audio (like hooter) or Visual (like lamp) gadget.
Reverse : The Relay remains OFF under Alarm condition; ON
otherwise. Useful for Tripping the system under monitoring.
1 to No. of
Alarms per channel
(Default : NA)
SELECT OUTPUT RELAY NUMBER
The Scanner features 4 Relay Outputs (RLY-1 to RLY-4) that are mapped to AL-1 to AL-4 of each channel. The relay outputs can be used for either activating Audio/Visual gadgets (Normal Logic) or for Tripping the system being monitored (Reverse Logic). Further the output can be programmed to either switch ON/OFF with Alarm switching (Relay Latch = No) or remain Latched until acknowledged (Relay Latch = Yes).
This parameter allows to select 1 out of 4 Relays for ‘Logic’ and ‘Latch’ parameter setting.
1 to 4
(Default : 4)
NUMBER OF ALARMS PER CHANNEL
The instrument is provided with 4 independently settable soft Alarms per channel. However, the actual number of Alarms required per channel may vary from application to application. This parameter allows selecting the exact number of Alarms required per channel (Maximum 4).
Normal
Reverse
(Default : Normal)
The parameters presented on this page allow configuring the number of Alarms per channel, the Alarm output function (Audio /
Visual or Tripping) and Alarm latching.
PAGE 11 : ALARM CONFIGURATION PARAMETERS
Parameter Description
Settings
(Default Value)
Table 6.1
No
Yes
(Default : No)
User Manual
SCANEX PLUS
Section 6
Page 21
19
ALARM INHIBIT
Yes : The Alarm activation is suppressed until the PV is within
Alarm limits from the time the Scanner is switched ON. This allows suppressing the Alarm during the start-up conditions.
No : The Alarm is not suppressed during the start-up conditions.
0.1 to 3000.0
(Default : 2.0)
This parameter value sets a differential (dead) band between the ON and OFF Alarm states. Keep it large enough to avoid frequent switching of the Alarm relay near setpoint.
ALARM HYSTERISIS
Min. to Max. of selected
input type range
(Default : 0)
ALARM SETPOINT
This parameter value sets the Process High or Process Low limit for Alarm.
ALARM TYPE
None : Disable the Alarm.
Process Low : The Alarm activates when the PV equals or falls
below the ‘Alarm Setpoint’ value.
Process High : The Alarm activates when the PV equals or
exceeds the ‘Alarm Setpoint’ value.
1 to User
Selected Alarm
(Default : NA)
ALARM NUMBER
Select the Alarm Number whose parameters are to be set.
1 to Max.
Channels
(Default : NA)
CHANNEL NUMBER
Select the Channel Number for which the alarm parameters are to be set.
None
Process Low
Process High
(Default : None)
PAGE 10 : ALARM SETTING PARAMETERS
The Alarm setting parameters define how the alarm will function with respect to process value variations.
Parameter Description
Settings
(Default Value)
Table 7.1
No
Yes
(Default : No)
User Manual
SCANEX PLUS
Section 7
Page 22
20
The Scanner may have up to 16 Channels and each Channel may have up to 4 Alarms. In order to set the Alarm parameters for a specific Alarm, the Alarm must first be identified by its number (1 to 4) and the Channel number (1 to 16) to which it belongs.
The parameters listed in this page include Channel number selection followed by Alarm number selection, followed by Alarm parameters.
Refer Figure 7.1 below for the navigation diagram.
Select Channel Number
(1 to 16)
Select Alarm Number
(1 to 4)
Figure 7.1
Set ‘Type’
for the selected Alarm
Set ‘Setpoint’
for the selected Alarm
Set ‘Hysterisis’
for the selected Alarm
Set ‘Inhibit’
for the selected Alarm
Note : Press PAGE Key to Revert to Main Mode.
User Manual
SCANEX PLUS
Page 23
21
User Manual
SCANEX PLUS
APPENDIX A
As is evident from the aforementioned transmitter examples, different transmitters produce signals varying both in Type (mV/V/mA) and Range. Most PPI instruments, thus, provide programmable Signal Type and Range to facilitate interface with a variety of transmitters. A few industry standard signal types and ranges offered by the PPI instruments are: 0-80mV, 0-5 V, 1­5 V, 0-10V, 0-20 mA, 4-20 mA, etc.
Also, the output signal range (e.g. 1 to 4.5 V) from different transmitters corresponds to different process value range (e.g. 5 to 95 %RH); the instruments thus also provide facility for programming the measured process value range with programmable Resolution.
The linear transmitters usually specify two signal values (Signal Low and Signal High) and the corresponding Process Values (Range Low and Range High). In the example Pressure Transmitter above; the Signal Low, Signal High, Range Low & Range High values specified are: 4 mA, 20 mA, 0 psi & 5 psi, respectively.
In summary, the following 6 parameters are required for interfacing Linear Transmitters:
1. Input Type : Standard DC Signal Type in which the transmitter signal range fits (e.g. 4-20 mA)
2. Signal Low : Signal value corresponding to Range Low process value (e.g. 4.00 mA)
3. Signal High : Signal value corresponding to Range High process value (e.g. 20.00 mA)
4. PV Resolution : Resolution (least count) with which to compute process value (e.g. 0.01)
5. Range Low : Process value corresponding to Signal Low value (e.g. 0.00 psi)
6. Range High : Process value corresponding to Signal High value (e.g. 5.00 psi)
X
Y
Process Value
Transmitter Signal
ΔY
ΔX
Y = mX + C
C
m = / ΔY ΔX
DC LINEAR SIGNAL INTERFACE
This appendix describes the parameters required to interface process transmitters that produce Linear DC Voltage (mV/V) or Current (mA) signals in proportion to the measured process values. A few examples of such transmitters are;
1. Pressure Transmitter producing for 4 to 20 mA 0 to 5 psi
2. Relative Humidity Transmitter producing for 1 to 4.5 V 5 to 95 %RH
3. Temperature Transmitter producing for 0 to 20 mA -50 to 250 °C
The instrument (indicator / controller / recorder) that accepts the linear signal from the transmitter computes the measured process value by solving the mathematical equation for Straight-Line in the form:
Y = mX + C Where;
X : Signal Value from Transmitter
Y : Process Value Corresponding to Signal Value X
C : Process Value Corresponding to X = 0 (Y-intercept)
m : Change in Process Value per unit Change in Signal Value (Slope)
Page 24
22
User Manual
SCANEX PLUS
The following examples illustrate appropriate parameter value selections.
Example 1: Pressure Transmitter producing for 4 to 20 mA 0 to 5 psi
Example 2: Relative Humidity Transmitter producing for 1 to 4.5 V 5 to 95 %RH
Example 3: Temperature Transmitter producing for 0 to 20 mA -50 to 250 °C
Presume the Temperature is to be measured with 0.1 Resolution, that is -50.0 to 250.0°C.
Input Type : 0-20 mA Signal Low : 0.00 mA Signal High : 20.00 mA PV Resolution : 0.1 Range Low : -50.0 Range High : 250.0
X (mA)
Y (psi)
4.00 20.00
Signal Low Signal High
0.00
Range Low
5.00
Range High
Presume the pressure is to be measured with 0.01 Resolution, that is 0.00 to 5.00 psi.
Input Type : 4-20 mA Signal Low : 4.00 mA Signal High : 20.00 mA PV Resolution : 0.01 Range Low : 0.00 Range High : 5.00
X (V)
Y (% RH)
0 5
Signal Low Signal High
0
95.0
1.000 4.500
5.0
Range Low
Range High
Presume the humidity is to be measured with 0.1 Resolution, that is 0.0 to 100.0 %.
Input Type : 0-5 V Signal Low : 1.000 V Signal High : 4.500 V PV Resolution : 0.1 Range Low : 5.0 Range High : 95.0
X (mA)
Y (°C)
Signal Low
Signal High
250.0
0.00
20.00
-50.0
Range Low
Range High
0
Page 25
23
BOTTOM / TOP CLIPPING
APPENDIX B
For mA/mV/V inputs the measured PV is a scaled value between the set values for ‘PV Range Low’ and ‘PV Range High’ parameters corresponding to the Signal Minimum and Signal Maximum values respectively. Refer Appendix A.
The Figure B.1 below illustrates an example of flow rate measurement using a transmitter / transducer producing a signal range of 4 - 20 mA corresponding to 0.0 to 100.0 Liters per Minute (LPM).
If this transmitter is to be used for a system having a flow rate range of 0.0 to 75.0 LPM then the actual useful signal range from the example transmitter is 4 mA (~ 0.0 LPM) to 16 mA (~ 75.0 LPM) only. If no Clipping is applied on the measured flow rate then the scaled PV will also include ‘out-of-range’ values for the signal values below 4 mA and above 16 mA (may be due to open sensor condition or calibration errors). These out-of-range values can be suppressed by enabling the Bottom and/or Top Clippings with appropriate Clip values as shown in figure B.2 below.
Y
Transducer Signal (4 - 20 mA)
(0mA, -25.0)
(4mA, 0.0)
(20mA, 100.0)
Flow Rate (0 - 100.0 LPM)
X
Figure B.1
Figure B.2
Y
Transducer Signal (4 - 20 mA)
(0mA, 0.0)
(4mA, 0.0)
Scaled PV (0 - 100.0 LPM)
X
Bottom Clipping
(16mA, 75.0)
Top Clipping
(20mA, 75.0)
PV Range Low : 0.0
PV Range High : 100.0
Enable Bottom Clipping : Yes
Bottom Clip Value : 0.0
Enable Top Clipping : Yes
Top Clip Value : 75.0
Parameter Values
User Manual
SCANEX PLUS
Page 26
24
w w w . p p i i n d i a . n e t
Process Precision Instruments
101, Diamond Industrial Estate, Navghar, Vasai Road (E),
Dist. Palghar - 401 210.Maharashtra, India
0250 - 2391722/33/37/42 07498799226, 09321985369
support@ppiindia.net sales@ppiindia.net,
Mar 2017
Loading...