PPI neuro 100EX User Manual

neuro 100EX
User Manual
Enhanced Universal Process Indicator
CONTENTS
User Manual
1. FRONT PANEL LAYOUT 1
2. BASIC OPERATION 3
3. SET-UP MODE ACCESS AND OPERATION 5
4. ALARM PARAMETERS 7
5. RETRANSMISSION PARAMETERS 9
6. INPUT CONFIGURATION 10
7. SUPERVISORY PARAMETERS 14
8. USER LINEARISATION PARAMETERS 16
9. HARDWARE ASSEMBLY & CONFIGURATIONS 17
10. MECHANICAL INSTALLATION 24
11. ELECTRICAL CONNECTIONS 26
1
FRONT PANEL LAYOUT
The indicator front panel comprises of digital readouts, LED indicators and tactile keys as shown in Figure 1.1 below.
Figure 1.1
Upper Readout
Lower Readout
Enter Key
Up Key
Down Key
Page Key
Alarm-3 Status
Alarm-1 Status
PPI
neuro 100 EX
ACK OPR
AL3 AL4
AL1
AL2
Alarm-2 Status
Alarm-4 Status
Alarm Acknowledge Key
Operator Key
READOUTS
The Upper Readout is a 5 digit, 7-segment bright red LED display and usually displays the PV (Process Value). In Set-up
Mode, the Upper Readout displays parameter values/options.
The Lower Readout is a 5 digit, 7-segment bright green LED display and usually displays Process Value Units. In case of any active Alarm(s), the Lower Readout flashes Alarm Status information. In Set-up Mode, the Lower Readout displays the names (identifier tags) for the parameters.
INDICATORS
The front panel comprises 4 LED indicators that show Alarm status. Refer Table 1.1 below for details.
KEYS
There are six tactile keys provided on the front panel for configuring the indicator, setting-up the parameter values and selecting Operation / Display Modes. Refer Table 1.2 below.
Table 1.1
Flashes while Alarm-1 is active.
AL1
AL2
Flashes while Alarm-2 is active.
LED
Status
AL3
Flashes while Alarm-3 is active.
AL4
Flashes while Alarm-4 is active.
User Manual
Section 1
2
User Manual
Table 1.2
OPR
OPERATOR
PAGE
ACK
ENTER
Symbol
Key
Function
PAGE
DOWN
UP
ALARM
ACKNOWLEDGMENT
Press to access ‘Operator-Page’ parameters.
(The parameters are listed and described in section 2 : Basic Operations)
Press to store the set parameter value and to scroll to the next parameter on the PAGE.
Press to enter or exit set-up mode.
Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change.
Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.
Press to acknowledge any pending Alarm(s). This also turns­off the Alarm relay.
3
BASIC OPERATION
Table 2.1
PV above Max. Range
PV below Min. Range
Message Error Type
Cause
Thermocouple / RTD broken
Sensor Open
Under-range
Over-range
ALARM STATUS UNDER PV ERROR CONDITIONS
For Alarm activation, the under-range condition is treated as minimum PV, whereas the over-range and open conditions are treated as maximum PV. Thus, Process High Alarm turns ON under Over-range/Open error. Similarly, Process Low Alarm turns ON under Under-range error.
OPERATOR PAGE AND PARAMETERS
The parameters that require frequent settings are organized on a separate page, called the Operator Page. The availability of operator parameters is controlled at supervisory level and the parameter setting cannot be locked by the Master Lock.
Accessing Operator Page & Adjusting Parameters
Step through the following sequence to open the Operator Page and to adjust the operator parameter values.
1. Press and release ‘OPR’ key. The Lower Readout shows prompt for the first available operator parameter and the Upper Readout shows value for the parameter.
2. Use UP / DOWN keys to adjust the value and then press ENTER key to store the set value and scroll to the next parameter.
The automatically reverts to MAIN Display Mode upon scrolling through the last operator parameter. indicator
Alternatively, use PAGE key to return to MAIN Display Mode.
Note:
The Operator Page can also be accessed through PAGE-0. (The pages and parameters are explained in next section).
The operator parameters are described in Table 2.2. Note that the parameters presented on Operator Page depend upon the
functions selected/enabled and supervisory level permissions.
POWER-UP
Upon power-up, all displays and indicators are lit on for approximately 3 seconds. This is followed by the indication of the indicator model name on the Upper Readout and the firmware version on the Lower Readout, for approximately 1 second.
MAIN DISPLAY MODE
After the Power-up display sequence, the Upper Readout starts showing the measured PV (Process Value) and the Lower Readout displays the user set Units for Process Value. This is the MAIN Display Mode that shall be used most often.
Alarm Status Information
In case of any Alarm (or Alarms) becoming active, the Lower Readout flashes the related Alarm details in the format ‘Ax.YY’, where x is the Alarm Number (1, 2, 3 or 4) and YY is Alarm Type (Lo or Hi) For example means Alarm-1 is active and the set Alarm Type is Low. In case of multiple Alarms, each Alarm Status is flashed sequentially with 3 Seconds time interval.
PV Error Indications
The PV Error type is flashed on the Upper Readout. For different errors and the causes, refer Table 2.1 below.
User Manual
Section 2
4
Table 2.2
Throughout the range for
the selected Input Type.
(Default :
For Process Low : -200.0
For Process High : 1376.0)
Parameter Description
Settings
(Default Value)
View Only
(Default : NA)
MAXIMUM PV
This indicates the highest value attained by the Process Value. This is a read only value and is available only if Min/Max monitoring is enabled.
MINIMUM PV
This indicates the lowest value attained by the Process Value. This is a read only value and is available only if Min/Max monitoring is enabled.
RESET COMMAND
Available only if Min/Max monitoring is enabled. Set this parameter to ‘Yes’ followed by correct password entry (through next parameter) to clear the current Min/Max values and start afresh monitoring the PV for new Min/Max values.
No
Yes
(Default : No)
RESET PASSWORD
For resetting the Min/Max values, set the reset command to ‘Yes’ and then enter the correct password.
0 to 250
(Default : 0)
ALARM-1 SETPOINT
The setpoint for Alarm-1. This parameter is not available if the selected Alarm type for Alarm-1 is ‘None’.
ALARM-2 SETPOINT
The setpoint for Alarm-2. This parameter is not available if the selected Alarm type for Alarm-2 is ‘None’.
ALARM-3 SETPOINT
The setpoint for Alarm-3. This parameter is not available if the selected Alarm type for Alarm-3 is ‘None’.
ALARM-4 SETPOINT
The setpoint for Alarm-4. This parameter is not available if the selected Alarm type for Alarm-4 is ‘None’.
View Only
(Default : NA)
User Manual
The operator parameter list mainly includes :
a) Min / Max Process Monitoring Parameters.
b) Setpoint Values for all 4 Alarms ( Alarm-1 to Alarm-4).
5
The various parameters are arranged in different groups, called PAGES, depending upon the functions they represent. Each group is assigned a unique numeric value, called PAGE NUMBER, for its access.
The parameters are always presented in a fixed format: The Lower Readout displays the parameter prompt (Identification Name) and the Upper Readout displays the set value. The parameters appear in the same sequence as listed in their respective sections.
SET-UP MODE
The Set-up Mode allows the user to view and modify the parameter values. Follow the steps below for setting the parameter values:
1. Press and release PAGE key. The Lower Readout shows PAGE and the Upper Readout shows page number 0. Refer
Figure 3.1.
2. Use UP / DOWN keys to set the desired PAGE NUMBER.
3. Press and release ENTER key. The Lower Readout shows the prompt for the first parameter listed in the set PAGE and the
Upper Readout shows its current value. If the entered PAGE NUMBER is invalid (contains no parameter list or any associated function), the reverts to the MAIN Display Mode.indicator
4. Press and release the ENTER key until the prompt for the required parameter appears on the Lower Readout. (The last
parameter in the list rolls back to the first parameter).
5. Use UP / DOWN keys to adjust the parameter value. (The display flashes if UP key is pressed after reaching the maximum value or DOWN key is pressed after reaching the minimum value).
6. Press and release the ENTER key. The new value gets stored in the indicator’s non-volatile memory and the next
parameter in the list is displayed.
The Figure 3.1 illustrates the example of altering the value for the parameter ‘Input type’.
Figure 3.1
SET-UP MODE : ACCESS AND OPERATION
User Manual
Press PAGE
key to enter Set-up mode
Press ENTER
key to open the Page
Use UP/DOWN
keys to set the Page Number
Default Page
Page NumberMAIN Display
Mode
Use UP/DOWN
keys to change the value
Press ENTER key
to store the value &
move to next parameter
First Parameter
on PAGE-12
Next Parameter
on PAGE-12
New Parameter
value
Section 3
or
or
6
Notes
1. Each page contains a fixed list of parameters that are presented in a pre-determined sequence. Note however that availability of a few parameters, called Conditional Parameters, depend upon the settings for some other parameters. For example, the parameter ‘Alarm Setpoint’ is available if corresponding ‘Alarm type’ is set to other than ‘none’.
2. To exit the set-up mode and return to the MAIN Display Mode, press and release PAGE key.
3. If no key is pressed for approximately 30 seconds, the set-up mode times out and reverts to the MAIN Display Mode.
MASTER LOCKING
The indicator facilitates locking all the PAGES (except Operator PAGE) by applying Master Lock Code. Under Locking, the parameters are available for view only and cannot be adjusted. The Master Lock, however, does not lock the operator parameters. This feature allows protecting the rather less frequently used parameters against any inadvertent changes while making the frequently used operator parameters still available for any editing.
For enabling / disabling the Lock, step through the following sequence:
Locking
1. Press and release PAGE key while the indicator is in the MAIN Display Mode. The Lower Readout shows PAGE and the
Upper Readout shows 0.
2. Use UP / DOWN keys to set the Page Number to 123 on the Upper Readout.
3. Press and release ENTER key. The indicator returns to the MAIN Display Mode with the Lock enabled.
The Figure 3.2 below illustrates the Locking procedure.
Figure 3.2
UnLocking
Repeat the Locking procedure twice for unlocking.
User Manual
Press PAGE
key to enter Set-up mode
Use UP/DOWN
keys to set the ‘Locking’ Code
Press ENTER key to
Lock & Return to
MAIN Mode
Default Page Locking Code
MAIN Mode
MAIN Mode
or
7
ALARM PARAMETERS
Visit www.ppiindia.net for technical notes on ALARM for detailed understanding of the parameters / terminologies used for describing the Alarm parameters in this section.
The parameters required for configuring Alarms are grouped on PAGE-10. The configuration includes selecting the type of Alarm, setting the hysteresis value, enabling / disabling start-up Alarm suppression, etc. Refer Table 4.1 for parameter description & settings.
Table 4.1
ALARM INHIBIT
Yes
The Alarm activation is suppressed until the PV is within Alarm limits from the time the indicator is switched ON. This allows suppressing the Alarm during the start-up Alarm conditions.
No
The Alarm is not suppressed during the start-up Alarm conditions.
ALARM HYSTERISIS
This parameter value sets a differential (dead) band between the ON and OFF Alarm states. Keep it large enough to avoid frequent switching of the Alarm relay.
No
Yes
(Default : No)
Settings
(Default Value)
Parameter Description
ALARM SET POINT
This parameter sets the Process High or Process Low limit for Alarm.
ALARM NUMBER
Select Alarm Number for parameter setting. For example; setting the value to 1, selects Alarm-1.
ALARM TYPE
None Disable the Alarm .
Process Low
The Alarm activates when the PV equals or falls below the ‘Alarm Setpoint’ value.
Process High
The Alarm activates when the PV equals or exceeds the ‘Alarm Setpoint’ value.
1 to 4
(Default : 1)
Min. to Max. of selected
input type range
(Default : For
Process Low : -200.0
& Process High : 1376.0)
None
Process Low
Process High
(Default : None)
(Default : 2.0)
For DC Lin. Volts/Current
1 to 30000 Counts
For Thermocouple/RTD
1 to 3000 or 0.1 to 3000.0
User Manual
Section 4
8
ALARM LATCH
No
The Relay switches ON/OFF with Alarm switching.
Yes
The Relay Output switches (ON for Normal Logic / OFF for Reverse logic) upon Alarm activation. However, Alarm de­activation does not affect the Relay status. The Relay status can only be regained by pressing ‘Acknowledge-key’ provided the Alarm has de-activated.
ALARM LOGIC
Select ‘Normal’ if Alarm is to activate an Audio / Visual alarm. Select ‘Reverse’ if Alarm is to Trip the system.
Settings
(Default Value)
Parameter Description
Reverse
Normal
(Default : Normal)
No
Yes
(Default : No)
User Manual
Loading...
+ 22 hidden pages