PPI HumiTherm-i Operating Manual

Page 1
Parameters
Settings
(Default Value)
Operation Manual
This brief manual is primarily meant for quick reference to wiring connections and parameter sear ching. For more details on operation and application; please log on to www.ppiindia.net
101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar - 401 210. T: 0250 - 2391722/33/37/42 M: 07498799226 09321985369 E: [email protected], [email protected]
Parameters
Parameters
Temperature Alarm Type
Temperature Alarm Setpoint
Temperature
Alarm Hysteresis
0.1 to 25.0 °C or °F ( 0.2)Default :
Direct
Reverse
( Direct)Default :
Temperature
Alarm Logic
( Yes)Default :
Yes
No
Temperature
Alarm Inhibit
Alarm Type
0.0 to 100.0%
(Default :
For Process Low : 0.0
For Process High : 100.0)
0.1 to 25.0%
(Default : 0.2)
-25.0 to +25.0°C
(Default : 0.0)
-25.0 to +25.0%
(Default : 0.0)
Settings
(Default Value)
Settings
(Default Value)
(Default : None)
None
Process High
Process Low
ALARM PARAMETERS FOR TEMPERATURE: PAGE-10
ALARM PARAMETERS FOR RELATIVE HUMIDITY: PAGE-11
ZERO-OFFSET PARAMETERS: PAGE-12
%RH Alarm Setpoint
%RH Alarm Hysteresis
%RH Alarm Logic
%RH Alarm Inhibit
Zero Offset for Temp. Value
Zero Offset for %RH Value
Parameters
Settings
(Default Value)
OPERATOR PAGE AND PARAMETERS : PAGE - 0
View Only
Maximum Dry Bulb Temperature Value
Minimum Dry - Bulb Temperature Value
View Only
Maximum %RH Value
View Only
Minimum Peak of RH
View Only
Reset Command
Reset Pass - Code
0 to 250
(Default : 0)
Keys Operation
Symbol
Key
Function
Press to enter or exit set-up mode.
DOWN
UP
ENTER
Press to store the set parameter value and to scroll to the next parameter on the PAGE.
Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change.
Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.
PAGE
Front Panel
-50.0 to 150.0°C or
-58.0 to 302.0°F (Default :
For Process Low : -50.0
For Process High : 150.0)
(Default : None)
Direct
Reverse
( Direct)Default :
( Yes)Default :
Yes
No
Parameters
0 to 250
(Default : 0)
Password For Resetting PV High - Low
Baud Rate
(Default : 4800)
1 to 8
(Default : 1)
Settings
(Default Value)
(Default : °C)
°C
°F
(Default : No)
Yes
No
SUPERVISORY PARAMETERS: PAGE-13
Unit Selection for Temperature
Dry-Bulb Temperature and % RH Min / Max Monitoring
ID Number for RH Loop
ID Number for Temperature Loop
1 to 8
(Default : 2)
(Default : No)
Yes
No
PV Error Indications
Message
Over-range (Dry-Bulb Temp. above Max. Range)
Under-range (Dry-Bulb Temp. below Min. Range)
Open (Sensor open / broken)
PV Error Type
FRONT PANEL LAYOUT
None
Process High
Process Low
Lower Readout
DOWN Key
PAGE Key
Alarm -1 Indicator
Upper Readout
Alarm-2 Indicator
ENTER Key
UP Key
PPI
HumiTherm-i
AL1
AL2
°C
%RH
Version : RTD Pt100, 3-wire for Temperature DC Linear (Voltage) for Humidity
Composite Temperature + Humidity Indicator
HumiTherm-i
Page 2
JUMPER SETTINGS
OUTPUT-1
MOUNTING DETAILS
OUTPUT-2 MODULE
ENCLOSURE ASSEMBLY
ELECTRICAL CONNECTIONS
MOUNTING DETAILS
SERIAL COMM. MODULE
‘UP’ inscribed on topside
UP
UP
Placing Back
Removal
Pullout Grip
Bezel
Front Label
PPI
HumiTherm-i
AL1
AL2
%RH
°C
HumiTherm-i
1
2
3
4
5
6
7
8
9
10
1
1 12
13
14
15
16
17
18
Pt100
INPU T1
OUTP
UT2
+
R
H
SEN
SO
R
SERIAL
COMMS.
+
SSR
RELAY
N/O
N/C
C
PPI
L N
AC DC
SUPPLY
-
Ex
IN
P
U
T2
_
GND
SSR
N/O
C
RELAY
N/C
+
_
OUTPUT1
HumiTherm-i
Jumper Setting-A
Jumper Setting-B
JUMPER SETTINGS
OUTPUT-2
HumiTherm-i
1
2
3
4
5
6
7 8
9
10
11 12
13
14
15
16
17
18
Pt100
IN P U T 1
OUTPU T 2
+
RH SENSOR
85~264
VAC
+
SSR
RELAY
NONCC
PPI
L N
SU P PLY
-
Ex
IN P U T 2
_
GND
SSR
NO C
RELAY
NC
+
_
OUTPU T 1
RS 485
SE RIA L
CO MM.
Output Type
Jumper Setting - A Jumper Setting - B
SSR Voltage
Pulses
Relay
Output Type
Relay
SSR Voltage
Pulses
1 2 3 4
1 2 3 4
1
2
3
1
2
3
Jumper Setting - BJumper Setting - A
PPI
Plug & Socket Connectors
Serial Communication Module
Power Supply Board
Front Label Upside-down
HumiTherm-i
PPI
Link
Pins
A
B
1
2
3
1 2 3 4
HumiTherm-i
Page 3
Parameters
Settings
(Default Value)
Operation Manual
This brief manual is primarily meant for quick reference to wiring connections and parameter sear ching. For more details on operation and application; please log on to www.ppiindia.net
101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar - 401 210. T: 0250 - 2391722/33/37/42 M: 07498799226 09321985369 E: [email protected], [email protected]
Parameters
Parameters Parameters
Alarm Type
-50.0 to 150.0°C or
-58.0 to 302.0°F (Default :
For Process Low : -50.0
For Process High : 150.0)
Alarm Setpoint
Alarm Hysteresis
0.1 to 25.0 °C or °F ( 0.2)Default :
Direct
Reverse
( Direct)Default :
Alarm Logic
( Yes)Default :
Yes
No
Alarm Inhibit
ALARM PARAMETERS FOR TEMPERATURE : PAGE 10
Alarm Type
0.0 to 100.0% (Default :
For Process Low : 0.0
For Process High : 100.0)
Alarm Setpoint
0.1 to 25.0%
(Default : 0.2)
Alarm Hysteresis
Reverse
Direct
(Default : Direct)
Alarm Logic
Alarm Inhibit
ALARM PARAMETERS FOR RELATIVE HUMIDITY : PAGE 11
-25.0 to +25.0°C
(Default : 0.0)
Zero Offset for Dry Bulb Temp.
Zero Offset for Wet Bulb Temp.
-25.0 to +25.0%
(Default : 0.0)
Zero Offset for RH Value
ZERO-OFFSET PARAMETERS : PAGE 12
Unit Selection for PV
Dry-Bulb Temperature and % RH High-Low Monitoring
0 to 250
(Default : 0)
Password For Resetting PV High - Low
Baud Rate
(Default : 4800)
1 to 8
(Default : 1)
ID for %RH Loop
UTILITY PARAMETERS : PAGE 13
Settings
(Default Value)
Settings
(Default Value)
Settings
(Default Value)
(Default : None)
None
Process High
Process Low
(Default : None)
None
Process High
Process Low
(Default : °C)
°C
°F
(Default : No)
Yes
No
PV Error Indications
Message
Over-range (Dry-Bulb Temp. above Max. Range)
Under-range (Dry-Bulb Temp. below Min. Range)
Open (RTD Pt100 (Dry Bulb) Sensor open / broken)
PV Error Type
Front Panel
( Yes)Default :
Yes
No
-25.0 to +25.0°C
(Default : 0.0)
1 to 8
(Default : 2)
HumiTherm-i
1
2
3
4
5
6
7 8
9
10
11 12
13
14
15
16
17
18
Pt100
IN P U T 1
OUTPU T 2
SERIAL
COMMS.
+
SSR
RELAY
N/O
N/C
C
PPI
L N
AC DC
SU P PLY
_
GND
SSR
N/O
C
RELAY
N/C
+
_
OUTPU T 1
IN P U T 2
Pt100
Keys Operation
Symbol
Key
Function
Press to enter or exit set-up mode.
DOWN
UP
ENTER
Press to store the set parameter value and to scroll to the next parameter on the PAGE.
Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change.
Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.
PAGE
FRONT PANEL LAYOUT
ELECTRICAL CONNECTIONS
ID for Temperature Loop
Lower Readout
DOWN Key
PAGE Key
Alarm -1 Indicator
Upper Readout
Alarm-2 Indicator
ENTER Key
UP Key
PPI
HumiTherm-i
AL1
AL2
°C
%RH
Version : RTD Pt100, 3-wire Dry Bulb for Temperature & RTD Pt100, 3-wire Wet Bulb for Humidity
Composi te Temper ature + Humidi ty Indicator
HumiTherm-i
Page 4
JUMPER SETTINGS
OUTPUT-1
MOUNTING DETAILS
OUTPUT-2 MODULE
ENCLOSURE ASSEMBLY
MOUNTING DETAILS
SERIAL COMM. MODULE
‘UP’ inscribed on topside
UP
UP
Placing Back
Removal
Pullout Grip
Bezel
Front Label
PPI
HumiTherm-i
AL1
AL2
%RH
°C
HumiTherm-i
1
2
3
4
5
6
7
8
9
10
1
1 12
13
14
15
16
17
18
Pt100
INPU T1
OU
T
P
U
T2
+
RH
SE
NSOR
SERIAL
COMMS.
+
SSR
RELAY
N/O
N/C
C
PPI
L N
A
C
DC
SUPPLY
-
Ex
I
N
P
UT2
_
GND
SSR
N/O
C
RELAY
N/C
+
_
OUTPUT1
HumiTherm-i
PPI
Link
Pins
A
B
1
2
3
1 2 3 4
HumiTherm-i
JUMPER SETTINGS
OUTPUT-2
Jumper Setting-A
Jumper Setting-B
Output Type
Jumper Setting - A Jumper Setting - B
SSR Voltage
Pulses
Relay
Output Type
Relay
SSR Voltage
Pulses
1 2 3 4
1 2 3 4
1
2
3
1
2
3
Jumper Setting - BJumper Setting - A
PPI
Plug & Socket Connectors
Serial Communication Module
Power Supply Board
Front Label Upside-down
HumiTherm-i