This is to certify that this heater is guaranteed for two years parts and one year labour from the date
of original commissioning. The heater must be commissioned within 4 weeks of installation.
To make a claim
In the first instance you must contact your appliance supplier, or installer and provide:-
1. The appliance type and serial number.
2. The original commissioning documentation. As much detail as possible on the fault.
3. Your supplier, or installer, will then contact Powrmatic to make a guarantee claim on your behalf.
Conditions of Guarantee
1. The heater must have been installed by a competent qualified installer, and in
accordance with the manufacturer’s instructions, building regulations and local regulations.
2. The heater has been professionally commissioned, within 4 weeks of installation, and a copy of
the commissioning sheet returned to Powrmatic.
3. The heater has been maintained on a yearly basis by a competent and qualified servicing
company.
4. The heater has been used in accordance with the manufacturer’s instructions.
5. The correct specification fuel has been used.
6. No unauthorised repairs of modifications have been made. Powrmatic ‘General Conditions of
Sales’ have been observed.
7. Except for the obligation of Powrmatic Ltd to perform warranty repairs during the guarantee
period, Powrmatic will not be liable in respect of any claim for direct or indirect consequential
losses, including loss of profits or increased cost arising from loss of use of the heater, or any
event arising there from.
Exclusions
Consumables such as gaskets, ignition electrodes, flame rectification electrodes, drive belts, fusible
links, control batteries are all excluded from guarantee.
Appendices
Information required for ecodesign (ErP) Directive 2009/125 37
Warnings
When working on this appliance the following warnings
must be observed:
Danger: Electricity
Warning: Flammable Materials
Warning: Hot Surfaces
Warning: Contains Moving Parts
Read and understand this Service Manual
Instructions before operating or servicing
this appliance
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 3 of 40
Page 4
User Instructions
If the heater has not been left operational
proceed as follows.
A) Checks before operating the Air Heater
The following preliminary checks should be made before
lighting the heater(s)
a) Ensure that the ELECTRICAL supply to the heater is
switched OFF.
b) Check that any warm air delivery outlets are open.
c) Check that the thermostat is set.
d) Check that the clock control is set to an ON period.
e) Check that any other controls are calling for heat.
B) Operating the Air Heater
1. Switch on the electrical supply at the isolator
2. If the Red Limit indicator lamp is illuminated, identify
the limit stat, remove the black cap and press the reset
button.
3. The startup sequence will commence. After a short
delay the burners will light and the green ‘ON’ indicator on
the front of the heater will be illuminated.
4. If the burners fail to light the control box will
automatically restart the ignition sequence. If after 5
attempts at ignition the burners have still failed to light
the control box will go to lockout and the Amber lockout
lamp on the front of the heater (or on the low level remote
reset, or MC200/MC300 if fitted) will be illuminated. To
restart the ignition sequence depress the reset button on
the low level reset for about 1-2 seconds.
WARNING: If it is not possible to light the
heater after several attempts, contact the
installer or local service company.
C) To Shut Down the Air Heater
1) For Short Periods:
Turn the room thermostat to the OFF, or set to 'Summer
Mode'.
2) For Long Periods:
Complete step 1 above. Wait for 5 minutes and then turn
OFF the electrical supply at the isolator.
D) Description of Operation
Important: The heater must NOT be
controlled by switching ON and OFF the
main electrical supply to it.
1) Standard Units
The ignition sequence commences each time the external
controls e.g. time clock, room thermostat, controller etc.
call for heat. The internal exhaust fan will run and, when
sufficient combustion airflow is proved by the air pressure
switch, the ignition spark will be generated, the main
gas valve opens and the burners will light on HIGH FIRE
for the first 30 seconds irrespective of the requirements
of the external control. The green ‘ON’ indicator will be
illuminated. The heater fan will automatically start 30
seconds after the burners light. After the first 30 seconds,
the heat output will then be controlled either to high fire
or low fire depending on the requirements of the space
being heated and the external controls fitted. When the
external controls are satisfied the burners will be turned
off and 2½ minutes later the heater fan will automatically
stop. If the burners fail to light the control box will make
another four attempts at ignition before going into burner
lockout. The amber ‘Lockout’ indicator/reset switch will be
illuminated.
2) Modulating Units
When the burners are alight, the heat output will be
controlled to any point between high and low fire;
depending on the requirements of the space being heated
and the external controls fitted.
3) Summer / Winter Modes
Certain types of external controls will provide for two
modes of operation i.e:
Summer: The heater fan alone will run at the dictate of
the external controls to provide air movement.
Winter: The heater will operate normally.
4) Overheat Thermostat
This operates if high temperatures within the heater are
detected, the burners are turned off and a Red indicator
lamp on the front panel is illuminated. VPx35 - 70 units
have a single thermostat located inside the heater.
VPx90 - 140 units have an additional thermostat on the
side of the unit at the opposite end to the controls (either
thermostat can go to limit and shut off the burners). The
fault condition must be identified and rectified and the
thermostat manually reset via the red high limit reset
switch. When the unit has cooled, identify the limit stat,
remove the black cap and press the reset button. The red
indicator lamp will go out and the unit is operational again.
page no. 4 of 40
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 5
User Instructions
Note: The limit thermostat(s) can only be reset
once the unit has cooled down. Unless the
cause of the fault condition is readily obvious,
for example a power cut whilst the heater was
operating, a service engineer should be contacted.
E) Maintenance
To maintain efficient, reliable and safe operation of the
heater it must serviced annually by a qualified person.
F) IMPORTANT
Free access must be maintained to and around the heater
for servicing purposes and the air supply to the heater
must not be restricted in any way. Combustible materials
must not be stored adjacent to the heater.
If at any time a gas leak is suspected, turn OFF the gas
supply at the meter and contact the local gas undertaking
immediately.
All Powrmatic heaters use gas and electricity to power
them, they may also contain moving parts such as pulleys
and belts. It would be hazardous to tamper with or
attempt to service unless you are a competent person in
the field of Gas and Electrical work.
If you have any safety questions reference the servicing
and installation of any of our heaters please do not
hesitate to contact our head office for expert advice. Your
safety is paramount to us.
Gas Safety (Installation & Use) (Amendment)
Regulations 2018
It is law that all gas appliances are installed,
adjusted and, if necessary, converted by
qualified persons* in accordance with the
current issue of the above regulations.
Failure to install appliances correctly can lead to
prosecution. It is in your own interests and that of safety
to ensure that the law is complied with.
* Gas Safe Registered Engineer
The VPx range are highly efficient, gas fired, fanned
circulation air heaters that cover heat outputs of 35kW to
140kW, have a closed combustion circuit and are supplied
complete with a flue system that can be either vertical or
horizontal.
VPx heaters are certified for use on Natural Gas, Group H
- G20*. Appliance Categories are Cat II2H (GB, IE). All VPx
heaters are CE certified and conform to all the European
directives stated in section 1.3.1
VPx heaters are designed to be floor standing and have a
centrifugal fan assembly fitted at the base of the heater
to circulate the air being heated past the formed tube
heat exchanger.
VPx heaters feature a closed combustion circuit and have
an internal exhaust fan, mounted downstream of the
heat exchanger, to evacuate the products of combustion
and draw in air for combustion. The air heater must be
connected to a flue system that is approved by Powrmatic
Ltd.
1.1 Introduction
as defined in BS 5345: Part 2. They are not suitable for
siting externally.
Heaters are fitted as standard with inshot burners, a fully
automatic control for ignition, flame sensing, gas supply
control and safety functions, an internal exhaust fan,
main air fan, fan command module and a limit thermostat.
Options include Modulating burner controls, inlet duct
connection, outlet duct connection, 90° outlet bend and a
full range of modular duct components.
IMPORTANT
Service and Maintenance Engineers shall
ensure that replacement items are fitted,
adjusted and set in accordance with the
data and detail set out in these instructions. If in doubt
consult Powrmatic Technical Department.
* LPG conversion kits available.
The heaters intended primarily for heating commercial
or industrial premises. They must not be used where the
atmosphere inside the premises could be contaminated
e.g. Dust, oil mist etc. or in areas classified as hazardous
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 5 of 40
Page 6
Technical Specification
VPx
Model35507090120140
Output (nominal)
Input (nett CV)
Air Flow Volumem
Heads34
Airflow
Electrics
Fuel
Overall
Dims
Install
Clearance
Flue
Combustion Air Spigotmm Ø100130
Noise Levels VPx UFdB(A)606263686970
Nett WeightVPx UFkg180209287426468542
Throwm122225273032
Fan Static
Supply
ConnectionBSP/Rc¾"
Nominal Inlet
Pressure
Consumption
VPx UF
VPx UF
Diametermm Ø100100130130130130
Maximum
Length
High Fire (max)
Low Fire (min)
High Fire (max)
Low Fire (min)
StandardPa250250250180290250
UpratedPa400400400400400400
StandardV/ph/Hz230/1/50
Optional*V/ph/Hz N/A(400/3/50)
Start Currentamp15.626.338(18)34(14)34(14)46(29)
Run Currentamp4.77.611(5.3)9.8(4.18)9.8(4.18)13.1(8.43)
Nat Gas mbar20.0
LPGmbar37.0
Nat Gas m
LPGm
Heightmm218422862381260726072722
Widthmm819819819819819819
Depthmm132513251325195019501950
Frontmm1000
Blank Sidemm150 (wall facing side)
Louvred Sidemm500
Rearmm500
Abovemm1000
Flue Onlym12
Room Sealedm6
Model35507090120140
kW34.050.570.590.0118.5137.0
kW23.833.947.865.383.593.3
kW36.554.576.597.5127.0146.0
kW26.0837.4152.9171.6590.83101.16
3
/s1.111.511.942.813.563.75
3
/h3.865.778.1010.3213.4415.45
3
/h1.522.203.164.015.105.90
Notes:
Fuel Consumption and input figures based upon nett calorific values as
follows: Natural Gas (G20) nett CV 34.02 MJ/m
3
MJ/m
• Heaters have efficiency levels which meet with the minimum
heater efficiency requirements of UK Part L Building Regulations.
• VPx heaters comply with the seasonal efficiency and NOx limits
requirements of the Ecodesign regulation (EU) 2015/1188,
Directive 2009/125/EC – Lot 21 Tier 1
• Standard heaters configured as High/Low. Optional modulation
available.
• Air handling data is assessed at room ambient conditions
• Throw figures provide the distance to the point where the terminal
velocity degrades to 0.25m/s
page no. 6 of 40
3
- Propane (G31) nett CV 88.00
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
• Noise levels are applicable to standard VPx models and are
measured 5m from appliance in a free field.
• Motor kW, run and start amps apply to standard electrical supply as
stated. For optional data contact sales office.
• Optional 3 phase direct drive centrifugal blowers shown in italics within
brackets().
• Connection of combustion air duct is not required for ‘flue only’
applications.
• It is the responsibility of the installing contractor to ensure that
ductwork is correctly sized and balanced when installing VPx
Centrifugal units.
Page 7
1
2
3
4
5
6
7
8
B
M
1
2
Dimensions
VPx
K
COMBUSTION
AIR INLET
0
.
0
5
1
J
EXHAUST
AIR OUTLET
J
ØD
ALTERNATIVE FLUE
& COMBUSTION AIR
POSITIONS
1
J
HL
G
E
G
J
M
LH
M
C
F
B
Model
Amm132513251325195019501950
Bmm819819819819819819
Cmm167216721672190019001900
DØmm100100130130130130
Emm356356356337337337
Fmm131413141236154715471547
Gmm142142220220220220
Hmm237237237247247247
Jmm255286345345345400
J1mm512614709707707822
Kmm207256308308308320
Lmm915915915148514851485
Mmm685685685685685685
35507090120140
A
B
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 7 of 40
Page 8
Accessories
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
HeadPlan1
(35,50&70)
HeadPlan2
(90,120&140)
Side/rear Inlet SpigotsFiltersDampers
0
2
1
0
5
5
8
6
Model
L
35507090120140
5
5
8
6
0
2
7
0
0
6
0
7
69
L
N
Lmm9151485
Nmm9951620
Pmm9001525
Notes -
• All dimensions are outside dimensions
• Standard filter specification is 10ppi
• Higher specification filters available on request - contact our sales team for more information
• Standard dampers are manual operation - motorised options available
0
6
1
2
0
0
9
6
0
5
7
9
1
8
1
0
6
0
6
7
0
7
9
6
P
N
16
0
0
6
0
7
9
6
5
2
7
9
1
8
Head Plans
Head Plan 1
(35, 50 & 70)
Head Plan 2
(90, 120 & 140 only)
page no. 8 of 40
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 9
1.2 Technical Data
Injector Sizes & Burner Pressures - Natural Gas - Group H - G20 Net CV (Hi = 34.02MJ/m³)
(All variants)
Injectors
MODELNo.Size (mm)Markedmbarm³/hmbarm³/ h
VPx3552.2658013.23.865.82.76
VPx50102.547509.55.774.53.96
VPx70102.547509.48 .104.65.60
VPx9083.5150 06.010.323.07.5 8
VP x120103.515006.713.443.39.61
VPx140123.515006.215.452.910.7
High FireLow Fire
Burner
Pressure
Gas Rate
Pressure
Burner
Gas Rate
Nominal Inlet
Pressure = 20mbar
Minimum Inlet
Pressure = 17.5mbar
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 9 of 40
Page 10
1.3 General Requirements
1.3.1. Related Documents
All VPx heaters comply with the following European
Directives:
Energy Related Product Directive: 2009/125/EC*
Gas Appliance Directive: 2009/142/EC
Electromagnetic Compatibility Directive: 2004/108/EC
Low Voltage Directive: 2006/95/EC
Machinery Directive: 2006/42/EC
Air heater(s) must be installed in accordance with BS6230
and BS5440 plus any relevant requirements of local and
national building codes. * where appropriate.
1.3.2 Location
Powrmatic VPx units are designed to operate within an
ambient temperature range of -10 to 25°C.
VPx heaters should be located on a solid and level surface.
The location chosen must have adequate space for
servicing and air circulation around the air heater as well
as an adequate air supply.
Consideration should be given to flue routes and points of
exit, gas, electrical and control connections. Consideration
should also be given to the throw characteristics of the
heater, issues of public access and siting of environmental
control stations and/or remote temperature sensors
where the position needs to be representative of the zone
temperature to which they refer.
conditions. Please consult our Technical Department for
further information.
1.3.2.1 Sizing of the heater
The heater should be correctly sized for the area that it is
heating, Full calculations need to be preformed to ensure
the correct KW output heater is fitted (CIBSE elemental
methodology can be used, or the Powrmatic Technical
Department can provide guidelines).
1.3.3 Electrical Supply
Wiring external to the air heater must be installed in
accordance with the I.E.E. Regulations for Electrical
Installations and any local regulations which apply.
All standard heaters are supplied by 230V - 1ph, 50Hz.
The method of connection to the main electricity supply
must:-
- facilitate the complete electrical isolation of the unit(s)
via a suitable fused isolator (see section 2.4.5 for ratings)
- be in a readily accessible position adjacent to the unit(s)
- serve only the unit(s)
- have a contact separation of at least 3mm in all poles.
See the accompanying wiring diagram for the heater
electrical connections
VPx 90-140 units can also be supplied for 400V 3N, 50Hz.
Where the location of the air heater is such that it might
suffer external mechanical damage e.g. from overhead
cranes, fork lift trucks, it must be suitably protected.
Heaters should not be installed in hazardous areas or
areas where there is a foreseeable risk of flammable
or corrosion inducing particles, gases or vapours being
drawn into the combustion air or main fan circuits.
Areas where special consideration or advice may be
required could include but is not limited to –
• Where de-greasing solvents are present, even in
minute concentrations
• Where paint spraying is carried out
• Where styrenes or other laminating products are
used
• Where airborne silicone is present
• Where petrol engine vehicles are stored or
maintained
• Where dust is present (i.e. wood working or
joinery shops)
• Where high levels of extract persist.
Installation in such areas may be possible under specific
1.3.4 Gas Supply
A servicing valve and union to facilitate servicing must
be fitted to the gas inlet pipe work of the heater. The
gas supply must be completed in solid pipe work and be
adequately supported.
Heaters suspended by drop rods, straps or chains must
have a flexible connection as the final link between the
gas supply pipe work and the heater. Sufficient slack
must be left in the connection to take account of normal
movement of the heater.
WARNING: When completing the final gas
connection to the heater do not place undue
strain on the gas pipe work of the heater.
1.3.4.1 Service Pipes
The local gas undertaking should be consulted at the
installation planning stage in order to establish the
availability of an adequate supply of gas to suit the
building requirements. An existing service pipe must not
be used without prior consultation with the local gas
undertaking.
page no. 10 of 40
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 11
1
2
3
4
5
6
7
1.3 General Requirements
1
2
3
1.3.4.2 Meters
An existing meter should be checked, preferably by the
gas undertaking, to ensure that the meter is adequate
to deal with the total rate of gas supply required by all
connected equipment.
1.3.4.3. Installation Pipes
Installation pipes should be fitted in accordance with IGE/
UP/2. Pipe work from the meter to the air heater must be
of adequate size.
Do not use pipes of a smaller size than the inlet gas
connection of the heater.
The complete installation must be tested for soundness
as described in the above Code.
1.3.5 Flue System
Only flue systems supplied through Powrmatic Ltd may
be used with VPx units. Several configurations of flue and
combustion air ducts are available.
The flue must terminate in a freely exposed position and
be sited to prevent the products of combustion entering
any opening in a building in such concentration as to be
prejudicial to health or a nuisance.
Type B22
Installation.
Horizontal Outlet
Type C12 or C32 Installation.
Vertical Outlet
Type B22 Installation.
Vertical Outlet
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Type C12 or C32 Installation.
Horizontal Outlet
page no. 11 of 40
Page 12
1.3 General Requirements
1.3.6 Ventilation Requirements
Type B flued installations.
Where VPx heaters are installed within the heated space
(ie not in a plant room or an enclosure)and having a
building design air change rate of greater than 0.5/h,
additional provision for ventilation is not required.
If the building design air change rate isless than 0.5/h,
additional provision for natural or mechanical ventilation
is required. These being:
• Natural Ventilation:
Grilles having a free area of at least 2cm² per kW of rated
heat input shall be provided at low level i.e. below the level
of the heater flue connection.
• Mechanical Ventilation:
Must ensure that the space air change rate is at least
0.5/h, must be of the ‘input’ type and interlocked to
ensure the heaters cannot work if the input system is not
working.
Type B flued installations.
Where VPx heaters are installed in a plant room or
an enclosure (i.e. not within the heated space) having
combustion air drawn directly from the room and
connected to a flue that evacuates the products of
combustion directly from the room additional provision
for natural or mechanical ventilation is required.
These being:
• Natural Ventilation:
There must be permanent air vents communicating
directly with the outside air, at high level and at low level.
Plant Rooms
Low level (inlet) 4cm²/kw of total rated net heat input
High level (outlet) 2cm²/kw of total rated net heat input
Enclosures
Low level (inlet) 10cm²/kw of total rated net heat input
High level (outlet) 5cm²/kw of total rated net heat input
• Mechanical Ventilation:
The minimum flow rate of ventilation shall be 4.14m³/h
per kilowatt of total rated heat input.
Type C flued installations.
Where VPx heaters are Installed within the heated
space (i.e. not in a plant room or an enclosure) having
combustion air ducted to the appliance and combustion
products ducted to the outside air, NO additional
provision for the supply of either combustion air or for
combustion products dilution or additional provision for
the supply of air is necessary.
Type C flued installations.
Where VPx heaters are installed in a plant room or
an enclosure (i.e. not within the heated space)having
combustion air ducted to the appliance and combustion
products ducted to the outside, air vents shall be
provided and be permanently open.
• To room or internal space
Low level (inlet) 10cm²/kw of total rated net heat input
High level (outlet) 10cm²/kw of total rated net heat input
• Direct to outside air
Low level (inlet) 5cm²/kw of total rated net heat input
High level (outlet) 5cm²/kw of total rated net heat input.
Typ e C
12 or C32 Installation (these refer to section 2.2
of these instructions)
VPx
Input
kW
Typ e B22 Installation (these refer to section 2.2 of
these instructions)
Air vents shall be permanently open.
In all cases figures are per heater installed.
For multi heater installations the appropriate
values for each heater must be added together
In the
heated
space
Low level
grille.
Free area
cm²
In a plant room,
ventilation to
outside
Low level
grille.
Free area
cm²
High level
grille.
Free area
cm²
In an enclosure,
ventilation to
outside
Low level
grille.
Free area
cm²
High level
grille.
Free area
cm²
Air vents shall be permanently open.
Figures are for heaters in plant rooms or
enclosures ONLY
In all cases figures are per heater installed.
For multi heater installations the appropriate
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 13
1.3 General Requirements
1.3.7 Air Distribution System
VPC units used in buildings having a low heat loss i.e.
where single units are required to cover a large floor
area,and in buildings with high roof or ceiling heights
Calecon thermal economiser units may be considered to
ensure even heat distribution and minimise stratification.
Care should be taken to avoid impeding the air throw with
racking, partitions, plant or machinery etc. Various outlet
configurations are available as optional extras to modify
the air throw pattern to suit particular site conditions.
For VPx UD units, the duct work must comply to current
regulations and be correctly calculated to match the
particular heaters resistance and air flow.
A full and unobstructed return air path to the air heater(s)
must be provided.
1.3.7.1 Ducting Requirements
If the air heater(s) are installed in a plant room, the return
air intake(s) and the warm air outlet(s) from the heater(s)
must be fully ducted, into and out of the plant room to
avoid interference with the operation of the heater.
The openings in the structure of the plant room/enclosure
through which the ducting passes must be fire stopped.
Care must be taken to ensure that return-air intakes are
kept clear of sources of smells and fumes, and where
there is any possibility of pollution of the air by dust,
shavings etc., precautions must be taken to prevent
contamination.
If necessary, suitable barrier rails should be provided to
prevent any combustible material being placed within
900mm of the outlets.
It is recommended that
you have a minimum
of 2000mm from the
heater outlet prior to
any restriction
Air VolumeMax Duct Resistance
Model
m³/h(Pa)
VPx35 UD4000200
VPx50 UD5450250
VPx70 UD7000250
VPx90 UD10100180
VP x120 UD1280 0290
VPx140 UD13500250
Airflow
VPx Heater
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 13 of 40
Page 14
1
2
3
4
5
6
7
2.1 Fitting the Unit
2.1.1 Fitting space requirement
D*
D*
VPx UF
Front View
C
D*D*B
E*A
Side View
B
A
C
VPx UF
Distance from outside of heater to closest obstacleDistance
AFrontmm1000
BRearmm500
CAbovemm1000
Side adjacent to wallmm150
D*
Opposite Sidemm500
Note: The minimum clearances must be
observed for installation and servicing.
Warning: Any combustible material adjacent
to the air heater and the flue system must
be so placed or shielded as to ensure that its
temperature does not exceed 65 °C.
Note: The access door to the controls section
may be removed to improve access. Open the
door to 90°, remove the earth cable at the
bottom, and then lift the door vertically
upwards to disengage the hinge plates. Refit in reverse
order. Ensure that the earth cable is refitted.
Before installation, check that the local distribution
conditions, nature of gas and pressure, and adjustment of
the appliance are compatible.
The air heater must be installed in accordance with
the rules in force and the relevant requirements of any
fire regulations or insurance company's requirements
appertaining to the area in which the heater is located,
particularly where special risks are involved such as
areas where petrol vehicles are housed, where cellulose
page no. 14 of 40
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 15
2.1 Fitting the Unit
spraying is carried out, in wood working departments etc.
If necessary consideration should be given to mounting
the heater on resilient pads, or equivalent, to minimise
transfer of noise and vibration to the structure of the
building.
Floor mounted heaters must be installed on a level
noncombustible surface.
Heaters mounted at high level must be supported on
a purpose designed platform or framework that is
suspended from vertical drop rods, chains or straps or
mounted on specifically designed cantilever brackets from
a non-combustible wall.
The method of installation support must be capable of
adequately supporting the weight of the unit (See section
1.2) and any ancillary equipment.
Before installing the heater the existing structure must be
inspected to ensure it is suitable.
All supports should be protected against the effects of
rust or corrosion.
If the method of mounting allows for any movement of
the heater it is essential that all gas, duct, and electrical
connections to the heater are made with flexible
connections to maintain continuity of connection.
2.1.3 Air Distribution System
2.1.3.1 General
VPC heaters, if required, can be used with duct work
either to more precisely define the point of air delivery,
and / or provide ducted return air or ducted fresh air inlet.
2.1.3.2 Noise Reduction
Ducting should be connected to the heater spigots via an
airtight flexible coupling of noncombustible material.
Before fitting the coupling it must be ensured that a
minimum clearance of approximately 15mm will be
maintained between the ends of the ducting and the
heater spigots.
Sound attenuators may be fitted in inlet and outlet ducts
to reduce airborne fan noise. If sound attenuators are
used then these must be factored into the total static
resistance of the ductwork. Materials used in outlet sound
attenuators must be capable of withstanding 100°C air
temperature without any deterioration.
2.1.4 Room Thermostat Siting
The room thermostat should be fitted at a point which
will be generally representative of the heated area as
far as temperature is concerned. Draughty areas, areas
subjected to direct heat e.g. from the sun, and areas
where the air movement is relatively stagnant e.g. in
recesses, should be avoided. The thermostat should be
mounted approximately 1.5m from the floor.
Any room thermostat, frost thermostat, time clock etc.
must be suitable for switching 230V, 5A and must be of
the 'snap action' type to minimise contact bounce.
For electrical connections of external controls see section
2.5 or the accompanying wiring diagram.
The system should be checked to ensure that the
installation work has been carried out in accordance with
the design requirements.
Particular attention should be given to the correct
arrangement of delivery ducts and registers, return air
ducts and grills and general adequacy of return air paths.
Ensure that the total duct system resistance does not
exceed the available air pressure of the equipment
supplied refer to section 1.2. If the duct system resistance
is less than the available air pressure of the equipment
supplied additional resistance must be introduced e.g. by
adjustment of duct outlet nozzles and balancing of the
duct system. Conversely if the duct system resistance
is greater than the available air pressure of the heater
supplied the system resistance must be reduced.
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 15 of 40
Page 16
2.2 Flue/Combustion Air Duct System
The minimum distance between surfaces of the flue pipe
and any surfaces made from combustible materials is
300mm. If it is necessary for the flue pipe to pass through
a structure made from combustible materials a metal
sleeve must be used so that the minimum clearance of
300mm is maintained.
The flue and combustion air ducts supplied with the
heater are capable of withstanding their own weight
over the allowable flue lengths. Wall bands and bracing
brackets, or equivalent, must be used to provide lateral
stability and should be used at centres not exceeding 2.5
metres.
All models are supplied as standard with a top flue
outlet and the flue outlet and combustion air sockets
temporarily fitted.
2.2.1 Conversion to Side Flue Outlet
1. Remove the two blanking plates from the flue /
combustion air openings at the side of the unit.
2. Remove the four screws from the exhaust fan outlet
flange.
3. Remove the screws securing the fan mounting box to
the exhaust header plate.
The maximum permitted length of flue system is 6m, or
12m if the flue outlet only is used. If an offset is required
two sets of 45° bends should be used each set being
equivalent to 0.5m of flue length. 90° bends may be used
but each set will be equivalent to 1.0m of flue length.
All outer joints must be finished with the provided locking
bands. A smear of silicon grease to the inside of sockets
will assist in fitting components together. All flue and
combustion air ducts must be supported independently
of the air heater. The flue or flue/combustion air terminal
must not be installed so as to be less than:
- 300mm below an opening e.g. window, air brick etc.
- 200mm below eaves or gutter.
- 300mm from an internal or external corner.
- 600mm from a surface facing the terminal.
- 1500mm vertically from another terminal on the same
wall.
- 300mm horizontally from another terminal on the same
wall.
- 2000mm from ground level.
2.2.4. Installation of Flue System
Note: A terminal guard, as supplied by
Powrmatic Ltd, must be fitted to horizontal
flue terminals.
4. Remove fan assembly and rotate the assembly 90°
clockwise.
5 Refit the fan assembly to the exhaust header plate
ensuring that the gasket is not damaged, if necessary
replace or make good with silicon sealant.
6. Secure the exhaust fan outlet flange to the inside of the
side panel and fit the blanking plates to the top panel.
2.2.2. Fitting Flue/Combustion Air Sockets
1. Apply a bead of silicon sealant around the face of the
flange on the exhaust fan outlet tube that can be seen
from the outside of the heater. Place the flue socket on
the outside of the heater to mate with this flange and
clamp the two flanges together, on either side of the
heater panel using the screws provided. Ensure that the
silicon sealant has sealed between the two flanges.
2. Apply silicon sealant and refit blanking plates as
required to seal unused panel holes.
2.2.3. General Requirements
See Figures 1a to 2b for the different types of flue
installation. In all cases the flue outlet socket must be
connected via the provided flue system to outside air.
Notes for all systems.
i) Final overall length of adjustable
disconnection piece must be between 360 -
415m m.
ii) 45° offsets may be used if required. Each set is
equivalent to 0.5m of flue length.
iii) Where VPx heaters are used in clean environments it is
permissible to take the combustion air directly from the
heated space.
2.2.4.1. Horizontal System - Rear Outlet
Note: If the outlet is required to the side of the
unit 90° bends may be fitted directly onto the
inlet/outlet spigots on the heater.
1. Locate the position of the flue terminal, allowing for
a slight gradient running down from the heater to the
terminal of 2° - 3° and cut a hole to suit.
2. Fit the flue terminal, securing via the wall plate and
weather with silicon sealant or similar.
3. Fit the twin to concentric adapter to the terminal
section and extend the flue and combustion air ducts to
the heater using straight lengths.
Fit an adjustable length prior to the unit, to facilitate flue
page no. 16 of 40
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 17
1
2
3
4
5
6
7
8
Totalfluelength
12mmaximum
Lengths
Adjustablelength
ombustionairentry
ttedwithinletgrille)
Combustionairentry(fittedwithinletgrille)
Terminal
90°Elbow
Fluesocket
1
2
m
m
a
x
i
m
u
m
Flashing
Lengths
Adjustable length
Condensate drain length
Terminal
Flue socket
Combustion air entry(fitted with inlet grille)
6m maximum12m maximum
Combustion air socket
Lengths
Adjustable lengths
Flue socket
Single to twin adaptor
Terminal
Combustion air entry (fitted with inlet grille)
Lengths
Adjustable length
Flue socket
Combustion air entry(fitted withinlet grille)
Combustion air entry(fitted with inlet grille)
Terminal
1
2
3
4
(
2.2 Flue/Combustion Air Duct System
disconnection for servicing. Extend the adjustable lengths
to make the final connection to the appropriate heater
inlet/outlet spigots.
4. Ensure that internal silicon sealing rings are in place and
that all tubes are pushed fully home. Secure concentric
lengths with the locking bands provided.
Fig 1a. Individual system - Type C12 horizontal
Single to twin adaptor
90° Elbow
Combustion
air socket
Adjustable length
Flue socket
Lengths
Total flue length
6m maximum
Terminal
C(fi
Fig 1b . Individual system - Type C32 vertical
Terminal
Flashing
mu
m
i
x
am
m
6
Maximum 6m, Minimum 80Ø=1480mm; 10 0Ø=1560mm; 130Ø=1560mm
Combustion air socket
Single to twin adaptor
Lengths
Adjustable lengths
Condensate drain lengths
Flue socket
2.2.4.3. Internal Combustion Air System
1. Complete the run of flue sections from the terminal
2.2.4.2. Vertical System - Top Outlet
1. Locate the position of the flue terminal cut a hole in the
roof to suit.
spigot to the flue outlet socket of the heater generally as
described in 2.2.4.1. and 2.2.4.2., ensuring that the internal
silicon sealing rings are in place.
2. It is recommended that both air inlets are utilized and
that both are fitted with the mesh inlet plates supplied. In
2. Fit the flashing and the flue terminal so that the lower
edge of the outer case is over the top of the flashing.
Weather with silicon sealant or similar.
addition a 90° bend should be fitted to the rear inlet, the
inlet opening of the bend facing to the side of the heater i.e.
away from the main air fan.
Fit a condensate drain length into the flue socket on
the heater and an equivalent straight length onto the
Fig 2a. Exhaust only system -Type B22 horizontal
combustion air socket.
3. Fit the twin to concentric adapter to the terminal
section and then extend down to the heater using straight
lengths.
Combustion air entry
fitted with inlet grille)
90° Elbow
Fit adjustable lengths as the final connection pieces, to
facilitate flue disconnection for servicing. Extend the
adjustable lengths to make the final connection but
do not exceed the maximum extended length so as to
maintain joint integrity.
Extend the drainage off take of the condensate drainage
length to a suitable gully or drain.
4. Ensure that internal silicon sealing rings are in place and
that all tubes are pushed fully home. Secure concentric
lengths with the locking bands provided.
Adjustable length
Lengths
Flue socket
Combustion air entry
(fitted with inlet grille)
Total flue length
12m maximum
Terminal
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 17 of 40
Page 18
Lengths
Adjustable length
Flue socket
Combustion air entry(fitted withinlet grille)
Combustion air entry(fitted with inlet grille)
Terminal
2.2 Flue/Combustion Air Duct System
Fig 2b. Exhaust only system - Type B22 vertical
Terminal
Flashing
Lengths
Adjustable length
Condensate drain length
Combustion air entry
(fitted with inlet grille)
Flue socket
Combustion air entry
(fitted with inlet grille)
2.2.5. Condense Length
We recommend installing an inline condense flue
drain when flued vertically, due to the lower flue gas
temperatures experienced when the heater is operating
at low firing rates.
Other relevant factors include installations where
m
u
m
i
x
a
m
m
2
1
significant length of the flue is used which may cause
chilling, or if heater may be exposed to high winds and
heavy rain, which may ingress the flue.
We would always recommend fitting the inline condense
drain even if the drain point is capped, should the drain be
required in the future. Any clarification can be achieved by
consulting with Powrmatic.
The condensate drainage pipe should be run in a standard
drain pipe material and have a fall of at least 2.5° in every
50m. Copper or copper based alloy shall not be used for
condensate drains. See BS 6896.
Condensate drainage pipe should run and terminate
internally to a soil and vent stack or a waste pipe.
Alternatively, the condensate can be discharged into the
rainwater system or a purpose-made soakway.
2.3 General Identificationof ElectricalItems
GAS VALVEPRESSURE SWITCH
SECOND
HIGH LIMIT
RESET.
90-140 only
HIGH LIMIT RESET
HIGH LIMIT INDICATION
BURNER LOCKOUT RESET
BURNER ON INDICATION
EXHAUST FAN
ENGINEERS SWITCH
CONTRACTORS
TERMINALS
PACTROL
FAN COMMAND
INTERFACE BOARD
Modulation only)
MAINS
INPUT
BOARD
MODULE
page no. 18 of 40
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 19
2.4ElectricalCableInstallation
2.4.1. Electrical Connections
Warning: THIS APPLIANCE MUST BE
EARTHED.
Warning: Lockout reset is by a switched
Neutral to the controls in the heater.
Warning: Wiring external to the unit must be
carried out by an appropriately qualified
person to current IEE regulations for
Electrical Installations and any local regulations which
apply.
The local electrical supply must be run to a point adjacent
to the heater and be suitably terminated to provide an
isolation point that will prevent remote activation of
the unit during servicing. Wiring should be completed in
flexible conduit.
The local electrical supply conditions must be compatible
with the electrical data given on the appliance data plate.
Heaters are for use with 230V, 1N, 50Hz supplies.
(230V) via a room thermostat, time clock etc. and, if
applicable, the remote low level lockout reset see 2.4.5.
Note: To achieve maximum system efficiency it
is recommended that VPx units are controlled
by an MC200 or MC300 unit. Simple room
thermostat and thermostat/time clock control
systems will not provide optimum system efficiency and
fuel savings.
Wiring drawings and instructions are supplied with the
respective controller.
Key:
Mains supply = 2 core and earth
MC200 Controller = 8 core and earth
alt. MC300 Controller = 6 core screened + LNE
Optional MC200 sensor = Screened 2 core*
* (screen must be grounded only at the MC200, See
instructions supplied with controller for wiring sizing,
Max. 100m)
The method of connection to the main electricity supply
must:-
- facilitate the complete electrical isolation of the
heater(s) via a suitable fused isolator that will prevent
remote activation of the heater during servicing (see
section 2.4.5 for ratings).
- be in a readily accessible position adjacent to the
heater(s).
- serve only the heater(s).
- have a contact separation of at least 3mm in all poles.
See section 2.5 or the accompanying wiring diagram for
the heater electrical connections.
Reference must be made to Section 2.4.5 to ascertain
the electrical loading of the unit(s) being installed so that
cables of adequate cross-sectional area are used for
the electrical installation. The length of the conductors
between the cord anchorage and the terminals must be
such that the current carrying conductors become taut
before the earth conductor if the cable or cord slips out
of the cord anchorage. All external controls must be of an
approved type.
Typical wiring
installation
Optional
Remote Controller
(MC200 shown)
Remote
Sensor
(optional)
Fused
Isolator
All units are fully prewired and only require final
connections for the incoming mains supply. Heaters not
supplied with inbuilt time and temperature controls will
also require completion of the external control circuit
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
230V Supply shown
(415V option on 90-140)
page no. 19 of 40
Page 20
2.4ElectricalCableInstallation
2.4.3. Wiring
The wiring terminals are located on the electrical panel
behind the side door of the heater which firstly has to be
opened.
2.4.3.1. Mains Supply
L
E
N
2.4.3.2. Intergral Control Wiring
Mains input of either 230V 50Hz 1Ph or 415V 50Hz 3Ph
supply connections are via a separate terminal block. For
input power refer to table below.
L1
L2
3 phase 1 phase
L3
E
N
2.4.4. External Fuses
Single Phase UnitsThree Phase Units
Model
VPx35
VPx50
VPx70
VPx90
Running
Current (A)
4.710 / 6N/AN/A
7.610 / 10N/AN/A
11.015 / 165.310 / 10
9.815 / 164.25 / 6
Fuse/MCB Rating (A)
Integral control
wiring terminal
Running
Current (A)
0V
V+
COM
SEN1
SEN2
Fuse/MCB Rating (A)
(motor rated Protection Device)
VP x120
VPx140
page no. 20 of 40
9.815 / 164.25 / 6
13 .115 / 168.510 / 10
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 21
N
L
-N.O. Thermostat or Relay
-230vin. (Delayon, DelayO)
-AccessoryTerminal.4A FuseProtected
-230vin.Notusedonmodulatingheaters
MAINS SUPPLY230V AC50HZ
-Momentaryswitchtoneutral
- 230vout
2.4.5. Wiring Connections
2.4ElectricalCableInstallation
Controlling circuitry is via a numbered terminal strip wired
back to the in-built MC200/CAB controller. If an external
control panel is to be used, then these terminals must be
used. Connection terminals are:
terminal 1 230V Heat Low Demand
terminal 3 230V Main Fan Only
terminal 4 & 5 Heat High Circuit
terminal 6 Lockout indication - 230V Output
terminal 7 Burner reset - Neutral Switch
terminal 8 0-10V d.c. Modulation
terminal 9 0V Modulation
terminal 10 Live to Controller
terminal 11 Neutral to Controller
terminal E Earth to Controller
Wiring terminal strip for External Controller
E
1
1
0
1
9
8
7
6
5
4
3
2
1
N
L
Modulating (-)
Modulating (+) 0-10v
230v Supply
for Controller
Lockout Reset
Lockout Indication
!
High Fire
Call for Fan Only
230v Out
Call for Heat
213456789101112
* when used
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
t1
Heat On Signal 230V
t3
Fan Only Signal 230V
t4
t5
Input 230V
Output 230V
High Fire
Circuit
t6
Lockout Signal 230V
t7
*Lockout Reset
t8
(Switched Neutral)
t9
t10
0Vdc
0-10 V d c
*Modulating signal
*Modulating signal
t11
Live Output
230V Supply
for Controller
t
Earth
Neutral
page no. 21 of 40
Page 22
2.4ElectricalCableInstallation
2.4.6. Interconnecting Wiring:
2.4.6.1. VPx High / Low to Remote MC200
Warning: External controls
MUST be powered via heater
terminal 10, 11 and Earth
2.4.6.2. VPx Modulation to Remote MC200
page no. 22 of 40
Warning: External controls
MUST be powered via heater
terminal 10, 11 and Earth
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 23
VPx High / Low Internal Wiring 1pha
2.5 Wiring Diagrams
Blk
Gry
Brn
21C
LIMIT
STAT2
r
/
G
n
e
l
Y
(when
is fitted).
connections
Stat extension
secondary stat
T6A
21C
LIMIT
STAT1
Red
Gry
Wht
RED NEON
Red Neon
Terminal 1
Pactrol
RESET
AMBER
INDICATOR/
SUPPLY
FAN
FAN MOTOR
CENTRIFUGAL
NLE
G/Y 2.5
Br 2.5
Blu 2.5
230V AC
50HZ 1PH
MAINS SUPPLY
N
L
Blu 1.0
CONTROL
NLE
Or 1.0
SIGNAL
GREEN NEON
G/Y 1.0
1
/Y
.
G
0
LIMIT
STAT1
Blu
Red
Grn
Vi
Blu
Or
Grn
450mm
AIR
21C
450mm
SWITCH
PRESSURE
N
C
N
C
O
Yel
Wh
Gry
3-PHASE
FAN
EXHAUST
LNEEN
Red
Blk
G/Y 0.5
G/Y 0.5
OPTION
400V AC
50HZ 3PH
MAINS SUPPLY
1
3
N
0
.5
l
B
u
r
/
G
n
Y
1
.
5
r
B
1
.
5
T6A
GAS
VALVE
L
Vi
Wh
L2L
L
7
8
Br
Blu
SUPPLY
FAN MOTOR
CENTRIFUGAL
Gry 1.5
Blk 1.5
Br 1.5
Grn/Y 1.5
Hi-Lo
Head
Gas Valve
Yel
Wh
Controller, L
Controller, N
Controller, E
1
1
0
18171615141
Blu
Blu
Engineer's Switch
(if fitted)
8
9
1
3
Grn
Grn
2
1
W
h
CON 1CON 4
V
i
k
B
l
R
d
e
h
W
Y
l
e
Y
l
e
L
PACTROL
N
V
i
S
R
/
O
r
O
L
/
y
G
r
T
S
u
B
l
N
B
r
CON 5
L
Vi
Wh
Blu 1.0
Or 1.0
Br 1.0
Blk 0.5
B
R
T
W
S
N
I
K
I
I
E
L
U
M
D
N
A
M
M
O
C
GV PACTROL
Heat
Aux 230v out
Fan
Lockout Ind.
Lockout Reset
Hi-Fire
Hi-Fire
345
6
7
G/Y 0.5
JT 1JT 2
CON 6 CON 7
MicroGas P25
CON 3
N
Wh
A
NCNOC
L
D
O
N
A
l
B
k
M
r
B
F
C
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 23 of 40
Page 24
2.5 Wiring Diagrams
B
lk
VPx Modulation Internal Wiring 1pha
Blk
Gry
Brn
LIMIT
connections
Stat extension
21C
STAT2
/Y
e
l
(when
is tted).
secondary stat
N
LIMIT
r
G
n
L
21C
STAT1
Red
Gry
Wht
Pactrol
Red Neon
MAIN
FAN(S)
Terminal 1
G/Y 1.0
Or 1.0
AIR
SWITCH
LIMIT
STAT
C
21
Blu
Blu
RESET
AMBER
INDICATOR/
Or
Vi
.
1
0
/Y
G
Blu
Grn
Grn
Blu
Red
PRESSURE
C
N
N
O
C
Yel
Wh
Gry
FAN
GAS
EXHAUST
Red
Blk
G/Y 0.5
VALVE
7
8
Vi
Wh
G/Y 0.5
Yel
Wh
Main loom assembly
Wiring Legend
7
8
1
9
1
1
0
1
7
1
8
2
Loom sub-assembly
Wire size: 0.5mm
16151
Blu
2
Wire size: 1.0mm
1
3
4
Grn
Grn
Bullet connector
Spliced connection
Male
3
2
456
1
W
h
CON 1
V
i
B
lk
R
d
e
W
h
CON 4
Y
l
e
Y
l
e
L
PACTROL
N
V
i
S
R
/
O
r
L
/O
y
G
r
T
S
u
B
l
N
B
r
L
h
W
i
V
GV PACTROL
MicroGas P25
CON 5
Blu 1.0
Or 1.0
Br 1.0
Blk 0.5
N
SWTRL
R
E
IV
R
D
V
G/Y 0.5
JT 2
JT 1
CON 6 CON 7
CON 3
N
NCNOC
G
M
Female
page no. 24 of 40
+
0v-
v
0
1
e
d
R
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 25
2.6 Commissioning and Testing
Gas Safety (Installation & Use) (Amendment)
Regulations
It is law that all gas appliances are installed,
adjusted and, if necessary, converted by
qualified persons* in accordance with the
current issue of the above regulations.
Failure to install appliances correctly can lead to
prosecution. It is in your own interests and that of safety
to ensure that the law is complied with.
* Gas Safe Registered Engineer
2.6.1. Electrical Installation
Checks to ensure electrical safety must be carried out by
a qualified person.
2.6.2. Gas Installation
For new installations, the whole of the gas installation,
including the meter, should be inspected and tested
for soundness and purged in accordance with the
recommendations of IGE/UP/1 (Edition 2) or IGE/UP/2A
as appropriate.
2.6.5. Operating the Air Heater
NOTE: On initial lighting of the heater(s), it may
take some time to purge the internal pipe work
of air.
IMPORTANT: The internal pipe work of the
appliance has been tested for soundness
before leaving the factory. After establishing
the main burners test round the gas inlet
connection using a leak detection fluid.
1. Switch on the electrical supply at the isolator.
NOTES: If the red indicator illuminates, remove
the adjacent black cap and press the High Limit
Reset button. If the amber rocker switch
illuminates, depress the switch for 2 seconds
to reset the burner lockout.
2. The ignition sequence should now commence. After
a delay of approximately 45 seconds the ignition spark
will be generated and the main gas valves energized. The
burners will then light.
2.6.3. Air Distribution System
The system should be checked to ensure that the
installation work has been carried out in accordance with
the design requirements.
Particular attention should be given to the correct
arrangement of delivery ducts and registers, return air
ducts and grills and general adequacy of return air paths.
Ensure that the duct work is balanced so that the
specified motor running currents are achieved See section
1.2
2.6.4. Checks before Operating the Air Heater
The following preliminary checks should be made before
lighting the heater(s)
a) Ensure that the ELECTRICAL supply to the heater is
switched OFF.
b) Check that all warm air delivery outlets are open.
c) Check that all external controls are calling for heat.
d) If an MC200 or MC300 is being used ensure that the
control is set to winter operation.
3. If the burners fail to light the control box will complete
a further four ignition attempts. If at the end of five
attempts the burners have still not lit the control box
will go to lockout and the amber rocker switch will be
illuminated. To restart the ignition sequence depress the
illuminated reset button for about 1-2 seconds.
4. SHUT OFF Set the external controls to OFF or MIN.
2.6.6 Adjustments
2.6.6.1. Burner Gas Pressures
This is set for the required heat input before despatch.
High and low pressures should be checked in the following
manner:
2.6.6.1.1. High/Low Regulation
1. Set external controls to ensure the main burner is off.
Open the side access panel. Connect a pressure gauge
to the burner pressure test point on the multifunctional
control.
2. Set external controls to turn on the main burner and
maintain high fire. Compare the measured burner gas
pressure to that stated on the data plate. In addition it
is advisable to check the gas rate using the gas meter
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 25 of 40
Page 26
2.6 Commissioning and Testing
dial pointer ensuring that no other appliances supplied
through the meter are in operation.
3. Repeat 2 above with external controls set to maintain
low fire.
4. If it is necessary to adjust either the high fire or low fire
pressures proceed as follows after levering off the plastic
cover from the High/Low regulator.
Note: High fire setting must be adjusted first
after which the low fire setting can be set. Any
adjustment of the high fire setting alters the
minimum setting.
2.6.6.1.1.1. SIT Sigma 843 Adjustment
Maximum Setting.
With the controls set to high fire, use an adjustable
or 10mm spanner to screw the adjustment nut in to
increase and out to decrease, until the required pressure
is obtained.
Turn the burner On and OFF several times to check the
pressure setting and then turn off.
Minimum Setting.
Disconnect electrical connection to the regulator and turn
the burner back on and wait until the burner pressure has
stabilised.
Keeping the nut stationary, use a 6 x 1 screwdriver to turn
the slotted adjustment screw clockwise to increase and
counter-clockwise to decrease, until the required pressure
is obtained.
Reconnect high/low regulator and check high fire
pressure.
Repeat both steps if necessary and then replace cover cap
Cap
2.6.6.1.1.2. Honeywell V4336 Adjustment
Maximum Setting
With the controls set to high fire, use an adjustable or
8mm spanner to turn the adjustment screw, clockwise
to increase and counter-clockwise to decrease, until the
required pressure is obtained
Turn the burner On and OFF several times to check the
pressure setting and then turn off.
Minimum Setting
Disconnect electrical connection to the regulator and turn
the burner back on and wait until the burner pressure has
stabilised.
Use a screwdriver to turn the slotted adjustment screw
clockwise to increase and counter-clockwise to decrease,
until the required pressure is obtained.
Reconnect high/low regulator and check high fire
pressure.
Repeat both steps if necessary and then replace cover
cap.
Hexagonal
adjustment screw for
maximum pressure
setting
Cover
Lever point
5. Turn off the main burner, disconnect the pressure
gauge and replace the sealing screw.
Internal slotted
adjustment screw for
minimum pressure
setting
Adjustment nut (10mm)
for maximum pressure
setting
5. Turn off the main burner, disconnect the pressure
gauge and replace the sealing screw.
page no. 26 of 40
Adjustment screw
for minimum
pressure setting
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
2.6.6.1.2. Modulating Regulation
1. Set external controls to ensure that the main burner is
off. Open the side access panel. Connect a pressure gauge
to the burner pressure test point on the multifunctional
control.
2. Set external controls so as to turn on the main burner
and maintain high fire. Compare the measured burner
gas pressure to that stated on the data plate. In addition
it is advisable to check the gas rate using the gas meter
dial pointer ensuring that no other appliances supplied
through the meter are in operation.
Page 27
2.6 Commissioning and Testing
3. Repeat 2 above with external controls set to maintain
low fire.
4. If it is necessary to adjust either the high fire or low fire
pressures proceed as follows after removing the plastic
cover from the Modulating regulator.
Note: Minimum fire setting must be adjusted
first after which the high fire setting can be
set. Any adjustment of the minimum fire
setting alters the maximum setting.
Minimum Setting.
Disconnect electrical connection of modulating regulator
and turn burners back on and wait until the burner
pressure has stabilised.
Turn 9mm adjustment nut for low fire pressure clockwise
to increase and counter-clockwise to decrease until the
required pressure is obtained.
Reconnect modulating regulator and check high fire
pressure, readjust if necessary.
2.6.6.1.3. Modulating Control Board
For Modulation a modulating control board is fitted (which
also includes the fan command outputs). The board
interfaces between a 0-10VDC control signal and the
modulating regulator.
Basic operation method
1. With the 0 to 10 signal at 0, the gas valve drive signal
will be de-energised.
2. When the input control signal goes to >2V, the gas valve
drive output will be at its maximum output value for a
preset 2 minutes.
3. An input signal from the burner controller - when
received by the board continually for more than 30
seconds - will switch an output to the main heater fan.
4. After the preset 2 minutes of maximum output, the 0
to 10V input signal will take control of the gas valve drive.
Maximum Setting.
Disconnect electrical connection of modulating regulator
and turn burners back on and wait until the burner
pressure has stabilised.
Push shaft gently downwards to the maximum
adjustment screw and hold there. Turn 7mm adjustment
nut for high fire pressure, clockwise to increase and
counter-clockwise to decrease, until the required pressure
is obtained. Release shaft.
Repeat both settings if necessary and then replace cover
cap.
Shaft
Cap
Adjustment nut (7mm)
for maximum pressure setting
Adjustment nut (9mm)
for minimum pressure setting
‘O’ ring
6.3mm AMP terminals
5. When the 0 to 10V signal drops below 1V the signal will
drop to zero and the gas valve drive signal will be deenergised.
6. The fan output will continue for a further 2.5 minutes.
2.6.6.2. Final Adjustments
1. In addition it is advisable to check the gas rate using the
gas meter dial pointer. Ensure that no other appliances
supplied through the meter are in operation.
2. If required, after checking or setting the burner
pressures, the CO2 content in the flue gases can be
checked by sampling in the first section of flue fitted to
the flue outlet of the unit. Nominal CO2 values are given
for guidance in the table at the bottom of the previous
page.
3. Turn on the main burner as before and test for gas
soundness around pressure test joint using a leak
detection fluid e.g. soap solution. Replace access panel.
2.6.6.3. Flame Current
1. To measure the flame current connect a multimeter
capable of measuring micro amps as shown in the
following diagram.
5. Turn off the main burner, disconnect the pressure
gauge and replace the sealing screw.
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 27 of 40
Page 28
2.6 Commissioning and Testing
Model35507090120140
High Fire CO2%8.028.69.157.5 08.408.72
FGT (nominal)°C150.5152.0158.6132.0153.0128.0
Low Fire CO2%4.764.95.004.505.004.99
FGT (nominal)°C124.0120.5121.7123.0121.098.4
2.6.6.5. Limit Thermostat
Limit Thermostat settings:-
VPx (all) = 90°C
Note: VPx35 & 90 - 140 units have a single
limit thermostat whereas VPx 90 to VPx 140
units have two. The second stat is at the
Flame Current
Measurement
controls end. The limit thermostats are wired in series
(either thermostat will shut down the burner).
opposing side of the heater to the burner/
2. Minimum current reading is 0.5µA and normal value
should be 1.5µA or higher.
2.6.6.4. Fan Adjustments
The running current of the centrifugal fan must be
checked once the heater is running and compared with
the following table.
Typical
Running
Current
Model
Pha
Motor
kW
VPx3511.15.7A6.8A
VPx5011.18.5A9.8A
VPx7011.411.0A12.0A
VPx9012 x 0.556.4A8.0A*
VPx12012 x 1.48.5A10.0A*
VPx14012 x 1.410.0A10.0A*
Max
Running
Current
2.6.7. Air Heater Controls
1. Close the gas service tap and ensure that the gas valve
is heard to close within 1 second and that the lockout light
is illuminated. Note that the heater may attempt five
re-ignitions before going to lockout. Open the gas service
tap and reset the unit from lockout.
2. Check that the room thermostat and all automatic
controls are operating satisfactorily.
2.6.8. Handing over the Air Heater
Hand these instructions to the user or purchaser for
retention and instruct in the efficient and safe operation
of the air heater and associated controls. Adjust the
automatic controls to those values required by the User.
Finally, advise the user or purchaser that, for continued
efficient and safe operation of the air heater, it is
important that servicing is carried out annually.
* current shown for each fan
WARNING: Exceeding the MAX running
current will cause the fan’s thermal overload
to trip!
Adjust the balancing dampers within the airflow ductwork
system to achieve a current suitable for the model in
question.
page no. 28 of 40
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
In the event that the premises are not yet occupied turn
off the gas and electricity supplies and leave instructional
literature adjacent to gas meter.
Page 29
2.7 Servicing
Gas Safety (Installation & Use) (Amendment)
Regulations
It is law that all gas appliances are installed,
adjusted and, if necessary, converted by
qualified persons* in accordance with the
current issue of the above regulations.
Failure to install appliances correctly can lead to
prosecution. It is in your own interests and that of safety
to ensure that the law is complied with.
* Gas Safe Registered Engineer
WARNING: Always switch off and disconnect
electricity supply and close the gas service
valve before carrying out any servicing work
or replacement of failed components.
NOTE: If a suspended air heater is to be
serviced do not lean ladders against the
heater.
Ensure that an access tower or equivalent is
used.
NOTE: The access door to the controls section
may be removed to improve access.
Open the door to 90°, remove the earth cable
at the bottom, and then lift the door vertically
upwards to disengage the hinge plates.
Refit in reverse order. Ensure that the earth
cable is refitted.
2. Disconnect the spark and rectification leads from the
control box and remove the electrical plug connections
from the top of the gas control valve assembly.
3. Remove the burner heat shield, 3 screws.
4. Release the inlet connection flange from the gas valve
by removing the four screws.
5. If required remove the manifold by removing the four
screws securing it to the burner assembly.
6. Remove the two screws that secure the top of the
burner assembly to the bulkhead and lift out burner
assembly.
7. Using a stiff brush, not a wire brush, brush the
burners to dislodge accumulated deposits. Inspect the
burners both internally and externally to ensure that
they are clean. Examine the injectors and if damaged or
deteriorated, replace with new ones of the correct size
and marking. If deemed necessary, clean the injectors. Do
not broach out with wire.
8. Reassemble the injectors, manifold and burners in
reverse order to that above.
2.7.1. General
Full maintenance should be undertaken not less than once
per year by a qualified person.
No 'specialised 'tools will be required to carry out this
service.
A fault finding guide is given in section 3.1 to aid servicing.
After any servicing work has been complete, or any
component replaced, the air heater(s) must be fully
commissioned and tested for soundness as described in
Section 2.6.
To commence servicing, firstly open the side access door
by rotating the quarter turn screw(s).
2.7.2. Main Burner Assembly Removal
1. Ensure that the gas service valve is turned OFF
and then unscrew the union nut situated immediately
downstream of it.
2.7.3. Ignition and Rectification Electrodes
Note: The ignition electrode is located at the
bottom of the burner assembly, the
rectification electrode is located at the top of
the burner assembly.
Inspect the electrodes, making sure that they are in a
sound and clean condition. In particular check that the
ignition electrode is clean and undamaged. Check that the
spark gap is 2.5mm and that the rectification probe is 10 12mm forward of the burner.
2.5mm
Ignition Electrode Spark Gap
2.7.4. Exhaust Fan
1. Remove the four screws securing the flue outlet socket.
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 29 of 40
Page 30
2.7 Servicing
2. Disconnect the fan electrical connections from the main
terminal strip
3. Remove the screws securing the fan mounting box to
the exhaust header plate.
4. Clean impeller by brushing with a stiff brush.
5. Re-assemble using a new sealing gasket to the fan
mounting box. Use silicon sealant around the joints
.
2.7.5 Heat Exchanger
Whilst the main burner assembly is removed from the
unit, check that the primary sections that the burners fire
into are clean.
2.7.5 Main Fan Assembly
1. Remove section side panel(s) and inspect the fan blades
for any damage or excessive buildup of deposits that
could give rise to an imbalance. Remove the assembly for
cleaning as follows.
downstream of the gas service valve.
2. Remove the electrical plug connections from the top of
the multifunctional control.
3. Release the flanged connections at the inlet and
outlet of the multifunctional control and remove the
multifunctional control.
4. Reconnect the new valve in the reverse order to that
above ensuring that the valve is correctly orientated.
Renew the sealing 'O' rings if necessary.
2.7.6.2. Burners
1. Remove the burner assembly as described in Section
2.7.2.
2. Remove the end plates of the burner assembly and the
central burner support plate.
3. Exchange burners as required and reassemble
components in reverse order.
2. Slacken the cable gland on the casing through which
the fan electrical cable passes.
3. Disconnect the fan leads from the electrical terminals
in the contactor enclosure.
4. Withdraw cable through entry grommet.
5. Remove the complete fan assembly by removing the
fixings securing the fan to the base rails.
6. Reassemble in reverse order.
2.7.6. Replacement of Faulty Components
Only parts supplied via or authorised by Powrmatic
should be used. A short list of parts and part numbers are
detailed in section 3.2 of this manual. If in doubt, please
contact Powrmatic.
2.7.6.1 Multifunctional Control
1. Ensure that the gas service valve is turned OFF. If
a flexible gas connection has been used go to step 2
otherwise unscrew the union nut situated immediately
4. Re-commission the appliance as described in Section
2.6.
2.7.6.3. Electrode Assemblies
1. Disconnect the electrode leads from the control box as
appropriate.
2. Remove the screw securing the electrode assembly
to the burner assembly side plate and withdraw the
assembly.
3. Fit replacement and reassemble in reverse order.
Check that the spark gap is 2.5mm (See section 2.7.3) and
the rectification electrode is 10 - 12mm forward of the
burner.
2.7.6.4. Limit Thermostat
NB. Ensure that the thermostats are set correctly before
fitment
Limit Thermostat settings:-
1. Remove the screws securing the thermostat phial
mounting plate to the inner bulkhead*, withdraw
assembly and unclip the phial.
VPx (all) = 90°C
page no. 30 of 40
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 31
2. Remove the electrical connections from the limit
thermostat.
Model
2.7 Servicing
Pressure SwitchSetting (Pa)
3. Remove the securing nut and remove thermostat from
the front panel.
4. Fit replacement thermostat in reverse order.
Note*: VPx35 & 90 - 140 units have a second
limit stat at the opposing end of the heater to
the burner/controls. Remove the two small
cover plates and replace as above.
2.7.6.5. Exhaust Fan
1. Remove the four screws securing the flue outlet socket.
2. Disconnect the fan electrical connections from the main
terminal strip
3. Remove the screws securing the fan mounting box to
the exhaust header plate.
4. Remove fan assembly.
LNVx35
LNVx50180
146522176
180
LNVx70200
LNVx90
LNVx120350
146522177
300
LNVx140330
2.7.6.7. Control Box
1. Unplug all the electrical connections.
2. Remove the two screws that secure the control box in
place.
3. Fit replacement in reverse order.
5. If needed, transfer the fan mounting box to the
replacement fan.
6. Fit replacement exhaust fan, using new gaskets and
silicon sealant as necessary, and reassemble in reverse
order.
2.7.6.6. Air Pressure Switch
1. Remove the two screws securing the cover and remove
cover.
2. Disconnect electrical connections.
3. Pull off the sensing tube from the air pressure switch.
4. Remove the screws fixing the air pressure switch and
remove switch.
5. Fit replacement in reverse order refitting the sensing
tube to the negative (- or L) tapping on the pressure
switch.
6. Adjust pressure switch set point to that shown in the
following table:
2.7.6.8. Fan Command Module
1. Unplug all the electrical connections by squeezing each
side to release.
2. Using a small flat screwdriver push on the locking tab
of each PCB mount and gently ease the board upwards to
release.
3. Fit replacement in reverse order.
2.7.6.9. Centrifugal Fan/Motor
1. Disconnect the electrical connections to the centrifugal
fan section.
2. Remove the side panels of the section for access to the
fan and motor.
3. Fit replacements as appropriate and reassemble in
reverse order.
Note: If a 3ph motor is being replaced ensure
that the direction of rotation is correct. If it is
not interchange any two of the three phases
connected to the motor.
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 31 of 40
Page 32
3.1 Fault Finding
START
Is there
230V between
Pactrol controller terminals
CON5 - pin 1 and
pin 2?
YES
YES
Is there
continuity between
Pactrol controller terminals
CON5 - pin 1 and
pin 7?
YES
Is there
230V between
Pactrol controller terminals
CON5 - pin 3 and
Neutral?
NO
TURN ON MAINS
ISOLATOR!
YES
Is there
now 230V between
Pactrol controller terminals
CON5 - pin 1 and
pin 2?
NO
NO
Check the
internal fuse
inside the
Pactrol
in overheat trip?
RED lamp will be
Is the unit
indicating
NO
Check for break
in BROWN cable.
NOW continuity
between Pactrol controller
terminals CON5 - pin
1 and pin
YES
NO
Is
there
7?
Is
there
230V at
contractors
terminal
1?
NO
Replace
Pactrol!
NO
No call for heat!
Check controller!
YES
Is
there
230V at
contractors terminal 6?
AMBER lamp will be
indicating
NO
Is the exhaust fan
running?
YES
Is
there 230V on the
YELLOW cable to the 'C'
terminal of the Pressure
switch?
YES
Continued on
next page
YES
Burner in Lockout.
Press the illuminated
amber rocker switch
NO
NO
YES
NO
Is there
230V on the WHITE
cable to the 'N.O' terminal
of the Pressure
switch?
Is
the inpulse tube
connected to the negative
connection ofthe pressure
switch?
NO
Swap terminals
Still not
working?
Heater in Overheat.
Remove the black cap
and press the button
Replace
Pactrol!
YES
YES
YES
Pressure Swirch stuck
in a closed position
Chan ge A.P. S.!
YES
Is
there 230V on the
YELLOW cable to the 'C'
terminal of the Pressure
switch?
Replace
Pactrol!
NO
Check for break
in WHITE &
GREY cables.
NO
Replace
Combustion
Fan!
page no. 32 of 40
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 33
Continued from
previous page
3.1 Fault Finding
Is there
230V between
contractors terminals 14 and
15? Green lamp will be
indicating?
NO
Check for break in
VIOLET & WHITE
YESYES
NO
Has the Gas Solenoid
Valve energised?
YES
Is the Gas
Solenoid Valve
energised to HIGH FIRE?
(for only 30 seconds if input
is at low fire)?
NO
BROWN cable from
terminal 'C' of the
YES
cables.
Replace
Gas Valve and
Lead!
YES
Is there
230V on the
Fan Comand
Module?
Is
there
NOW 230V
between contractors
terminals 14
and 15?
NO
WHITE & PURPLE cables to
terminal 'GV PACTROL' of
the Fan Command
YES
Is there
230V on the
Module?
Replace
Pactrol!
NO
Replace
Pactrol!
NO
NO
Replace Main
Fan Command
Manual!
Is
there
NOW a
spark present
at the ignition
Electrode?
Is a
spark present and
the Ignition Electrode and
flame present during the 5
second period?
YES
Is the
flame sensor
sending a rectification
signal back to the
controller?
YES
Continued on
next page
NO
• Ensure spark gap is 2.5mm
• Ensure there are no cracks on
• Clean electrode with wire wool
• Ensure heater has a good earth
• Ensure there are no cracks on
• Clean electrode with wire wool
the ceramic
• Check cable to Pactrol
the ceramic
• Ensure mains polarity is
correct
• Check cable to Pactrol
YES
YES
Is
there
NOW a
spark present
at the ignition
Electrode?
Has the
flame rectified
NOW?
Replace
Pactrol!
NO
NO
• Minimum reading is 1.0μA a
NO
Replace
Electrode!
• Check flame current by
connecting a sensitive
multi-meter capable of
measuring micro amps
normal value should
be 1.5μA or higher.
Has the
flame rectified
NOW?
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 33 of 40
Page 34
3.1 Fault Finding
Burner Fired!
Continued from
previous page
Has the main fan
star ted after the 30 second
delay?
YES
Heater Working!
Does
the burner
go into high limit
trip after a period
of time?
YES
• Check burner pressure for
correct setting.
• Check Overheat Stat for
incorrect limit setting.
• Check fan rotation.
• Remove the black cap and
press the reset button
NO
Is there
230V at terminal
'SW' on the Fan Command
Module?
Replace Main
Fan Assembly!
NO
• Check for 230V on terminals L & N
on Fan Command Module.
• Check for 230V between terminals
GV on Fan Command Module.
YES
Has
the main fan
star ted
NOW?
NO
• Check the operation
of the main fan by
connecting it to
a permanent mains
supply.
NO
Has
the main fan
star ted
NOW?
YES
Burner
STILL in high
limit trip?
YES
Replace
Limit Stat!
3.1.1 Modulation Driver LED Indication
The unit will have a single LED indicator and will provide
the following information :-
Steady on LED
Unit in standby mode (all outputs off)
1 LED Blink
Summer fan “ON” mode active.
2 LED Blinks
DC control signal received >2V, Heating mode gas valve
drive at maximum.
Replace Main
Fan Command
Manual!
4 LED Blinks
DC control signal <2V. Heating mode now off but fan in
overrun mode (2.5 mins max)
Slow on off @ 50%
Auto Time Out has occurred. (i.e. DC control signal
received >2V but no trigger from sequence controller
within 5 mins.
3 LED Blinks
Fan output on, (heating mode) Heating mode gas valve
drive follows DC input.
page no. 34 of 40
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 35
3.2 List of Parts
ItemDescriptionUsagePart No.
Gas Valve SIGMA 84335-50145035208HL-SIT/KIT
Gas Valve VK4105A35-50145035208/KIT
Gas Valve VR4605AB70-90145035204/KIT
Gas Valve V425AB120/140141378715 /K IT
Ignition Electrode
35-7 0
90 -14 0
Rectification (Flame Sensor) ProbeAll142423003
35-7 0
Burner
90 -14 0
Limit StatAll142403609
142423010
142423004
142400240
142400241
Control Box (Sequence Controller)
All High/Low
All Modulation
High/Low Governor Head35-14 0 -/HL142466402
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
145030846
145030847
page no. 35 of 40
Page 36
3.2 List of Parts
Modulation Governor Head35-140 -/MOD142466403
Fan & Modulation Burner Controller 35-140 -/MOD142400303M
Lockout Reset SwitchAll143070276
Fan Command Module MkIIIAll (except /MOD)142403603
Pressure Switch HUBA 604
Exhaust Fan
Exhaust Fan c/w Mounting Brackets
Exhaust Fan
Exhaust Fan c/w Mounting Brackets
Exhaust Fan
Exhaust Fan c/w Mounting Brackets
Main Centrifugal Blower - VPx
35-7 0
90 -14 0
35-50
35-50
70
70
90 -14 0
90 -14 0
35
50/90
70
120/14 0
146522176
142522177
140210496
NV X1050EXH/SP
140201505
NVX6075EXH/SP
140201506
NVX90140EXH/SP
tba
1402CFAN210/T/15
1402CFAN550/T/15
1402CFAN580/T/15
Contactor
page no. 36 of 40
120 -14 0
70-90
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
143000600
143000601
Page 37
Information required for ecodesign (ErP) Directive 2009/125
Model355070
Rated Heat Capacity
Low Heat Input
Minimum Heat Capacity
Useful Efficiency
Electrical Power Consumption*
NOx Seasonal (Gross)
Envelope Loss Factor
Emission Efficiency
Seasonal Space Heating Energy Efficiency
Model cont.90120140
Rated Heat Capacity
Low Heat Input
Minimum Heat Capacity
Useful Efficiency
Electrical Power Consumption*
NOx Seasonal (Gross)
Envelope Loss Factor
Emission Efficiency
Seasonal Space Heating Energy Efficiency
Nett CVkW26.137.452.9
High Fire%93%93%92%
Low Fire%91%91%90%
High FirekW0.070.060.06
Low FirekW0.070.060.06
StandbykW<0.01<0.01<0.01
IgnitionkW
Nett CVkW71.790.8101.2
High Fire%92%93%94%
Low Fire%81%92%92%
High FirekW0.060.060.06
Low FirekW0.060.060.06
StandbykW<0.01<0.01<0.01
IgnitionkW
Appendices
kW36.554.476.5
kW23.833.947.8
0.000.000.00
mg/kWh
%N/AN/AN/A
% hs, flow
% hs,h
kW97.5126.8146.1
kW65.383.593.3
mg/kWh
%N/AN/AN/A
% hs, flow
% hs,h
<96.0<96.0<96.0
94%94%93%
74%72.8%72.1%
0.000.000.00
<96.0<96.0<96.0
93%93%93%
72.1%73.7%73.7%
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
page no. 37 of 40
Page 38
Notes:
page no. 38 of 40
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
Page 39
Notes:
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
More information is available from our website by scanning the following QR code.
Powrmatic Ireland
45 Broomhill Close
Tallaght
Dublin 24
tel: +353 (0) 1452 1533
fax: +353 (0) 1452 1764
e-mail: info@powrmatic.ie
web: www.powrmatic.ie
Powrmatic pursues a policy of continues improvement in both design and performance of its products and therefore reserves the right to change, amend or
vary specifications without notice. Whilst the details contained herein are believed to be correct they do not form the basis of any contract and interested
parties should contact the Company to confirm whether any material alterations have been made since publication of this brochure.
page no. 40 of 40
ICOM
Energy Association
VPx Range Users, Installation & Servicing Instructions Doc Ref M205 issue 1.2 Nov 2018.
EURO-AIR
QUALITY
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.