Page 10 VPC Range Users, Instrucons & Service Instrucons Issue 5.1 Sept 2014
ensure that its temperature does not exceed 65 °C.
If the method of mounting allows for any movement of the
heater it is essential that all gas, duct, and electrical
connections to the heater are made with flexible connections to maintain continuity of connection.
2.1.3 Gas Connection
To facilitate servicing a servicing valve and downstream
union must be fitted at the inlet to the air heater. The gas
supply to the air heater must be completed in solid pipe
work and be adequately supported. Heaters suspended
by drop rods, straps or chains must have a flexible
connection as the final link between the gas supply pipe
work and the heater. Sufficient slack must be left in the
connection to take account of normal movement of the
heater.
Warning
When completing the final gas connection to the
heater do not place undue strain on the gas pipe
work of the heater.
2.1.4 Air Distribution System General
VPC heaters, if required, can be used with duct work
either to more precisely define the point of air delivery,
and /or provide ducted return air or ducted fresh air inlet.
The system should be checked to ensure that the installation work has been carried out in accordance with the
design requirements. Particular attention should be given
to the correct arrangement of delivery ducts and registers, return air ducts and grills and general adequacy of
return air paths. Ensure that the total duct system resistance does not exceed the available air pressure of the
equipment supplied refer to Table 2 Page 16. If the duct
system resistance is less than the available air pressure
of the equipment supplied additional resistance must be
introduced e.g. by adjustment of duct outlet nozzles and
balancing of the duct system. Conversely if the duct
system resistance is greater than the available air pressure of the heater supplied the system resistance must
be reduced.
2.1.5 Room Thermostat Siting
If a separate room thermostat is used it should be fitted at
a point which will be generally representative of the
heated area as far as temperature is concerned. Draughty areas, areas subjected to direct heat e.g. from the sun,
and areas where the air movement is relatively stagnant
e.g. in recesses, are all positions to be avoided for siting
the thermostat. The thermostat should be mounted about
1.5m from the floor. Any room thermostat, frost thermostat, time clock etc. must be suitable for switching 230V,
5A and must be of the 'snap action' type to minimise
contact bounce. For electrical connections of external
controls see the accompanying wiring diagram.
2.2 Flue/Combustion Air Duct System
All models are supplied as standard with a top flue outlet
and combustion air inlet.
2.2.1.1. Conversion to Side Flue Outlet
(1) Remove the two blanking plates from the flue
/combustion air openings at the side of the unit.
(2) Disconnect the flexible pipe from the exhaust
spigot.
(3) Remove the four screws securing the exhaust
spigot and reposition the spigot to the side of the
heater using the top position. Refit the flexible
pipe.
(4) Remove the four screws securing the combustion
air spigot and reposition spigot to the side of the
heater.
(5) Refit the blanking plates to cover the holes in the
top of the heater.
2.2.1.2 Internal Combustion Air
1. If ducted combustion air is not required (see Section
3.5) fit the mesh inlet plate (supplied loose) behind the
unused combustion air inlet hole.
2.2.2. General Requirements
See Figures 2a to 3b Page 11 for the different types of flue
installation. In all cases the flue outlet socket must be
connected via the provided flue system to outside air. The
maximum permitted length of flue system is 6m, or 12m if
the flue outlet only is used. If an offset is required two sets
of 45° bends may be used each set being equivalent to
0.5m of flue length. The minimum flue length (end of flue
terminal to side or top of heater) shall not be less than
1.3m.
All outer joints must be finished with the provided locking
bands. A smear of silicon grease to the inside of sockets
will assist in fitting components together. All flue and combustion air ducts must be supported independently of the
air heater. The flue or flue/combustion air terminal must
not be installed so as to be less than:
- 300mm below an opening e.g. window, air brick
etc.
- 200mm below eaves or gutter.
- 300mm from an internal or external corner.
- 1200mm from a surface facing the terminal.
- 1500mm vertically from another terminal on the
same wall.
- 300mm horizontally from another terminal on the
same wall.
- 2000mm from ground level.
2.2.3 Installation of Flue System
2.2.3.1 Horizontal System - Side Outlet
1. Locate the position of the flue terminal, allowing
for a slight gradient running down from the heater
to the terminal of 2° - 3° and cut a hole in the
building wall to suit.
2. Fit the flue terminal, securing via the wall plate
and weather with silicon sealant or similar.
3. Fit the twin to concentric adaptor to the terminal
section and extend the flue and combustion air
ducts to the heater using straight lengths. Fit an
adjustable length prior to the unit, to facilitate flue
disconnection for servicing. Extend the
adjustable lengths to make the final connection to
the appropriate heater inlet/outlet spigots.
4. Ensure that internal silicon sealing rings are in
place and that all tubes are pushed fully home.
Secure concentric lengths with the locking bands
provided.
2.2 Flue fitting