1. Checks before lighting the Air Heater
The following preliminary checks should be made before lighting
the heater(s)
a) Ensure that the ELECTRICAL supply to the heater is
switched OFF.
b) Check that all warm air delivery outlets are open.
c) Check that the thermostat is set at MAX.
d) Check that the clock control is set to an ON period.
e) Check that any other controls are calling for heat.
2. Lighting the Air Heater
NOTE:
On initial lighting of the heater(s), it may take some time to
purge the internal pipe work of air. If it is not possible to light
the heater after several attempts contact the local service
company.
1. Switch on the electrical supply at the isolator and the start up
sequence will commence.
Note: Check that the red overheat indicator on the front of the
unit is not alight. If it is refer to Section 4.4
After a short delay the burners will light and the green ‘ON’
indicator on the front of the heater will be illuminated.
2. If the burners fail to light the control box will automatically
restart the ignition sequence. If after 5 attempts at ignition the
burners have still failed to light the control box will go to lockout
and the lockout light on the low level remote reset (or MC200
or Powrtrol RR if fitted) will be illuminated. To restart the
ignition sequence depress the reset button on the low level reset
for about 1-2 seconds.
If the heater will not light after two or three attempts shut down
the heater and contact a service engineer.
3. To Shut Down the Air Heater
3.1 For Short Periods: Turn the room thermostat to the OFF
or lowest setting.
3.2 For Long Periods: Complete step 3.1 above. Wait for 5
minutes and then turn OFF the
electrical supply at the isolator.
4. Description of Operation
Important: All heaters must be controlled by the fitted external
controls and not by use of the main switch in the electrical
supply to the heater.
4.1 Standard Units
The ignition sequence will commence each time that the external
controls e.g. Time clock, room thermostat etc. call for heat. The
internal exhaust fan will run and when sufficient combustion
airflow is proved by the air pressure switch the ignition spark
will be generated, the main gas valves opened and the burners
lit. The green ‘ON’ indicator will be illuminated. The heater fan
will automatically start approximately 2 minutes after the burners
light. When the external controls are satisfied the burners will
be turned off and approximately 2 - 3 minutes later the heater
fan will be automatically stopped.
4.2 High / Lo & Modulating Units
When the burners are alight the heat output will be controlled
either to high fire or low fire or, in the case of modulating units,
to any point between high and low fire; depending on the
requirements of the space being heated and the external controls
fitted.
4.3 Summer / Winter Modes
Certain types of external controls will provide for two modes
of operation i.e.
Summer: The heater fan alone will run at the dictate of the
external controls to provide air movement.
Winter: The heater will operate normally.
4.4 Overheat Thermostat
This operates if high temperatures within the heater are detected,
the burners are turned off and a red indicator light on the front
panel is illuminated. NVx10 - 75 units have the thermostat
located inside the controls section. NVx90 - 140 units have an
additional thermostat on the side of the unit at the opposite end
to the controls (either thermostat can go to limit and shut off
the burners). The fault condition must be identified and rectified
and the thermostat manually reset.
Isolate the electrical supply to the heater and open the controls
section door. Push in the red button on the fan/limit thermostat
(located towards the top of the compartment) to reset. On NVx90
- 140 units also reset the second limit thermostat.
Note: The thermostat can only be reset once the unit has cooled
down.
Unless the cause of the fault condition is readily obvious, for
example a power cut whilst the heater was operating, a service
engineer should be contacted.
5. Maintenance
To maintain efficient, reliable and safe operation of the heater
it must serviced by a qualified person at least annually and
preferably at the end of the heating season.
6. IMPORTANT
Free access must be maintained to and around the heater for
servicing purposes and the air supply to the heater must not be
restricted in any way. Combustible materials must not be stored
adjacent to the heater.
If at any time a gas leak is suspected turn OFF the gas supply
- DO NOT USE A NAKED FLAME - and contact the local gas
undertaking immediately.
All Powrmatic heaters use gas and electricity to power them,
they may also contain moving parts such as pulleys and belts.
It would be hazardous to tamper with or attempt to service unless
you are a competent person in the field of Gas and Electrical
work.
If you have any safety questions reference the servicing and
installation of any of our heaters please do not hesitate to contact
our head office for expert advice. Your safety is paramount to us.
Gas Safety (Installation & Use) (Amendment) Regulations
It is law that all gas appliances are installed, adjusted and, if
necessary, converted by qualified persons* in accordance with
the current issue of the above regulations. Failure to install
appliances correctly can lead to prosecution. It is in your own
interests and that of safety to ensure that the law is complied
with.
* An approved class of person listed on the gas register.
Users Instructions