Powrmatic NCA-G Series, NCA-G 200, NCA-G 300, NCA-G 100, NCA-G 150 Installation And Servicing Instructions

Page 1
The NCA-G Range
CE
Installation and Servicing
Instructions
WARNING: THIS APPLIANCE MUST BE EARTHED
£2.50 When supplied separately.
NCA-G Range Issue 4 Feb 1999
Page 2
CONTENTS
1. Introduction 1
2. Technical Data 2
3. General Requirements 3
4. Installation 4
5. Air Distribution System 5
6. Commissioning & Testing 5
7. Servicing 6
8. Connections to Powrmatic External Controls 7
9. Fault Finding 8
10. Short List of Parts 8
Tables Title Page
1. Dimensions 2
2. Performance Data 2
3.1 Burner Pressures - Natural Gas Group H - G20 2
3.2 Burner Pressures - Propane - G31 2
4. Electrical Loadings 3
Figure Title Page
1. Gas Control Schematic NCA-G 100 - 300 6
2a. Gas Controls Layout NCA-G 100, 150 6 2b. Gas Controls Layout NCA-G 200, 300 6
3. Honeywell L4064N 7
Appendix Title Page
A Calculation Of Flue System Inside
Equivalent Resistance Back Cover
Page 3
1. INTRODUCTION
The Powrmatic NCA -G range of gas fired for ced dr augh t, cl osed flue, fanned circulation air heaters cover a heat output range of 29.3 kW (100000 Btu/h) to 88.0 kW (300000 Btu/h) and are intended primarily for heating commercial or industry premises. They are certified for use on Natural Gas, Group H ­G20 and Propane - G31.
The heaters are for floor mounting and ar e av ailabl e in UF and UD variants. (U - Upright; F - Freeblowing; D - Ducted).
NCA-G heaters have a cen trifugal f an assembly fitted upstr eam of the combustion chamber / heat exchanger assembly to circulate the air being heated. Heaters are fitted as standard with fully automatic monoblock forced draught gas burn ers and m onoblock gas contr ol assemblies.
Options include High/Lo w or modulatin g burner s, Deep V filters , proportional air dampers, combustion air inlet adaptors and inlet and outlet duct spigots.
Each air heater must be conn ected t o a closed flue s ystem only.
Gas Safety (Installation & Use) Regulations 1994
It is law that all gas appliances are installed, adjusted and, if necessary, converted by qualified persons* in accordance with the above regulations. Failure to install appliances correctly can lead to prosecution. It is in your own interests and that of safety to ensure that the law is complied with. * e.g. Corgi Registered
1
Page 4
2. Technical Data
2.1 Dimensions NCA-G 100 - 300 UF & UD Models
NCA-G 200UD SHOWN
H
D
F
C
G
B
FRONT
VIEW
A
SIDE
VIEW
B
FRONT
VIEW
Table 1 - Dimensions
A B C D F G H J K L M
NCA-G 100 1112 603 1645 254 125 1390 502 375 629 NCA-G 150 NCA-G 200 203 NCA-G 300 1390 730 2076 150 1810 629 525 756 47
1340 629 1822 125 1530 527 450 705 50
72
G
Gas connection size All Units R½
A
SIDE
VIEW
K
L
F
C
J
K
M
M
Table 2 - Performance Data
HIGH FIRE LOW FIRE
INPUT OUTPUT
MODEL
NCA-G 100 33.3 29.3 N/A N/A 0.5192 150 N/A 0.335 N/A 152 NCA-G 150 50.0 44.0 N/A N/A 0.7788 290 N/A 0.55 N/A 215 NCA-G 200 66.9 58.6 N/A N/A 1.0383 200 N/A 0.56 N/A 215 NCA-G 300 100.0 88.0 N/A N/A 1.5575 250 N/A 1.5 N/A 304
(Net) (Net)
kw kw m³/s pa kw kg
INPUT OUTPUT
AIR
VOLUME
MAXIMUM DUCT
RESISTANCE
Standard L.H.P. Standard L.H.P.
FAN MOTOR WEIGHT
Table 3.1 - Burner Pressures - Natural Gas - Group H - G20 - NetCV (Hi) = 34.02MJ/m³
Powrmatic Burners Riello Burners
Type Pressure Pressure Type Pressure Pressure
MODEL
NCA-G 100 PCGS 2 N/A 4.8 GS 5 N/A 4.3 3.40 120.0 NCA-G 150 PCGS 2 N/A 9.9 GS 5 N/A 4.2 5.12 180.8 NCA-G 200 PCGS 3 N/A 12.2 GS 10 N/A 3.7 7.08 250.0 NCA-G 300 PCGS 5 N/A 10.4 GS 10 N/A 5.2 10.89 384.5
Start Gas Main Burner Start Gas Main Burner Gas Rate
mbar mbar mbar mbar m³/h ft³/h
Table 3.2 - Burner Pressures - Propane - G31 - NetCV (Hi) = 88.00MJ/m³
Powrmatic Burners Riello Burners
Type Pressure Pressure Type Pressure Pressure
MODEL
NCA-G 100 PCGS 2 N/A 6.9 GS 5 N/A 3.1 1.31 46.3 NCA-G 150 PCGS 2 N/A 11.3 GS 5 N/A 6.4 1.98 69.9 NCA-G 200 PCGS 3 N/A 20.0 GS 10 N/A 4.1 2.74 96.7 NCA-G 300 PCGS 5 N/A 14.2 GS 10 N/A 8.3 4.21 148.7
Start Gas Main Burner Start Gas Main Burner Gas Rate
mbar mbar mbar mbar m³/h ft³/h
2
Page 5
Table 4 Electrical Loadings
Standard Larger Horsepower Motor
NOM. PLATE START RUN FUSE NOM. PLATE START RUN FUSE
MODEL
NCA-G 100 1000 2.6 5.0 2.6 3 NCA-G 150 NCA-G 200 NCA-G 300 7.0 18.0 8.1 10
MOTOR AMPS AMPS AMPS RATING MOTOR AMPS AMPS AMPS RATING
ph R.P.M. (A) (A) (A) (A) R.P.M. (A) (A) (A) (A)
500 5.0 8.5 6.1 7
1
1000
4.1 10.0 4.5 5
N/A
3. General Requirements
3.1 Related Documents
The installation of the air heater(s) must be in accordance with the rules in force and the relevan t requirements of th e Gas Safety Regulations, Building Regulations and the I.E.E. Regulations for Electrical Installations. It should be in accor dance al so with any r ele vant r equirem ents of the local gas region, l ocal auth ority an d fire auth ority an d the relevant recommendations of the following documents.
British Gas Plc Publications
IM/11 : 1989 Flues for Commercial and Industrial Gas Fired Boilers and Air Heaters IM/16 : 1988 Guidance notes for the installation of gas pipework, boosters and compressors in Customer’s premises (excluding domestic installation of 25mm and below).
British Standards Code of Practice
BS 5588 Fire precautions in the design and construction of buildings. Part 2 : 1985 Code of Practice for Shops Part 3 : 1983 Code of Practice for Office Buildings BS 6230: 1991 Installation of Gas Fired Forced Convection Air Heaters for Commercial and Industrial Space Heating.
Those appliances having an input ratin g n ot e xceedin g 60kW viz. NCA-G 100 and NCA-G 150 mu st be install ed in accor dance with the relev ant recomm endations of th e follo wing documen ts. BS 5440 Flues and Air Supply for gas appliances of rated input not exceeding 60kW (1st and 2nd family gases). Part 1 - Flues, Part 2 - Air Supply
For NCA-G100 and NCA-G150 units reference should also be made to BS 5864. Code of Practice for installation of gas­fired ducted-air heaters of rated input not exceeding 60kW.
3.2 Location
The location chosen for the air heater must permit the provision of a satisfactory flue system and an adequate air supply. The location must also provide adequate space for servicing and air circulation around the air heater. The heater(s) must not be installed in conditions for which it is not specifically designed e.g. where the atmospheric is corrosive or salty and where high wind speeds may affect burner operation, and they are not suitable for outd oor use. Where the location of the air heater is such that it might suffer external mechanical damage e .g. fr om ov erh ead cr anes , fork lift trucks, it must be suitably protected. NCA-G units are designed to operate in a maximum ambient temperature of 25°C.
3.3 Gas Supply
3.3.1 Service Pipes
The local gas undertaking should be consulted at the installation planning stage in or der to establish th e availability of an adequate supply of gas. An existing service pipe must not be used without prior consultation with the local gas undertaking.
3.3.2 Meters
A gas meter is connected to the service pipe b y th e l ocal gas undertaking or a local gas un dertakin g contr actor. An existing meter should be check ed, pr efer ably b y th e gas un d ertaking, to ensure that the meter is adequate to deal with the total rate of gas supply required.
3.3.3. Installation Pipes
Installation pipes should be fitted in accordance with IM/16:1988. Pipework from the m eter to the air heater must be of adequate size. Do not use pipes of a smaller size than the inlet gas connection of the heater. The complete installation must be tested for soun dn ess as d escribed in th e above Code. The complete installation must be tested for soundness as described in BS 6230.
3.3.4. Boosted Supplies
Where it is necessary to employ a gas pressure booster the controls must include a low pressure cut off switch at the booster inlet. The local gas undertaking must be consulted before a gas pressure booster is fitted.
3.4 Flue System
Detailed recommendations for fluing are given in BS 5440, Part 1 (Flues) and IM/11.
The air heater must be connected to a closed flue system. The cross sectional area of the flue serving the appliance must be not less than the area of the flue outlet to the air heater. Materials used for the flue system should be mechanically robust, resistant to internal and external corrosion, noncombustible and durable under the conditions to which they are likely to be subjected. Prevention of condensation within the flue should be an important factor in the design of the flue system. In order to minimise condensation the use of double wall ed flue pipe or insulation is recommended. If double walled flue pipe is used it should be of an acceptable type. Where condensation in the flue is unavoidable provision should be made for condensation to flo w fr eely t o a point at which it can be released, preferably into a gully. The condensation pipe from th e flue t o th e disposal poin t sh oul d be of non-corrodible material o f not l ess than 22mm diameter . Facilities should be made for disconnecting the flue pipe(s) from the air heater(s) for inspection and servicing purposes. Bends with removable covers shoul d be fitted for inspection and cleaning purposes where considered appropriate. The flue should terminate in a freely exposed position and must be so situated as to pre v ent th e pr oduct s o f combustion entering any opening in a building in such concentration as to be prejudicial to health or a nuisance. It is recommended that consideration be given to th e fittin g of a terminal at the flue outlet, however, where the heater flue is less than 200mm in diameter an approved terminal must be fitted.
3.5 Air Supply
In buildings having a design air change rate of less than
0.5/h, and where NCA-G h eater s ar e to be in stall ed in h eated spaces having a volume less than 4.7 m3 /kW of total rated heat input grilles shall be provide at low level as follows:-
3
Page 6
(1) for heaters of heat input less than 60 kW, the total
minimum free area shall not be less than 4.5 cm2 per kilowatt of rated heat input.
(2) for heaters of h eat input 60 kW or more, the total minimum
free area shall not be less than 270cm2 plus 2.25 cm
per kilowatt in excess of 60 kW rated heat input. The air vent(s) should have negligible resistance and must not be sited in any position where it is likely to be easily blocked or flooded or in an y position a djacent t o an extr action system which is carrying flammable vapour.
Where the air heater(s) is t o be in stall ed in a plant room the air heater(s) requires the plant room housing it to have permanent air vent s comm unicating dir ectly with the out sid e air, at high l e vel an d at lo w l ev el. Wher e comm unication with the outside air is possible only by means of high level air vents, ducting down to floor l e v el f or the lower vent s sh oul d be used. Air vents should have negligible resistance an d must not be sited in any position where th ey ar e likely to be easily bl ocked or flooded or in any position a djacen t to an e xtra ction sy stem which is carrying flammable vapour. Grilles or louvres should be so designed that high velocity air streams do not occur within the plant room.
2
clear of sources of smells and fumes, and in special circumstances where there is any possibility of pollution of the air by dust, shavings etc., precautions mu st be taken by carefully positioning return air intakes and by the provision of screens to prevent contamination. In addition, where there is a risk of combustible material being placed close to the warm air outlets, suitable barrier rails should be pr ovided to preven t any combustible material being within 900mm of the outlets.
3.7 Electrical Supply
Wiring external to the air h eater must be in stalled in accordan ce with the I.E.E. Regulations for Electrical Installations and any local regulation s which apply . Wirin g shoul d be completed in flexible conduit. Heaters NCA-G 100 - 300 are supplied by 230V - 1ph, 50Hz. The method of connection to the main electricity supply must facilitate the complete electrical isolation of the air heater(s) and the supply shoul d serv e only th e air h eater(s). The isolator must have a contact separation of at least 3mm in all poles. The method of connection should be provided adjacent to the air heater(s) in a readily accessible position. See the accompanyin g wiring dia gram f or the h eater electrical connections.
The basic minimum effective area requirements of the air vents are as follows:
(a) Low Level (inlet)
(1) for heaters of total rated heat input less than 60
kW: 9 cm2 per kilowatt of rated heat input;
(2) for heaters of total rated heat input 60 kW or mor e:
540 cm2 plus 4.5 cm2 per kilowatt in excess of 60 kW total rated input.
(b) High Level (outlet)
(1) for heaters of total rated heat input less than 60
kW: 4.5 cm2 per kilowatt of rated heat input;
(2) for heaters of total rated heat input 60 kW or mor e:
270 cm2 plus 2.25 cm2 per kilowatt in excess of 60kW total rated input.
3.6 Air Distribution System
The following notes are of particular importance. For free-blowing units it must be taken into account that the buoyancy of the heated air leaving the heater and air patterns within the space being heated will modify the air throw pattern achieved. In buildings having a low heat loss where single units are required to cover a large floor area and in buildings with high roof or ceiling heights Calecon thermal economiser units should be fitted to ensure even heat distribution and minimise stratification respectively. Care should be taken to avoid impeding the air throw with racking, partitions, plant or machinery etc.
For ducted units all delivery and return air ducts, including air filters, jointing and any insulation or lining must be constructed entirely of materials which will not contribute to a fire, are of adequate strength and dimensionally stable for the maximum internal an d external temper atures t o which they are to be exposed during commissioning and normal operation. In the selection of materials account must be taken of the working environment and the air temper atures which will result when the ov erh eat limit therm ostat is being commissioned. Where inter-joist spaces are used as duct routes they should be suitably lined with a fire-resisting material. A full and unobstructed return air path to the air heater(s) must be provided. If the air heater(s) is installed in a plan t room the return air intake(s) and the w arm air outl et(s) fr om th e h eater(s) m u st be fully ducted, in to and out of the plant room to avoid interference with the oper ation of the flue b y the air circulation fan. The openings in the structure of the plant room through which the ducting passes must be fire stopped. Care must be taken t o en sur e that return-air in tak es are k ept
4. Installation of Air Heater(s)
4.1 General
Before installation, check that the local distribution conditions, nature of gas and pressure, and adjustment of the appliance are compatible.
The air heater must be in stall ed in a ccor dan ce with th e rul es in force and the r el e van t r equir emen t s of any fire regulations or insurance company’s requirements appertaining to the area in which the heater is located, particularly wh er e special risks are involved such as areas where petrol vehicles are housed, where cellulose spraying is carried out, in wood working departments etc. The followin g minimum clear ances for installation an d servicing must be observed. To the front The depth of the heater To the rear 1.0m To at least one side 1.0m Above the heater 1.00m
Any combustible material adjacent to the air heater and the flue system must be so placed or shielded as to ensure that its temperature does not exceed 65°C.
IMPORTANT:
1. No air heater shall be installed where there is a f oreseeable risk of flammable particles, gases vapours or corrosion inducing gases or vapours being drawn into either the heated air stream or the air for combustion. In such cases installation may only proceed if the air to be heated and the air for combustion are ducted to the heater from an uncontaminated sour ce preferably out side the building. In certain situations where only airborne particles are present it may suffice to fit filters on the air inlet ducts of the heater. Advice in these instances may be obtained from Powrmatic Ltd.
4.2 Fitting the Air Heater
The heaters must be installed on a level noncombustible surface. If noise level s ar e o f particular importan ce th e h eater sh oul d be insulated from the structure of the building by in stalling it on suitable anti-vibration mountings. In all such cases it is essential that all gas, duct, electrical an d flue conn ection s to the heater are ma d e with fl e xibl e connection s t o main tain continuity of connection. In the case of the flue connection single wall stainless steel flue is deemed to flex sufficiently to meet the requirements.
4
Page 7
4.3 Connection of Air Heater(s) to Flue System
A single wall Tee piece is supplied with each heater and must be fitted to the flue outlet socket on the heater. The flue system then connects directly on to the tee. For flue sizes refer to Table 1, Page 2. Horizontal runs of flue are not permitted. If necessary a single offset using two 45° bends can be included to av oid obstructions . The maximum equival ent resistance of the flue system must not exceed 20pa. Details of how to calculate the resistance of the flue t o be installed are given in Appendix A.
4.4 Condensate Drainage
The design of the flue s y stem sh oul d minimise the f ormation of condensation, however when this is envisaged to be a problem provision should be made for condensation to flow to a joint where it can be drained, preferably into a gully.
4.5 Gas Connection
A servicing valve and downstream union must be fitted at the inlet to the air heater gas controls assembly to fa cilitate servicing. The gas supply to the air h eater m ust be compl eted in solid pipework and be adequately supported. Warning: When completing the final gas connection to the heater do not place undue strain on the gas pipework of th e heater.
4.6 Electrical Connections
All units are fully pre-wired an d only requir e final connections for the incoming main s supply an d compl etion of th e con tr ol circuit (230V) via a room thermostat, time clock etc. The electrical supply must be run to a point adjacent to the heater and be suitably terminated to provide an isolation point that will prevent remote activation of th e unit during servicing. The heater electrical panel is located behind the front panel and cabl e entry poin ts are pr ovided in th e adja cent heater framework. Reference must be ma de to Table 4 (Page
3) to ascertain the electrical loading of the air heater(s) being installed so that cables of adequate cross-sectional area to safely carry that load are used for the electrical installation. The length of the conductors betw een the cord anchorage and the terminals must be such that the current carrying conductors become taut before the earth condu ct or if the cable or cord slips out of the cord anchorage. All external controls must be of an approved type.
See the wiring diagram accompanying these instructions.
5. Air Distribution System
5.1 General
NCA-G ###UD models are designed for use with duct w ork t o more precisely defin e the poin t of air d elivery, and /or provide ducted return air or ducted fresh air inlet. All ducting must be independently supported of the air heater. Joints and seams of supply ducts an d fittin g s m u st be secur ely f asten ed and made airtight.
5.2 Noise Reduction
If deemed necessary consid eration shoul d be given to m ounting the heater on resilient pads, or equivalent, to minimise transfer of noise an d vibration t o the structur e of the buil ding. It is recommended that ducting should be connected t o the heater spigots via an airtight flexible coupling of noncombustible material. Before fitting coupling it must be ensured that a maximum clear ance of 13mm will be main tained between the ends of the ducting and the heater spigots. If required sound attenuators may be fitted in inlet and outlet ducts to reduce airborne fan noise. Materials used in outlet sound attenuators must be capable of withstanding 100°C air temperature without any deterioration.
temperature is concerned. Draughty areas, areas subjected to direct heat e.g. from the sun, and areas where the air movement is relatively stagnant e.g. in recesses, are all positions to be avoided for siting the thermostat. The thermostat should be mounted about 1.5m from the floor. Any room therm ostat, fr ost th ermostat, time clock etc. mu st be suitable for switching 230V, 5A and must be of the 'snap action' type to minimise contact bounce.
For electrical connections of external controls see the accompanying wiring diagram.
6. Commissioning & Testing
6.1 Electrical Installation
Checks to ensure electrical safety must be carried out by a competent person.
6.2 Gas Installation
The whole of th e gas in stallation, inclu ding th e meter, should be inspected and tested for soundn ess and purg ed in accordance with the recommendations of IM/16:1988.
6.3 Air Distribution System
The system shoul d be ch eck ed to en sur e that th e installation work has been carried out in accordance with the design requirements. Particular attention shoul d be given to th e correct arran gemen t of delivery ducts and registers, return air ducts and grills and general adequacy of return air paths. For NCA-G ###UD heaters ensure that the total duct system resistance does not exceed the available air pressure of the equipment supplied refer to Table 2, (Page 2). If the duct system resistance is less than the available air pressure of the equipment supplied additional resistance must be introduced e.g. by adjustment of duct outlet nozzles and balancing of the duct system.
6.4 Lighting the Air Heater
6.4.1 Gas Controls Assembly - Soundness Check
1. Ensure the gas service valve at the inl et to th e gas control s assembly is shut.
2. To prove soun dn ess of th e fir st main safety sh ut-off v alv e and first start gas safety shut-off valve:­a) Connect pressure gauge to the inlet pressure test
point on the main valve block or inlet pipework.
b) Open gas service valv e and allow pressure to stabilise
before shutting it again. The valves are sound if no pressure drop is observerved. If a pressure drop is observed do not proceed until the fault has been rectified. Remove pressure gauge and refit sealing screw in pressure test point.
6.4.2 Sequence Check
1. Ensure that the gas service valve is closed and that the main electrical supply to the heater is switched off.
2. Check that all external controls are eith er "ON" or at "MAX"
3. Turn "ON" the main electrical supply and check that the following sequence of events occurs. i) Burner fan runs ii) Ignition spark is heard iii) Main gas valves open. iv) Burner goes to lockout as there is no gas supply.
4. Switch off main electricity supply.
6.4.3 Final Adjustment
IMPORT ANT: Th e maxium flo w and start gas flo w adju stmen ts provided on the GM main gas block valve assembly (Fig 2b - 4) are not used and must not be adjusted.
5.3 Room Thermostat Siting
The room thermostat should be fitted at a point which will be generally representative of the heated area as far as
1. Remove the sealing screw from the pressure test point located on the side of the gas inlet to the burner head and attach a pressure gauge. Remove the sample point
5
Page 8
Fig 1 Gas Controls Schematics
1st Main Gas
Safety Shut-off
Valve
Gas
Inlet
Fig 2a Gas Controls Layout NCA-G 100, 150
1) 1st Main gas safety shut off valve.
2) 2nd Main gas safety shut off valve.
3) Main burner pressure adjustment screw. Notes:-
i) Electrical connection plugs not shown.
Fig 2b Gas Controls Layout NCA-G 200, 300
1) Main gas safety shut-off valves.
3
2) Main burner pressure adjustment screw.
3) Inlet Pressure test point.
4) Flow rate and valve opening speed adjustments.
Gas
Inlet
2nd Main Gas
Safety Shut-off
Main Gas Governor
Inlet
1
Gas
Valve
Pressure
Test
Point
To Burner
1 2
To
Burner
3
2
4
To
T
E
P
S
O
.
I
N
G
E
T
R
T
R
A
T
S
X
V
A
M
V
3
Burner
cover plug from the outlet flue length and insert a CO measuring instrument.
2. Turn "ON" the main electricity supply and check that the following sequence of events occur. i) Burner fan runs. ii) Ignition spark is heard iii) Main gas valves open iv) Main gas flame is established.
3. Check that the main burner gas pressure agr ees with that in Tables 3.1 or 3.2. If necessary adjust the main burner gas pressure (Fig 2a - 3 or Fig 2b - 2).
4. Measure the CO2 content of the flue gases. If necessary adjust the combustion air damper of the burner (Refer to the Burner Supplement) to obtain a r ea din g o f 9.0 - 9.5%.
5. Turn "OFF" the main electricity supply, remove pressure gauge and refit sealing screw in pressure test point and flue sample point cover plug.
6.5 Final Soundness Test
1. After making final gas rate checks all joints on the gas controls assenbly mu st be tested f or soundn ess u sing l eak detection fluid.
6.6 Flame Safeguard
1. Whilst the burner is in operation close the gas service valve. The burner should go to lockout within 1 second.
2
6.7 Handing over the Air Heater
Hand the Users Instructions to the user or purchaser for retention and instruct in the efficient and safe operation of the air heater and associated controls. Adjust the automatic controls to those values required by the User. Finally, advise the user or purchaser that, for continued efficient and safe operation of the air heater, it is important that servicing is carried out annually. In the event that the premises are not yet occupied turn off the gas and electricity supplies and leave instructional literature adjacent to gas meter.
7. Servicing
WARNING: Always switch off and disconnect electricity supply and close the gas service valve before carrying out any servicing work or replacement of failed components.
7.1 General
Full maintenance should be undertaken not less than once per year. After any servicing work has been complete or any component replaced the air heater(s) must be fully commissioned and tested for soundness as described in Section 6.
6
Page 9
7.2 Burner Maintenance
1. Refer to the Burner Supplemen t supplied with th e heater. Note: Any referen ces th erein t o th e gas con trol s assembly should be ignored.
7.3 Heat Exchanger Cleaning
1. Disconnect the gas supply at the inlet to the gas con tr ol s assembly.
2. Disconnect the electrical connections from the heater electrical panel to the buner at the burner.
3. Remove the nut s securing the burn er to the h eat exchan ger and remove the burner.
4. Remove the fan/limit thermostat as described in 7.5.4 and then remove the inner panel of th e h eater t o expose the heat exchanger clean out panel. Remove the nuts securing the panel and remove the panel.
5. Remove the nuts securing the heat exchanger baffles retention strip and remove strip.Withdraw the baffles.
6. Brush through heat exchanger tubes and remove loose material using a vacuum cl eaner . R emove an y loose material from the base of the combu stion chamber , workin g through the burner port.
7. Reassemble all components in reverse order. Inspect all gaskets and replace if necessary.
7.4 Fan Assembly
1. Remove the upper and lower side panels on one side of the heater to gain access to the fan.
2. Inspect the fan blades to see that they are not damaged and that there is no excessive build up of deposits that could give rise to an imbalance. If necessary clean the fan blades using a stiff brush and vacuum cleaner. If it is required to rem o v e th e fan f or cl eanin g r efer t o section
7.4.3
7.5 Replacement of Faulty Components
the heater.
3. Remove the two set screws, one on each side of the fan mounting flange, the secure the fan to the fan shroud.
4. Withdraw the fan from the slide rails.
5. Reassemble in reverse order.
7.5.4 Fan and Limit Thermostat (Honeywell L4064N )
1. Release the single screw securing the fan and limit thermostat cover and remove cover by pulling forward.
2. Release wiring from clamp terminals by pushing a small screwdriver into the clamp release holes adjacent to the clamps.
3. Remove the 2 scre ws securin g the therm ostat to th e heater panel and withdraw thermostat.
4. Reassemble new unit in reverse order refering to the heater wiring diagram to ensure correct wiring location.
Fig 3 Honeywell L4064N
Set Point Dial
Fan Circuit
Summer / Winter Switch
0
2
T
CAUTION
DO NOT ROTATE - HOLD
2
0
DIAL WHEN SETTING POINTERS
4
1
I
M
I
0
L
0
F
N
A
1
0
8
0
6
0
Limit Circuit
Limit Reset
7.5.1. Burner Components
1. Refer to the burner supplemen t supplied with th e h eater.
7.5.2 Gas Controls Assembly
7.5.2.1 NCA-G 100, 150
7.5.2.1.1 Gas Valve Coil.
1. To fit a new valve operating coil remove the electrical supply plug, release the securing nut on top of the valve stemand remove the nut and washer. Lift of the faulty coil and fit the new coil in reverse order.
7.5.2.1.2 Block Valve Assemby.
1. Remove the electrical supply plug,
2. Release the unions on the connection s at ea ch end o f th e assemby and remo ve compl ete assembly. Fit new assembly in reverse order ensuring the valv e assembly is correctly orientated for the direction of gas flow.
7.5.2.2 NCA-G 200, 300
7.5.2.2.1 Block Valve Assembly.
1. Release the union on the gas service valve
2. Remove the electrical conn ection from th e valv e assembly.
3. Release the socket head cap scr ews securin g the connection flanges to the main gas bl ock v alve an d rem o ve th e block. Fit new assembly in reverse order ensuring correct orientated for the direction of gas flow.
7.5.3 Main Air Fan and Motor
Note: On heaters supplied as specials with 3ph m ot ors en sure that the fan direction of rotation corresponds with the direction of rotation arrow on the fan guard or case. If necessary reverse the direction of rotation by in terchanging any two of the motor live leads at the terminal strip in the electrical panel.
1. Disconnect the fan motor electrical l ea ds fr om th e h eater terminal strip (Refer to the Wiring Diagram supplied)
2. Remove the upper and lower side panels on one side of
Limit CircuitFan Circuit
Jumper Location
Important: As supplied by the Manufacturer this fan/limit thermostat is fitted with a brass jumper between th e bott om fan terminal and the bottom limit terminal (situated in the slot between the two terminals). This MUST be removed, by using a pair of thin nose pliers, before the replacement thermostat is installed.
5. Ensure that the fan and limit settings are as follows:­Fan ON 50°C Fan OFF 30°C Limit 110°C
8. Connections to Powrmatic External Contr ols
8.1 Powrtrol
NCA-G
Terminals Terminals
connect to
1 1 2 2 8 5 9 6
Powrtrol
8.2 Eurotrol
NCA-G
Terminals Terminals
connect to
1 CTRL CCT 2 CTRL CCT 8 FAN CCT 9 FAN CCT
Eurotrol
7
Page 10
9. Fault Finding
Refer also to the burner supplement supplied with the heater
Fault Cause Action
Main burner will not light Electrical 1. Check electrical and gas supplies are ON.
2. Check controls are ON or calling for heat.
Main burner lights, but goes Electrical 1. Unit goes out on high limit ­out before main fan comes on. a. Check fan thermostat setting - See Section
7.6.5.
b. Faulty fan thermostat - change c. Check limit thermostat setting - See Section
7.6.5. d. Faulty limit thermostat - change.
2. Faulty fan assembly - change.
3. (Ducted Units Only) -fan motor out on thermal overload. - Check running amps. See table 4.­check duct resistance See Table 5.
Main fan runs continuously Electrical 1. Summer/Winter switch set to Summer.
2. Fan thermostat set too low - check setting. See
Section 7.6.5
3. Faulty fan thermostat - change
Main fan fails to run Electrical 1. Fan motor or capacitor failed - replace.
2. Fan thermostat faulty - replace.
3. Fan contactor failed - replace (3ph units)
10. Short List of Parts
Refer also to the burner supplement supplied with the heater. Refer to Powrmatic Ltd for the details of any parts not listed here.
ITEM APPLICATION PART NUMBER
Johnson Controls GM-7742-3503 - ½"BSP. 100, 150 141379957 Johnson Controls GM-2540-2000 - ¾"BSP 200, 300 141379954 Thermostat - Fan / Limit Honeywell L4064N. ALL 143000303 Heat Exchanger Cleanout Door Gasket. ALL 170246006 Pressure Relief Door Gasket - 114mm dia. ALL 142202110 Pressure Relief Door Gasket - 95mm dia. ALL 142202257 Pressure Relief Door Gasket - 166mm x 166mm. ALL 142202310 Burner Gasket - Nu-Way PCGS 2/3/5. ALL 144704004 Burner Gasket - Riello GS5. 100 141937080 Burner Gasket - Riello GS510 150 - 300 141930806
8
Page 11
Appendix A Calculation Of Flue System Equivalent Resistance
The pressure resistance of the flue system (Pr) can be calculated from Pr = 1.5 * [(PFF*H/D+SRF)Q
m/Wm
2]
Where Pr = Pressure resistance of the flue system in pa
PRF = Pipe Friction Factor H = Effective flue height in m D = Internal Diameter of flue in m SRF = Sum of individual resistance factors Q
= Mean Density of the column of exhaust gas in kg/m
m
W
= Mean exhaust gas velocity in m/s
m
PRF
3
Can be calculated from PRF = 0.118*(0.21147/D
0.4
)
Where D = Internal Diameter of flue in m
SRF
Typical resistance factors for individual components are as follows Segmented 90° bend 0.5
45° Elbow 0.4 Cowl 1.0
Q
m
Q
= 97000/(300*Tm)
m
Where The mean temperature of the column of exhaust gas (T
T
= 288+((Te-TL)/0.2)*(0.18)
m
Where Te is the exhaust gas temperature in °C
T
W
m
L is the external air temperature in °C
Wm = M/(A*Qm)
Where A is the cross sectional area of the flue in m
2
M is the exhaust gas mass flow in kg/s which is as follows for the various units
m) can be calculated from
Page 12
BSI Registered Firm
FM 414
Ind. & Comm. Air Heaters;
Air Moving Equipment;
Flues & Chimneys; Natural
Smoke & Heat Ventilators; Powered Supply & Extract
Fans & Systems.
HEATING DIVISION
Winterhay Lane
Ilminster, Somerset TA19 9PQ
Tel: 01460 53535 Fax: 01460 52341
Every effort is made to ensure accuracy at time of going to press. However as part of our policy of continual product improvement, we reserve the right to alter specifications without prior notice.
Loading...