Model 15 20 25 35 40 45 50 60 70 90 120 140
Output (nominal)
High Fire (max)
kW 14.5 19.0 24.0 34.0 37.5 44.0 50.5 60.0 70.5 90.0 118.5 137.0
Low Fire (min)
kW 8.6 12.7 16.3 23.8 25.5 29.8 33.9 40.8 47.8 65.3 83.5 93.3
Input (nett CV)
High Fire (max)
kW 15.5 20.5 26.0 36.5 40.5 47.0 54.5 65.0 76.5 97.5 127.0 146.0
Low Fire (min) kW 9.53 14.07 18.16 26.08 28.17 32.46 37.41 45.07 52.91 71.65 90.83 101.16
Airflow
Volume
LNVx F/CCF/V m
3
/s 0.42 0.56 0.78 1.11 1.18 1.51 1.51 1.83 1.94 2.81 3.56 3.75
LNVx D
Min m
3
/s 0.42 0.56 0.78 1.11 1.18 1.51 1.51 1.83 1.94 2.81 3.56 3.75
Max m
3
/s 0.46 0.62 0.86 1.22 1.30 1.67 1.67 2.02 2.14 3.09 3.91 4.13
Airflow
Throw LNVx F m 10.0 14.0 20.0 28.0 30.0 35.0 35.0 38.0
42.0 44.0 45.0 45.0
Fan
Static
LNVx CCF Pa 220 320 220 N/A 150 250 250 250 250 180 290 250
Electrics
Supply
Standard V/ph/Hz 230/1/50
Optional* V/ph/Hz 400/3/50 *on Centrifugal Units Only. 3Ph units shown in brackets ()
LNVx F Run amp 0.40 0.45 0.52 1.14 0.85 1.53 1.57 2.30 2.20 3.06 4.35 4.45
LNVx
CCF
Start amp 5.0 8.5 13.3 N/A 18.0 26.3 26.3 29(16.5) 38(18) 31.0 40(14.9) 44(16.8)
Run amp 2.0 3.1 4.2 N/A 5.8 7.6 7.6 10(4.8) 11(5.3) 12.8 17(4.6) 20(4.9)
Fuel
Connection BSP/Rc ¾"
Nominal Inlet
Pressure
Nat Gas mbar 20.0
LPG mbar 37.0
Consumption
Nat Gas m
3
/h 1.64 2.17 2.75 3.86 4.29 4.97 5.77 6.88 8.10 10.32 13.44 15.45
LPG m
3
/h 0.63 0.83 1.06 1.52 1.66 1.90 2.20 2.65 3.16 4.01 5.10 5.90
Mounting
Height
LNVx F/Duo
Crossflow
Min m 2.5 3.0
Max m 3.0 5.0
LNVx V
Downflow
Min m
4.0 5.0 6.0
Max m 6.0 7.0 8.0 10.0 12.0
Overall
Dims
LNVx F
Height mm 430 500 570 532 720 684 684 760 912 810 975 1140
Width mm 997 997 997 1325 997 1325 1325 1325 1325 1950 1950 1950
Depth mm 800 869 819 918 839 938 938 915 915 938 915 915
Install
Clearance
LNVx F
Top mm 200
LH Side mm 200
RH Side mm 1000
Rear mm 400
Flue
Diameter mm Ø 80 80 80 100 100 100 100 130 130 130 130 130
Max
Length
Flue Only m 12
Room Sealed m 6
Combustion Air Spigot mm Ø 80 80 80 100 100 100 100 130 130 130 130 130
Noise Levels
LNVx F dB(A) 48 47 47 50 58 59 59 60 60 63 64 64
LNVx CCF dB(A) 55 55 54 N/A 60 60 61 62 62 66
67 67
Nett Weight
LNVx F kg 59.5 73.0 76.5 84.0 103 122 122 135 149 202 238 286
LNVx CCF kg 71.0 83.6 86.4 N /A 122 143 143 170 213 329 364 430
Model 15 20 25 35 40 45 50 60 70 90 120 140
Notes:
Fuel Consumption and input figures ba sed upon nett calorific values as
follows: Natural Gas (G20) nett CV 34.02 MJ/m
3
- Propane (G31) nett CV 88.00
MJ/m
3
• Heaters have efficiency levels which meet with the minimum
heater efficiency requirements of UK Part L Building Regulations.
• LNVx heaters comply with the seasonal efficiency and NOx
limits requirements of the Ecodesign regulation (EU) 2015/1188,
Directive 2009/125/EC – Lot 21 Tier 1
• Standard heaters configured as High/Low. Optional modulation
available.
• Air handling data is assessed at room ambient conditions
• Throw figures provide the distance to the point where the terminal
velocity degrades to 0.25m/s
• Dimensions, weights and clearance data in the table above refer
to LNVx F units only - for data on all other models refer to the
dimensions page and/or the installation instructions.
• Noise levels are applicable to standard LNVx F and LNVx V models
and are measured 5m from appliance in a free field.
• Motor kW, run and start amps apply to standard electrical supply as
stated. For optional data contact sales office.
• Optional 3 phase direct drive centrifugal blowers shown in italics
within brackets().
• Connection of combustion air duct is not required for ‘flue only’
applications.
• It is the responsibility of the installing contractor to ensure that
ductwork is correctly sized and balanced when installing LNVx
Centrifugal units.
Technical Specification
LNVx