Powrmatic HEMNVx 25-5, HEMNVx 10-3, HEMNVx 15-4, HEMNVx 30-6, HEMNVx 40-8 User, Installation And Service Manual

...
www.powmatic.co.uk
+44 (0) 1460 53535
info@powrmatic.co.uk
Doc Ref: M103 Issue 3.1 Feb 2018
Industrial & Commercial Heating Systems
HEMNVx & SL Heat Exchanger Modules
page no. 2 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
Installer Date:________________Signed: _____________________________________Installer
Commissioned Date:________________Signed:_______________________Commissioning Engineer
Important: This certicate
must be kept with the appliance
Failure to provide a copy of the commissioning sheet invalidates the heater warranty
----------------------------------------------------
Powrmatic Ltd, Hort Bridge, Ilminster, Somerset, TA19 9PS Tel: 01460 53535 Fax: 01460 52341 Web: www.powrmatic.co.uk e-mail: warranty@powrmatic.co.uk
Certificate of Guarantee
Dear Customer
This is to certify that this heater is guaranteed for two years parts and one year labour from the date of original commissioning. The heater must be commissioned within 4 weeks of installation.
To make a claim
In the rst instance you must contact your appliance supplier, or installer and provide:-
1. The appliance type and serial number.
2. The original commissioning documentation. As much detail as possible on the fault.
3. Your supplier, or installer, will then contact Powrmatic to make a guarantee claim on your behalf.
Conditions of Guarantee
1. The heater must have been installed by a competent recognised installer, and in accordance with the manufacturer’s instructions, building regulations and local regulations.
2. The heater has been professionally commissioned, within 4 weeks of installation, and a copy of the commissioning sheet returned to Powrmatic.
3. The heater has been maintained on a yearly basis by a competent servicing company.
4. The heater has been used in accordance with the manufacturer’s instructions.
5. The correct specication fuel has been used.
6. No unauthorised repairs of modications have been made. Powrmatic ‘General Conditions of Sales’ have been observed.
7. Except for the obligation of Powrmatic Ltd to perform warranty repairs during the guarantee period Powrmatic will not be liable in respect of any claim for direct or indirect consequential losses, including loss of prots or increased cost arising from loss of use of the heater, or any event arising there from.
Exclusions
Consumables such as gaskets, ignition electrodes, ame rectication electrodes, fusible links, control batteries etc. are all excluded from guarantee.
page no. 3 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
Dear Customer - thank you for choosing Powrmatic.
We appreciate you buying one of our high quality products and know that you have made the best choice. By choosing Powrmatic, you are investing in UK manufacturing & its workforce. We pride ourselves by manufacturing products that provide clean, comfortable and safe working environments worldwide together with the personal & professional service and back-up you deserve. If you have any questions or concerns regarding this product, please contact our Technical Support Team by calling 01460 53535.
Title Section Contents Page
User Instructions 4
Pre Installation
1.1 Introduction 5 Duties 6 Dimensions 7
1.2 Technical data 10
1.3 General Requirements 14
Installation
2.1 Fitting the unit 17
2.2 General Identication of Items 21
2.3 Electrical Cable Installation 22
2.4 Wiring Terminal Connections 22
2.5 Wiring Diagrams 24
2.6 Commissioning and Testing 30
2.7 Servicing 34
Additional Documents
3.1 Fault Finding Flow Chart 36
3.2 List of Parts 37
Appendices
1. Information required for ecodesign (ErP) Directive 2009/125 HEM NVx 40
2. Information required for ecodesign (ErP) Directive 2009/125 HEM SL 41
3. Flueing and Ventilation requirements for 'stand alone' units 42
Users, Installation and Servicing Instructions
CONTENTS
page no. 4 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
D) Description of Operation
Important: The heater must NOT be controlled by switching ON and OFF the main electrical supply to it.
1) Standard Units
The ignition sequence commences each time the external controls e.g. Time clock, room thermostat etc. call for heat. The internal exhaust fan will run and, when sucient combustion airow is proved by the air pressure switch, the ignition spark will be generated, the main gas valve opens and the burners light. The green ‘ON’ indicator will be illuminated. The heater fan will automatically start approximately 2 minutes after the burners light. When the external controls are satised the burners will be turned o and approximately 2 - 3 minutes later the heater fan will be automatically stopped. If the burners fail to light the control box will make another four attempts at ignition.
2) High / Low & Modulating Units
When the burners are alight, the heat output will be controlled either to high re or low re or, in the case of modulating units, to any point between high and low re; depending on the requirements of the space being heated and the external controls tted.
3) Overheat Thermostat
This operates if high temperatures within the heater are detected, the burners are turned o and a Red indicator switch light on the front panel is illuminated. The fault condition must be identied and rectied.
When the unit has cooled, push the Red indicator switch inside the front panel to reset the limit thermostat interlock relay, the red indicator light will go out and the unit is operational again.
Note: The limit thermostat(s) can only be reset once the unit has cooled down. Unless the cause of the fault condition is
readily obvious, for example a power cut whilst the heater was operating, a service engineer should be contacted.
E) Maintenance
To maintain ecient, reliable and safe operation of the heater it must serviced by a qualied person at least annually and preferably at the end of the heating season.
If the heater has not been left operational proceed as follows.
A) Checks before lighting the Air Heater
The following preliminary checks should be made before lighting the heater(s)
a) Ensure that the ELECTRICAL supply to the heater is switched OFF. b) Check that all warm air delivery outlets are open. c) Check that the thermostat is set at MAX. d) Check that the clock control is set to an ON period. e) Check that any other controls are calling for heat.
B) Lighting the Air Heater
1. Switch on the electrical supply at the isolator
2. If the Limit indicator light comes on press the limit interlock reset switch inside the heater.
3. The startup sequence will commence. After a short delay the burners will light and the green ‘ON’ indicator on the front of the heater will be illuminated.
4. If the burners fail to light the control box will automatically restart the ignition sequence. If after 5 attempts at ignition the burners have still failed to light the control box will go to lockout and the Amber lockout light on the front of the heater (or on the low level remote reset, MC200 or Powrtrol RR if tted) will be illuminated. To restart the ignition sequence depress the reset button on the low level reset for about 1-2 seconds.
WARNING: If it is not possible to light the heater after several attempts, contact the installer or local service company.
C) To Shut Down the Air Heater
1) For Short Periods:
Turn the room thermostat to the OFF, or set to it’s lowest setting.
2) For Long Periods:
Complete step 1 above. Wait for 5 minutes and then turn OFF the electrical supply at the isolator.
User Instructions
page no. 5 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
F) IMPORTANT
Free access must be maintained to and around the heater for servicing purposes and the air supply to the heater must not be restricted in any way. Combustible materials must not be stored adjacent to the heater.
If at any time a gas leak is suspected, turn OFF the gas supply at the meter and contact the local gas undertaking immediately.
All Powrmatic heaters use gas and electricity to power them, they may also contain moving parts such as pulleys and belts. It would be hazardous to tamper with or attempt to service unless you are a competent person in the eld of Gas and Electrical work.
If you have any safety questions reference the servicing and installation of any of our heaters please do not hesitate to contact our head oce for expert advice. Your safety is paramount to us.
Gas Safety (Installation & Use) (Amendment) Regulations
It is law that all gas appliances are installed, adjusted and, if necessary, converted by qualied persons* in
accordance with the current issue of the above regulations. Failure to install appliances correctly can lead to prosecution. It is in your own interests and that of safety to ensure that the law is complied with.
* An approved class of person listed on the gas safe register.
The HEM Range are gas-red insertion heaters covering a range of heat outputs from 10.0kW to 200.0kW. They are certied for use on Natural Gas, Group H - G20, and Propane - G31 only. Appliance Categories are Cat II2H3P (GB, IE).
HEM heaters are based on aluminised mild steel tube heat exchanger elements with each tube having dedicated inshot burners, a closed combustion circuit and have an internal exhaust fan, mounted downstream of the heat exchanger, to evacuate the products of combustion and draw in air for combustion, a fully automatic control for ignition, ame sensing, gas supply control and safety functions.
Standard units are for internal use and are supplied without a burner/controls housing for insertion into air handling units or duct sections. Each unit is tted with a condense drain point from an all stainless steel exhaust box. Optional items include a room sealed burner/controls housing, T316 stainless steel heat exchanger tubes and units specically designed for fresh air input and where condensate may be generated.
IMPORTANT Service and Maintenance Engineers shall
ensure that replacement items are tted,
adjusted and set in accordance with the data and detail set out in these instructions. If in doubt consult Powrmatic Technical Department.
Gas Safety (Installation & Use) Regulations 1998
It is law that all gas appliances are installed, adjusted and, if necessary, converted by qualied persons* in
accordance with the current issue of the above regulations. Failure to install appliances correctly can lead to prosecution. It is in your own interests and that of safety to ensure that the law is complied with.
* An approved class of person listed on the gas safe register.
1.1 Introduction
page no. 6 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
C
B
A D
Duties & Dimensions
HEM-NVx Unit Dimensions
Model 10-3 15-4 18-5 25-5 30-6 40-8 50-6 60-7 75-9 100-12 110-13 125-15 150-18 175-21 200-24
Dimension
A
550
550 550 680 680 680 1050 1050 1050 1050 1050 1050 1050 1050 1050
B
305
458 458 531 531 741 531 601 741 950 1132 1272 1482 1690 1900
C
590
590 590 648 648 648 800 800 800 800 930 930 930 930 930
D 400 400 380 400 380 380 400 400 400 400 500 500 500 500 550
Flue Diameter
80
80 80 100 100 100 100 130 130 130 130 130 130 130 130
HEM-NVx
Model HEM-NVx
10-3 15-4 18-5 25-5 30-6 40-8 50-6 60-7 75-9 100-12 110-13 125-15 150-18 175-21 200-24
Output
On/Off
Max kW 10.0 15.0 18.0 25.0 30.0 40.0 50.0 60.0 75.0 100.0 110.0 125.0 150.0 175.0 200.0
Min kW n/a
High/Low & Modulating
N.G. G20
Max kW 10.0 15.0 18.0 25.0 30.0 40.0 50.0 60.0 75.0 100.0 110.0 125.0 150.0 175.0 200.0
Min. kW 5.4 8.0 9.6 13.4 16.0 21.6 26.5 31.7 39.9 53.3 58.7 66.7 80.0 93.3 106.7
LPG G31
Max KW 10.0 15.0 18.0 25.0 30.0 40.0 50.0 60.0 75.0 100.0 110.0 125.0 150.0 175.0 200.0
Min. kW 5.4 7.7 9.8 14.4 16.5 21.5 25.2 28.0 38.0 54.0 59.8 68.0 81.6 95.2 108.8
Temp
Rise Max Δt °C 35
Air Off Max °C 70
Airflow
Min. Volume
Natural Gas m
3
/s 0.34 0.44 0.58 0.71 0.86 1.01 1.55 1.90 2.22 2.78 2.99 3.39 4.14 4.67 5.31
LPG m
3
/s 0.33 0.35 0.50 0.83 0.69 0.99 1.19 1.90 1.73 2.50 2.64 2.99 3.67 4.17 4.75
Pressure Drop
At above Airflow
Pa 43 26 45 32 47 31 59 67 59 54 43 43 47 45 46
Electrics
V/ph/Hz 230/1/50 @ 0.3A
Current A/pha 0.304
Power Total kW 0.07
Fuel
Connection BSP/Rc ¾
Minimum Inlet Pressure
Natural Gas mbar 20.0
LPG mbar 37.0
Rate
Natural Gas m
3
/h 1.16 1.74 2.09 2.91 3.49 4.65 5.87 7.05 8.91 11.75 12.79 14.45 17.69 20.33 23.60
LPG m
3
/h 0.44 0.65 0.78 1.09 1.31 1.74 2.18 2.61 3.26 4.35 4.79 5.44 6.53 7.61 8.70
Flue
Diameter mm ø 80 100 130
Max Length m 12
Nett Weight (single units) kg 38 45 53 60 68 74 91 114 123 140 145 168 195
230 270
Two Modules in Series
Δt = 70°C
Heat Output kW 20 30 36 50 60 80 100 120 150 200 220 250 300 350 400
Minimum Airflow
@ 0°C air inlet
m
3
/s 0.34 0.44 0.58 0.71 0.86 1.01 1.55 1.90 2.22 2.78 2.99 3.39 4.14 4.67 5.31
Pressure Drop At Minimum Airflow
Pa 87 52 91 65 95 62 117 134 119 108 86 86 93 91 92
page no. 7 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
C
B
A D
HEM-SL Unit Dimensions
Model 30-6 45-9 50-6 60-12 75-9 75-15 90-18 100-12 125-15 150-18 175-21 200-24
Dimension
A
1250
1250 1850 1250 1850 1250 1250 1850 1850 1850 1850 1850
B
531
741 531 950 741 1272 1482 950 1272 1482 1690 1900
C
400
400 400 400 400 400 400 400 400 400 400 530
D
450 450 450 450 450 450 450 450
500 500 500 550
Flue Diameter
100
100 100 130 130 130 130 130 130 130 130 130
HEM-SL
Model - HEM-SL
30-6 45-9 50-6 60-12 75-9 75-15 90-18 100-12 125-15 150-18 175-21 200-24
Output
On/Off
Max kW 30.0 45.0 50.0 60.0 75.0 75.0 90.0 100.0 125.0 150.0 175.0 200.0
Min kW n/a
High/Low Modulating
Nat Gas G20
Max kW 30.0 45.0 50.0 60.0 75.0 75.0 90.0 100.0 125.0 150.0 175.0 200.0
Min kW 16.7 26.1 26.6 28.2 46.1 46.1 55.7 57.9 72.4 88.8 102.5 117.1
LPG G31
Max KW 30.0 45.0 50.0 60.0 75.0 75.0 90.0 100.0 125.0 150.0 175.0 200.0
Min kW 16.6 24.5 25.3 28.3 38.1 38.1 54.4 54.5 68.2 83.7 96.5 110.3
Temp
Rise Max Δt °C 25
Air Off Max °C 70
Airflow
Minimum Volume
Nat Gas m
3
/s 0.97 1.45 1.61 1.94 2.68 2.68 2.90 3.23 4.03 4.84 5.64 6.45
LPG m
3
/s 0.97 1.45 1.61 1.94 2.42 2.42 2.90 3.23 4.03 4.84 5.64 6.45
Pressure Drop At above airflow Pa 16 17 20 18 21 15 19 22 19 19 20 21
Electrics
V/ph/Hz 230/1/50@ 0.3A
Current A/pha 0.304 0.304 0.304 0.304 0.304 0.304 0.304 0.304 0.90 0.90 0.90 3.5
Power Total kW 0.07 0.07 0.07 0.07 0.07 0.07 0.07 0.07 0.207 0.207 0.207 0.80
Gas
Connection BSP/Rc ¾
Minimum Inlet Pressure
Nat Gas mbar 20
LPG mbar 37.0
Rate
Nat Gas m
3
/h 3.53 5.29 5.88 7.05 8.82 8.82 10.58 11.76 14.7 18.04 20.81 23.78
LPG m
3
/h 1.36 2.04 2.27 2.73 3.41 3.41 4.09 4.54 5.68 6.97 8.07 9.19
Flue
Diameter mm ø 100 130
Maximum Length m 18
Nett Weight (single units) Kg 59 85 79 118 106 139 165 130 185 204 235 265
Two Modules in Series
Max Δt = 50°C
Heat Output kW 60 90 100 120 150 150 180 200 250
300 350 400
Minimum Airflow @ 0°C air inlet m
3
/s 0.97 1.45 1.61 1.94 2.42 2.42 2.90 3.23 4.03 4.84 5.64 6.45
Pressure Drop At Above Airflow Pa 27 29 33 30 35 35 30 37 31 32 34 35
Three Modules in Series
Max Δt = 75°C
Heat Output kW 90 135 150 180 225 225 270 300 375 450 525 600
Minimum Airflow @ 0°C air inlet m3/s 1.04 1.56 1.73 2.08 2.59 2.59 3.11 3.46 4.32 5.18 6.05 6.91
Pressure Drop At Above Airflow Pa 46 49 54 50 59 43 52 63 52 54 57 58
page no. 8 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
HEM-NVx Pressure Drop Graph
Note:
HEM NVx
The above data refers to a single module pressure drop. For twin models, refer to manufacturer.
10-3
720
1800
2880
3960
5040
6120
7200
7200
8280
9360
10440
11520
12600
13680
14760
14760
15840
16920
18000
19080
20160
21240
22320
22320
23400
24480
25560
26640
27720
28800
29880
29880
30960
32040
33120
34200
35280
36360
37440
37440
38520
39600
40680
41760
42840
43920
45000
45000
46080
47160
48240
49320
50400
51480
52560
52560
53640
54720
55800
56880
57960
59040
60120
60120
Airow m³/h
15-4
18-5
25-5
30-6
40-8
50-6
60-7
75.9
100-12
110-13
125-15
150-18
175-21
200-24
page no. 9 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
HEM-SL Pressure Drop Graph
30-6
45-9
50-6
60-12
75-9
75-15
90-18
100-12
125-15
2160
3600
5040
6480
7920
9360
10800
10800
12240
13680
15120
16560
18000
19440
20880
20880
22320
23760
25200
26640
28080
29520
30960
30960
32400
33840
35280
36720
38160
39600
41040
41040
42480
43920
45360
46800
48240
49680
51120
51120
52560
54000
55440
56880
58320
59760
Airow m³/h
150-18
175-21
200-24
Note:
HEM-SL
The above data refers to a single module pressure drop. For twin & triple models, refer to manufacturer.
page no. 10 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
(Max) (Min)
Injectors
Burner
Pressure
Gas Rate
(nominal)
Burner
Pressure
Gas Rate
(nominal)
MODEL No. Size (mm)
Marked mbar m³/ h mbar m³/h
HEMNVx 10-3 3 1.67 380 10.7 1.16 3.2 0.63 HEMNVx 15-4 4 1.67 380 13. 6 1.74 4.1 0.95 HEMNVx 18-5 5 1.67 380 10.7 2.09 3.2 1.15
HEMNVx 25-5 5 1.94 500 13. 3 2.91 4.0 1.60 HEMNVx 30-6 6 1.94 500 13.6 3.49 4.1 1.92 HEMNVx 40-8 8 1.94 500 13.2 4.65 4.0 2.56 HEMNVx 50-6 6 2.54 750 12.6 5.87 3.8 3.19 HEMNVx 60-7 7 2.54 750 12 . 8 7.05 3.9 3.84 HEMNVx 75-9 9 2.54 750 12. 5 8.91 3.8 4.79
HEMNVx 100-12 12 2.54 750 12.7 11. 75 3.8 6.39 HEMNVx 110-13 7+6 2.54 750 12.9 12.79 3.9 7. 03 HEMNVx 125-15 9+6 2.54 750 12. 5 14.45 3.8 7.9 9 HEMNVx 150-18 9+9 2.54 750 12. 5 17.69 3.8 9.59 HEMNVx 175-21 12+9 2.54 750 12. 5 20.33 3.8 11.19 HEMNVx 200-24
12+12 2.54 750 12.5 23.60 3.8 12.78
Injector Sizes & Burner Pressures - Natural Gas - Group H - G20 Net CV (Hi = 34.02MJ/m³
Minimum Inlet Pressure = 20.0mbar Maximum Inlet Pressure = 60mbar
(Max) (Min)
Injectors
Burner
Pressure
Gas Rate
(nominal)
Burner
Pressure
Gas Rate
(nominal)
MODEL No. Size (mm)
Marked mbar m³/h mbar m³/h
HEMSL 30-6 6 1.94 500 13.8 3.53 4.4 1.99 HEMSL 45-9 9 1.94 500 13.4 5.29 4.6 3.16 HEMSL 50-6 6 2.54 750 12 . 3 5.88 3.7 3.20
HEMSL 60 -12 12 1.94 500 13.6 7. 0 5 3.2 3.40
HEMSL 75-9 9 2.54 750 12. 5 8.82 4.9 5.54 HEMSL 75-15 15 1.94 500 13.6 8.82 5.4 5.54 HEMSL 90-18 18 1.94 500 13.7 10.58 5.2 6.51
HEMSL 100-12 12 2.54 750 12.7 11.76 4.3 6.86 HEMSL 125 -15 15 2.54 750 12.3 14.70 4.2 8.58 HEMSL 150-18 18 2.54 750 13.4 18.04 4.6 10.53 HEMSL 175-21 21 2.54 750 12.6 20.81 4.3 12 .14
HEMSL 200-24 24 2.54 750 13. 3 23.78 4.5 13. 88
HEM-SL
HEM-NVx
1.2 Technical Data
page no. 11 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
Injector Sizes & Burner Pressures - Propane G31 Net CV (Hi = 88.00MJ/m³
(Max) (Min)
Injectors
Burner
Pressure
Gas Rate
Burner
Pressure
Gas Rate
MODEL No. Size (mm)
Marked mbar m³/ h mbar m³/h
HEMNVx 10-3 3 1.1 tba 23.9 0.45 9.0 0.28 HEMNVx 15-4 4 1.15 tba 25.3 0.67 7.9 0.38 HEMNVx 18-5 5 1.15 tba 23.3 0.81 8.8 0.49 HEMNVx 25-5 5 1. 36 240 23.0 1.12 10.0 0.74 HEMNVx 30-6 6 1.36 240 22.9 1. 35 8.6 0.83 HEMNVx 40-8 8 1.36 240 22.9 1.80 8.4 1.09 HEMNVx 50-6 6 1.75 500 23.2 2.25 7. 5 1.28 HEMNVx 60-7 7 1.75 500 24.5 2.70 8.2 1.47 HEMNVx 75-9 9 1.75 500 23.2 3.37 8.5 1.92
HEMNVx 100-12 12 1.75 500 23.2 4.50 8.7 2.76
HEMNVx 110-13 7+6 1.75 500 23.9 4.95 9.0 3.03 HEMNVx 125-15 9+6 1.75 500 23.2 5.62 8.7 3.45 HEMNVx 150-18 9+9 1.75 500 23.2 6.74 8.7 4.14 HEMNVx 175-21 12+9 1.75 500 23.2 7.87 8.7 4.82
HEMNVx 200-24 12+12 1.75 500 23.2
8.99 8.7 5.51
(Max) (Min)
Injectors
Burner
Pressure
Gas Rate
Burner
Pressure
Gas Rate
MODEL No. Size (mm)
Marked mbar m³/h mbar m³/h
HEMSL 30-6 6 1.36 240 20.5 1.36 6.5 0.76 HEMSL 45-9 9 1.36 240 20.4 2.04 6.4 1.15 HEMSL 50-6 6 1.94 500 14.6 2.27 3.9 1.18
HEMSL 60 -12 12 1.36 240 19.5 2.73 4.9 1.36
HEMSL 75-9 9 1.94 500 14.8 3.41 4.0 1.77
HEMSL 75-15 6+9 1.36 240 20.2 3.41 5.5 1.77
HEMSL 90-18 9+9 1.36 240 20.5 4.09 7. 4 2.45 HEMSL 100-12 12 1.94 500 14. 8 4.54 4.6 2.54 HEMSL 125 -15 6+9 1.94 500 14.6 5.68 4.6 3.18 HEMSL 150-18 9+9 1.94 500 16.0 6.97 5.0 3.90 HEMSL 175-21 9+12 1.94 500 15.2 8.07 4.8 4.50
HEMSL 200-24 12+12 1.94 500 15.0 9.19 4.7 5.14
Minimum Inlet Pressure = 37mbar Maximum Inlet Pressure = 60mbar
HEM-SL
HEM-NVx
page no. 12 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
High Fire
Low Fire
Min Air Flow
Natural Gas LPG
Input
(Nett)
Output
Input (Nett)
Output
Input (Nett)
Output Natural Gas LPG
MODEL
kW kW kW m³/s m³/h m ³/s m³/h
HEMSL 30-6 33.3 30 18.8 16.7 18.7 16.6 0.97 3492 0.97 3492 HEMSL 45-9 50.0 45 29.2 26.1 28.0 24.5 1.45 5220 1.45 5220 HEMSL 50-6 55.6 50 30.3 26.6 28.9 25.3 1.61 5796 1.61 5796
HEMSL 60 -12 66.7 60 32.2 28.2 33.3 28.3 1.94 6984 1.94 6984
HEMSL 75-9 83.3 75 52.4 46.1 43.3 38.1 2.68 9648 2.42 8712
HEMSL 75-15 83.3 75 52.4 4 6.1 43.3 38.1 2.68 9648 2.42 8712
HEMSL 90-18 100.0 90 61.6 55.7 60.0 54.4 2.90 10440 2.90 10440 HEMSL 100-12 111.1 100 64.9 57.9 62.2 54.5 3.23 11628 3.23 11628 HEMSL 125 -15 138.9 125 81.1 72.4 7 7.8 68.2 4.03 14508 4.03 14508 HEMSL 150-18 170 . 5 150 99.6 88.8 95.5 83.7 4.84 17424 4.84 17424 HEMSL 175-21 196.6 175 114. 8 102.5 110 .1 96.5 5.64 20304 5.64 20304 HEMSL 200-24 224.7 200 131. 3 117.1 125.8 110. 3 6.45 23220 6.45 23220
High Fire
Low Fire
Min Air Flow
Natural Gas LPG
Input (Nett)
Output
Input
(Nett)
Output
Input
(Nett)
Output Natural Gas LPG
MODEL
kW kW kW m³/s m³/h m³/s m³/h
HEMNVx 10-3 11. 0 10 6.0 5.4 6.8 5.4 0.34 1224 0.33 118 8 HEMNVx 15-4 16.5 15 9.0 8.0 9.2 7.7 0.44 1584 0.35 1260 HEMNVx 18-5 19. 8 18 10.9 9.6 12.1 9.8 0.58 2088 0.50 1800 HEMNVx 25-5 2 7. 5 25 15.1 13.4 18.03 14.4 0.71 2556 0.83 2988 HEMNVx 30-6 33.0 30 18.1 16.0 20.2 16.5 0.86 3096 0.69 2484 HEMNVx 40-8 44.0 40 24.2 21.6 26.6 21.5 1.01 3636 0.99 2564 HEMNVx 50-6 55.0 50 30.2 26.5 31.3 25.2 1.55 5580 1.19 4284 HEMNVx 60-7 65.9 60 36.3 31.7 35.9 28.0 1.90 6840 1.90 6840 HEMNVx 75-9 82.4 75 45.3 39.9 47.0 38.0 2.22 7992 1.73 6228
HEMNVx 100-12 109.9 100 60.4 53.3 67.5 54.0 2.78 10008 2.50 9000
HEMNVx 110-13 120.9 110 66.5 58.7 74.2 59.8 2.99 10764 2.64 9504 HEMNVx 125-15 137. 4 125 75.6 66.7 84.3 68.0 3.39 12204 2.99 10764 HEMNVx 150-18 164.8 150 90.7 80.0 101.2 81.6 4.14 14904 3.67 13212 HEMNVx 175-21 192. 3 175 105.8 93.3 118 .1 95.2 4.67 16812 4.17 15012 HEMNVx 200-24 219.8 200 120.9 106.7 134.9 108.8 5.32 19152 4.75 1710 0
Heater Specications
HEM-SL
HEM-NVx
page no. 13 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
Heater Specications cont
Power
Conpumption
Nominal CO Values Weights
Nat Gas (G20)
(High Fire)
Propane (G31)
(High Fire)
Module
only
Packaging Total
MODEL
VA % % kg kg kg
HEMNVx 10-3 140.4 6.0 6.2 38 12 50 HEMNVx 15-4 140.4 6.5 6.6 45 12 57 HEMNVx 18-5 14 0.4 6.3 7. 3 53 15 68 HEMNVx 25-5 140.4 7. 2 7. 4 60 15 75 HEMNVx 30-6 140.4 7.9 7.9 68 15 83 HEMNVx 40-8 140.4 7.5 7.8 74 15 89 HEMNVx 50-6 140.4 7.6 8.6 91 18 99 HEMNVx 60-7 121.1 8.2 9.0 114 18 132
HEMNVx 75-9 121.1 7.0 8.0 123 18 141 HEMNVx 100-12 164.4 7.0 8.3 140 21 161 HEMNVx 110-13 164.4 7.9 9.6 145 21 166 HEMNVx 125-15 314.4 8.3 8.5 168 25 193 HEMNVx 150-18 314.4 8.4 9.6 195 30 225 HEMNVx 175-21 314.4 8.6 9.7 230 32 262
HEMNVx 200-24 540.4 8.2 8.2 270 35 305
HEM-NVx
Power
Conpumption
Nominal CO Values Weights
Nat Gas (G20)
(High Fire)
Propane (G31)
(High Fire)
Module
only
Packaging Tot al
MODEL
VA % % kg kg kg
HEMSL 30-6 140.4 8.2 8.4 58.5 15 73.5
HEMSL 45-9 140.4 8.4 8.5 85 15 100
HEMSL 50-6 140. 5 8.5 8.6 79 18 97
HEMSL 60 -12 121.2 8.1 8.6 118 15 133
HEMSL 75-9 121.2 7.0 7.8 105. 5 18 123. 5
HEMSL 75-15 170.4 8.3 9.1 139 18 157
HEMSL 90-18 170.4 8.2 9.0 165 18 183 HEMSL 100-12 16 4.4 8 .1 8.8 130 21 151 HEMSL 125 -15 314.4 8.0 9.0 184.5 25 209.5 HEMSL 150-18 314.4 7. 7 9.1 206.5 30 236.5 HEMSL 175-21 314.4 8 .1 10.0 234.5 32 266.5 HEMSL 200-24 520.4 7. 2 7. 5 265 35 300
HEM-SL
page no. 14 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
1.3.1. Related Documents
The installation of the module(s) must be in accordance with the rules in force and the relevant requirements of the Gas Safety Regulations, Building Regulations and the I.E.E. Regulations for Electrical Installations. It should also be in accordance with any relevant requirements of the local gas region, local authority and re authority and the relevant recommendations of the following documents.
Institution of Gas Engineers & Managers IGE/UP/1 (Ed.2) Strength and tightness testing and
purging of industrial and commercial gas installations.
IGE/UP/1A Soundness testing and direct purging of small low pressure industrial and commercial gas installations.
IGE/UP/2 Gas installation pipe work, boosters and compressors on industrial and commercial premises.
IGE/UP/10 (with Amendments October 2010) Installation gas appliances in industrial and commercial premises.
British Standards Code of Practice BS 5588 Fire precautions in the design and construction of
buildings. Part 2 : 1985 Code of Practice for Shops Part 3 : 1983 Code of Practice for Oce Buildings
BS 6230 Installation of Gas Fired Forced Convection Air Heaters for Commercial and Industrial Space Heating.
Those appliances having a gross input rating not exceeding 60kW and installed to take their combustion air from within the building must be installed in accordance with the relevant recommendations of the following document.
BS 5440 Flues and Air Supply for gas appliances of rated input not exceeding 60kW (1st and 2nd family gases), Part 2 – Air Supply
BS 5864 Code of Practice for installation of gas-red ducted-air heaters of rated input not exceeding 60kW.
Electromagnetic Compatibility (EMC)
These heaters pass the following standards for Electromagnetic Compatibility: EN 61000-6-3:2007 A1 (Generic Emissions for Residential, Commercial and Light Industrial Environments) and EN 61000-6-2:2005 (Generic Immunity for Industrial Environments).
1.3.2 Electrical Supply
Wiring external to the air heater must be installed in accordance with the I.E.E. Regulations for Electrical Installations and any local regulations which apply. All modules are supplied by 230V - 1ph, 50Hz. The method of connection to the main electricity supply must:-
- facilitate the complete electrical isolation of the unit(s)
- be in a readily accessible position adjacent to the unit(s)
- serve only the unit(s)
- have a contact separation of at least 3mm in all poles.
See the accompanying wiring diagram for the heater electrical connections
1.3.3 Gas Supply
A servicing valve and union to facilitate servicing must be tted to the gas inlet pipe work of the heater. The gas supply must be completed in solid pipe work and be adequately supported.
Warning When completing the nal gas connection to the heater do not place undue strain on the gas pipe work of the heater.
1.3.3.1 Service Pipes
The local gas undertaking should be consulted at the installation planning stage in order to establish the availability of an adequate supply of gas. An existing service pipe must not be used without prior consultation with the local gas undertaking. The inlet gas pressure under running conditions must not be less than 20.0mb.
1.3.3.2 Meters
An existing meter should be checked, preferably by the gas undertaking, to ensure that the meter is adequate to deal with the total rate of gas supply required by all connected equipment.
1.3.3.3. Installation Pipes
Installation pipes should be tted in accordance with IGE/ UP/2. Pipe work from the meter to the air heater must be of adequate size. Do not use pipes of a smaller size than the inlet gas connection of the heater. The complete installation must be tested for soundness as described in the above Code.
1.3 General Requirements
page no. 15 of 48
HEMNVx & HEMSL Range Users, Installation & Servicing Instructions Doc Ref M103 issue 3.1 Feb 2018.
1.3.4 Ventilation Requirements for AHU's
Refer to tables detailed on next page for calculated free areas of ventilation grilles. Refer to Index 1 for Air inlet/exhaust ue and ventilation sketches
1.3.4.1 Type B ued installations.
Where AHU's are installed within the heated space (ie not in a plant room) and having a building design air
change rate of greater than 0.5/h, additional provision for ventilation is not required.
If the building design air change rate is less than 0.5/h, additional provision for natural or mechanical ventilation
is required.
These being: Natural Ventilation: Grilles having a free area of at least 2cm² per kW of rated heat input shall be provided at low level i.e. below the level of the heater ue connection.
or
Mechanical Ventilation: Must ensure that the space air change rate is at least 0.5/h, must be of the ‘input’ type and interlocked to ensure the heaters cannot work if the input system is not working.
1.3.4.2 Type B ued installations.
Where AHU's are installed in a plant room (ie not within the heated space)
having combustion air drawn directly from the room and connected to a ue that evacuates the products of combustion directly from the room additional provision for natural or mechanical ventilation is required.
These being:
Natural Ventilation:
There must be permanent air vents communicating directly with the outside air, at high level and at low level.
For Plant Rooms
Low level (inlet) 4cm²/kw of total rated net heat input High level (outlet) 2cm²/kw of total rated net heat input
Mechanical Ventilation: The minimum ow rate of ventilation shall be 4.14m³/h per kilowatt of total rated heat input.
1.3.4.3 Type C ued installations.
Where AHU's are Installed within the heated space (ie not in a plant room)
having combustion air ducted to the appliance and combustion products ducted to the outside air, NO additional provision for the supply of either combustion air or for combustion products dilution or additional provision for the supply of air is necessary.
1.3.4.4 Type C ued installations.
Where AHU's are installed in a plant room (ie not within the heated space)
having combustion air ducted to the appliance and combustion products ducted to the outside, air vents shall be provided and be permanently open.
To room or internal space
Low level (inlet) 10cm²/kw of total rated net heat input High level (outlet) 10cm²/kw of total rated net heat input
Direct to outside air
Low level (inlet) 5cm²/kw of total rated net heat input High level (outlet) 5cm²/kw of total rated net heat input.
1.3.5 Burner/Controls Enclosure
Where the ue system is a Type C12 or C32 the burner and controls enclosure, whether it is part of the unit the module is tted in or an enclosure in its own right, must meet the requirement of BS EN1020 Clause 6.1.1.24 i.e. the air leakage rate from the enclosure shall not exceed 0.5m³/h per kW of heat input, with a maximum of 25 m³/h.
With the ue connected the terminal is sealed, any access door is closed and the gas inlet is isolated. Air is passed into the appliance via a ow meter and the air ow rate is noted when the pressure inside the enclosure is steady at 0,5mbar above the atmospheric pressure.
NOTE A convenient method of testing the appliance is to enclose the terminal in a plastic bag into which an air entry pipe and tube connected to a pressure gauge can be tted.
Loading...
+ 33 hidden pages