Powrmatic ErP NVS 30, ErP NVS 60, ErP NVS 90, ErP NVS 140 User, Installation & Servicing Manual

Page 1
Doc Ref: M102 Issue 2.4 May 2018
NVS Condensing Gas Unit Heater
Industrial & Commercial Heating Systems
User, Installation & Servicing Manual
www.powmatic.co.uk
+44 (0) 1460 53535
info@powrmatic.co.uk
Page 2
Certificate of Guarantee
Dear Customer
This is to certify that this heater is guaranteed for two years parts and one year labour from the date of original commissioning. The heater must be commissioned within 4 weeks of installation.
To make a claim
In the rst instance you must contact your appliance supplier, or installer and provide:-
1. The appliance type and serial number.
2. The original commissioning documentation. As much detail as possible on the fault.
3. Your supplier, or installer, will then contact Powrmatic to make a guarantee claim on your behalf.
Conditions of Guarantee
1. The heater must have been installed by a competent recognised installer, and in accordance with the manufacturer’s instructions, building regulations and local regulations.
2. The heater has been professionally commissioned, within 4 weeks of installation, and a copy of the commissioning sheet returned to Powrmatic.
3. The heater has been maintained on a yearly basis by a competent servicing company.
4. The heater has been used in accordance with the manufacturer’s instructions.
5. The correct specication fuel has been used.
6. No unauthorised repairs of modications have been made. Powrmatic ‘General Conditions of Sales’ have been observed.
7. Except for the obligation of Powrmatic Ltd to perform warranty repairs during the guarantee period Powrmatic will not be liable in respect of any claim for direct or indirect consequential losses, including loss of prots or increased cost arising from loss of use of the heater, or any event arising there from.
Exclusions
Consumables such as gaskets, ignition electrodes, ame rectication electrodes, drive belts, fusible links, control batteries are all excluded from guarantee.
----------------------------------------------------
Powrmatic Ltd, Hort Bridge, Ilminster, Somerset, TA19 9PS Tel: 01460 53535 Fax: 01460 52341 Web: www.powrmatic.co.uk e-mail: warranty@powrmatic.co.uk
Important: This certicate
must be kept with the appliance
Failure to provide a copy of the commissioning sheet invalidates the heater warranty
Installer Date:________________Signed: _____________________________________Installer
Commissioned Date:________________Signed:_______________________Commissioning Engineer
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 3
Dear Customer - thank you for choosing Powrmatic.
We appreciate you buying one of our high quality products and know that you have made the best choice. By choosing Powrmatic, you are investing in UK manufacturing & its workforce. We pride ourselves by manufacturing products that provide clean, comfortable and safe working environments worldwide together with the personal & professional service and back-up you deserve. If you have any questions or concerns regarding this product, please contact our Technical Support Team by calling 01460 53535.
Users, Installation and Servicing Instructions
CONTENTS
Title Section Contents Page
User Instructions 4
Pre Installation
1.1 Introduction 5 Duties 6 Dimensions 7
1.2 Technical data 9
1.3 General Requirements 10
Installation
2.1 Fitting the unit 14
2.2 Flue/Combustion Air Duct System 16
2.3 General Identication of Electrical Items 19
2.4 Electrical Cable Installation 19
2.5 Wiring Diagrams 21
2.6 Commissioning and Testing 23
2.7 Servicing 27
Additional Documents
3.1 Short List of Parts 30
3.2 Gas Conversion 32
Appendices Information required for ecodesign (ErP) Directive 2009/125 34
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
page no. 3 of 36
Page 4
User Instructions
If the heater has not been left operational proceed as follows.
A) Checks before lighting the Air Heater
The following preliminary checks should be made before lighting the heater(s)
a) Ensure that the ELECTRICAL supply to the heater is switched OFF. b) Check that all warm air delivery outlets are open. c) Check that the thermostat is set at MAX. d) Check that the clock control is set to an ON period. e) Check that any other controls are calling for heat.
B) Lighting the Air Heater
1. Switch on the electrical supply at the isolator
2. If the Red Limit indicator light at the front of the heater is illuminated, press the limit interlock reset switch at the side of the lamp.
3. The startup sequence will commence.
4. If the burners fail to light the control box will automatically restart the ignition sequence. If after 5 attempts at ignition the burners have still failed to light the control box will go to lockout and the Red lockout light inside the heater (or on the low level remote reset, MC200 or Powrtrol RR if tted) will be illuminated. To restart the ignition sequence depress the reset button for about 1-2 seconds.
WARNING: If it is not possible to light the heater after several attempts, contact the installer or local service company.
C) To Shut Down the Air Heater
1) For Short Periods:
Turn the room thermostat to the OFF, or set to it’s lowest setting.
D) Description of Operation
Important: The heater must NOT be controlled by switching ON and OFF the main electrical supply to it.
1) Standard Units
The ignition sequence commences each time the external controls e.g. Time clock, room thermostat etc. call for heat. The internal exhaust fan will run and, when sucient combustion airow is proved by the air pressure switch, the ignition spark will be generated, the main gas valve opens and the burners light. The heater fan will automatically start approximately 0 - 30 seconds (depending on the setting of the internal timer) after the burners light. When the external controls are satised the burners will be turned o and approximately 2 - 3 minutes later the heater fan will be automatically stopped. If the burners fail to light the control box will make another four attempts at ignition.
2) High / Lo & Modulating Units
When the burners are alight, the heat output will be controlled either to high re or low re or, in the case of modulating units, to any point between high and low re; depending on the requirements of the space being heated and the external controls tted.
3) Summer / Winter Modes
Certain types of external controls will provide for two modes of operation i.e. Summer: The heater fan alone will run at the dictate of the external controls to provide air movement. Winter: The heater will operate normally.
4) Overheat Thermostat
This operates if high temperatures within the heater are detected, the burners are turned o and a Red indicator switch light on the front panel is illuminated. The fault condition must be identied and rectied and the thermostat manually reset. The thermostat is located next to the indicator light and unscrewing the cover cap exposes the reset button which can then be depressed.
2) For Long Periods:
Complete step 1 above. Wait for 5 minutes and then turn OFF the electrical supply at the isolator.
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Note: The limit thermostat(s) can only be reset once the unit has cooled down. Unless the cause of the fault condition is
readily obvious, for example a power cut whilst the heater was operating, a service engineer should be contacted.
Page 5
E) Maintenance
To maintain ecient, reliable and safe operation of the heater it must serviced by a qualied person at least annually and preferably at the end of the heating season.
F) IMPORTANT
Free access must be maintained to and around the heater for servicing purposes and the air supply to the heater must not be restricted in any way. Combustible materials must not be stored adjacent to the heater.
If at any time a gas leak is suspected, turn OFF the gas supply at the meter and contact the local gas undertaking immediately.
to service unless you are a competent person in the eld of Gas and Electrical work.
If you have any safety questions reference the servicing and installation of any of our heaters please do not hesitate to contact our head oce for expert advice. Your safety is paramount to us.
Gas Safety (Installation & Use) (Amendment) Regulations
It is law that all gas appliances are installed, adjusted and, if necessary, converted by qualied persons* in
accordance with the current issue of the above regulations. Failure to install appliances correctly can lead to prosecution. It is in your own interests and that of safety to ensure that the law is complied with.
All Powrmatic heaters use gas and electricity to power them, they may also contain moving parts such as pulleys and belts. It would be hazardous to tamper with or attempt
1.1 Introduction
The NVS range are highly ecient, fully condensing, gas red, fanned circulation air heaters that cover heat outputs of 30kW to 140kW, have a closed combustion circuit and are supplied complete with a ue system. They are certied for use on Natural Gas, Group H - G20, and Propane - G31 only. Appliance Categories are Cat II2H3P (GB, IE).
The heaters are designed to be suspended from suitable roof points or alternatively to be mounted on purpose designed brackets and are intended primarily for heating commercial or industrial premises. All variants are for internal use only.
NVS heaters feature a closed combustion circuit and have an internal exhaust fan, mounted downstream of the heat exchanger, to evacuate the products of combustion and draw in air for combustion. The air heater must be connected to a ue system that is approved by Powrmatic Ltd.
* An approved class of person listed on the gas safe register.
are for use in air handling units. NVS units are not suitable for siting externally.
Heaters are tted as standard with inshot burners, a fully automatic control for ignition, ame sensing, gas supply control and safety functions, an internal exhaust fan, main air fan (/F and /C models), and fan/limit thermostat.
Options include High/Low or Modulating burner controls, inlet duct connection, outlet duct connection, 30°, 45° head, 90° outlet bend, vertical/horizontal outlet louvre assembly and a full range of modular duct components.
IMPORTANT Service and Maintenance Engineers shall
ensure that replacement items are tted,
adjusted and set in accordance with the data and detail set out in these instructions. If in doubt consult Powrmatic Technical Department.
They may be used where the atmosphere inside the premises could be contaminated e.g. Dust, oil mist etc. but the heaters are not airtight and therefore may not be used in areas classied as hazardous as dened in BS 5345: Part 2 or areas subjected to signicant negative pressures due to extract systems.
NVS/F heaters have an axial fan assembly tted at the rear to circulate the air being heated through the formed tube heat exchanger. NVS/C units are supplied with a centrifugal fan and NVS/D units for use with ducted systems where the air moving fan is by others or a centrifugal fan section is used adjacent to or remote from the heater. NVS/DH units
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Gas Safety (Installation & Use) Regulations 1998
It is law that all gas appliances are installed, adjusted and, if necessary, converted by qualied persons* in
accordance with the current issue of the above regulations. Failure to install appliances correctly can lead to prosecution. It is in your own interests and that of safety to ensure that the law is complied with.
* An approved class of person listed on the gas safe register.
page no. 5 of 36
Page 6
Duties
Model 30 60 90 140
Output kW 30 60 90 140
Input (nett CV) kW 29.02 59.22 86.74 137.95
Volume (All Models) m
Airflow
Throw NVS F m 24 25 31 37
Fan Static
Supply
NVS C Pa 250 250 200 285
Standard V/ph/Hz 230/1/50
Optional V/ph/Hz 415/3/50
Motor kW 0.39 0.66 2 x 0.39 2 x 0.66
Electrics
NVS F
Start amp 3.76 5.5 5.0 10.6
Run amp 1.70 2.4 2.3 5.3
Motor kW 1.10 1.40 2 x 1.10 2 x 1.40
NVS C
Start amp 18.50 28.90 31.0 40.0
Run amp 6.40 9.50 12.80 17
Connection BSP/Rc ¾”
Nat Gas mbar 17.5
LPG mbar 37.0
Nat Gas m
LPG m
Min m 2.50 3.00
Max m 3.00 5.00
Fuel
Mounting Height
Minimum Inlet Pressure
Consumption
NVS F
Height mm 818 818 Overall Dimensions
NVS F
Width mm 1050 1345 2345 2345
Depth mm 1187 1204 1187 1204
Top mm 200
Installation Clearances
NVS
LH Side mm 200
RH Side mm 1000
Rear mm 600
Connection mm 15 15 15 15 Condensate Output
Natural Gas l/h 2.3 3.4 6.0 8.8
Propane l/h 1.2 1.7 3.0 4.4
Diameter mm ø 100 130
Flue
Maximum Length
Flue Only m 12
Room Sealed m 6
Combustion Air Spigot mm ø 100 130
Noise Level dB(A) 54 62 66 67
Nett Weight
NVS F kg 124 177 245 350
NVS C kg 195 252 384 514
3
/s 0.78 1.56 2.34 3.64
3
/h 3.07 6.26 9.17 14.60
3
/h 1.21 2.42 3.55 5.64
705 1035
Notes –
Fuel consumption and output figures based upon nett calorific values as follows
- Natural gas (G20) nett CV 34.02 MJ/m³
- Propane (G31) nett CV 88.00 MJ/m³
Heaters have efficiency levels which meet with the minimum efficiency requirements of UK PartL2B Building Regulations
Heaters have efficiency levels which meet the criteria of the Enhanced Capital Allowance Scheme (Excluding NVS30)
Air handling data is assessed at room ambient conditions
Throw figures provide the distance to the point where the terminal velocity degrades to 0.25 m/s
Dimensions and clearance data in table above refer to NVS F units only.
Condensate rates are approximate and for when heaters are working at maximum output.
Noise levels are applicable to standard NVS F models and are measured 5m from appliance and in free field conditions
Motor kW, run and start amps apply to standard electrical supply as stated. For optional data contact sales office
Connection of combustion air duct is not required for ‘flue only’ applications.
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 7
P
Y
N
X
GAS ENTRY POINT
CONDENSATE DRAIN POINT
FRONT VIEW
PLAN VIEW
R/H SIDE VIEW
GAS ENTRY POINT
REAR VIEW
C
A
B
Q
ØD
G
F
P
N
122
394
394
M
K
J
H
SUSPENSION POINTS M10
P
Dimensions
NVS F - Axial Fan Crossow Units
NVS 30 & 60
ØD
G
C
P
A B
FRONT VIEW
M
K
NVS 90 & 140
PLAN VIEW
J
394
394
122
H
R/H SIDE VIEW
SUSPENSION POINTS M10
Q
Detailed View Of Gas Entry Point & Condensate Drain Point
GAS ENTRY POINT
F
N
REAR VIEW
Model X Y
30/60 280 90
90/140 280 65
C
ØD
G
GAS ENTRY POINT
F
N
A
FRONT VIEW
REAR VIEW
K
B
R/H SIDE VIEW
PLAN VIEW
J J
Q
SUSPENSION POINTS M10
M
394
394
122
H
Model A B C D F G H J K M N P Q
NVS-F 30 1050 1031
818
100 552
142
347 445 258 201 144 225 156
NVS-F 60 1345 1031 818 130 475 220 347 740 258 201 144 301 173
NVS-F 90
NVS-F 140 2345 1031
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
2345
1031 705 130 356 220 347 870 258 201 88 237 156
1035
130
686
220 347 870 258 201 88 147 173
page no. 7 of 36
Page 8
NVS C - Centrifugal Close Coupled Fan Units
P
Y
N
X
GAS ENTRY POINT
CONDENSATE DRAIN POINT
FRONT VIEW
PLAN VIEW
R/H SIDE VIEW
GAS ENTRY POINT
REAR VIEW
C
A B
63
ØD
G
F
P
N
122
394
394
M
K
J
H
SUSPENSION POINTS M10
63
L
S R
T
P
Y
N
X
GAS ENTRY POINT
CONDENSATE DRAIN POINT
C
ØD
G
GAS ENTRY POINT
F
P
T
A B
FRONT VIEW
63
R/H SIDE VIEW
L
63
N
REAR VIEW
S R
Detailed View Of Gas Entry Point & Condensate Drain Point
M
SUSPENSION POINTS M10
PLAN VIEW
K
J
394
394
122
H
Model X Y
30/60 280 90
90/140 280 65
Model A B C D F G H J K L M N P R S T
NVS-C 30 1050 1031
NVS-C 60 1345 1031 818 130 475 220 347 740 258 1589 201 144 301 1010 940 748
2345
1031 705 130 356 220 347 870 258 1589 201 88 237 2014 1944 635
NVS-C 90
NVS-C 140 2345 1031
NVS D - Ducted Heat Module Units (No fan)
818
1035
100 552
130
142
347 445 258 1589 201 144 225 696 626 748
686
220 347 870 258 1664 201 88 147 2014 1944 965
ØD
C
FRONT VIEW
PLAN VIEW
K
A B
J
H
63
R/H SIDE VIEW
M
SUSPENSION POINTS M10
394
394
122
63
Detailed View Of Gas Entry Point & Condensate Drain Point
G
GAS ENTRY POINT
F
P
N
REAR VIEW
S R
T
Model X Y
30/60 280 90
90/140 280 65
Model A B C D F G H J K M N P R S T
NVS-D 30 1050 1031
818
100 552
142
347 445 258 201 144 225 696 626 748
NVS-D 60 1345 1031 818 130 475 220 347 740 258 201 144 301 1010 940 748
NVS-D 90
NVS-D 140 2345 1031
2345
1031 705 130 356 220 347 870 258 201 88 237 2014 1944 635
1035
130
686
220 347 870 258 201 88 147 2014 1944 965
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 9
1.2 Technical Data
Injector Sizes & Burner Pressures - Natural Gas - Group H - G20 Net CV (Hi = 34.02MJ/m³)
High Fire Low Fire
Injectors
MODEL No. Size (mm)
Burner
Pressure
Marked mbar m³/h mbar m³/h
Gas Rate
Burner
Pressure
Gas Rate
NVS30 6 1.94 194 10.0 3.07 3.3 1.67
NVS60 8 2.54 254 8.3 6.26 2.6 3.46
NVS90 6 3.5 350 8.2 9.17 2.8 5.40
NVS140 10 3.5 350 7.9 14.60 2.3 8 .17
Injector Sizes & Burner Pressures - Propane G31 Net CV (Hi = 88.00MJ/m³)
High Fire Low Fire
Injectors
MODEL No. Size (mm)
Burner
Pressure
Marked mbar m³/h mbar m³/h
Gas Rate
Burner
Pressure
Gas Rate
NVS30 6 1.25 125 26.5 1.21 7.6 0.65
NVS60 8 1.55 155 20.0 2.42 7.4 1. 34
NVS90 6 2.1 210 24.0 3.55 8.4 2.08
NVS140 10 2.10 210 22.6 5.64 6.9 3.16
Electrical Loadings - 1Pha
Nominal Inlet Pressure = 20mbar
Minimum Inlet Pressure = 17.5mbar
Nominal Inlet Pressure = 37mbar
Minimum Inlet Pressure = 37mbar
Motor
MODEL
NVS30
NVS60
NVS90
NVS140
kW
0.39 930 1.8 3.76 1.7 3 1.1 900 9.8 18.5 6.4 7
0.66 860 3.0 5.5 2.8 5 1.4 930 10.0 28.9 9.5 16
2 x 0.39 930 2 x 1.8 5.0 2.3 5 2 x 1.1 900 2 x 8.0 31.0 12.8 16
2 x 0.66 860 2 x 3.0 10.6 5.3 7 2 x 1.4 900 2 x 10 40.0 17.0 20
Heater Specications
Input (Nett)
MODEL
NVS30
NVS60
NVS90
NVS140
F
29.02 30.0 15.78 15. 2 0.7804 2809
C 250 1.1 n/a 195
F
59.22 60.0 32.72 32.29 1.5608 5618
C 250 1.4 n/a 252
F
86.74 90.0 51.00 52.53 2. 3412 8428
C 200 2 x 1.1 n/a 384
F
137.95 140.0 77.26 76.64 3.6418 13110
C 285 2 x 1.40 n/a 514
/F Models /CCF Models
Nominal
Motor R. P.M .
High Fire Low Fire
kW kW m³/s m³/h Pa kW dB(A) kg
Output
Rated Amps
(A)
Start
Amps
Input (Nett)
(A)
Run
Amps
(A)
Output
Fuse
Rating
(A)
Air Volume
Motor
kW
Nominal
Motor R. P.M .
Maximum
Resistance
Duct
Rated Amps
(A)
Motor
Fan
Start
Amps
(A)
Amps
Noise
Level
n/a 0.39 54 124
n/a 0.66 62 176.5
n/a 2 x 0.39 66 245
n/a 2 x 0.66 67 350
Run
(A)
Fuse
Rating
(A)
Weight
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
page no. 9 of 36
Page 10
1.3 General Requirements
1.3.1. Related Documents
The installation of the air heater(s) must be in accordance with the rules in force and the relevant requirements of the Gas Safety Regulations, Building Regulations and the I.E.E. Regulations for Electrical Installations. It should also be in accordance with any relevant requirements of the local gas region, local authority and re authority and the relevant recommendations of the following documents.
Institution of Gas Engineers & Managers IGE/UP/1 (Ed.2) Strength and tightness testing and
purging of industrial and commercial gas installations.
IGE/UP/1A Soundness testing and direct purging of small low pressure industrial and commercial gas installations.
IGE/UP/2 Gas installation pipe work, boosters and compressors on industrial and commercial premises.
IGE/UP/10 (with Amendments October 2010) Installation gas appliances in industrial and commercial premises.
British Standards Code of Practice BS 5588 Fire precautions in the design and construction of
buildings. Part 2 : 1985 Code of Practice for Shops Part 3 : 1983 Code of Practice for Oce Buildings
BS 6230 Installation of Gas Fired Forced Convection Air Heaters for Commercial and Industrial Space Heating.
Those appliances having a gross input rating not exceeding 60kW viz. NVS30 and installed to take their combustion air from within the building must be installed in accordance with the relevant recommendations of the following document.
BS 5440 Flues and Air Supply for gas appliances of rated input not exceeding 60kW (1st and 2nd family gases), Part 2 – Air Supply
For NVS30/D units, reference should also be made to: BS 5864 Code of Practice for installation of gas-red ducted-air heaters of rated input not exceeding 60kW.
Electromagnetic Compatibility (EMC)
These heaters pass the following standards for Electromagnetic Compatibility: EN 61000-6-3:2007 A1 (Generic Emissions for Residential, Commercial and Light Industrial Environments) and EN 61000-6-2:2005 (Generic Immunity for Industrial Environments).
1.3.2 Location
Powrmatic NVS units are designed to operate within an ambient temperature range of -10 to 25°C.
NVS heaters can be installed in several ways: i) suspended from ‘drop rods’ via purpose designed M10 suspension xing points on the heater, ii) attached to our optional wall support brackets or iii) positioned on a level, non­combustible base. In all cases, it is important that all supporting structures have been assessed with regard to the relevant weight loadings.
Consideration should be given to ue routes and points of exit, condensate, gas, electrical and control connections. Consideration should also be given to the throw characteristics of the heater, issues of public access and siting of environmental control stations and/or remote temperature sensors where the position needs to be representative of the zone temperature to which they refer.
Where the location of the air heater is such that it might suer external mechanical damage e.g. from overhead cranes, fork lift trucks, it must be suitably protected.
Heaters should not be installed in hazardous areas or areas where there is a foreseeable risk of ammable or corrosion inducing particles, gases or vapours being drawn into the combustion air or main fan circuits.
Areas where special consideration or advice may be required could include but is not limited to –
Where de-greasing solvents are present, even in minute concentrations
Where paint spraying is carried out
Where styrenes or other laminating products are used
Where airborne silicone is present
Where petrol engine vehicles are stored or main tained
Where dust is present (i.e. wood working or joinery shops)
Where high levels of extract persist Installation in such areas may be possible under specic conditions. Please consult our Technical Department for further information.
1.3.2.1 Sizing of the heater
The heater should be correctly sized for the area that it is heating, Full calculations need to be preformed to ensure the correct KW output heater is tted (CIBSE elemental methodology can be used, or the Powrmatic Technical Department can provide guidelines).
page no. 10 of 36
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 11
1.3.3 Electrical Supply
1.3.5 Flue System
Wiring external to the air heater must be installed in accordance with the I.E.E. Regulations for Electrical Installations and any local regulations which apply. All standard heaters are supplied by 230V - 1ph, 50Hz. The method of connection to the main electricity supply must:-
- facilitate the complete electrical isolation of the unit(s)
- be in a readily accessible position adjacent to the unit(s)
- serve only the unit(s)
- have a contact separation of at least 3mm in all poles. See the accompanying wiring diagram for the heater electrical connections NVS/C and fan/silencer units can also be supplied for 400V 3N, 50Hz.
1.3.4 Gas Supply
A servicing valve and union to facilitate servicing must be tted to the gas inlet pipe work of the heater. The gas supply must be completed in solid pipe work and be adequately supported. Heaters suspended by drop rods, straps or chains must have a exible connection as the nal link between the gas supply pipe work and the heater. Sucient slack must be left in the connection to take account of normal movement of the heater.
Warning
When completing the nal gas connection
to the heater do not place undue strain on
the gas pipe work of the heater.
NVS units feature a closed combustion circuit and have an internal exhaust fan, mounted downstream of the heat exchanger, to evacuate the products of combustion and draw in air for combustion. The air heater must be connected to the ue system that is provided by Powrmatic Ltd. Several congurations of ue and combustion air ducts are available.
The ue must terminate in a freely exposed position and be sited to prevent the products of combustion entering any opening in a building in such concentration as to be prejudicial to health or a nuisance
Type B22 Installation.
Combustion air entry
(fitted with inlet grille and inlet bend (not shown))
1.3.4.1 Service Pipes
The local gas undertaking should be consulted at the installation planning stage in order to establish the availability of an adequate supply of gas. An existing service pipe must not be used without prior consultation with the local gas undertaking. The inlet gas pressure under running conditions must not be less than 17.5mb.
1.3.4.2 Meters
An existing meter should be checked, preferably by the gas undertaking, to ensure that the meter is adequate to deal with the total rate of gas supply required by all connected equipment.
1.3.4.3. Installation Pipes
Installation pipes should be tted in accordance with IGE/ UP/2. Pipe work from the meter to the air heater must be of adequate size. Do not use pipes of a smaller size than the inlet gas connection of the heater. The complete installation must be tested for soundness as described in the above Code.
Type C32 Installation.
Combustion air entry
(fitted with inlet grille and inlet bend (not shown))
Combustion air socke t
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
page no. 11 of 36
Page 12
Type C12 Installation.
Combustion air socket
1.3.6 Ventilation Requirements
Type B ued installations.
Where NVS heaters are installed within the heated space (ie not in a plant room or an enclosure) and having
a building design air change rate of greater than 0.5/h, additional provision for ventilation is not required.
If the building design air change rate is less than 0.5/h, additional provision for natural or mechanical ventilation is required. These being:
Natural Ventilation:
Grilles having a free area of at least 2cm² per kW of rated heat input shall be provided at low level i.e. below the level of the heater ue connection.
Mechanical Ventilation:
Must ensure that the space air change rate is at least 0.5/h, must be of the ‘input’ type and interlocked to ensure the heaters cannot work if the input system is not working.
Type B ued installations.
Where NVS heaters are installed in a plant room or an enclosure (ie not within the heated space)
having combustion air drawn directly from the room and connected to a ue that evacuates the products of combustion directly from the room additional provision for natural or mechanical ventilation is required. These being:
Natural Ventilation:
There must be permanent air vents communicating directly with the outside air, at high level and at low level.
Plant Rooms
Low level (inlet) 4cm²/kw of total rated net heat input High level (outlet) 2cm²/kw of total rated net heat input
Enclosures
Low level (inlet) 10cm²/kw of total rated net heat input High level (outlet) 5cm²/kw of total rated net heat input
Mechanical Ventilation:
The minimum ow rate of ventilation shall be 4.14m³/h per kilowatt of total rated heat input.
Type C ued installations.
Where NVS heaters are Installed within the heated space (ie not in a plant room or an enclosure) having
combustion air ducted to the appliance and combustion products ducted to the outside air, NO additional
provision for the supply of either combustion air or for combustion products dilution or additional provision for the supply of air is necessary.
Type C ued installations.
Where NVS heaters are Installed in a plant room or an enclosure (ie not within the heated space) having
combustion air ducted to the appliance and combustion products ducted to the outside, air vents shall be provided and be permanently open.
To room or internal space
Low level (inlet) 10cm²/kw of total rated net heat input High level (outlet) 10cm²/kw of total rated net heat input
Direct to outside air
Low level (inlet) 5cm²/kw of total rated net heat input High level (outlet) 5cm²/kw of total rated net heat input.
Type C
12 or C32 Installation (these refer to section 2.2
of these instructions)
Air vents shall be permanently open. Figures are for heaters in plant rooms or enclosures ONLY In all cases gures are per heater installed. For multi heater installations the appropriate values for each heater
must be added together.
In the
heated
space
Free area grille cm²
Ventilation is to a
room or internal
space
Low level
grille. Free
area cm²
High level
grille. Free
area cm²
Ventilation is to a
outside air
Low level
grille. Free
area cm²
High level
grille. Free
area cm²
NVS
Input kW
Type B22 Installation (these refer to section 2.2 of these
instructions)
Air vents shall be permanently open. In all cases gures are per heater installed. For multi heater installations the appropriate values for each heater
must be added together
In the
heated
space
Low level
grille. Free
area cm²
In a plant room,
ventilation to
outside
Low level
grille. Free
area cm²
High level grille. Free
area cm²
In an enclosure,
ventilation to
outside
Low level
grille. Free
High level
grille. Free
area cm²
area cm²
30 29.02 58.0 116.0 58.0 290.0 145.0 n/a 290.0 290.0 145.0 145.0 60 59.22 118.4 236.8 118 .4 592.2 296.1 n/a 592.2 592.2 296.1 296.1 90 86.74 173.5 295.0 173.5 867.4 438.2 n/a 867.4 867.4 438.2 438.2 140 137.95 275.9 551.8 275.9 1379.5 689.8 n/a 1379. 5 1379. 5 489.8 489.8
page no. 12 of 36
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 13
1.3.7 Air Distribution System
should be suitably lined with a re-resisting material.
Where single NVS/F units are required to cover a large oor area, and in buildings with high roof or ceiling heights Calecon thermal economiser units should be tted to ensure even heat distribution and minimise stratication.
Care should be taken to avoid impeding the air throw with racking, partitions, plant or machinery etc. Various outlet congurations are available as optional extras to modify the air throw pattern to suit particular site conditions.
For ducted units all delivery and return air ducts, including air lters, jointing and any insulation or lining must be constructed entirely of materials which will not contribute to a re, are of adequate strength and dimensionally stable for the maximum internal and external temperatures to which they are to be exposed during commissioning and normal operation.
Where inter-joist spaces are used as duct routes they
1.3.7.1 NVS C Ducting Requirements
Model Air Volume m³/h
Maximum Duct
Resistance Pa
A full and unobstructed return air path to the air heater(s) must be provided.
If the air heater(s) is installed in a plant room the return air intake(s) and the warm air outlet(s) from the heater(s) must be fully ducted, into and out of the plant room to avoid interference with the operation of the heater.
The openings in the structure of the plant room through which the ducting passes must be re stopped.
Care must be taken to ensure that return-air intakes are kept clear of sources of smells and fumes, and where there is any possibility of pollution of the air by dust, shavings etc., precautions must be taken to prevent contamination.
If necessary suitable barrier rails should be provided to prevent any combustible material being placed within 900mm of the outlets.
NVxCCF heater unit
NVS C
heater unit
NVS30C 2808 250 NVS60C 5616 250 NVS90C 8424 200 NVS140C 13104 285
1.3.7.2 NVS D Pressure Drop Across Heat Exchanger
250
NVS 60
200
150
NVS 30
100
Pressure Drop (Pa)
NVS 90
NVS 140
50
0
0
1
2 3 4
5
6
Air Volume (m³/s)
7 9
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
8
10 11 12
page no. 13 of 36
Page 14
2.1 Fitting the Unit
C
B
A
Front View
D D
E
Distance from outside of heater to closest obstacle Distance
R/H Side Views
A RHS Clearance (when viewed at front of heater) mm 1000
B LHS Clearance (when viewed at front of heater) mm 200
C Top of heater mm 200
D Rear of heater (dependent on ue system) mm 600
NVS30F - 40F mm 2500-3000
E Recommended mounting heights (oor level to underside of unit)
For multi air heater installations the following minimum distances between units must be observed
Between units, side to side mm 3000
Between units, back to back mm 3000
page no. 14 of 36
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
NVS60F - 140F mm 3000-5000
NVS D mm N/A
Page 15
2.1.1 General
Before installation, check that the local distribution conditions, nature of gas and pressure, and adjustment of the appliance are compatible.
The air heater must be installed in accordance with the rules in force and the relevant requirements of any re regulations or insurance company's requirements appertaining to the area in which the heater is located, particularly where special risks are involved such as areas where petrol vehicles are housed,
reducing noise levels is important the heater should be insulated from the structure by installing it on suitable anti-vibration mountings. In all such cases and when the heater is suspended it is essential that all gas, duct, and electrical connections to the heater are made with exible connections to maintain continuity of connection.
2.1.4 Air Distribution System
2.1.4.1 General
Where cellulose spraying is carried out, in wood working departments etc.
NVS/C units are supplied with a centrifugal fan.
2.1.2 Fitting space requirement
For NVS/D units the normal air ow direction is from right to left when viewing the heater from the burner/controls end with the fan unit upstream.
The minimum clearances must be observed for installation and servicing.
Any combustible material adjacent to the air heater and the ue system must be so placed or shielded as to ensure that its temperature does not exceed 65 °C.
When NVS modular components are used in conjunction with the heater each component must be individually supported.
2.1.3 Suspending the heater
The air heater may be installed either: a) suspended from suitable vertical drop rods. b) on specically designed cantilever brackets from a non combustible wall. c) on a level noncombustible surface. The surface must not extend past the front edge of NVS/F heaters.
The method of installation must be capable of adequately supporting the weight of the unit (See section 1.2) and any ancillary equipment. Before installing the heater the existing structure must be inspected to ensure it is suitable. All supports should be protected against the eects of rust or corrosion.
Raise the heater up to the point of installation using suitable and safe means and connect to the means of suspension.
NVS/D and NVS/C models are designed for use with duct work to more precisely dene the point of air delivery, and /or provide ducted return air or ducted fresh air inlet. All ducting must be independently supported of the air heater.
Joints and seams of supply ducts and joints between NVS ancillary components must be securely fastened and made airtight using appropriate sealants or sealing strips. If required the duct work should be insulated to reduce heat loss.
2.1.4.2 Noise Reduction
Ducting should be connected to the heater spigots via an airtight exible coupling of noncombustible material. Before tting the coupling it must be ensured that a minimum clearance of approximately 15mm will be maintained between the ends of the ducting and the heater spigots.
Sound attenuators may be tted in inlet and outlet ducts to reduce airborne fan noise. Materials used in outlet sound attenuators must be capable of withstanding 100°C air temperature without any deterioration.
2.1.5 Room Thermostat Siting
The room thermostat should be tted at a point which will be generally representative of the heated area as far as temperature is concerned. Draughty areas, areas subjected to direct heat e.g. from the sun, and areas where the air movement is relatively stagnant e.g. in recesses, should be avoided. The thermostat should be mounted approximately 1.5m from the oor.
Any room thermostat, frost thermostat, time clock etc. must be suitable for switching 230V, 5A and must be of the 'snap action' type to minimise contact bounce. For electrical connections of external controls see the accompanying wiring diagram.
Threaded drop rods must have lock nuts tted that are tightened down onto the 10mm xings in the heater. If
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
page no. 15 of 36
Page 16
2.2 Flue/Combustion Air Duct System
The minimum distance between surfaces of the ue pipe and any surfaces made from combustible materials is 300mm.
If it is necessary for the ue pipe to pass through a structure made from combustible materials a metal sleeve must be used so that the minimum clearance of 300mm is maintained.
The ue and combustion air ducts supplied with the heater are capable of withstanding their own weight over the allowable ue lengths. Wall bands and bracing brackets, or equivalent, must be used to provide lateral stability and should be used at centres not exceeding 2.5 metres.
All models are supplied as standard with a rear ue outlet and the ue outlet and combustion air sockets temporarily tted.
2.2.1. Fitting Flue/Combustion Air Sockets
1. Apply a bead of silicon sealant around the face of the ange on the exhaust fan outlet tube that can be seen from the outside of the heater. Place the ue socket on the outside of the heater to mate with this ange and clamp the two anges together, on either side of the heater panel using the screws provided. Ensure that the silicon sealant has sealed between the two anges.
- 300mm below an opening e.g. window, air brick etc.
- 200mm below eaves or gutter.
- 300mm from an internal or external corner.
- 1200mm from a surface facing the terminal.
- 1500mm vertically from another terminal on the same wall.
- 300mm horizontally from another terminal on the same wall.
- 2000mm from ground level.
2.2.3. Installation of Flue System
Note: A terminal guard, as supplied by Powrmatic Ltd, must be tted to horizontal ue terminals.
Notes for all systems. i) Final overall length of adjustable disconnection piece must be between 360 - 415mm.
ii) 45° osets may be used if required. Each set is equivalent to 0.5m of ue length. iii) Where NVS heaters are used in clean environments it is permissible to take the combustion air directly from the heated space. The supplied mesh intake plate, must be tted to the combustion air inlet on the rear of the heater.
2. If ducted combustion air is not required (see Section
1.3.7.) t the mesh inlet plate behind the unused combustion air inlet hole.
3. Apply silicon sealant and ret blanking plates as required to seal unused panel holes.
2.2.2. General Requirements
See Figures 1a to 2b for the dierent types of ue installation. In all cases the ue outlet socket must be connected via the provided ue system to outside air.
The maximum permitted length of ue system is 6m, or 12m if the ue outlet only is used. If an oset is required two sets of 45° bends should be used each set being equivalent to 0.5m of ue length. 90° bends may be used but each set will be equivalent to 1.0m of ue length.
All outer joints must be nished with the provided locking bands. A smear of silicon grease to the inside of sockets will assist in tting components together. All ue and combustion air ducts must be supported independently of the air heater. The ue or ue/combustion air terminal must not be installed so as to be less than:
2.2.3.1. Horizontal System - Rear Outlet
Note: If the outlet is required to the side of the unit 90° bends may be tted directly onto the inlet/outlet spigots on the heater.
1. Locate the position of the ue terminal, allowing for a slight gradient running down from the heater to the terminal of 2° - 3° and cut a hole to suit.
2. Fit the ue terminal, securing via the wall plate and weather with silicon sealant or similar.
3. Fit the twin to concentric adaptor to the terminal section and extend the ue and combustion air ducts to the heater using straight lengths. Fit an adjustable length prior to the unit, to facilitate ue disconnection for servicing. Extend the adjustable lengths to make the nal connection to the appropriate heater inlet/outlet spigots.
4. Ensure that internal silicon sealing rings are in place and that all tubes are pushed fully home. Secure concentric lengths with the locking bands provided.
5. A suitable 90° elbow should be tted to the ue condense drain pipe which in turn is connected to the
condense trap. See 2.2.4
page no. 16 of 36
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 17
Fig 1a Individual system - horizontal
Type C installation
Fig 1b Individual system - vertical
Type C installation
Flue socket
Lengths
Adjustable length
Combustion air socket
Maximum 6m, Minimum 980mm
Note: A terminal guard may be required.
Single to twin adaptor
Combustion air duct
Terminal
2.2.3.2. Vertical System - Rear Outlet
1. Locate the position of the ue terminal cut a hole in the roof to suit.
2. Fit the ashing and the ue terminal so that the lower edge of the outer case is over the top of the ashing. Weather with silicon sealant or similar.
Fit a condensate drain length into the ue socket on the heater and an equivalent straight length onto the combustion air socket.
3. Fit the twin to concentric adaptor to the terminal section and then extend down to the heater using straight lengths. Fit adjustable lengths as the nal connection pieces, to facilitate ue disconnection for servicing.
Extend the adjustable lengths to make the nal connection but do not exceed the maximum extended length so as to maintain joint integrity.
Extend the drainage o take of the condensate drainage length to a suitable gully or drain.
Single to twin adaptor
Lengths
e
h
Adjustable lengths
Condensate drain length
Flue socket
Lengths
200mm Length
90° Bend
Combustion air socket
Terminal
Flashing
*
*
*
*
Adjustable length
200mm Length
Combustion air socket
Terminal
Flashing
6m maximum
Adjustable length
200mm Length
90° Bend
*
*
*
Maximum 6m Minimum 80Ø - 1480mm
6m maximum
100Ø - 1560mm 130Ø - 1860mm
*
*
*
*
2.2.3.3. Internal Combustion Air System
1. Complete the run of ue sections from the terminal spigot to the ue outlet socket of the heater generally as described in 2.2.3.1. and 2.2.3.2., ensuring that the internal silicon sealing rings are in place.
Fig 2a Exhaust only system - horizontal
Type B installation
OPTION 1 Combustion air entry
(fitted with i nlet g rille)
Flue outlet
Adjustable length
Lengths
Terminal
4. Ensure that internal silicon sealing rings are in place and that all tubes are pushed fully home. Secure concentric lengths with the locking bands provided.
Note: A terminal guard may be required.
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
OPTION 2 Combustion air entry
(fitted with inlet grille and inlet bend (not shown))
12m maximum, Minimum 980mm
page no. 17 of 36
Page 18
Fig 2b Exhaust only system - vertical
Type B installation
Terminal
If the condensate outlet from the heater is blocked for any reason e.g. freezing, and consequently condensate builds up in the heater a oat switch will operate and shut the heater down.
The outlet from the trap must be run to a local drain point.
Flashing
Maximum 12m
Lengths
Adjustable length
Condensate drain length
Flue socket
Combustion air entry
(fitted with inlet grille
80Ø - 1480mm 100Ø - 1560mm 130Ø - 1860mm
2.2.4. Condense Length
Note: NVS heaters are NOT tted with an internal trap and must be tted with an external trap similar to drawing that is shown
below. The trap can be fabricated using standard domestic 32mm waste water ttings. Ensure that the dimensions shown are adhered to.
As NVS heaters will generally be mounted at high level drainage under gravity will be adequate. Where this is not possible a proprietary condensate pump should be used. Install following the instruction provide with the condensate pump.
Notes: Trap must be positively connected to both the heater andthe ue condense outlets.
Two separate traps may be used if required. Access points and/or unions must be included to allow for trap cleaning.
The approximate amount of condensate the units will produce per hour is:
Natural Gas G20
Model l/h l/m
NVS30 2.3 0.038 NVS60 3.4 0.056 NVS90 6.0 0.098 NVS140 8.8 0.147
Propane LPG
Fit the condensate drain trap to the drain pipe at the rear of the heater (15mm). Connect the condense drain length (or condense drain Tee) (15mm) to the same trap assembly. See Fig 3. The traps must be lled with water after installation and before the heater is commissioned.
page no. 18 of 36
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Model l/h l/m
NVS30 1.2 0.020 NVS60 1.7 0.028 NVS90 3.0 0.050 NVS140 4.4 0.073
Where it is necessary to route some, or all, of the drain pipe external to the building precautions must be taken to prevent the condensate freezing in low temperature conditions. The drain pipe must be insulated and, if necessary, tted with a trace heating cable.
Page 19
2.3 General Identication of Electrical Items
HIGH LIMIT RESET
PRESSURE SWITCH
BURNER RESET
(ON/OFF UNITS ONLY)
* PACTROL BOARD
EXHAUST FANGAS VALVE
** BRAHMA BOARD
(HI/LO & MODULATION ONLY
2.4 Electrical Cable Installation
2.4.1 Electrical Connections
Warning: THIS APPLIANCE MUST BE EARTHED.
Wiring external to the air heater must be installed in accordance with the I.E.E. Regulations for Electrical Installations and any local regulations which apply. Wiring should be completed in exible conduit.
Heaters are for use with 230V, 1N, 50Hz supplies.
The method of connection to the main electricity supply must:-
- facilitate the complete electrical isolation of the heater(s) that will prevent remote activation of the heater during servicing.
- be in a readily accessible position adjacent to the heater(s).
- serve only the heater(s).
- have a contact separation of at least 3mm in all poles. See the wiring diagram for the heater electrical
connections.
All units, (with the exception of units supplied with a centrifugal fan/silencer duct section) are fully prewired and only require nal connections for the incoming mains supply and completion of the control circuit (230V).
Warning: Lockout reset is by a switched Neutral to the controls in the heater.
The electrical supply must be run to a point adjacent to the heater and be suitably terminated to provide an isolation point that will prevent remote activation of the unit during servicing.
Reference must be made to Section 1.2 to ascertain the electrical loading of the unit(s) being installed so that cables of adequate cross-sectional area are used for the electrical installation. The length of the conductors between the cord anchorage and the terminals must be such that the current carrying conductors become taut before the earth conductor if the cable or cord slips out of the cord anchorage. All external controls must be of an approved type.
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
page no. 19 of 36
Page 20
NVS/D models supplied less fan must be electrically interlocked to the air movement system so that this is started in the same manner as the air heater fan would be viz. A connection from heater terminal number 9 must be
2.4.2 Initial Wiring Instalation
Key A = 2 core and earth B = Powrtrol = 4 core and earth Powrtrol RR= 6 core and earth MC200 On/O = 6 core and earth MC200 Hi/Lo = 7 core and earth MC200 Mod = 8 core and earth C= 4 core and earth D= Screened 2 core (MC200 models only)* * (screen must be grounded only at the MC200, See
instructions supplied with controller for wiring sizing, Max. 100m)
2.4.3 External Wiring
made to one side of the fan motor contactor coil, the other side of the coil being connected to Neutral. The fan motor electrical supply must not be taken direct from the internal wiring of the NVS heater.
The wiring terminals are located inside the electrical box behind the side door which rstly has to be opened.
The mains supply connections are via a Hylec terminal block. Control Circuitry connections are via a 30A numbered terminal strip. They are:
terminal 1 - 230V Heat Demand terminal 9 - 230V Main Fan Only terminal 13 - Burner reset - Neutral Switch terminal 14 - Lockout indication 230V Output terminal 16* - 0V (modulating negative) terminal 17* - 0 - 10V (modulating) OR 230V High
Used where required
Fire *
2.4.4 External Fuses
Model
NVS30 NVS60 NVS90 NVS140
F - Free Blowing
Unit
Fuse Rating (A)
2 5 3 16 5 16 7 25
'C' - Centrifugal
Unit
Fuse Rating (A)
t1
t9
t13
t14
E
N
L
Note: To achieve maximum system eciency it is
recommended that NVx units are controlled by an MC200 Fuel Saver unit. Simple room
page no. 20 of 36
thermostat and thermostat/time clock control systems will not provide optimum system eciency and fuel savings.
Wiring drawings and instructions are supplied with the respective controller.
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 21
COMPONENT LIST
A. Ignition Sequence Controller
B. High Limit Thermostat
C. Neon Indicator CO430A A
D. Fan Command Module
E. Air Pressure Switch LGW3 A2
F. Ignition Electrode
G. Rectification Probe
I. Internal Lockout Reset Button
J. Modulating Driver Board
K. Jox Relay
2.5 Wiring Diagrams
NVS 30-140 Axial Fan Crossow Units
NV CONTROL PANEL
NV0162100 / P25 / NVS
B
C
Blu 0.5
r
B
e
l
Y
21 C
Or
W
h
r
B
l
B
u
r
O
D
Br
Gr/Yel
Gr/Yel
Br 1.5
LL
LL
EEEENN
Br
Blu
Blu 1.5
NN
Blu
*
Br
Blu
Red
2233445566
11
Blu
Br
Blu 1.5
7777888899
A
r
B
l
B
u
13 14 15
1
l
B
u
r
B
e
l
Y
W
20
19
I
18
18
C
O
N
C
N
E
Blu 1.5
Blu 1.5
*
Wh
Wh
Br 1.5
Br 1.5
*
99
Yel
BluWhBl
11 11
12 12
10 10
h
8 9 10 11 12
l
u
B
W
h
l
B
k
r
O
l
B
u
e
l
Y
1 2 3 4 5 6 7
*
*
*
Or
13 13
14 14
15 15
16 16
17 17
18 18
JT 1 JT 2
1
1
K
Gr/Yel
J6/CON 6 J7/CON 7
16171819
1
Vi
Blk
C
O
M
N
O
N
C
F G
= Brahma NDM32
= Pactrol P25
1 2 3 4
1
If HEAT ENABLE is
required from the
modulating voltage (e.g. for
BMS control) then link T18
to T1.
e
0
-
1
0
v
r
o
i
H
-
i
F
r
0
v
c
t
o
k
u
L
o
t
e
s
e
R
a
F
n
a
l
n
b
E
e
a
n
l
b
e
e
a
t
H
E
L
A
R
T
U
E
I
L
E
V
H
T
R
A
Wiring Legend
Connections made by Control
board Assembler
Connections made by Final
Assembler
Connections made by
Installer
r
B
0
.
7
5
r
G
/
e
l
Y
0
.
7
5
5
r
B
0
.
7
145030846 (P25) / 145030844 (NDM32)
142403609
143100661
142403605
146522174
142423002
142423003
143070274
142400303
PART NO.
143000816
5
.
7
5
r
G
/
e
l
Y
0
l
B
u
0
.
7
5
EXHAUST
FAN
l
B
u
0
.
7
5
l
0
.
7
5
.
7
5
MAIN FAN(S)
E
r
B
0
.
7
e
r
G
/
Y
l
B
u
0
EXTERNAL CONTROLS
N
230V 50Hz
MAINS SUPPLY
Additional fan on
NV/S 90 onwards
5
0
.
7
5
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
7
l
B
u
0
.
r
G
/
e
l
Y
r
B
0
.
7
5
GAS VALVE
page no. 21 of 36
Page 22
77
EE
Additional Wiring for Optional Items
5
6
NV Panel Terminals
7
1
1
5
887
8 7 15 16 17
u
l
r
B
B
6
1
1
k
l
B r O
1 2 3 5 6
Interconnecting Wiring: Powrmatic MC200
7
8
1
1
7
8
18
1
1
d e
R
i V
On/O Burner
MC200 fuelsaver
Modulating Burner
Hi/Lo Burner
GAS VALVE HEAD, HI-LO 142466402
J
Or
7
Yel
8
GAS VALVE HEAD, MODULATING 142466403
ON
1
2
+- com+
61 62 63 64 65 66
Blk
3 core cable
7
8
Br 0.75
Blu0.75
Gr/Yel 0.75
Red
17 17
1
M
N
2
O
E
C
IN
S
Hi/Lo Burner
1
M
N
2
O
E
C
IN
S
t
+
-
v
v
0
0
-1
-1
0
0
i
u
t
o
e
t H
k
s
a
c
e
e
o
R
H
L
MC200 fuelsaver
t
i
+
-
u
t
v
v
o
e
0
0
-1
-1
0
0
t H
k
s
a
c
e
e
o
R
H
L
i
o
o
t
t H
t L
t L
u
a
a
a
In
In
O
e
e
e
H
H
H
t
t
u
t u
O
u
In
O
n
n
a
a
F
F
E
N
O L
L
LN911413
i
o
o
t
t H
t L
t L
u
a
a
a
In
In
O
e
e
e
H
H
H
t
t
u
t u
O
u
In
O
n
n
a
a
F
F
E
N
O L
L
LN911413 17
page no. 22 of 36
Modulating Burner
MC200 fuelsaver
t
i
i
+
-
1 N E S
v
M
0
2
O
-1
C
IN
0
u
t
v
o
e
0
-1 0
t H
k
s
a
c
e
In
e
o
R
H
L
o
o
t
t H
t L
t L
u
a
a
a
In
O
e
e
e
H
H
H
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
t
t
u
t u
O
u
In
O
n
n
a
a
F
F
E
N
O L
L
LN9114131617
Page 23
2.6 Commissioning and Testing
2.6.1. Electrical Installation
Checks to ensure electrical safety must be carried out by a qualied person.
2.6.2. Gas Installation
For new installations, the whole of the gas installation, including the meter, should be inspected and tested for soundness and purged in accordance with the recommendations of IGE/UP/1 (Edition 2) or IGE/UP/2A as appropriate.
2.6.3. Air Distribution System
The system should be checked to ensure that the installation work has been carried out in accordance with the design requirements.
Particular attention should be given to the correct arrangement of delivery ducts and registers, return air ducts and grills and general adequacy of return air paths.
1. Switch on the electrical supply at the isolator.
2. If the High limit indicator light comes on press the limit reset switch on the front panel. The Red indicator light will go out and the ignition sequence will commence. After a delay of approximately 45 seconds the ignition spark will be generated and the main gas valves energized. The burners will then light.
3. If the burners fail to light the control box will complete a further four ignition attempts. If at the end of ve attempts the burners have still not lit the control box will go to lockout and the red indicator light, internal and remote lockout lights will be illuminated. To restart the ignition sequence depress the illuminated reset button for about 1-2 seconds.
4. SHUT OFF Set the external controls to OFF or MIN.
2.6.6 Adjustments
Nominal CO values are given for guidance in the following table:
For NVS/D units ensure that the duct work is balanced so that the specied motor running currents are achieved See section 1.2
2.6.4. Checks before lighting the Air Heater
The following preliminary checks should be made before lighting the heater(s)
a) Ensure that the ELECTRICAL supply to the heater is switched OFF.
b) Check that all warm air delivery outlets are open. c) Check that all external controls are calling for heat. d) If an MC200 or Powrtrol is being used ensure that the
control is set to winter operation.
2.6.5. Lighting the Air Heater
NOTES: On initial lighting of the heater(s), it may take some time to purge the internal pipe work of air.
IMPORTANT: The internal pipe work of the appliance has been tested for soundness before leaving the factory. After establishing the main burners test round
the gas inlet connection using a leak detection uid.
Model 30 60 90 140
Natural Gas G20
High Fire CO %
Low Fire CO %
Propane G31
High Fire CO %
Low Fire CO %
7.5 7. 3 7.9 8.9
3.72 3.1 3.6 3.9
7.3 7.9 8.5 8.1
4.1 3.8 3.7 4.1
2.6.6.1. Burner Gas Pressures
This is set for the required heat input before despatch. In the case of Hi/Lo and Modulating units both high and low pressures are set. Pressures should be checked in the following manner.
2.6.6.1.1. Standard On/O Units
1. Set external controls to ensure that the main burner is o. Open the side access door. Connect a pressure gauge to the burner pressure test point on the multifunctional control.
2. Set external controls so as to turn on the main burner. Compare the measured burner gas pressure to that
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
page no. 23 of 36
Page 24
stated on the data plate. If necessary adjust the burner gas pressure by turning the regulator screw anticlockwise to decrease the pressure, or clockwise to increase the pressure.
3. In addition it is advisable to check the gas rate using the gas meter dial pointer. Ensure that no other appliances supplied through the meter are in operation.
4. If required, after checking or setting the burner pressures, the CO content in the ue gases can be checked by sampling in the rst section of ue tted to the ue outlet of the unit. Nominal CO values are given for guidance in the Table at the bottom of the previous page.
2.6.6.1.2. High/Lo Regulator
Cover Lever point
Hexagonal adjustment screw for maximum pressure setting
Internal slotted adjustment screw for minimum pressure setting
5. Turn o the main burner and disconnect the pressure gauge and replace the sealing screw. Turn on the main burner as above and test for gas soundness around pressure test joint using a leak detection uid e.g. soap solution.
Governor adjustment screw under cover cap (Honeywell VR4605AB1027)
Fitted to the NVS 30, 60, 90
Governor adjustment screw under cover cap (Honeywell VK425AB1007)
1. Set external controls to ensure the main burner is o. Open the side access panel. Connect a pressure gauge to the burner pressure test point on the multifunctional control.
2. Set external controls to turn on the main burner and maintain high re. Compare the measured burner gas pressure to that stated on the data plate. In addition it is advisable to check the gas rate using the gas meter dial pointer ensuring that no other appliances supplied through the meter are in operation.
3. Repeat 2 above with external controls set to maintain low re.
4. If it is necessary to adjust either the high re or low re pressures proceed as follows after levering o the plastic cover from the Hi/Lo regulator.
Note: High re setting must be adjusted rst after which the low re setting can be set. Any adjustment of the high re setting alters the minimum setting.
Maximum Setting
With the controls set to high re use an adjustable or 8mm spanner to turn the adjustment screw for high re pressure, clockwise to increase and counter-clockwise to decrease, until the required pressure is obtained. Turn the burner On and OFF several times to check the pressure setting and then turn o.
Fitted to the NVS 140
page no. 24 of 36
Minimum Setting
Disconnect electrical connection of high/low regulator and turn burners back on and wait until the burner pressure has stabilized. Use a screwdriver to turn the slotted adjustment screw for low re pressure, clockwise to increase and counter-clockwise to decrease, until the required pressure is obtained. Reconnect high/low regulator and check high re pressure. Repeat both steps if necessary and then replace cover cap.
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 25
5. Turn o the main burner, disconnect the pressure gauge and replace the sealing screw. Turn on the main burner and test for gas soundness around pressure test joint using a leak detection uid. Replace access panel.
2.6.6.1.3. Modulating Regulator
Shaft
Cap
Adjustment nut (7mm) for maximum pressure setting
Adjustment nut (9mm) for minimum pressure setting
‘O’ ring
6.3mm AMP terminals
to decrease until the required pressure is obtained. Reconnect modulating regulator and check high re pressure, readjust if necessary.
Maximum Setting
Disconnect electrical connection of modulating regulator and turn burners back on and wait until the burner pressure has stabilized. Push shaft gently downwards to the maximum adjustment screw and hold there. Turn 7mm adjustment nut for high re pressure, clockwise to increase and counter-clockwise to decrease, until the required pressure is obtained. Release shaft. Repeat both settings if necessary and then replace cover cap.
5. Turn o the main burner, disconnect the pressure gauge and replace the sealing screw. Turn on the main burner and test for gas soundness around pressure test joint using a leak detection uid. Replace access panel.
2.6.6.1.4. Modulating Interface Board
1. Set external controls to ensure that the main burner is o. Open the side access panel. Connect a pressure gauge to the burner pressure test point on the multifunctional control.
2. Set external controls so as to turn on the main burner and maintain high re. Compare the measured burner gas pressure to that stated on the data plate. In addition it is advisable to check the gas rate using the gas meter dial pointer ensuring that no other appliances supplied through the meter are in operation.
3. Repeat 2 above with external controls set to maintain low re.
4. If it is necessary to adjust either the high re or low re pressures proceed as follows after removing the plastic cover from the Modulating regulator.
Note: Minimum re setting must be adjusted rst after which the high re setting can be set. Any adjustment of the minimum re setting alters the maximum setting.
Modulatiing Regulator
Minimum Setting
Disconnect electrical connection of modulating regulator and turn burners back on and wait until the burner pressure has stabilized. Turn 9mm adjustment nut for low re pressure clockwise to increase and counter-clockwise
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Modulating Interface Board
page no. 25 of 36
Page 26
The MIB interfaces between a 0-10VDC control signal and the modulating regulator. The following are applicable to this application.
1. The setting of the slide switches 1 & 2 should both be to OFF.
2. Potentiometer P1 (Default setting 100%) The control current of the V7335A is controlled by P1, varying between 50% and 100% of the input signal. E.g.
-When P1 is set at 100% (fully clockwise) maximum power (165mA @ 22VDC) is provided to the modulation coil with a 10VDC input control signal.
-When P1 is set at 50% (fully anticlockwise) maximum power (165mA @ 22VDC) is provided to the modulation coil with a 5VDC input control signal.
3. Potentiometer P2 Controls the minimum drop-out voltage between 0% and
40% E.g.
- When P2 is set at 0% the drop-out voltage with an input control signal of 0-10V-DC is 0.3V-DC.
- When P2 is set at 40% the drop-out voltage with an input control signal of 0-10V-DC is 4.0V-DC.
4. Potentiometer P3 (Default setting 100%) Controls the maximum hold-in voltage. Its proportional
value is added to the P2 setting E.g.
- When P2 is set at 0% and P3 is set at 5%, the hold-in voltage of the burner relay is adjustable between 5% and 100% of the input control signal. If the input control signal is set at 0-10V-DC the hold-in voltage of the relay is 0.5V­DC.
- When P2 is set at 40% and P3 is set at 5%, the hold-in voltage of the burner relay is adjustable between 45% and 100% of the input control signal. If the input control signal is set at 0-10V-DC the hold-in voltage of the relay is 4.5V­DC.
The following table shows the relationship between P2 and P3 settings.
5 10 20 30 40 50 60 70 80 90 100
P2%
0 10 20 30 40
Drop Out
Volts
0.3 0.5 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
1.0 1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
2.0 2.5 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
3.0 3.5 4.0 5.0 6.0 7.0 8.0 9.0 10.0
4.0 4.5 5.0 6.0 7. 0 8.0 9.0 10.0
2.6.6.2. Flame Current
1. To measure the ame current connect a multimeter capable of measuring micro amps as shown in the following diagram.
P3%
Hold-in Voltage
2. Minimum current reading is 0.5µA and normal value should be 1.5µA or higher.
2.6.6.3. Air Heater Controls
1. Close the gas service tap and ensure that the gas valve is heard to close within 1 second and that the lockout light is illuminated. Note that the heater may attempt ve re­ignitions before going to lockout. Open the gas service tap and reset the unit from lockout.
Flame Current Measurement
page no. 26 of 36
2. Check that the room thermostat and all automatic controls are operating satisfactorily.
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 27
2.6.7. Limit Thermostat
Thermostat settings:-
Limit
NVS 15-140SF 90°C
the air heater and associated controls. Adjust the automatic controls to those values required by the User.
Finally, advise the user or purchaser that, for continued ecient and safe operation of the air heater, it is important that servicing is carried out annually.
2.6.8. Handing over the Air Heater
Hand these instructions to the user or purchaser for retention and instruct in the ecient and safe operation of
2.7 Servicing
WARNING: Always switch o and disconnect electricity supply and close the gas service valve before carrying out any servicing work or replacement of failed components.
NOTE: If a suspended air heater is to be serviced do not lean ladders against the heater.
Ensure that an access tower or equivalent is used.
NOTE: The access door to the controls section may be removed to improve access.
Open the door to 90°, remove the earth cable at the bottom, and then lift the door vertically
upwards to disengage the hinge plates. Ret in reverse order. Ensure that the earth cable is
retted.
In the event that the premises are not yet occupied turn o the gas and electricity supplies and leave instructional literature adjacent to gas meter.
from the top of the gas control valve assembly.
3. If required remove the manifold by removing the four screws securing it to the burner assembly.
4. Remove the two screws that secure the top of the burner assembly to the bulkhead and lift out burner assembly.
5. Using a sti brush, not a wire brush, brush the burners to dislodge accumulated deposits. Inspect the burners both internally and externally to ensure that they are clean. Examine the injectors and if damaged or deteriorated, replace with new ones of the correct size and marking. If deemed necessary, clean the injectors. Do not broach out with wire.
6. Reassemble the injectors, manifold and burners in reverse order to that above.
2.7.1. General
2.7.3. Ignition and Rectication Electrodes
Full maintenance should be undertaken not less than once per year by a qualied person. After any servicing work has been complete, or any component replaced, the air heater(s) must be fully commissioned.
2.7.2. Main Burner Assembly Removal
1. Ensure that the gas service valve is turned OFF and then unscrew the union nut situated immediately downstream of it.
2. Disconnect the spark and rectication leads from the control box and remove the electrical plug connections from the top of the gas control valve assembly.
2. Disconnect the spark and rectication leads from the electrodes and remove the electrical plug connections
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Inspect the electrodes, making sure that they are in a sound and clean condition. In particular check that the ignition electrode is clean and undamaged. Check that the spark gap is 2.5mm and that the rectication probe is 10 ­12mm forward of the burner.
Ignition Electrode Spark Gap
Note: The ignition electrode is located at the bottom of the burner assembly, the rectication electrode is located at the top of the burner assembly.
2.5mm
page no. 27 of 36
Page 28
2.7.4. Heat Exchanger
2.7.6. Condense Drain & Trap
Whilst the main burner assembly is removed from the unit, check that the primary sections that the burners re into are clean.
2.7.5 Main Fan Assembly
2.7.5.1. NVS/F Models
1. Inspect the fan blades for any damage or excessive buildup of deposits that could give rise to an imbalance. Remove the assembly for cleaning as follows.
2. Slacken the cable gland on the heater casing through which the fan electrical cable passes.
3. Disconnect the fan leads from the electrical terminals.
4. Withdraw cable through entry grommet.
5. Remove the fan and motor assembly complete by removing the hexagon headed screws that secure the fan to the rear panel.
Ensure that the condense trap is clean and that the drainage pipe work is not blocked or damaged.
2.7.7. Replacement of Faulty Components
2.7.7.1 Multifunctional Control
1. If there is movement available on the incoming gas pipe work e.g. a exible connection has been used go to step 2 otherwise remove the burner assembly as previously described in Section 2.7.2.
2. Remove the electrical plug connections from the top of the multifunctional control.
3. Release the anged connections at the inlet and outlet of the multifunctional control and remove the multifunctional control.
4. Reconnect the new valve in the reverse order to that above ensuring that the valve is correctly orientated. Renew the sealing 'O' rings if necessary.
6. Reassemble in reverse order.
2.7.5.2. Centrifugal Fan/Silencer Section
1. Remove section side panel(s) and inspect the fan blades for any damage or excessive buildup of deposits that could give rise to an imbalance. Remove the assembly for cleaning as follows.
2. Slacken the cable gland on the casing through which the fan electrical cable passes.
3. Disconnect the fan leads from the electrical terminals in the contactor enclosure.
4. Withdraw cable through entry grommet.
5. Remove the complete fan assembly by removing the xings securing the fan to the base rails.
6. Reassemble in reverse order.
2.7.7.2. Burners
1. Remove the burner assembly as described in Section
2.7.2.
2. Remove the end plates of the burner assembly and the central burner support plate.
3. Exchange burners as required and reassemble components in reverse order.
4. Re-commission the appliance as described in Section 2.6.
2.7.6.3. Electrode Assemblies
1. Disconnect the electrode leads from the control box as appropriate.
2. Remove the screw securing the electrode assembly to the burner assembly side plate and withdraw the assembly.
page no. 28 of 36
3. Fit replacement and reassemble in reverse order. Check that the spark gap is 2.5mm (See section 2.6.3) and the rectication electrode is 10 - 12mm forward of the burner.
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 29
2.7.7.4. Limit Thermostat
2.7.7.7. Control Box
Limit NVS 15-140SF 90°C
1. Remove the screws securing the thermostat phial mounting plate to the inner bulkhead, withdraw assembly and unclip the phial.
2. Remove the electrical connections from the limit thermostat. Remove the securing nut and remove thermostat from the front panel.
3. Fit replacement thermostat in reverse order.
2.7.7.5. Exhaust Fan
1. Remove the four screws securing the ue outlet socket.
2. Disconnect the fan electrical connections from the main terminal strip
3. Remove the screws securing the fan mounting box to the exhaust header plate.
4. Remove fan assembly by pulling forwards and to the left to disengage the retaining lugs.
5. If needed, transfer the fan mounting box to the replacement fan.
1. Unplug all the electrical connections.
2. Remove the screws that secure the control box in place.
3. Fit replacement in reverse order.
2.7.7.8. Fan Command Module
1. Trace the wires from the module and disconnect.
2. Remove the two securing screws.
3. Fit replacement in reverse order.
2.7.7.9. Centrifugal Fan/Motor
1. Disconnect the electrical connections to the centrifugal fan section.
2. Remove the side panels of the section for access to the fan and motor.
3. Fit replacements as appropriate and reassemble in reverse order.
6. Fit replacement exhaust fan, using new gaskets and silicon sealant as necessary, and reassemble in reverse order.
2.7.7.6. Air Pressure Switch
1. Remove the two screws securing the cover and remove cover.
2. Disconnect electrical connections.
3. Pull o the sensing tube from the air pressure switch.
4. Note the setting of the old pressure switch.
5. Remove the screws xing the air pressure switch and remove switch.
6. Fit replacement in reverse order retting the sensing tube to the negative (- or L) tapping on the pressure switch. Adjust setting to that of the old pressure switch.
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
page no. 29 of 36
Page 30
3.1 List of Parts
Item Description Usage Part No.
Gas Valve V4105A 30 145035208/KIT
Gas Valve VR4605AB 60 - 90 145035204/KIT
Gas Valve V425AB 140 141378715/KIT
Ignition Electrode
30/60 90/140
Rectication (Flame Sensor) Probe All 142423003
30/60
Burner
90/140
Limit Stat All 142403609
Fan Command Module All 142403605
142423002 142400004
142400240 142400241
Control Box (Sequence Controller) All 145030847
Pressure Switch Dungs LGW All 14 6522174
Float switch All 144807869
page no. 30 of 36
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 31
JOX Relay All 143000816
Hi/Lo Governor Head 30-140 -/HL 142466402
Modulation Governor Head 30-140 -/MOD 142466403
Modulation Driver (GM44) 30-140 -/MOD 142400303
Exhaust Fan Exhaust Fan c/w Mounting Brackets
Exhaust Fan Exhaust Fan c/w Mounting Brackets
Exhaust Fan Exhaust Fan c/w Mounting Brackets
Main Air Fan - NVS F
Main Centrifugal Blower NVS C
30 30
60 60
90/140
30/90 60/140
30 60 90 140
140210496 NV1050EXH
140201505 NVS6075EXH
140201506 NVS90140EXH
140232006/E /15 140232007/E/15
1402CFAN150/T/15 1402CFAN580/ T/15 tba tba
Contactor
120SF-140SF, All -/C 60-90SF, All -/C
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
143000600 143000601
page no. 31 of 36
Page 32
3.2 Gas Conversion
Gas Safety (Installation & Use) (Amendment) Regulations
It is law that all gas appliances are installed, adjusted and, if necessary, converted by qualied persons* in
accordance with the current issue of the above regulations. Failure to install appliances correctly can lead to prosecution. It is in your own interests and that of safety to ensure that the law is complied with.
* An approved class of person listed on the gas safe register.
3.2.1. General
Heater conversion between gases will require a change of burner injectors, alteration of burner pressure and re-commissioning of the heater. (Refer to section 2.6 for commissioning details.)
Ensure that the gas inlet pressure to the heater
is correct for the new gas, and that the gas
supply has been purged of the old gas. (Refer
to tables opposite for new gas inlet pressures.)
3.2.2. Burner Conversion
3.2.3.1. Sigma 843 Adjustment
Cap
Adjustment nut (10mm) for maximum pressure setting
Adjustment screw for minimum pressure setting
3.2.3.2. Honeywell High/Low Adjustment
Hexagonal adjustment screw for maximum pressure setting
Cover Lever point
Internal slotted adjustment screw for minimum pressure setting
1. Ensure that the gas service valve is turned OFF.
2. Remove the burner heat shield, 3 screws.
3. Release the outlet connection ange from the gas valve by removing the four screws.
4. Remove the manifold by removing the four screws securing it to the burner assembly.
5. Remove the main burner injectors and washers.
6. Replace with the new injectors/washers for the new gas ensuring a gas tight seal.
7. Ret all other components in reverse order.
3.2.3. Gas Valves
All gas valves used on the NVS range have pressure regulators that may be set to operate on natural gas or propane (LPG).
Conversion is carried out by adjusting the high and low burner pressures to the value in the tables opposite.
(Refer to full regulator adjustment in section 2.6.6.1)
3.2.3.3. Honeywell Modulating Adjustment
Shaft
Cap
Adjustment nut (7mm) for maximum pressure setting
Adjustment nut (9mm) for minimum pressure setting
‘O’ ring
6.3mm AMP terminals
Note*: Ensure the original data badge is removed and replaced with new data badge and "change of gas" stickers.
page no. 32 of 36
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 33
Natural Gas to Propane (LPG) Conversion Data
Nominal Inlet Pressure = 37mbar, Minimum Inlet Pressure = 37mbar
Injectors
MODEL
Conversion Kit
part number
No. Size (mm)
Marked
Injector part
number
High Fire Low Fire
Burner
Pressure
mbar mbar
NVS30 NV30LPG 6 1.25 125 142401673 26.5 7.6
NVS60 NV60LPG 8 1. 55 155 142401675 20.0 7. 4
NVS90 NV90LPG 6 2.10 210 142401676 24.0 8.4
NVS140 NV140LPG 10 2.10 210 142401676 22.6 6.9
Propane (LPG) to Natural Gas Conversion Data
Nominal Inlet Pressure = 20mbar, Minimum Inlet Pressure = 17.5mbar
Injectors
MODEL
Conversion Kit
part number
No. Size (mm)
Marked
NVS30 NV30NG 6 1.94 194 14240166 4 10.0 3.3
Injector part
number
High Fire Low Fire
Burner
Pressure
mbar mbar
Burner
Pressure
Burner
Pressure
NVS60 NV60NG 8 2.54 254 142401665 8.3 2.6
NVS90 NV90NG 6 3.5 350 142401666 8.2 2.8
NVS140 NV140NG 10 3.5 350 142401666 7. .9 2.3
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
page no. 33 of 36
Page 34
Appendices
Information required for ecodesign (ErP) Directive 2009/125
Model NVS30 NVS60 NVS90 NVS140
High Heat Input kW 29.0 59.2 86.7 138.0
Rated Heat Capacity kW 30.0 60.0 90.0 140.0
Low Heat Input Nett CV kW 15.8 32.7 51.0 77.3
Minimum Heat Capacity kW 15.2 32.7 51.0 77.3
Useful Efficiency
Electrical Power Consumption*
NOx Seasonal (Gross) mg/kWh 143.7 153.6 149.8 148.3
Envelope Loss Factor % n/a n/a n/a n/a
Emission Effiency
Seasonal Space Heating Energy Efficiency
High Fire % 103% 101% 104% 101%
Low Fire % 96% 100% 100% 100%
High Fire kW 0.07 0.07 0.07 0.07
Low Fire kW 0.07 0.07 0.07 0.07
Standby kW <0.01 <0.01 <0.01 <0.01
Ignition kW 0.00 0.00 0.00 0.00
On/Off
Hi/Lo & Mod 94% 94% 93% 94%
On/Off
Hi/Lo 79% 81% 83% 81%
Mod 80% 82% 84% 82%
% hs, flow
% hs,h
90% 90% 90% 90%
78% 76% 79% 77%
page no. 34 of 36
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Page 35
Notes
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
page no. 35 of 36
Page 36
More information is available from our web site on:-
http://www.powrmatic.co.uk/products/heating/browse/view/product/nvs-condensing-unit-heater/
HEATING DIVISION
Hort Bridge
Ilminster, Somerset TA19 9PS
Tel: 01460 53535
Fax: 01460 52341
Every effort is made to ensure accuracy at time of going to press. However as part of continued product improvement,
we reserve the right to alter specication without prior notice.
page no. 36 of 36
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Loading...