Powerwave Technologies 5JS0108 Users manual

WIDEBAND RADIO HEAD
INSTALLA TION AND SERVICE MANUAL
WRH
NEXUS FT
044-05251 Rev B March 2008
© 2008 Powerwave Technologies Incorporated. All rights reserved.
Powerwave Technologies and the Powerwave logo are registered trademarks.
This Powerwave product is designed to operate within the Normal Operating (typical operating) ranges or conditions specified in this document. Operation of this equipment beyond the specified ranges in this document may cause (1) spurious emissions that violate regulatory requirements; (2) the equipment to be automatically removed from service when maximum thresholds are exceeded; or (3) the equipment to not perform in accordance with its specifications. It is the Operator's responsibility to ensure this equipment is properly installed and operated within Powerwave operating specifications to obtain proper performance from the equipment and to comply with regulatory requirements.
The rated output power of a Nexus FT is for multiple carriers. As long as the composite power does not exceed the rated power (20W for North America), derating is not required for multiple carriers. For situations where regulatory requirements require reduced interference to adjacent band users, the rating would have to be reduced by 3 dB. This power reduction is to be by means of input power or gain reduction and not by an attenuator at the output of the device. Input power is rated at 115/230VAC, 50/60Hz, and should be protected based on the power and fuse specifications in Chapter 5 of this manual. Power strips should, at a minimum, conform to this requirement to prevent equipment dam­age and possible overload.
Federal Communications Commission (FCC)
This device complies with the technical standards governing mobile radio devices in accordance with FCC Rules. This device is intended to facilitate the reception and transmission of mobile radio devices in the cellular, PCS or other mobile services, and its operation by end users or others requires carrier consent under FCC rules. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to CRF47 part 15 of the FCC rules. This equipment is also certified to CRF47 part 22 (cellular), part 24 (PCS), part 27 and part 90 (public safety) of the FCC Rules depending on the band of operation. Changes or modifications not expressly approved by Powerwave Technologies, Inc. for compliance could void the user’s authority to operate this equipment. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environ­ment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accor­dance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Industry Canadian Requirements
All Powerwave apparatus introduced in the Canadian market meet all requirements of the Canadian Interference-Caus­ing Equipment Regulations. The -20dB bandwidth at 1900 MHz band is 80 MHz. The -20dB bandwidth at the 850 MHz is 34 MHz. The output impedance of the unit referenced in this document is 50 Ohms. The -20dB bandwidth at IDEN 800MHz band is 26 MHz. The Manufacturer's rated output power of this equipment is for single carrier operation. For situations when multiple carrier signals are present, the rating would have to be reduced. For example, at IDEN 800MHz band, the rating would have to be reduced by 3.5 dB, especially where the output signal is re-radiated and can cause interference to adjacent band users. This power reduction is to be by means of input power or gain reduction and not by an attenuator at the output of the device. The input signal is optical so input impedance requirements are not applicable.
European Requirements
The Powerwave Nexus FT apparatus introduced in EU markets are certified to ESTI EN 300 609-4 (GSM900 and DCS1800) and ESTI EN 301 908-11 (WCDMA).
Powerwave Technologies Inc., 1801 East St. Andrew Place, CA 92705 Santa Ana, USA. Phone +1 714 466 1000 – Fax +1 714 466 5800 – Internet www.powerwave.com
Warnings, Cautions, and Notes
Warnings, Cautions, and Notes are found throughout this manual where applicable. The associated icons in warnings and cautions are used to quickly identify a potential condition that could result in the consequences described below if precautions are not taken. Notes clarify and provide additional information to assist the user.
WARNING: The warning symbol means danger. You are in a situation that could cause bodily injury or death. Before you work on any equipment, be aware of the hazards involved with electrical and RF circuitry and be familiar with standard practices for preventing accidents.
CAUTION: The caution symbol means the potential exists for equipment damage or loss of data.
NOTE
Notes contain helpful suggestions or references to material not covered in the document.
044-05251 Rev B i
Revision Record Nexus FT
Revision Record
Revision Letter Date of Change Reason for Change
Rev A November 2007 Initial Release
Rev B March 2008 Renamed product to Nexus FT, added new
Chapter 1 - Preface, added text regarding FON maintenance to pag
es 3-8 and 4
-6.
ii 044-05251 Rev B
TABLE OF CONTENTS
Preface
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
Human Exposure to RF Radiation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viii
Antennas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii
Installation and Maintenance of Antenna Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii
Radiation Exposure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii
Electrostatic Discharge (ESD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii
Chapter 1 - Product Description
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Scope of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Chassis Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Wideband Amplifier PCBA (WBA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Multi-Carrier Power Amplifier PCBA (MCPA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Distribution PCBA (DIA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Control Unit PCBA (CU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Low Noise Amplifier (LNA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Duplex Filter (DPX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Fiber Optic Unit (FOU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Fiber Optic Node (FON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Power Supply Unit (PSU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Remote Control Unit (RCU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Alarm Interface PCBA (ALI) and Remote Control Interface PCBA (RCI) . . . . . . . . . . . . . . . . . . . 1-5
Chapter 2 - Controls, Indicators and Connectors
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Front Cover Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Cabinet Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
PCBA Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
PCBA Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Software and Hardware Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Chapter 3 - Installation
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Site Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
WRH Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Main Power and Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Fiber Optic and RF Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
WRH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Optional Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
External Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Door Open Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Main Power Breakdown Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
21-60 Volt DC PSU Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
044-05251 Rev B iii
Table of Contents Nexus FT
Passive Intermodulation (PIM) Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Chapter 4 - Maintenance
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Periodic Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Clearing Alarm Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Field Replaceable Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
FON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
PSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
WRH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Remote Control Unit (RCU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
RCU for Radio Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
RCU for Telephone Line Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Return For Service Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Obtaining an RMA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Repackaging for Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Chapter 5 - Specifications
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Appendix A - Block Diagrams
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Non-Diversity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Diversity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
List of Figures
1-1 Powerwave WRH Radio Head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1-2 DIA PCBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1-3 CU PCBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1-4 LNA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1-5 FOU in Nexus FT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1-6 Nexus FT Sub Unit Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
1-7 Fiber Optic Star Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
1-8 Multi-operator System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
2-1 External Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2-2 Cabinet Internal Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2-3 CU PCBA Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2-4 FON LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2-5 DIA PCBA Connectors and Testpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2-6 LNA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2-7 FON Connector Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2-8 PSU Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
3-1 -Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3-2 Mounting Bracket Installation on Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3-3 Attaching the Bracket to a Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3-4 Attaching the Bracket to a Mast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3-5 Attaching the WRH to the Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3-6 WRH Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3-7 External Alarm Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
iv 044-05251 Rev B
Nexus FT Table of Contents
3-8 Main Power Breakdown Relay Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
3-9 Connecting a PC for Local Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
3-10 PIM testing two carriers and one WRH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
3-11 PIM testing one carrier over each of two WRHs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
4-1 PSU Cable, Switch and Lable locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
4-2 RCU in the WRH cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
A-1 WRH Block Diagram - Non-Diversity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
A-2 WRH Block Diagram - Diversity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
List of Tables
2-1 CU PCBA LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2-2 FON LED Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2-3 WRH Base Unit Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2-4 WRH Cover Unit Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2-5 DIA PCBA Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2-6 LNA Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2-7 FON Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2-8 Hardware / Software Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
3-1 Cable Connection Priocedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3-2 Main Power Breakdown Relay Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
3-3 Initial Statup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
3-4 PIM Testing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
4-1 Recommended Periodic Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4-2 Alarm Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4-3 FON Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4-4PSU Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
4-5 WRH Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
5-1 WRH Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
044-05251 Rev B v
Table of Contents Nexus FT
This page intentionally left blank
vi 044-05251 Rev B
Preface
Safety
Any personnel involved in installation, operation, or service of units included in a Powerwave Distributed Antenna System (DAS) must understand and follow the points below.
Powerwave Nexus FTs are designed to receive and amplify signals from one or more
base stations a act the other way round, that is to receive signals from one or more mobile stations, amplify and retransmit the signals to the base stations. Powerwave Nexus FT systems must be used exclusively for this purpose and nothing else.
Units supplied from the mains must be connected to grounded outlets and in conformity
with the local presc
For outdoor use, the power cord should meet at least IP65 encapsulation requirements.
Do not turn the main
Power supply units supplied from the mains contain dangerous voltage that can cause
electric shoc are to be followed when servicing such units. Only authorized service personnel are allowed to service units while the mains are connected.
When opened, the Nexus FT cover must be secured. Otherwise, the cover can be
closed by the wi
When working on a Nexus FT on high ground, for instance on a mast or pole, be careful
not to drop par
All RF transmitting units, including Nexus FTs, will generate radio signals and thereby
give rise to ele who is extensively exposed close to an antenna.
A lithium battery is permanently mounted on the CU and FON PCBAs. Due to the risk
of explosion, this ba authorized service technician.
NiCd batteries are mounted on the FON PCBA. These batteries contain environmental
poisonous substanc the local prescriptions.
The FON unit contains a Class 1M laser transmitter that emits 2—4 mW invisible laser
radiation at 155 direct exposure from a disconnected laser transmitter or fiber cord. For example, do not view directly with optical instruments (magnifiers) and do not view directly with non-attenuating optical instruments.
T
he FON Unit has this label attached:
nd retransmit the signals to one or more mobile stations. And, also to
riptions.
power on until you are ready to commission the Nexus FT.
k. Disconnect the mains prior to any work in such a unit. Local regulations
nd and cause your fingers getting pinched or your head being hit.
ts or the entire Nexus FT. Falling parts can cause serious personal injury.
ctromagnetic fields that may be hazardous to the health of any person
ttery must only be removed from the board by a Powerwave
es. If replaced, the old batteries should be disposed of as stated in
0 nm during operation and is intended for a restricted location. Avoid
Do not power up the FON unit if a fiber cable is not connected to the fiber output UL
Never look at the end of a fiber cable. The 1310nm and 1550n
044-05251 Rev B vii
t, or if a fiber
por
visible. Always use an instrument, such as a power meter, to detect signaling.
cable is connected to the port but disconnected at the other end.
m laser light is not
Electrostatic Discharge (ESD) Nexus FT
Human Exposure to RF Radiation
Safe distances must be kept when working around antennas. The following paragraphs describe the cautions to be aware of during the installation and maintenance of antenna systems and how to calculate safety distances needed for RF radiation at different antenna power and frequencies.
Antennas
To be able to receive and transmit signals, a Nexus FT is connected to a donor antenna directed towards the base station and a s station might, however, be substituted for the donor antenna.
Installation and Maintenance of Antenna Systems
Installation and maintenance of all antenna systems must be performed with respect to the radiation exposure limits for transmission devices such as cables, connectors, splitters and feeders. Also have in mind the system minimum coupling loss, typically between 25dB and 35dB, is determined by a standard with the purpose to protect base stations from noise and other performance dropping effects.
Radiation Exposure
The World Health Organization (WHO) and International Commission on Non-Ionising Radiation Protection
ICNIRP) have
( following radiation power for public exposure:
Frequency Radiation power
800/900 MHz 4.5W/m² 1800/1900 MHz 9.0W/m² 2100 MHz 10.0W/m²
For antennas larger than 20cm the maximum radiation power can be calculated by using the following formula:
public areas. The antenna radiation level is affected by Nexus FT output power, antenna gain, and
S= P/(4
ervice antenna directed towards the coverage area. A fiber optic cable from the base
determined recommendations for radiation exposure. ICNIRP recommends not to exceed the
S = Radiation power in W/m² P = Output power in W r = Distance between antenna and human in meters
πr
2
)
Electrostatic Discharge (ESD)
ESD can severly damage essential parts of the equipment if not handled carefully. Parts on printed circuit board assemblies (PCBA) as well as other parts in the equipment are sensitive to ESD. Never touch the PCBA or uninsulated conductor surfaces unless absolutely necessary.
If you must handle the PCBAs or uninsulated conductor surfaces, use ESD protective
quipment or first to
e uninsulated conductor surfaces and always store PCBAs in ESD-safe bags.
uch the chassis with your hand. Never let your clothes touch PCBAs or
viii 044-05251 Rev B
Chapter 1
Product Description
Introduction
This manual contains information and procedures for installation, operation, and maintenance of The Nexus FT High Power Wideband Radio Head - in this manual, referred to as WRH. The manual is organized into chapters as follows:
Chapter 1- Product Description
Chapter 2- Controls and Indicators
Chapter 3- Installation
Chapter 4- Maintenance
Chapter 5- Specifications
Scope of Manual
This manual is intended for use by service technicians familiar with similar types of equipment. It contains service information required for the equipment described and is current as of the printing date. Changes which occur after the printing date may be incorporated by a complete manual revision or alternatively as additions.
Overview
Figure 1-1 Powerwave WRH Radio Head
Powerwave Nexus FTs work as bi-directional on-frequency amplifiers used to extend coverage into uncovered areas in wireless buildings. It receives, amplifies, and transmits signals to/from a base transceiver station (BTS) to/from mobile stations (MS) with both directions being served simultaneously. Connections to the WRH are made with N-type or 7/16" male connectors.
mobile systems such as base station fringe areas, tunnels, convention centers, airports and
044-05251 Rev B 1-1
Overview Nexus FT
Nexus FTs are microprocessor controlled with alarm and operational status LEDs visible on the front cover. Cooling is provided through convection heat dissipation. Operational parameters, such as gain and power levels are set using a PC running Powerwave OM-Online software which communicates with the Nexus FTs either locally or remotely via modem. Remote operation can be performed via PSTN or a GSM net. The Operation and Maintenance System (OMS) provides for Network Operations Center (NOC) configuration and alarm monitoring.
Nexus FTs can be configured in many combinations depending on the wireless system, single or double
ystem operatio
s Nexus FTs available.
The WRH is a fiber fed system designed to provide a high output power level and comes equipped with a MCPA in the downlink path. T a high cover is used. The MCPA is located in the cabinet and is supplied from the existing PSU.
n, and output power. The following paragraphs provide a description of the different models of
he MCPA restricts the number of bands to one in the cabinet and one additional band if
Chassis Design
The WRH is housed in a cast aluminium waterproof chassis, class NEMA4 / IP65, approved for outdoor use but is also suited for indoor installations. The chassis consists of a cabinet and a cover attached with hinges. The cabinet contains the WRH circuitry. The cover comes as either a low or high version. The high cover can be used as an empty cover or be equipped as a part of the WRH or an independent WRH unit. A WRH with a high cover that is equipped as two independent units can, for example, be equipped for channel selective operation in the cabinet and band selective operation in the cover.
Inside the Nexus FT, a number of amplifier PCBAs are individually shielded and located under a metal cover
hat can be opened outward. T
t
hese PCBAs are of different types depending on the supported system.
Sub Unit Overview
A number of amplifier PCBAs are individually shielded and located under a metal cover inside the Nexus FT. This cover can be opened outward for access. These amplifier PCBAs are of different types depending on the supported system. All of the Nexus FTs are built up with a number of sub units which are described in the following sections.
Wideband Amplifier PCBA (WBA)
Nexus FTs can handle multiple carriers over a wide band. Each band requires one WBA for the uplink and downlink, and one asso along with two PAs supporting two bands or one MCPA supporting one band. Positions 1 and 3, shown in Figure 1-6, are assigned for a WBA.
Multi-Carrier Power Amplifier
The MCPA is direction. It req generated. The MCPA occupies positions 2 through 4 in the cabinet and 6 through 8 in a high cover, as shown in Figure 1-6.
used to amplify the output signal from the WBA. Each MCPA can handle one band in the downlink
uires an extra heat sink element on the outside of the cabinet or high cover to dissipate the heat
ciated PA or MCPA for the downlink. The cabinet can be equipped with up to two WBAs
PCBA (MCPA)
1-2 044-05251 Rev B
Nexus FT Overview
ALLGON INNOVATION SWEDEN M105 R6
1
PARKING FOR W5
W5
8
P27
W6B 10
1
P33
ALARM
P23 LNA
UP-LINK
P32
MODEM
A
U
X
1
P28 DOOR
5
9
6
1
1
16
1
1
M
-
>
S
P11
P34
8
9
15
P26
15 16
S
-
>
M
1
2
3
89
P
3
6
5
X0A
X0B
2
V2
1
16
P12 P13
1
1
1
16
16
16
P4
P5
P6
c b a
c b a
c b a
c b a
1P232
1
b a
1
16P3
16
1
16
P14
1
V1
1
1
1
1
1
4
6
1
15
6
9
15216
1
2
4
5
8
5
P35
P21 PSU
6
10
P31 PC
P29
P24
P25
GND
7
6V6
LNA
DOWN-LINK
LED P22
1
2
V6B
P27
P26
P23
XOA
XOB
P28
P4 P5 P6 P2 P3 P31 P21 P35 P33
P32
P11 P12 P13 V1P14 P22P29P34 V2P36
V6
GND
P25
P24
Distribution PCBA (DIA)
The DIA is the core distribution PCBA to which all other PCBAs and units connect in the cabinet with the exception o
f the PA. Figure 1-2 shows a DIA PCBA. A shielded metal frame on the DIA provides the mounting
location for the CU, ALI and RCIs, if used.
Figure 1-2 DIA PCBA
Control Unit PCBA (CU)
Figure 1-3 shows the CU, which is the core microprocessor controller in the WRH and is connected to P2 on the DIA. The CU contai
ns a microprocessor, main memory, flash memory for the CU software, EEPROM memory for parameters, memory for the event log and statistics, a REFO reference oscillator, ports for local and remote communication, a battery powered real-time clock, and a MAC identity circuit. It supervises and controls operational parameters such as gain control and channel handling, alarms, the event log, the password and the logon. The CU is also a control interface for OM-Online and OMS. Software for the CU can be downloaded from OM-Online, either locally or remotely. It is located in the lower right part of the shielded DIA frame.
Figure 1-3 CU PCBA
Low Noise Amplifier (LNA)
LNAs are used on the uplink and are located at the top of the cabinet and the high cover, if equipped. An
xample of an LNA i
e output are fed to the LNA input connector (IN). The OUT1 and OUT2 outputs feed the WBAs in the UL direction. The signal level at these connectors is +20dB referenced to the antenna input. The other output, OUT LOW, is an expansion output for an additional LNA if the WRH is equipped with a unit in the cover part of the chassis.
044-05251 Rev B 1-3
s illustrated in Figure 1-4. All of the coaxial connectors are SMA-type. Signals from the DPX
Overview Nexus FT
FON
DPX
The gain to this connector is +2dB. The +7V input is used for +7V supply from the DIA PCBA and the ATT connection is for the control signal for a controllable attenuator in the LNA.
Figure 1-4 LNA
Duplex Filter (DPX)
DPXs are located on the metal cover sheet in the upper part of the cabinet.
Fiber Optic Unit (FOU)
The FOU is a metal plate mounted on top of the cover plate in the upper part of the Nexus FT. The FON and f
iber optic co connectors mounted on the plate. It can also be configured with combiners, splitters, and Wave Division Multiplexers (WDMs) to obtain a desired combination of several branches with double or single fiber.
nnectors are mounted on the FOU. Figure 1-5 illustrates an FOU with the FON and fiber optic
Figure 1-5 FOU in Nexus FT
Fiber Optic Node (FON)
The FON is the main part of the FOU. It is a bi-directional electrical/optical signal converter and a node in a fiber network. In addit It has also functionality for:
There are two versions of the FON; one with three SMA ports (UL, DL and RX Mon) and the other with four SMA
orts (UL, DL
p
Power Supply Unit (PSU)
The PSU supplies DC power to all of the components in the Nexus FT.
Remote Control Unit (RCU)
The RCU is an optional communication unit for remote control of Nexus FTs via PSTN or RF modems. RCU types and details
1-4 044-05251 Rev B
ion, the FON has all the functionality included in the CU PCBA and contains battery backup.
• Electrical and optical signal supervision ernal and external
• Int
• RS232 interface for local PC control via an O&M software (OM-Online)
• Remote control via an O&M software (OM-Online or OMS)
• Interfaces for RCU and FLI
• Battery backup with charger
, RX Mon and TX Mon). The FON also has two optical ports for DL and UL fiber connections.
are described in Chapter 4.
alarm handling
Nexus FT Overview
1234
LNA - UL
PSU
(RCU)
DPX
CUALI/RCI
WBA
DL/UL
FOU
MCPA DL
5678
PSU
(RCU)
DPX
CUALI/RCI
WBA
DL/UL
FOU
MCPA DL
FON FON
Alarm Interface PCBA (ALI) and Remote Control Interface PCBA (RCI)
The ALI handles alarms and alarm communication. It is replace with an RCI if
an RCU is used and provides an interface between the CU and an RCU for remote communication via modem. The RCI also handles alarms and alarm communication. Either unit is located in the lower left part of the shielded DIA frame.
Sub Unit Locations
The MCPA is located at positions 3 and 4 in the cabinet. A WRH is equipped for one band in the cabinet and, if required, an additional band in a high cover. PCBA positions are illustrated in Figure 1-6 and a block diagram is located in Appendix A.
Figure 1-6 Nexus FT Sub Unit Locations
Fiber Optic Distribution Networks
Fiber optic networks are setup identically to data networks. Nexus FTs are connected in a star configuration as illustrated in Figure 1-7. In this example, a Base Station Master Unit (BMU) is fed by a BTS via an RF cable. An Optical Converter Module (OCM) could also be used depending on the system configuration. The BMU or OCM contain three FONs and provide continuity to the FONs in the four Nexus FTs. By using WDMs and Optical
044-05251 Rev B 1-5
Overview Nexus FT
BMU WRH
WRH
WRH
WRH
BTS
RF
Operator 1
Operator 2
OCM
OCM-POI
BTS-POI
BTS-POI
BTS-POI
BTS-POI
OCM-POI
Splitters (OSPs) in the Nexus FTs, the distribution net can be built up with a combination of star and daisy-chain connections using double or single fiber.
Figure 1-7 Fiber Optic Star Configuration
Multi-Operator Configurations
Multi-operator systems require the use of Point of Interconnect (POI) units and OCMs as illustrated in Figure 1-8. In this simple example, two operators have two sectors each. Each sector is connected to a POI and then to a RCM. The RCM is interconnected with an OCM via coaxial cables. The combined DL and UL signals are converted to optical signals in the OCM and then distributed to the Nexus FTs-V.
Sector 1
Sector 2
Sector 1
Sector 2
Figure 1-8 Multi-operator System
1-6 044-05251 Rev B
Controls, Indicators and Connectors
Red
Amber
MS
DPX
ANT
TEST
DC
-30 dB
-20 dB
MS
DPX
ANT
TEST
DC
-30 dB
-20 dB
ALLGON INNOVATION SWEDEN M105 R6
1
PARKING FOR W5
W5
8
P27
W6B10
1
P33 ALARM
P23 LNA
UP-LINK
P32 MODEM
A
U
X
1
P28 DOOR
5
9
6
1
1
16
1
1
M
-
>
S
P11
P34
8
9
15
P26
15 16
S
->
M
1
2
3
89
P
3
6
5
X0A
X0B
2
V2
1
16
P12 P13
1
1
1
16
16
16P4
P5
P6
c b a
c b a
c b a
c b a
1P232
1
b a
1
16P3
16
1
16
P14
1
V1
1
1
1
1
1
4
6
1
15
6
9
15216
1
2
458
5
P35
P21 PSU
6
10
P31
PC
P29
P24
P25
GND
7
6V6
LNA
DOWN-LINK
LED P22
1
2
POWER SUPPLY UNIT
CU
ALI
or
RCI
S
V
OPER
FAULT
POWER
10V
ALARM
POWER
BOOT
FAULT
OPER
WLI / R2R
DATA
Introduction
This chapter contains descriptions of the controls, indicators and connectors for the WRH.
Front Cover Indicators
Chapter 2
Figure 2-1 External Indicators
Two LEDs, shown in Figure 2-1, are located on the front cover to provide easy identification of a fault in the system. The amber
operation LED lights up approximately 15 seconds after the main power is switched on. When the LED is steady, the WRH is ready for operation. The red alarm LED indicates a system error alarm when flashing and a critical alarm when steady.
Cabinet Indicators
Figure 2-2 Cabinet Internal Indicators
044-05251 Rev B 2-1
PCBA Indicators Nexus FT
WLI DATA POWER BOOT FAULT OPER
Figure 2-2 shows the LED indicators located on the ALI or RCI, the CU PCBAs, the 115/220V main power switch (S) in the cabinet, and the voltage indicator (V). These indicators are described in further detail in the following sections.
PCBA Indicators
This following paragraphs describe the LED indicators on the main PCBAs inside the WRH.
CU PCBA
Figure 2-3 shows the location of the LEDs on the CU and Table 2-1 lists their indications.
Figure 2-3 CU PCBA Indicators
Table 2-1 CU PCBA LED Indicators
LED Description
WLI Wire Link Interface. A flashing green LED indicates the unit is receiving
data over the subcarr currently not receiving any data, is currently not a control station or there is no other node in the network
DATA Blue LED indicating data transmission in the W-net
POWER Yellow LED indicating present power and remains steady after power is
switched on
BOOT Steady r
switched on), then fla detected. If an error is detected LED will stay on
FAULT Flashing red LED for 15 – 20 seconds after main power is switched on.
Flashes for les (Critical)
OPER Steady green LED indicates WRH is ready for operation
WARNING: A lithium battery is permanently mounted on the CU PCBA. Due to risk of explosion, this battery must not be removed. In case of battery malfunction, replace the CU PCB.
ed LED when the CU boots (10 – 15 seconds after main power is
ier. A steady green LED indicates: the unit is
shing red (5 – 10 seconds), then off if no error is
s serious alarms (Error) and is on solid for fatal alarms
2-2 044-05251 Rev B
Nexus FT PCBA Connections
P117
FON PCBA
The FON is shown in Figure 2-4 and the LED indicators are listed in Table 2-2.
Figure 2-4 FON LED Indicators
Table 2-2 FON LED Indications
LED Description
FLI or
F2F
OPER Green LED. Lights up for approximately 5 seconds after the power is switched on.
FAULT Red LED. Flashes for 15 – 20 seconds after the mains is switched on. Will flash for
POWER Yellow LED. Indicates power is present
BOOT Red LED. Steady LED when the control unit boots up (10 – 15 seconds after the
WLI Green LED. Wire Link Interface. Flashing LED indicates unit is receiving data over
DATA Blue LED. Indicates data transmission in the W-net
BATT Green LED. Steady LED indicates battery pack is currently used as power source
CHARGE Yellow LED. Steady LED indicates battery charging
Green LED. Fiber data over the sub carrier. A steady LED indicates the unit has detected an FLI sub­carrier, but is not carrying any data
The LED is dark the unit is ready for operation
ess serious a
l
m
ains is switche
detected, the LED turns off. If an error occurs, the LED remains on
the subcarri receiving any data, the unit is not currently a control station or there is no other node in the network
Line Interface (FLI). Flashing LED indicates the unit is receiving
during the boot process and when it is steadily lit again, it indicates
larms and be steady for fatal alarms
d on). Next enters a flashing state for 5 – 10 seconds. If no error is
er. A steady LED indicates one of the following: The unit is not currently
PCBA Connections
The following tables list the connections from the main PCBAs to replaceable units inside the WRH. Table 2-3 lists the connections for a WRH configured for PCS both with and without diversity and Table 2-4 lists the connections for Cellular with and without diversity.
044-05251 Rev B 2-3
PCBA Connections Nexus FT
V
V
Table 2-3 WRH Base Unit Connections
From To Cable Number Non-Diversity Diversity
WBA P2401 M FON P101 VE007 06/3 Used Used
WBA P3401 D FON P101 700-16639-001 Not Used Used
WBA P1101 M FON P102 VE007 20/2 Used Used
PSU DIA P21, P35 VE007 98/1 Used Used
M FON P108 DIA P29 VE007 66/1 Used Used
D FON P108 M FON P116 VE007 66/1 Not Used Used
M FON P111 DIA P36 VE008 05/1 Used Used
D FON P111 DIA P112 VE008 05/1 Not Used Used
Table 2-4 WRH Cover Unit Connections
From To Cable Number Non-Diversity Diversity
Cover DIA P36 M FON P112 VE008 05/1 Used Not Used
Cover DIA P36 D FON P112 VE008 05/1 Not Used Used
PSU DIA P21, P35 VE007 98/1 Used Used
DX DL C M FON P102 700-14508-401 Used Used
DX UL1 C (M) M FON P101 700-14508-401 Used Used
DX UL2 C (D) M FON P101 VE007 52/2 Not Used Used
DIA PCBA
Figure 2-5 shows and Table 2-5 lists the connections on the DIA PCBA. The DIA provides most of the internal connection between the sub units and external ports. Connectors involved are also located on the DIA.
P11 P12 P13 V1P14 P22P29P34 V2P36
P11 P12 P13 V1P14 P22P29P34 V2P36
XOB
XOB XOA
XOA P26
P26 P28
P28 P23
P23 P37
P37
6B
6B
P27
P27
1
1
1
1
>M
>M
-
­S
S
15 16
15 16
P23
P23
UL LNA ATTN
UL LNA ATTN
W5
W5
P11
P11
5
5
P36
P36
2
2
1
1 X0A
X0A
89
89
3
3
1
1
P26
P26
2
2 1
1
6
6
2
2 1
1
9
9
DIV
DIV
MODEM
MODEM P27
P27
W6B 10
W6B 10
8
8
AUX1
AUX1
1
1
P28
P28 DOOR
DOOR
P32
P32
ALLGON INNOVATION
ALLGON INNOVATION SWEDEN M105 R6
SWEDEN M105 R6
PARKING
PARKING FOR W5
FOR W5
X0B
X0B
15
15
1
1
9
9
5
5
P32
P32
2
2
16
16
P34
P34
8
8
1
1
P33
P33
ALARM
ALARM
1
1
V2
V2
1
1
P6
P6
c
c b
b a
a
1
1
P5
P5
c
c b
b a
a
1
1
P4
P4
c
c b
b a
a
P4 P5 P6 P2 P3 P31 P21 P35 P33
P4 P5 P6 P2 P3 P31 P21 P35 P33
16
16
P12 P13
P12 P13
16
16
16
16
16
16
1
1
16
16
1
1
b
b a
1P232
1P232
c
c b
b a
a
a
1
1
16P3
16P3
Figure 2-5 DIA PCBA Connectors and Testpoints
The External Alarm Port P33 is used for external alarm sensors and alarm equipment. The four alarm inputs are low-level input
s with common ground (AIC). Use an insulated switch or relay to initiate alarms (open switches in normal operating mode, closed switches cause alarm). The alarm switch connection can be toggled between active open and active closed. The alarm input voltage ratings, related to ground (AIC), are: Vinmax= 5.5V, Vinmin= –0.5V.
The four alarm inputs are connected to the following pins:
Pin 14 AI1 External alarm input 1 - EAL1
Pin 15 AI2 External alarm input 2 - EAL2
Pin 7 AI3 External alarm input 3 - EAL3
Pin 8 AI4 External alarm input 4 - EAL4
2-4 044-05251 Rev B
1
1
16
V1
16
V1
P14
P14
LED
LED P22
P22
4
4
2
2
1
1
1
1
>S
>S
P25
P25
-
-
6
6
M
M
15
15
9
9
16
16
15
15
1
1
P25
P25
P29
P29
6
6
P31
P31 PC
PC
5
5
10
10
P21
P21 PSU
PSU
1
1
6
6
5
5
1
1
P35
P35
4
4
8
8
P24
P24
2
2
P24
P24
1
1
1
1
UL LNA ATTN
UL LNA ATTN
V6
V6
6V6
6V6
2
2
P38
P38
1
1
DIV
DIV
P38
P38
7
7
GND
GND
GND
GND
Nexus FT PCBA Connections
Pin 6 AIC Ground.
Two alarm outputs are 1 pole closing and 1 pole opening relay outputs insolated from each other. Maximum ratings, related follows:
Pin 9 and 1 AO1 and AO8 Closed when operating, otherwise open.
Pin 10 and 2 AO6 and AO7 Open when operating, otherwise closed.
Pin 11 and 3 AO2 and AO5 Closed at alarm state, otherwise open.
Pin 12 and 4 AO3 and AO4 Open at alarm state, otherwise closed.
to ground or any other alarm terminal, are 50 VAC / 60 VDC. The alarm outputs are defined as
Table 2-5 DIA PCBA Connections
Port Connected to
P2 CU PCBA
P3, 5, 6 Not Used
P4 ALI or RCI PCBA
P11 - 14 Channel PCBA positions 1 through 4
P21 PSU, connector 1
P22 LED PCBA in cover
P23 LNA/UL
P24 LNA/DL
P25 Expansion output port to cover circuitry. Only in cabinets
P26 Expansion input port to cover circuitry. Used in equipped high covers
P27 Auxiliary Port (8-pin male) - Pins 2 and 3 must always be interconnected to
p
rovide the CU an
connected, pins 2 and 3 must be interconnected with a jumper
P28 Door switch port - Normally, alarm input AI4 is used for door opening alarm
AL4 which is
E are thus available also in the P28 connector, to which the door switch is connected. The EAL4 door switch alarm is activated 10 – 30 seconds after the cover has been opened
P29 Power to FON
P31 RS-232 PC Port (9-pin D-sub female) - Used for local PC communication
P32 RS-232 Modem port (9-pin D-sub male)
P33 External Alarm Port (15-pin D-sub female) - Used for external alarm sensors
a
nd alarm equip
outputs
P34 Not used
P35 PSU, connector 2
P36 IP or R2R connection between CU and FON
P37 LNA Diversity DL
P38 LNA Diversity UL
d ALI/RCI PCBAs with voltage. If there is no cable
arranged using an optional door switch. Signal AI4 and AIC
ment. Four alarm inputs, EAL1 – EAL4, and two alarm
044-05251 Rev B 2-5
PCBA Connections Nexus FT
P117
LNA
Figure 2-6 shows the front of the LNA and Table 2-6 lists the connections.
Figure 2-6 LNA
Table 2-6 LNA Connections
LNA Port Connected to
OUT LOW IN on the LNA/UL in the cover, if equipped
IN LO on the service DPX duplex filter
ATT +7V P23 on the DIA PCBA
OUT1 P2101 on the WBA PCBA
OUT2 Diversity LNA connected to P3101 on WBA PCBA
FON
Figure 2-7 shows the locations of the connectors on the FON and Table 2-7 lists the port numbers, connector types, and port usage.
Figure 2-7 FON Connector Locations
Table 2-7 FON Connectors
Port Description
P101 SMA, electrical RF input port (to the optical TX port)
P102 SMA, electrical RF output port (from the optical RX port)
P103 SMA, electrical RF output port (15dB below the P102 port)
RX DIN/APC, optical input port (to the P102 and P103 RF ports)
TX DIN/APC, optical output port (from the P101 RF port)
P104 Used only for development and debugging
P105 4-pin male, door LED indicators. Used for the yellow and red LED indicators located
on t
he front cabinet door
06 9-pin D-sub female, RS-232 used for local PC communication
P1
P108/116 6-pin male, parallel connected power ports for the FON
P109 7-pin male, used for external alarm sensors
2-6 044-05251 Rev B
Nexus FT PCBA Connections
MS
DPX
ANT
TEST
DC
-30 dB
-20 dB
POWER SUPPLY UNIT
ALLGON INNOVATION SWEDEN M 105 R6
1
PARKING FOR W5
W5
8
P27
W6B 10
1
P33
ALARM
P23 LNA
UP-LINK
P32
MODEM
A
U
X
1
P28 DOOR
5
9
6
1
1
16
1
1
M
-
>
S
P11
P34
8
9
15
P26
15 16
S
-
>
M
1
2
3
89
P
3
6
5
X0A
X0B
2
V2
1
16
P12 P13
1
1
1
16
16
16
P4
P5
P6
c b a
c b a
c b a
c b a
1P232
1
b a
1
16P3
16
1
16
P14
1
V1
1
1
1
1
1
4
6
1
15
6
9
15
2
16
1
2
4
5
8
5
P35
P21 PSU
6
10
P31 PC
P29
P24
P25
GND
7
6V6
LNA
DOWN-LINK
LED P22
1
2
P21 P35
V1V2
AC
Power
MS
DPX
ANT
TEST
DC
-30 dB
-20 dB
MS
DPX
ANT
TEST
DC
-30 dB
-20 dB
POWER SUPPLY UNITPOWER SUPPLY UNIT
ALLGON INNOVATION SWEDEN M 105 R6
1
PARKING FOR W5
W5
8
P27
W6B 10
1
P33
ALARM
P23 LNA
UP-LINK
P32
MODEM
A
U
X
1
P28 DOOR
5
9
6
1
1
16
1
1
M
-
>
S
P11
P34
8
9
15
P26
15 16
S
-
>
M
1
2
3
89
P
3
6
5
X0A
X0B
2
V2
1
16
P12 P13
1
1
1
16
16
16
P4
P5
P6
c b a
c b a
c b a
c b a
1P232
1
b a
1
16P3
16
1
16
P14
1
V1
1
1
1
1
1
4
6
1
15
6
9
15
2
16
1
2
4
5
8
5
P35
P21 PSU
6
10
P31 PC
P29
P24
P25
GND
7
6V6
LNA
DOWN-LINK
LED P22
1
2
ALLGON INNOVATION SWEDEN M 105 R6
1
PARKING FOR W5
W5
8
P27
W6B 10
1
P33
ALARM
P23 LNA
UP-LINK
P32
MODEM
A
U
X
1
P28 DOOR
5
9
6
1
1
16
1
1
M
-
>
S
P11
P34
8
9
15
P26
15 16
S
-
>
M
1
2
3
89
P
3
6
5
X0A
X0B
2
V2
1
16
P12 P13
1
1
1
16
16
16
P4
P5
P6
c b a
c b a
c b a
c b a
1P232
1
b a
1
16P3
16
1
16
P14
1
V1
1
1
1
1
1
4
6
1
15
6
9
15
2
16
1
2
4
5
8
5
P35
P21 PSU
6
10
P31 PC
P29
P24
P25
GND
7
6V6
LNA
DOWN-LINK
LED P22
1
2
P21 P35
V1V2
AC
Power
Table 2-7 FON Connectors (Continued)
Port Description
P110 W-link jumper, used to terminate units in a W-link. It has to be set in the parking
state for all
units except for the first and last units in a W-link. The Parking state (P) has the jumper between the center and bottom pins. The opposite state, with the jumper between the tip and center pins, terminates(T) the W-link
P111/112 5-pin male, WLI ports used for interconnecting nodes in WLI-nets (IP or R2R
networks).
They are identical and connected in parallel. One of the connectors is intended to be used from the previous node and the other connector to the next node in the network. Either can be used for the first and the last unit in the net chain
P113 2-pin male, used for the on-PCBA backup batteries
P114 Backup power output jumper, sets the backup power output state. The OFF state
as jumper between th
h
e center and left pins. This jumper has to be in the OFF state
when used in an OCM. Otherwise, it shall be in the ON state
P115 3-pin male, intended for future use
P117 SMA, electrical RF output port (15dB below the P101 port)
P130 34-pin, 2-line male, RCU port used for connecting an RCU. The connector contains
both the modem co
nnection and RCU power supply
PSU
The PSU is located in the bottom middle of the cabinet or in an equipped high cover. The PSU has all the voltages required for the WRH. It has capacity for the radio circuitry, fiber optics, and modem. Multi-band WRHs always require a second PSU. There are two PSU types with different input voltages:
1. 115/230V 50/60Hz, 300W input max.
2. 21- 60V DC, 300W input max.
The PSU is connected to the DIA at P21 and P35, and voltage is tested at V1 (test point for P35) and V2 (test point for P21).
igure 2-8 PSU Location
F
044-05251 Rev B 2-7
Software and Hardware Compatibility Nexus FT
Software and Hardware Compatibility
There are different versions of CU PCBA software which can be combined with PCBAs of various revisions. These have unique part numbers and revision information. Table 2-8 lists the software currently available in combination with CU PCBA revisions.
Table 2-8 Hardware / Software Compatibility
CU PCBA part number CU Software part number
500-13817-001 (previously K103/3) D631-18072-001
D631-18072-003
This information is accurate as of 06/31/2007. As new versions of hardware and software are released without prior notice, contact your Powerwave sales representative for information on the latest revision.
For detailed information, refer to the release notes for the CU software to be downloaded (normally found in the readme.txt file prov
ided with the program files).
2-8 044-05251 Rev B
Chapter 3
Installation
Introduction
This chapter contains unpacking, inspection and installation instructions for installing and powering up the WRH.
Site Survey
Powerwave recommends that a site survey be performed prior to equipment ordering or installation. Performing a detailed site survey reduces or eliminates installation and turn-up delays. Pay particular attention to power plant capacity, cooling needs, floor space, and RF/DC cabling/breaker requirements. Cabinet dimensions and weights are listed in Chapter 5.
Unpacking and Inspection
This equipment has been operated, tested, and calibrated at the factory. Carefully open containers to remove equipment. Retain all packing material that can be reassembled in the event unit must be returned to the factory. Perform the following steps:
V
isually inspect equipment for damage that may have occurred during shipment. If possible, in the
presence of
Check for evidence of water damage, bent or warped chassis, loose screws or nuts, or extraneous
packing material in connectors.
If equipment is damaged, file a claim with the carrier once the extent of any damage is assessed.
If equipment must be returned to factory, please contact factory for a Return Material Authorization (RMA),
e Chapter 4
se
.
the delivery person.
WRH Location
The WRH is designed with a weather proof outdoor cabinet that can be mounted without any kind of shelter from rain, snow or hail. The same unit can be installed indoors. A preferable site for the WRH is a location free of obstructions, easily accessible and allows for proper air-flow and ventilation.
If a WRH is installed outdoors and can be exposed to direct sunshine, it is essential that air circulates around th
e WRH with no obstacles
to shade the WRH from direct sunshine.
Never open a WRH when rain, snow, hail, high humidity or high winds are present unless some kind of te
mporary shelte
r can be erected.
. The operating temperature must not exceed 131°F (55°C). A shelter can be used
Mounting
The WRH is easy to mount using the provided mounting bracket, which has 9/16-inch (14mm) holes for 3/8­inch (10mm) or 1/2-inch (12mm) fixing screws. Clamps with C-C measurements of 3.5-inch (90mm), 5.3-inch (135mm), 5.7-inch (144mm), 8.1-inch (205mm), 9.8-inch (250mm), and 11.8-inch (300mm) can be used as well. The vertical C-C measurement for these is 16.2-inch (411mm). There is a 9/16-inch (14mm) single hole in the middle of the mounting bracket, marked ‘A’ in the figure, which is intended for a locking screw to lock the bracket into place.
044-05251 Rev B 3-1
Mounting Nexus FT
90 135 144 205 250 300
Ø14
A
411
Figure 3-1 Mounting Bracket
Normally, the WRH is mounted on a wall, pole, or mast. Figure 3-2 illustrates the installation of the mounting bracket on a wall
using four fixing screws and a locking screw.
Figure 3-2 Mounting Bracket Installation on Wall
3-2 044-05251 Rev B
Nexus FT Mounting
Figure 3-3 illustrates the installation of the mounting bracket on a pole using two 5.7-inch (144mm) U-shaped clamps and a locking screw.
Figure 3-3 Attaching the Bracket to a Pole
Figure 3-4 illustrates a mast installation using two 11.8-inch (300mm) bar-shaped clamps and no locking
ew.
scr
Figure 3-4 Atta
ching the Bracket to a Mast
044-05251 Rev B 3-3
Connections Nexus FT
After installing the mounting bracket, hang the WRH on the upper supports, as illustrated in Figure 3-5. Tighten the upper and lower mounting screws to secure it into place using the 6mm hex socket wrench. Locking cylinders, used to prevent unauthorized removal of the repeater, can be inserted and locked with a key after the lower screws have been tightened. Make sure the donor antenna, directed towards the BTS antenna, and the service antenna, directed towards the area to be covered by the WRH, are mounted and installed properly.
Figure 3-5 Attaching the WRH to the Bracket
Connections
This section describes general examples of how to connect the input and output ports on the WRH.
Main Power and Grounding
Local regulations need to be followed for the main power connection. WRHs are approved in accordance with EN and UL/cUL regulations. This is, however, only valid if a classified power cord is used. For the Nexus FTto meet these regulati
EN – H 05 W5 - F HMRUL – AWM Style 2587CSA– AWM 1 A/B 11 A/B
For outdoor use, the power cord should meet at least IP65 encapsulation requirements. Do not turn the main power on until you ar
WARNING: For WRHs supplied from the main power source, the main outlet must be grounded.
Fiber Optic and RF Connections
Fiber optic and RF cable connections should be verified both internally and externally before powering up the equipment. This section illustrates the general internal connections of the WRH. Verify these connections with the as-built drawings and documents for your specific system configuration. Table 3-1 lists the steps to add the external connections to the WRH.
ons you must select one of the following classified and approved cord types:
e ready to commission the WRH.
3-4 044-05251 Rev B
Nexus FT Connections
1550
1310
Power connection
Fiber Optic Connection
Service Antenna Connection
Ground Points
Table 3-1 Cable Connection Procedure
Step Action
1 Connect service antenna coaxial cable to left-outside DIN connection on cabinet
2 Connect fiber optic cable from OCM or BMU to fiber optic cable demark on FOU
3 Connect station ground to appropriate ground point in cabinet
4 Mount main power plug to main power cord and insert into PSU
WRH
Figure 3-6 illustrates the cables and connections for the WRH.
044-05251 Rev B 3-5
Figure 3-6 WRH Cable Connections
Optional Connections Nexus FT
MS
DPX
ANT
TEST
DC
-30 dB
-20 dB
MS
DPX
ANT
TEST
DC
-30 dB
-20 dB
POWER SUPPLY UNIT
ALLGON INNOVATION SWEDEN M105 R6
1
PARKING FOR W5
W5
8
P27
W6B 10
1
P33
ALARM
P23 LNA
UP-LINK
P32
MODEM
A
U
X
1
P28 DOOR
5
9
6
1
1
16
1
1
M
-
>
S
P11
P34
8
9
15
P26
15 16
S
-
>
M
1
2
3
89
P
3
6
5
X0A
X0B
2
V2
1
16
P12 P13
1
1
1
16
16
16
P4
P5
P6
c b a
c b a
c b a
c b a
1P232
1
b a
1
16P3
16
1
16
P14
1
V1
1
1
1
1
1
4
6
1
15
6
9
15216
1
2
4
5
8
5
P35
P21 PSU
6
10
P31 PC
P29
P24
P25
GND
7
6V6
LNA
DOWN-LINK
LED P22
1
2
P28 P33
Optional Connections
Alarms
Alarm signals from external sensors are received by an ALI or RCI which forwards them to the CU. The RCI is used if the WRH has an RCU, otherwise the ALI is used. The software on the CU can activate acoustic or visual alarms or direct the alarm to the P33 alarm port for forwarding via an RCU through OM-Online. Alarms can also be handled by the FON. Alarms are configured through OM-Online.
External Alarm
Burglary, fire or other external alarms can be handled by the WRH. External alarm sensors and alarm signals are connected to the P33 alarm port located to the left in the cabinet, as illustrated in Figure 3-7. The P33 alarm port is described in Chapter 2. The cable for this installation is taken through a strain relief bushing at the bottom of the WRH cabinet.
Door Open Alarm
A door open alarm can be configured and installed in the WRH. This is arranged with a door switch connected to pin 8 (AI4) on P28, as described in chapter 2. The location of P28 is shown in Figure 3-7.
Figure 3-7 External Alarm Connection
Main Power Breakdown Relay
To be able to distinguish PSU faults from power failures, a main power breakdown relay can be used. This relay is not included in the WRH. It has to be mounted outside the WRH cabinet. The relay intended for this purpose must fulfil the following specifications:
Closing time: Max. 30 milliseconds
Insulation coil/contact: Min. 4KV
A main power connected relay must also be in compliance with valid local regulations. To install a main power
reakdown relay co
b
nnection, follow the steps listed in Table 3-2.
3-6 044-05251 Rev B
Nexus FT Commissioning
MS
DPX
ANT
TEST
DC
-30 dB
-20 dB
POWER SUPPLY UNIT
ALLGON INNOVATION SWEDEN M105 R6
1
PARKING FOR W5
W5
8
P27
W6B 10
1
P33
ALARM
P23 LNA
UP-LINK
P32
MODEM
A
U
X
1
P28 DOOR
5
9
6
1
1
16
1
1
M
-
>
S
P11
P34
8
9
15
P26
15 16
S
-
>
M
1
2
3
89
P
3
6
5
X0A
X0B
2
V2
1
16
P12 P13
1
1
1
16
16
16
P4
P5
P6
c b a
c b a
c b a
c b a
1P232
1
b a
1
16P3
16
1
16
P14
1
V1
1
1
1
1
1
4
6
1
15
6
9
15
2
16
1
2
4
5
8
5
P35
P21 PSU
6
10
P31 PC
P29
P24
P25
GND
7
6V6
LNA
DOWN-LINK
LED P22
1
2
P33:AICP33:AI1
Table 3-2 Main Power Breakdown Relay Connection
Step Action
1 Connect a currentless closed relay contact to pin AI1 and AIC on P33 alarm connector, as shown in
Figure 3-8. Alarm is initiated when pins AI1 and AIC are shorted
2 Connect relay coil. Coil must be supplied from same fuse as WRH
3 After commissioning, select Mains Breakdown in alarm configuration window in OM-Online. For
details on setting alarm configuration see OM-Online User Manual.
Figure 3-8 Main Power Breakdown Relay Connection
21-60 Volt DC PSU Installation
See the Field Replaceable Units, PSU section in Chapter 4 for details on replacing a 115/230 VAC PSU with a 21 to 60 Volt DC PSU.
Commissioning
Before proceeding, carefully read the Safety section and check all connections made during the installation. To fulfill the IP65 weather protective requirements, ensure cable strain relief bushings are properly tightened. Also, ensure gaskets at cable inlets and on the cabinet are properly fitted and not damaged.
044-05251 Rev B 3-7
Commissioning Nexus FT
MS
DPX
ANT
TEST
DC
-30 dB
-20 dB
POWER SUPPLY UNIT
ALLGON INNOVATION SWEDEN M105 R6
1
PARKING FOR W5
W5
8
P27
W6B 10
1
P33
ALARM
P23 LNA
UP-LINK
P32
MODEM
A
U
X
1
P28 DOOR
5
9
6
1
1
16
1
1
M
-
>
S
P11
P34
8
9
15
P26
15 16
S
-
>
M
1
2
3
89
P
3
6
5
X0A
X0B
2
V2
1
16
P12 P1 3
1
1
1
16
16
16P4
P5
P6
c b a
c b a
c b a
c b a
1P232
1
b a
1
16P3
16
1
16
P14
1
V1
1
1
1
1
1
4
6
1
15
6
9
15
2
16
1
2
4
5
8
5
P35
P21 PSU
6
10
P31
PC
P29
P24
P25
GND
7
6V6
LNA
DOWN-LINK
LED P22
1
2
P31
A WRH can be configured locally with OM-Online by connecting a standard serial cable from the COM port on the PC to the P31 PC port (RS-232) located to the right in the cabinet as shown in Figure 3-9. The P31 PC port is described in Chapter 2. Details on using OM-Online are described in the OM-Online User Manual.
Initial Startup
To complete the inital start-up of the WRH, follow the steps listed in Table 3-3.
Step Action
1 Turn main power on
Figure 3-9 Connecting a PC for Local Access
Table 3-3 Initial Statup Procedure
2 Check Yellow LED on power supply unit. Steadily lit = functioning correctly
3 Check the four CU PCBA LEDs. Refer to CU PCBA section in Chapter 2 for correct power up
ications
ind
4 Check the thre
section in Chapter 2 for
e ALI PCBA LEDs or corresponding LEDs on RCI PCBA. Refer to ALI or RCI PCBA
correct power up indications
NOTE When optimizing WRHs, offset the UL gain 20dB less than the DL gain as a starting point.
Always monitor the UL pass bands for noise levels and/or IMDs when optimizing and commissioning
.
For CDMA carriers, ensure that the UL pass band is well above the noise floor.
3-8 044-05251 Rev B
Nexus FT Commissioning
(
Passive Intermodulation (PIM) Testing
PIM is the non-linear effect of passive RF components in a desired RF transmission band. As higher per­carrier transmit power levels are applied to duplexed passive RF networks, PIM becomes an increasingly significant factor in potential receiver desensitization. A PIM tester may be used on the RF network prior to turn-on and commissioning of the unit, but if a PIM tester is not available, the following may be used:
The following equipment is required to test for PIM:
Anritsu Site eMaster or equivilent RF Spectrum AnalyzerAgilent ESG4432B or equivilent Multi-Signal Generator (or commissioned BTS)Guarateed/calibrated PIM load capable of handling 20W composite powerLow-PIM RF cable adaptors such as N-N female, Din male to N femaile, DIN-DIN, SMA-SMA
female, and N male to SMA female
Installed and operational WRH unitInstalled passive RF network under testTorque wrenches for DIN and N connectors
Two different types of setup are available, depeding on equipment availability and testing methods. Figure 3-10 shows PIM testing with two carriers over one WRH, and Figure 3-11 shows PIM testing with one carrier over each of two WRHs.
E4432B
SIG Gen
or BTS)
E4432B SIG Gen (or BTS)
Σ
OCM
E4402B
Spec. An.
WRH-V
Load /
DAS
Figure 3-10 PIM testing two carriers and one WRH
E4432B
Sig Gen /
BTS 1
E4432B
Sig Gen /
BTS 2
OCM
OCM
WRH-V
WRH-V
Under Test
E4402B
Spec. An.
Hybrid
Load /
DAS
Figure 3-11 PIM testing one carrier over each of two WRHs
The following PIM test uses the receive sensitivity and gain of the WRH under test to verify that the receive
ath is free of PIM n
p
oise. For PIM to be a problem at a particular site, TX signals must exist such that their
products fall into the RX band using the formulae:
3rd order product = (2 * f1) - f
2
and
3rd order product = (2 * f2) - f
1
044-05251 Rev B 3-9
Commissioning Nexus FT
Where f1 and f2 are two TX signals entering a WRH. The specification for the maximum allowed PIM is -115 dBm per 100 kHz resolution bandwidth at rated output power. To test for PIM follow the steps listed in Table 3-4.
Table 3-4 PIM Testing Procedure
Step Action
1 If BTS signals are present, continue with step 2. Otherwise, connect two signal generators to OCM
and set frequencies such that products are in relevent receive band (see equations above)
2 Set WRH UL gain to 60 dB and DL gain such that desired per carrier power is presented at output
port
3 Set Spectrum Analyzer to 100 kHz resolution bandwidth and view RX band at 3rd order product
frequency calculated in step 1
4 Loosen fastening screw in each corner on front cover of WRH under test, and open cover
5 Verify the noise floor specification for the Spectrum Analyzer. If the noise floor is higher than or equal
to -85 dBm/100 kHz, locate FON, disconnect UL cable from port P101 and connect SpectrumAnalyzer to the cable using an SMA female - female connector (noise limit becomes -115 dBm + 60 dB = -55 dBm). Continue with step 7.
6 If noise floor is lower than -85 dBm/100 kHz, locate the FON card and connect the Spectrum Analyzer
to P117 (noise limit becomes -115 dBm + 60 dB - 30 dB = -85 dBm). If the FON only has three RF ports on the left side, port P117 will not be available, so follow instructions listed in step 5.
7 Enable WRH TX signal. For details on using OM-Online, see OM-Online user manual
8 Using Spectrum Analyzer, measure noise level. If no noise exists above calculated limit in step 5
(-55 dBm) or step 6 (-85 dBm) above, as appropriate, then test is passed and no other action is necessary
9 If a higher level of noise exists, disable the WRH TX signal and disconnect cable to DAS at bottom-
left outside corner
10 Connect low PIM load onto WRH Service antenna connector at bottom-left outside corner. Tighten
connectors securely
11 Remeasure noise level. If no noise exists above calculated limit in step 5 (-55 dBm) or step 6 (-85
dBm) as appropriate, then DAS has a PIM issue. Tighen all connections in DAS with torque wrenches, replace any cripmed or severely bent cables, and retest. Repeat until all issues are solved
12 Otherwise, if noise is higher than limit, WRH is defective and must be replaced. See Chapter 4 for
Replacement procedures
3-10 044-05251 Rev B
Chapter 4
Maintenance
Introduction
This chapter contains periodic maintenance and performance test procedures for the WRH.
Periodic Maintenance
Periodic maintenance requirements are listed in Table 4-1, as well as the intervals at which the tasks should be performed.
Table 4-1 Recommended Periodic Maintenance
Task Interval Action
Inspection of cables and connectors
Clean equipment Clean as required depending on operating environment
12 months Inspect power, RF and Fiber cables for signs of damage or wear
(frayed insulation, cracks, punctures, etc.) Check connections to be sure they are tight
Optional Perform cable sweeps
Troubleshooting
The sections that follow contain a list of problems that could occur and a few suggested actions that might correct each problem. If the suggested corrective action does not eliminate the problem, please contact your Powerwave field representative or help line for further instruction.
Clearing Alarm Faults
Table 4-2 lists the alarms that can be generated in the WRH. Critical, Error and Warning alarms are sent automatically from a WRH to OM-Online, stored and then viewed in the Alarm window.
Table 4-2 Alarm Troubleshooting
ID Alarm Text Alarm Unit Alarm Description
1 Power PSU Critical PSU1 in the cabinet does not work properly. A sum signal from
the PSU1 indicates no mains breakdown relay is used, then the alarm will also be sent at mains breakdown
Ceasing PSU1 in the cabinet works properly again. Ceasing is sent if the
PSU1 works at sta PSU1 alarm logged in the Events log. The WRH will restart when the power is back and this alarm will be sent
that at least one voltage output has dropped. If
rt-up, and there is a corresponding critical
PSU Critical PSU2 in the cover does not work properly. A sum signal from the
PSU2 indicates that at le mains breakdown relay is used, then the alarm will also be sent at mains breakdown
044-05251 Rev B 4-1
ast one voltage output has dropped. If no
Troubleshooting Nexus FT
Table 4-2 Alarm Troubleshooting (Continued)
ID Alarm Text Alarm Unit Alarm Description
Ceasing PSU2 in the cover works properly again. Ceasing is sent if the
PSU2 works at start-up, and there is a corresponding critical PSU2 alarm logged in the Events Log. The WRH will restart when the power is back and this alarm will be sent
Power FON Error The FON 10 Volt charger voltage is below limit. Suggested
remedy: Replac
Ceasing The cause of the alarm has ceased
2 WRH restart CU None Power on start, or user ordered reboot. Logged to indicate a
normal power up
Warning Software error restart, 1st – 7th time. Restart 1st to 7th time during
a 14 day period. The co
from power up
Error Software error restart 8th – 10th time. Restart 8th to 10th time
uring the 14 day
d blocked and not used anymore until a user ordered reset is performed, or power is switched off/on
e the FON
, or a restart ordered by the operator
unter is reset every 14th day, counted
period. At the 11th time, the SW bank will be
3 Mains
breakdown
4 Alarm reset CU None Alarm reset by the user. All alarms are reset. The cause of the
5 Local bus
error
6 Main bkd w
backup
7 Err in AD-
converter
8 New unit
detected
9 Inst. unit lost Error Compared to the last power on, the CU lacks at least one
External Crit
WBA #, MCPA#
External Error Used to
ical The mains power is gone. Used with an external relay indicating
mains breakdown. The external relay should be connected to External Alarm 1 and the WRH configured to indicate this alarm. If no relay is used, a mains breakdown will be reported as a PSU fault
Ceasing The mains power is back. Sent if there is a corresponding critical
mains breakdown alarm logged in the Events Log. The WRH will restart when the power is back
larm will be
a
Error Error when com
with the WBA, or MCPA PCBA, which is taken out of service
powered by external battery backup unit. Suggested remedy: Check the mains power
Ceasing The cause of the alarm has ceased
Warning The ana
reliable values
None Compared
one additional hardware unit
hardware unit
re-evaluated and reported, if still active
municating on the bus. The CU has no contact
indicate that the mains is no longer available. WRH is
log-to-digital converter on the CU PCBA does not give
to the last power on, the CU has recognized at least
10 EEPROM
r
erro
11 Log memory
lt
fau
CU Error EEP read or write fail
EEPROM on the CU PCBA. User parameters are stored in the EEPROM
Error Log memory
is faulty. The WRH will not work. Not available in all CU software versions
fault. Indicates that the log memory on the CU PCBA
. Data cannot be written or read from the
4-2 044-05251 Rev B
Nexus FT Troubleshooting
Table 4-2 Alarm Troubleshooting (Continued)
ID Alarm Text Alarm Unit Alarm Description
12 High temp CU Warning The CU PCBA temperature is higher than 90°C
Ceasing The CU PCBA temperature has fallen below 90°C
13 REFO error Error Significant REFO drift or error detected by CU
14 Ext REFO
error
15 CU battery
fault
16 SW load error CU Error Software load error. An error has occurred during a software load
17 Log cleared CU None Log memory has been cleared. The check sum in the Events Log
18 RTC restarted CU None The time is changed by the operator (logged to keep track of
19 RTC error Error RTC does not operate. The CU has detected an error in the RTC
CU Warning CU RAM b
Warning Suggested remedy: Check the reference source and the cables
attery fault. The battery for the RAM on the CU PCBA has a voltage outside the normal 2.7 to 3.5 Volt. An alarm may be initiated at start-up if the WRH has been stored out of power for a long time. Suggested remedy: Ensure jumper P3 on the CU PCBA is mounted to charge the battery
Ceasing The cause of the alarm has ceased
process. The flash memory does not contain a proper software. Suggested remedy: Check the CU software using the OM-Online SW Manager. Do NOT restart the WRH
memory is faulty. The battery backup or low voltage to the RAM
anges made to the RT
ch
Warning Time reset to 1994-01-01. The RTC was unable to keep track of
the time and did a rese the CU PCBA is mounted to charge the battery
ration which mak
ope Replace the CU PCBA
log is cleared. Can be caused of a bad RAM
C)
t. Suggested remedy: Ensure jumper P3 on
es the time unreliable. Suggested remedy:
20 Door open
alarm
21 External
alarm 1
22 External
alarm 2
23 External
alarm 3
24 External
alarm 4
External Config The door has been open 30 seconds without disabling the alarm
Ceasing The door has been closed 30 seconds, or the alarm is disabled
External Confi
External Confi
External Confi
External Confi
g External alarm input EA1 active more than 1 second
Ceasing External alarm input EA1 no longer active
g External alarm input EA2 active more than 1 second
Ceasing External alarm input EA2 no longer active
g External alarm input EA3 active more than 1 second
Ceasing External alarm input EA3 no longer active
g External alarm input EA4 active more than 1 second
Ceasing External alarm input EA4 no longer active
044-05251 Rev B 4-3
Troubleshooting Nexus FT
Table 4-2 Alarm Troubleshooting (Continued)
ID Alarm Text Alarm Unit Alarm Description
30 No modem
found
33 No
connection
34 Login failed None Invalid WRH password
35 Remote
connection
36 Modem init
failed
37 Remote
eout
tim
38 PIN code
failed
Remote ctrl None No modem found, that is no answer is returned on a poll string to
the modem
Remote c
Remote c
Remote ctrl None Initiation string to modem not OK. The initiation string sent to the
Remote ctrl Wa
Remote ctrl Wa
trl None No connection at callback. The WRH has tried to call as many
times as stated in the alarm call settings. No connection was established.
Warning No connection at alarm call. The WRH has tried to call as many
times as stated in the alarm call settings. No connection was established. This alarm does not generate a new attempt to report alarm by alarm call.
trl None Modem connection to OM-Online opened. Not logged on CU2.
Login Registry gives the same function and more information
about CU2
modem is not OK. The string may contain commands not recognized by the modem. An alarm might be sent anyway. Suggested remedy: Check the modem using the OM-Online or OMS modem debugger
rning The time limit of 20 minutes is exceeded without extending the
timer. The modem connection is terminated by the WRH
rning The PIN code sent to MS is incorrect. To unlock the MS/SIM card,
the PUK code will probably be needed
39 No phone
detected
40 Battery fault RCU, FON
42 Antenna
isolation
48 Battery
backup fault
Remote ctrl Wa
charger
WBA #, Channel # UL/DL
External Error If
Ceasing The cause of the alarm has ceased
rning When using a PC-card together with the MS, the alarm indicates
contact with the PC-card, but MS is not present or turned off. Note: A Nokia MS does not power-up after power failure. Suggested remedy: Ensure the cellular phone is connected
Ceasing The cause of the alarm has ceased
Error The b
Ceasing The cause of the alarm has ceased
Warning Low antenna isolation. The antenna isolation is lower than the
,
Error Low antenna isolation at lowest gain. The gain has been reduced
Ceasing Normal operation again, that is no oscillation can be detected
ackup battery on the RCU or the FON PCBA does not work
properly. Suggested remedy: Check cables or replace battery
gain set. Gain is reduced by 10dB – 13dB below the oscillation point. Suggested remedy: Decrease gain or increase antenna isolation
as much as poss is turned off. Suggested remedy: Decrease gain or increase antenna isolation
13dB above the g
a battery backup unit alarm is connected to external alarm 2, then the operator can configure the WRH to display this alarm when the battery backup unit indicates alarm
ible but the oscillation still remains. The amplifier
ain set
4-4 044-05251 Rev B
Nexus FT Troubleshooting
Table 4-2 Alarm Troubleshooting (Continued)
ID Alarm Text Alarm Unit Alarm Description
Ceasing The cause of the alarm has ceased
50 Fiberoptical
error
70 Bad table
alarm
71 Table not
found
72 Table
database error
80 Antenna
SWR alarm
90 FON power
alarm
91 FON
TxStable alarm
FOT fiber optics
CU Error Requested table contains incorrect information (SW error)
CU Error Requested tabl
CU Error Tabl
Donor antenna service antenna
FON RF Error A DC voltage on
FON RF Error Laser trans
Configur able
Ceasing The cause of the alarm has ceased
Error Too low antenna return loss, caused either by cables, connectors,
Ceasing The cause of the alarm has ceased
Ceasing The cause of the alarm has ceased
If a fiber unit alarm is connected to external alarm 3, then the operator can configure the WRH to display this alarm when the fiber optical unit indicates alarm
e not found in the database (SW or calibration
error)
e database not found (calibration error)
or antenna problems.
Suggested remedy: Check antenna and cables
a FON PCBA is out of range. Suggested remedy:
Replace the FON PCBA.
mitter control loop voltage out of range. Suggested
remedy: Replace the FON PCBA
Ceasing The cause of the alarm has ceased
92 FON RxLevel
alarm
93 FON SPI
arm
al
245 Not In
Allowed Area
FON Warning Received optical level is below any of the two limits (one for
Warning and one for Error). Suggested remedy: Check optical cables
Error Received optical level is below any of the two limits (one for
Warning and one for Error). Su cables
Ceasing The cause of the alarm has ceased
FON F2F Error The SPI bus conn
Suggested remedy: Replace the FON PCBA
CU None WRH is
switched on or off
moved from the operating area and the RF HW is
ection to the RF modem does not work properly.
ggested remedy: Check optical
Remarks:
The Door Open alarm requires an optional door switch described in the Door Open Alarm section of Chapter 3.
The Main power breakdown alarm requires an optional relay described in the Main Power Breakdown Relay section of Chap
ter 3.
044-05251 Rev B 4-5
Field Replaceable Units Nexus FT
Field Replaceable Units
The following units can be replaced in the field on-site by a qualified technician with experience maintaining RF equipment:
FONPSUWRH
FON
To replace a FON PCBA, follow the steps listed in Table 4-3. For details on cables and connectors, see Chapter 2.
CAUTION: Do not look into the end of any fiber optic cable. Be sure to cap fiber optic cables to protect the connecting end from damage
CAUTION: Use of controls or adjustments or performance of procedures other than those specified herein may result in hazardous radiation exposure"
NOTE
Verify ‘Fiberoptical’ classmark in the FON Status window is checked, otherwise FON will not be operational. Classmarks are described in the OM-Online User Manual. Verify that the keyed angle polished connectors are aligned properly before tightening. Improper alignment
n result in high si
ca
gnal loss and/or no connectivity with that node.
Table 4-3 FON Replacement Procedure
Step Action
1 Loosen all four locking screws on front of cabinet
2 Open WRH door and secure
3 Locate power connector on FON and remove connector from PCBA
4 Verify all cables on FON are labeled before disconnecting, then disconnect all cables.
5 Remove screws securing FON PCBA to FOU and remove PCBA
6 Replace FON PCBA in reverse order and apply power
7 Connect PC to OM Online port, login to FON and verify configuration and IP address.
8 Close WRH door and secure
NOTE
After replacing the FON, if measurements taken at the fiber connector are correct but the OM Online measurement indicates a loss several dB higher, the likely causes are:
1) Dirty fiber.
2) The DIN to FC bulkhead adapter is bad.
3) Loose fiber connection on the FON board.
4) Bad WDM.
4-6 044-05251 Rev B
Nexus FT Field Replaceable Units
4
5
6
PSU
To replace a PSU, follow the steps listed in Table 4-4. For details on cables and connectors, see Chapter 2.
Figure 4-1 PSU Cable, Switch and Lable locations
Table 4-4 PSU Replacement Procedure
Step Action
1 Loosen all four locking screws on front of cabinet
2 Open WRH door and secure
3 Disconnect main power plug from PSU(Location 1 shown in Figure 4-1)
4 Disconnect power cable bundle from PSU(Location 2 shown in Figure 4-1)
5 Loosen but do not remove screws securing PSU using a 5mm Allen key and remove PSU (Location 3
own in Figure 4-1)
sh
6 On new AC power supply, if used, set input voltage switch on PSU to correct input voltage -- 115 VAC
or 230 VAC (Location 4 s
7 On new DC power supply, if used, verify that the supply voltage is 24 VDC or 48 VDC as stated on
label on PSU (Locat
8 Set new PSU to correct output supply voltage (27 VDC) by moving wire connection plug as illustrated
on label on PSU (Loc
9 Mount new PSU with all four fixing screws (Location 3 shown in Figure 4-1)
10 Connect PSU to DIA PCBA (Location 2 shown in Figure 4-9) with cable marked VE007 98/1. This
cable must be u connector may be tied out of the way with a cable tie
11 Insert power cord (AC power supply) or connect DC power cable brown wire (Europe) or black wire
positive (+) pole a
(US) to supply)
sed in all situations. If only one connection is available on DIA PCBA, the second
hown in Figure 4-1)
ion 5 shown in Figure 4-1)
ation 6 shown in Figure 4-1)
nd blue wire (Europe) or white wire (US) to negative (-) pole (DC power
12 Close WRH door and secure with four locking screws on front of cabinet
044-05251 Rev B 4-7
Remote Control Unit (RCU) Nexus FT
MS
DPX
ANT
TEST
DC
-30 dB
-20 dB
MS
DPX
ANT
TEST
DC
-30 dB
-20 dB
ALLGON INNOVATIO N SWEDEN M105 R6
1
PARKING FOR W5
W5
8
P27
W6B 10
1
P33
ALARM
P23 LNA
UP-LINK
P32
MODEM
A
U
X
1
P28 DOOR
5
9
6
1
1
16
1
1
M
-
>
S
P11
P34
8
9
15
P26
15 16
S
-
>
M
1
2
3
89
P
3
6
5
X0A
X0B
2
V2
1
16
P12 P13
1
1
1
16
16
16
P4
P5
P6
c b a
c b a
c b a
c b a
1P232
1
b a
1
16P3
16
1
16
P14
1
V1
1
1
1
1
1
4
6
1
15
6
9
15
2
16
1
2
458
5
P35
P21 PSU
6
10
P31
PC
P29
P24
P25
GND
7
6V6
LNA
DOWN-LINK
LED P22
1
2
POWER SUPPL Y UNIT
RCU
WRH
To replace a WRH, follow the steps listed in the Table 4-5.
WARNING: A fully loaded WRH can weigh 96lbs. Lifting of the WRH should be done by two people. Do not attempt to carry the WRH up a ladder.
.
Table 4-5 WRH Replacement Procedure
Step Action
1 Loosen all four locking screws on front of cabinet
2 Open WRH door and secure
3 Disconnect main power plug from PSU
4 Verify all external cables connected to WRH are labeled before disconnecting, then disconnect all
xternal cables
e
5 Remove mounting screws from bottom legs of WRH and loosen mounting screws in top legs
6 Close and secure door
7 Lift the WRH off of mount hinges
8 Replace WRH in reverse order
9 Connect PC to OM Online port and verify configuration. For Fiber Optic installations, verify IP
ddress
a
10 Close WRH d
oor and secure
Remote Control Unit (RCU)
The RCU provides remote control of Powerwave WRHs. It contains an integrated mobile phone, modem and power supply backup. The RCU is installed in the bottom front of the cabinet, on top of the PSU as illustrated in Figure 4-2.
The RCU is connected to P130 on either an RCI or FON. A jumper is required between pins 1 and 2 on the
CI if the P130 ca
R enough capacity for sending a number of alarms.
ble connector is disconnected. If a main power failure occurs, the unit has a battery with
Figure 4-2 RCU in the WRH cabinet
4-8 044-05251 Rev B
Nexus FT Return For Service Procedures
RCU for Radio Communication
The RCU antenna for a radio modem is connected to the BS antenna via the uplink DC, provided the RCU and the WRH operate in the same cell system. Otherwise, the modem must have a separate antenna. Data is transferred between the WRH and the RCU via the P130 modem port on the RCI or FON. The RCU is also powered via the same port and has a battery with enough capacity to send a number of alarms if a main power failure occurs.
RCU for Telephone Line Communication
The land line version uses a telephone line connected to a terminal block on the RCU. A free strain relief bushing at the bottom of the WRH is used for the external telephone line cable.
Return For Service Procedures
When returning products to Powerwave, the following procedures will ensure optimum response.
Obtaining an RMA
A Return Material Authorization (RMA) number must be obtained prior to returning equipment to the factory for service. Pease contact our Repair Department at +1-714-466-1000 to obtain this number, or FAX your request to +1-714-466-5800. Failure to obtain this RMA number may result in delays in receiving repair service.
Repackaging for Shipment
To ensure safe shipment of the unit, it is recommended that the original package designed for shipping the unit be reused. If it is not available, contact Powerwave’s Customer Service Department at 1-800-797-9283, +1-714-466-100 or by e-mail at support@pwav.com for packing material.
044-05251 Rev B 4-9
Return For Service Procedures Nexus FT
This page intentionally left blank
4-10 044-05251 Rev B
Introduction
This chapter provides specifications for the WRH.
Table 5-1: WRH Specifications
Electrical
Frequency band UL 824 to 849 MHz (Cellular)
806 to 824 MHz (800 iDEN) 880 to 915 MHz (GSM 900) 896 to 901 MHz (900 iDEN) 1710 to 1785 MHz (GSM 1800) 1850 to 1910 MHz (PCS) 1920 to 1980 MHz (UMTS) 1710 to 1755 MHz (AWS 2100)
Frequency band DL 869 to 894 MHz (Cellular)
851 to 869 MHz (800 iDEN) 935 to 940 MHz (GSM 900) 925 to 960 MHz (900 iDEN) 1805 to 1880 MHz (GSM 1800) 1930 to 1990 MHz (PCS) 2110to 2170 MHz (UMTS) 2110 to 2155 MHz (AWS 2100)
Chapter 5
Specifications
Max absolute delay <300 ns
Gain adjustment range (in 1 dB steps) 30 dB
Gain
Uplink Downlink Variation
Instantaneous bandwidth 25 MHz (Cellular)
Uplink AGC limit 0 dBm at FON input
Downlink AGC limit 43 dBm at antenna port
Return Loss 11 dB
35 to 60 dB typical - Excluding fiber link 45 to 70 dB typical - Excluding fiber link ± 1.5 dB versus temperature including fiber link ± 1.5 dB versus DL frequency including fiber link ± 0.5 dB versus DL output power including fiber link ± 0.5 dB versus input voltage including fiber link ± 2.0 dB versus UL frequency including fiber link
18 MHz (800 iDEN) 35 MHz (GSM 900) 5 MHz (900 iDEN) 75 MHz (GSM 1800) 60 MHz (PCS) 60 MHz (UMTS) 45 MHz (AWS)
044-05251 Rev B 5-1
Introduction Nexus FT
Table 5-1: WRH Specifications (Continued)
Downlink, Spurious and Emissions level -13 dBm/1 MHz (FCC)
-36 dBm (below 1 GHz, per ETSI EN 300 609-4)
-30 dBm (above 1 GHz, per ETSI EN 300 609-4)
Downlink power +43 dBm RMS (20 Watts) (for FCC - UMTS)
+40 dBm RMS (10 Watts) (for ETSI - GMS/EDGE)
Noise figure excluding fiber optic link 4 dB
Fiber-Optic Link Budget 10 dBo
Receiver input port return loss 14 dB
Power supply voltage 115/230 VAC
21-60 VDC
Maximum Current Draw (Single Band) 6 A @ 115 VAC
3 A @ 230 VAC 15A @ 21-60 VDC
Maximum Current Draw (Dual Band) 6 A @ 115 VAC
3 A @ 230 VAC 15A @ 21-60 VDC
Recommended Fuse size Single Band
10 A for AC voltage 20 A for DC voltage
Dual Band
Power consumption 210 W typical, 300 W max (Single band)
Impedance
Input Output
Mechanical
Dimensions (W x H x D in inches) 465 x 530 x 195 mm (18.3 x 20.9 x 8.3 in) incl. hinges (low cover)
Weight <25 kg (55 lbs) low cover
Service Antenna port connector 7/16 DIN Female
Donor Optical port connector FC/APC
Environmental
Operating Temperature Range -25 °C to +55 °C (-13°F to +131°F)
Altitude -142 m to 4000 m (-466 ft. to 13100 ft.
Casing class NEMA4/IP65
20 A for AC voltage 40 A for DC voltage
420 W typical, 600 W max (Dual band)
Not Applicable - Optical input 50 Ω
465 x 530 x 310 mm (18.3 x 20.9 x 12.3 in) incl hinges (high cover)
<44 kg (96 lbs) high cover
Fiber Optic Node (FON)
Bandwidth @ 3dB 800 – 2200 MHz
Power Consumption, total <5 W
5-2 044-05251 Rev B
Nexus FT Introduction
Table 5-1: WRH Specifications (Continued)
Wavelength TX: DFB 1310 or 1550 nm
RX: 1250 – 1600 nm
Transmit
Max continuous RF input Optical output power, two levels RF attenuation settable by SW in 1dB steps
Receive
Max optic power input RF attenuation settable by SW in 1dB steps Alarm threshold level, settable warning Alarm threshold level, settable error
+36dBm +3 or 0dBm 0-20dB
+5dBm 4-24dB 0-40dBm 0-40dBm
044-05251 Rev B 5-3
Introduction Nexus FT
This page intentionally left blank
5-4 044-05251 Rev B
Appendix A
WDM
FOU
DX
DX
DPX
DPX
WBA
WBA
DL
DL
UL
UL
LNA
LNA
MCPA
MCPA
To/From
OCM or
BMU
RCU
RCI
PSU
CU
FON
ALI
To
External
alarms
850 MHz
TX0/RX0
1900 MHz
TX0/RX0
Block Diagrams
Introduction
This appendix describes the main signals paths for the WRH.
Non-Diversity
Figure A-1 shows the non-diversity block diagram configuration of the WRH. The WRH is always fed by a BTS via either a BMU or an OCM. The TX signal from the BTS is converted to an optical signal in a BMU or OCM and fed to the WRH via a fiber optic cable. The optical signal is then received by the FON and converted to an RF signal. The FON supervises the signaling and reports errors via the RCU connected to the CU.
The RF signal enters the WBA, is amplified, and further amplified in amplifier stages followed by controllable
ttenuators. Th
a amplified output signal passes the DPX before it is fed to the service antenna.
The uplink signal path is located on the same WBA but goes through an LNA before entering the WBA.
e signal exits the WBA and enters the MCPA where it is amplified and fed to the DPX. The
Figure A-1 WRH Block Diagram - Non-Diversity
044-05251 Rev B A-1
Diversity Nexus FT
WDM
DX
DX
DPX
WBA
DL
LNA
MCPA
To/From
OCM or
BMU
RCU
RCI
PSU
CU
FON
ALI
To
External
alarms
FOU
DX
LNA
DPX
DPX
WBA
LNA
MCPA
LNA
DPX
UL
DL
FON
1900 MHz
TX0/RX0
850 MHz
TX0/RX0
850 MHz
RX1
1900 MHz
RX1
UL
UL
UL
Diversity
Figure A-2 illustrates the diversity block diagram configuration of the WRH. With diversity installed, there are two paths on the UL instead of one. This requires an additional FON for the added receive path signal. Signal flow is identical to the non-diversity version with the MCPA on the DL and LNAs on the UL providing the additional amplification out of and into the WBA.
Figure A-2 WRH Block Diagram - Diversity
A-2 044-05251 Rev B
Powerwave Installation and Service Manual
Worldwide Corporate Headquarters
801 East St. Andrew Place
anta Ana, CA 92705 USA Tel: 714-466-1000 Fax: 714-466-5800 www.powerwav e.com
©Copyright 2008, Powerwave Technologies, Inc. All Rights reserved. Powerwave, Powerwave Technologies, The Power in Wireless and the Powerwave logo are registered trademarks of Powerwave Technologies, Inc.
Main European Office
Knarramasgatan 7 8tr 164 40 Kista, Sweden Sweden Tel: +46 8 540 822 00 Fax: +46 8 540 824 91
Main Asia-Pacific Office
23 F Tai Yau Building 181 Johnston Road Wanchai, Hong Kong Tel: +852 2512 6123 Fax: +852 2575 4860
Loading...