Powerwave Technologies 5JS0098 Users manual

INDOOR MCPA PLATFORM
PAF
INDOOR MCPA PLATFORM
INSTALLATION AND SERVICE MANUAL
PAF-19XX-EX-XXX
044-05298 Rev A November 2007
© 2007 Powerwave Technologies Incorporated. All rights reserved.
This Powerwave product is intended only for installation in a RESTRICTED ACCESS LOCATION and is designed to operate within the Normal Operating (typical operating) ranges or conditions specified in this document. Operation of this equipment beyond the specified ranges in this document may cause:
1. Spurious emissions that violate regulatory requirements.
2. The equipment to be automatically removed from service when maximum thresholds are exceeded.
3. The equipment to not perform in accordance with its specifications.
It is the Operator's responsibility to ensure this equipment is properly installed and operated within Powerwave operat­ing specifications to obtain proper performance from the equipment and to comply with regulatory requirements.
For PERMANENTLY CONNECTED EQUIPMENT, a readily accessible disconnect device shall be incorporated in the building installation wiring.
PAF-19XX-EX-XXX Warnings, Cautions, and Notes
Warnings, Cautions, and Notes
Warnings, Cautions, and Notes are found throughout this manual where applicable. The associated icons are used to quickly identify a potential condition that could result in the consequences described below if precautions are not taken. Notes clarify and provide additional information to assist the user.
WARNING: This warning symbol means danger. You are in a situation that could cause bodily injury. Before you work on any equipment, be aware of the hazards involved with electrical and RF circuitry and be familiar with standard practices for preventing accidents
NOTE
CAUTION: This caution symbol means reader be careful. In this situation, the user might do something that could result in equipment damage or loss of data.
This note symbol means reader take note. Notes contain helpful suggestions or references to material not covered in the document. Procedures are not contained in notes.
044-05298 Rev A i
Revision Record PAF-19XX-EX-XXX
Revision Record
Revision Letter Date of Change Reason for Change
A November 2007 Initial release
ii 044-05298 Rev A
Table of Contents
Chapter 1 - Product Description
Introduction ................................................................................................................................................... 1-1
Scope of Manual ........................................................................................................................................... 1-1
Product Description ....................................................................................................................................... 1-1
Functional And Physical Specifications ........................................................................................................ 1-1
Chapter 2 - Controls and Indicators
Introduction ................................................................................................................................................... 2-1
Subrack ......................................................................................................................................................... 2-1
Ethernet Connector Pinout ..................................................................................................................... 2-2
RS-485 Interface .................................................................................................................................... 2-3
Filter I/O (if used) .................................................................................................................................... 2-3
MCPA ............................................................................................................................................................ 2-3
Filter (if used) ................................................................................................................................................ 2-4
Circuit Breaker Panel .................................................................................................................................... 2-6
Chapter 3 - Installation
Introduction ................................................................................................................................................... 3-1
Site Survey .................................................................................................................................................... 3-1
Space Requirements .................................................................................................................................... 3-1
Unpacking and Inspection ............................................................................................................................. 3-1
Electrical Service Recommendations ........................................................................................................... 3-1
Cooling Requirements .................................................................................................................................. 3-2
Installation Instructions ................................................................................................................................. 3-2
PAF ......................................................................................................................................................... 3-2
Seismic Brace (Optional) ........................................................................................................................ 3-3
DC Connections ..................................................................................................................................... 3-3
RS-485 Alarm Interface .......................................................................................................................... 3-5
MCPA ..................................................................................................................................................... 3-5
Initial Start-Up and Power Setting Procedures ............................................................................................. 3-6
Initial Start Up ......................................................................................................................................... 3-6
Chapter 4 - Maintenance
Introduction ................................................................................................................................................... 4-1
Periodic Maintenance ................................................................................................................................... 4-1
Troubleshooting ............................................................................................................................................ 4-1
Clearing Alarm Faults ............................................................................................................................. 4-2
System Component Part Numbers ............................................................................................................... 4-2
Field Replacement Procedures ..................................................................................................................... 4-2
MCPA ..................................................................................................................................................... 4-3
Subrack Cooling Fans ............................................................................................................................ 4-4
Inside Mount .................................................................................................................................... 4-4
Rear Mount ...................................................................................................................................... 4-5
Fan Inside Mount to Rear Mount Conversion .................................................................................. 4-6
Subrack .................................................................................................................................................. 4-7
Filter ........................................................................................................................................................ 4-8
Circuit Breaker Panel .............................................................................................................................. 4-9
Return For Service Procedures .................................................................................................................. 4-10
Obtaining An RMA ................................................................................................................................ 4-10
Repackaging For Shipment .................................................................................................................. 4-10
Chapter 5 - Specifications
Introduction ................................................................................................................................................... 5-1
044-05298 Rev A i
PAF-19XX-EX-XXX List of Tables
List of Tables
2-1 Subrack Faceplate Interface Connectors, and Indicators ........................................................................ 2-2
2-2 Ethernet Connector Pinout....................................................................................................................... 2-2
2-3 RS-485 Pinout.......................................................................................................................................... 2-3
2-4 MCPA Indicators and Controls................................................................................................................. 2-4
2-5 Filter Connector Descriptions................................................................................................................... 2-5
3-1 Sample of DC Cable Ratings ................................................................................................................... 3-2
3-2 PAF Frame Installation Procedure........................................................................................................... 3-3
3-3 DC Power Installation Procedure............................................................................................................. 3-4
3-4 RS-485 Alarm States ............................................................................................................................... 3-5
3-5 MCPA Installation Procedure................................................................................................................... 3-6
3-6 Initial Startup Procedure .......................................................................................................................... 3-6
4-1 Periodic Maintenance .............................................................................................................................. 4-1
4-2 Troubleshooting ....................................................................................................................................... 4-2
4-3 System Components Part Number List.................................................................................................... 4-2
4-4 MCPA Removal and Replacement Procedure......................................................................................... 4-3
4-5 Inside Mount Cooling Fan Removal and Replacement Procedure .......................................................... 4-4
4-6 Rear Mount Cooling Fan Removal and Replacement Procedure............................................................ 4-5
4-7 Fan Conversion Procedure ...................................................................................................................... 4-6
4-8 Subrack Removal and Replacement Procedure...................................................................................... 4-7
4-9 Filter Removal and Replacement Procedure ........................................................................................... 4-8
4-10 Circuit Breaker Panel Removal and Replacement Procedure ............................................................... 4-9
5-1 System Specifications.............................................................................................................................. 5-1
ii 044-05298 Rev A
List of Figures PAF-19XX-EX-XXX
List of Figures
1-1 System Block Diagram ............................................................................................................................ 1-2
1-2 PAF System Model .................................................................................................................................. 1-2
1-3 Subrack.................................................................................................................................................... 1-3
1-4 MCPA ...................................................................................................................................................... 1-3
1-5 Filter (if used)........................................................................................................................................... 1-3
1-6 Circuit Breaker Panel............................................................................................................................... 1-4
2-1 Subrack Interface Panel Connectors ....................................................................................................... 2-1
2-2 Subrack Rear +27 VDC Connector Block................................................................................................ 2-1
2-3 MCPA Controls and Indicators ................................................................................................................ 2-3
2-4 Filter Front Connections .......................................................................................................................... 2-4
2-5 Filter Front Plate Indicators...................................................................................................................... 2-5
2-6 Circuit Breaker Panel Front and Top View .............................................................................................. 2-6
3-1 Frame Installation .................................................................................................................................... 3-3
3-2 Power Connections.................................................................................................................................. 3-4
3-3 Return Bus connection ............................................................................................................................ 3-4
3-4 Frame to Halo Ground Connection Example........................................................................................... 3-5
3-5 MCPA Front Panel Features.................................................................................................................... 3-6
4-1 MCPA Removal and Replacement .......................................................................................................... 4-3
4-2 Inside Mount Cooling Fan Removal and Replacement ........................................................................... 4-4
4-3 Rear Mount Cooling Fan Removal and Replacement ............................................................................. 4-5
4-4 Fan Inside Mount to Rear Mount Conversion .......................................................................................... 4-6
4-5 Subrack Removal and Replacement ....................................................................................................... 4-7
4-6 Filter Removal and Replacement ............................................................................................................ 4-8
4-7 Breaker Panel Unit Removal and Replace .............................................................................................. 4-9
044-05298 Rev A iii
PAF-19XX-EX-XXX
This page intentionally left blank
iv 044-05298 Rev A
Chapter 1
Product Description
Introduction
This manual contains information and procedures for installation, operation, and maintenance of the PAF-19XX-EX-XXX Multi-Carrier Power Amplifier (MCPA) Indoor System. The manual is organized into chapters as follows.
Chapter 1 - Product Description
Chapter 2 - Controls and Indicators
Chapter 3 - Installation
Chapter 4 - Maintenance
Chapter 5 - Specifications
Scope of Manual
This manual is intended for use by service technicians familiar with similar types of equipment. It contains service information required for the equipment described and is current as of the printing date. Changes which occur after the printing date may be incorporated by a complete manual revision or alternatively as additions.
Product Description
The PAF-19XX-EX-XXX system, shown in the Figure 1-1 block diagram, is an 1900 MHz, 4-way combined, frame-mounted BTS solution. The PAF system contains three MCPA subracks, each capable of containing up to four MCPAs, three filters, and one DC circuit breaker panel.
The MCPA subrack, shown in Figure 1-3, contains linear, feed-forward MCPAs that operate in the 1930 - 1990 MHz range. Each subrack is also equipped with automatic power control (APC), an ethernet connection, an RS-485/RS-232 connection, a filter I/O port, and two cooling fans. The subrack is installed on sliding rails so that it can be pulled forward to allow access to the rear of the subrack.
The MCPA, shown in Figure 1-4, is a 1900 MHz module that produces a typical output of 160 watts (52.0 dBm) before system losses, with an instantaneous bandwidth of 25 MHz.
The filter assembly, shown in Figure 1-5, if used, supresses unwanted signals and non-linear components of the signal from the amplifiers.
The circuit breaker panel, shown in Figure 1-8, consists of two +27 VDC input buses (A and B), and a system circuit breaker panel. The panel receives +27 VDC from the BTS and then distributes circuit breaker protected DC power to the individual subracks.
Functional And Physical Specifications
PAF-19XX-EX-XXX system functional and physical specifications are listed in Chapter 5.
044-05298 Rev A 1-1
PAF-19XX-EX-XXX Functional And Physical Specifications
Main to/from Antenna
(TX / RX)
Analog
Input
MCPA-0
Diversity from Antenna
(RX)
Digital
Input
Input Combiner/ Splitter
MCPA-1
Combiner Filter
MCPA-2
MCPA-3
DC Power
Controller
Figure 1-1 System Block Diagram
Alcatel Lucent
Alcatel
Lucent
STA TU
S
Alcatel Lucent
S TATUS
R E S
E
T O N
O F
F
Alcatel Lucent
STA
T U
R
S
E S
E
T O N
S TA TU
R
O
S
E
F
S
F
E
T O N
R
O
E
F
S
F
E T
O
N O F
F
Analog 1 (Mai n ) to BTS Analog 2 (Main) to BTS Digital 1 (Main) to BTS Digital (Main) to BTS
2
Analog 1 (Diversity) to BTS Analog 2 (Diversity) to BTS Digital 1 (Diversity) to BTS
2
Digital (Diversity) to BTS
P C
I / O
P C
I / O
P C
I
/
O
P C
I /
850 MHz
Alc
atel
Luc
ent
STA
TUS
R E
S E
T O N O
F F
P C
I /
O
850 MHz
Alc
atel
Luc
ent
STA
TUS
R E
S
E
T
O
N O
F
F
P C
I
/
O
850 MHz
O
850 MHz
850 MHz
850 MHz
Alc
atel
Luc
ent
Alc
atel
Luc
S TA
ent
T US
Alc
atel
Luc
STA
ent
T
US
R E
S E
T O N
STA
TU
R
O
S
E
F
S
F
E
T O N
R
O
E
F
S
F
E
T O N
O F F
P C
I /
O
P C
I /
O
P C I /
O
850 MHz
850 MHz
850 MHz
Alc
atel
Luc
ent
Alc
atel
Luc
STA
ent
TUS
Alc
atel
Luc
STA
ent
TUS
R E
S E
T
O
N
STA
TUS
R
O
E
F
S
F
E
T
O
N
R
O
E
F
S
F
E
T O N O
F F
P C
I / O
P C
I / O
P C
I / O
850 MHz
850 MHz
850 MHz
Figure 1-2 PAF System Model
1-2 044-05298 Rev A
Functional And Physical Specifications PAF-19XX-EX-XXX
Alc
atel Lu cent
Alcatel
S
RESET
ON
Lucent
T A
T
U
S
O
FF
P C I/O
850 MHz
Alcatel Lucent
ST
A
T
US
R
ESET
O
N
O
FF
PC I/O
850 MHz
Alc
atel
S
RESE
O
N
Lucent
TA
TU
S
S
T A
T
U
S
T
R
OF
ESET
F
ON
O
FF
PC I/O
PC I/O
850 MHz
850 MHz
Alcatel Lucent
STA
TUS
R
E
S
E
T
O
N O
F
F
P
C
I/O
850 MHz
Front
Front
Rear
Figure 1-3 Subrack
Rear
Figure 1-4 MCPA
Figure 1-5 Filter (if used)
044-05298 Rev A 1-3
PAF-19XX-EX-XXX Functional And Physical Specifications
Figure 1-6 Circuit Breaker Panel
1-4 044-05298 Rev A
Chapter 2
RF OUT
Controls and Indicators
Introduction
This chapter contains descriptions of the PAF-19XX-EX-XXX subrack, MCPA, filter, and circuit breaker panel interface connections, controls and indicators.
Subrack
The location of the subrack interface controls, connectors, and indicator are shown in Figures 2-1 and 2-2 and feature descriptions are listed in Table 2-1.
DIGITAL
ETHERNET
RS485
FILTER I/O
CDMA1 CDMA2 CDMA3 CDMA4 CDMA5 CDMA6
Figure 2-1 Subrack Interface Panel Connectors
DC POWER
+27V
0
1
RETURN
3
2
0
3
2
1
Figure 2-2 Subrack Rear +27 VDC Connector Block
044-05298 Rev A 2-1
Subrack PAF-19XX-EX-XXX
Table 2-1 Subrack Faceplate Interface Connectors, and Indicators
Connectors Description
RF
DIGITAL (CDMA1 through CDMA6)
RF OUTPUT 7/16 DIN connector, composite transmit
Status
ETHERNET RJ-45 connector used for host alarm
RS-232/RS-485 DB-9 connector used for host alarm
Filter
Filter I/O DB-15 connector to provide control and
DC Power
+27 VDC Connector Block (Rear of Subrack)
Six SMA input connectors
signal output.
reporting, Pin layout is listed in Table 2-2
reporting. Pin Layout is listed in Table 2-3
communication to filter (if used)
Provide connections for +27 VDC circuit breaker protected power from breaker panel and frame ground bus return connections.
Ethernet Connector Pinout
The Ethernet port is used for commuication with a personal computer (PC) or with a base station. The pin layout for the Ethernet interface is listed in Table 2-2.
Table 2-2 Ethernet Connector Pinout
Pin Description
1 Transmit Data (TX) +
2 Transmit Data (TX) -
3 Receive Data (RX) +
4NC
5 NC
6 Receive Data (RX) -
7 NC
8NC
2-2 044-05298 Rev A
PAF-19XX-EX-XXX MCPA
z
RS-485 Interface
This RS-485 connector is used for serial communication and as an interface to the system for delivery of alarms. Grounding pin 8 disables RS-485 communication. Table 2-3 lists the pin descriptions.
Table 2-3 RS-485 Pinout
Pin Description
1 RS-485 RX+
2N/C
3 N/C
4 RS-485 RX-
5 Ground
6 RS-485 TX-
7 RS-485 TX+
8 Select = 1 (Not grounded)
9 Ground
Filter I/O (if used)
This port is used for communication with the filter tray associated with the subrack.
MCPA
The controls and indicators for the MCPA consist of an OFF/ON/RESET switch and tri-color LED status indicator as shown in Figure 2-3 with detailed functions listed in Table 2-2.
Multi-Color Status LED
3-Position Switch: RESET ON OFF
Connector
RJ-11
Figure 2-3 MCPA Controls and Indicators
Alcatel Lucent
STATUS
RESET
ON
OFF
PC I/O
850 MH
044-05298 Rev A 2-3
Filter (if used) PAF-19XX-EX-XXX
Table 2-4 MCPA Indicators and Controls
Control/Indicator Description
STATUS (Multi-colored LED Indicator)
LED Color MCPA Status.
Green (solid) RF enabled, OFF/ON/RESET switch
set to ON (middle position).
Green (blinking) Standby.
Yellow (solid) Major Alarm
Yellow (blinking) APC Activated
Red (solid) Critical Alarm, MCPA disabled.
Red (blinking) Over Temperature Alarm
Red/Yellow (blinking together) High Reverse Output Power 1 minute
validation period
Red/Yellow (alternating) Critical Alarm during remote firmware
download or checksum failure
Toggle Switch positions:
RESET (Up) ON (Middle) OFF (Down)
Resets MCPA. LED indicates boot mode, then turns solid green. Enables MCPA. LED indicates solid green. Disables MCPA. LED Indicates solid red.
RJ-11 RS-232 PC Interface for factory use only.
Filter (if used)
Figure 2-4 shows the front plate of the filter. Table 2-3 lists the descriptions of the connectors. Figure 2-5 shows the five indicators on the filter front panel. The LED will display a green light during normal operation and red light if the indicated stage has suffered a catastrophic failure.
Antenna Main Antenna Diversity
MCPA RF Out
IIC
Forward Main Power Coupler Port
Main Antenna Receive LNA Output Ports
CDMA 1
CDMA 2 CDMA 2
DC Power
RF Test Port
Diversity Antenna Receive LNA output port
CDMA 1
Figure 2-4 Filter Front Connections
2-4 044-05298 Rev A
PAF-19XX-EX-XXX Filter (if used)
Table 2-5 Filter Connector Descriptions
Connector/Cable Description
Antenna Connections
Antenna Main 7/16 connector - Dx0 (bi-directional) antenna port
Antenna Diversity 7/16 connector - Dx1 (simplex RX) antenna port
Subrack Connection
MCPA RF Out 7/16 connector - connects subrack to receive output signal
IIC DB-15 connector for communication between filter and subrack
BTS Connections
CDMA 1 Dx0 Receive LNA Output Port CDMA
CDMA 2 Dx0 Receive LNA Output Port CDMA
Dx0 Receive LNA Input Port AMPS
Dx0 Receive LNA Output Port AMPS
CDMA 1 Dx1 Receive LNA Output Port CDMA
CDMA 2 Dx1 Recevie LNA Output Port CDMA
Dx1 Receive LNA Output Port AMPS
Dx1 Receive LNA Output Port AMPS
Test Port Connections
RF Test Port SMA connector - Switched Coupler Port (4-way)
Forward Main Coupler Port SMA connector - Dx0 Forward Power Coupler Port
Power Connection
Power Power connection
DC Power
IIC
Figure 2-5 Filter Front Plate Indicators
044-05298 Rev A 2-5
TTLNA
DX1DX0
LNA
RF
ON
Circuit Breaker Panel PAF-19XX-EX-XXX
Circuit Breaker Panel
Figure 2-6 shows the switches on the front of the breaker panel and the cable connections on the rear. Chapter 3 discusses power cable connection.
SECTOR 0 SECTOR 1 SECTOR 2
ALPHA BETA GAMMA
AMP 0 AMP 2 AMP 0 AMP 2 AMP 0 AMP 2 AMP 1 AMP 3 AMP 1 AMP 3 AMP 1 AMP 3DIV 0 DIV 1
ONIONIONIONIONIONION
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
LOWEST SUBRACK LOWEST SUBRACK
FILTERS FILTERS
I
SECTOR 0 SECTOR 1 SECTOR 2
ALPHA BETA GAMMA
ONIONIONIONIONIONION
Top
Figure 2-6 Circuit Breaker Panel Front and Top View
I
Alcatel Lucent
2-6 044-05298 Rev A
Chapter 3
Installation
Introduction
This chapter contains unpacking, inspection, installation instructions, and recommendations for installing the PAF-19XX-EX-XXX MCPA Indoor System.
Site Survey
Powerwave recommends that a site survey be performed prior to equipment ordering or installation. Performing a detailed site survey reduces or eliminates installation and turn-up delays. Pay particular attention to AC or DC power availability, cooling needs, floor space, and RF/DC cabling/breaker requirements. See Chapter 5 for system dimensions and weights.
Space Requirements
The PAF system requires the following floor space for clearance (W x D x H): 28.5 inches (724 mm) x 78.2 inches (1986 mm) x 38.5 inches (978 mm). To properly service the system, an additional 48 inches (1220 mm) is required in the front of the unit. To permit proper airflow, allow a minimum of 8.27 inches (210 mm) behind the PAF.
Unpacking and Inspection
This equipment has been operated, tested and calibrated at the factory. Carefully open the containers and remove the equipment. Retain all packing material that can be reassembled in the event that the unit must be returned to the factory. Please perform the following steps:
Visually inspect equipment for damage that may have occurred during shipment. If possible, in
the presence of the delivery person.
Check for evidence of water damage, bent or warped chassis, loose screws or nuts, or extrane-
ous packing material in connectors.
If the equipment is damaged, file a claim with the carrier once the extent of any damage is assessed.
If the equipment must be returned to the factory, contact the factory for a Return Material Authorization (RMA) as described in Chapter 4.
Electrical Service Recommendations
Proper AC line conditioning and surge suppression is necessary on the primary AC input to the +27 VDC power source. Powerwave recommends that all electrical service be installed in accordance with the National Electrical Code (NEC) and any applicable state or local codes.
Table 3-1 lists a sample of DC cable ratings.
044-05298 Rev A 3-1
Cooling Requirements PAF-19XX-EX-XXX
Table 3-1 Sample of DC Cable Ratings
AWG
or
MCM
10 5 40 45 50 55 65
8 8 57 55 60 70 75 85
6 13 76 70 80 95 100 120
4 21 101 95 105 125 135 160
2 34 135 125 135 170 185 210
1 42 158 145 160 195 215 245
0 53 183 165 190 230 250 285
00 67 212 195 265 300
000 85 245 225 310 350
0000 107 287 260 360 405
MCM250 127 320 290 405 455
MCM300 152 359 320 445 505
Based on ambient temperature of 30×C (86×F)100% Load Factor
Source: Industrial Electric Wire & Cable Inc., Technical Guide Vol. 4M 11/99, Table III Suggested Ampacities - All Types of Insulations; Based on National Electric Code
mm
2
3 Conductor In Raceway Single Conductor In Free Air
75°C 90°C 110°C 75°C90°C110°C
Copper
Cooling Requirements
Each MCPA at full power generates the BTUs per hour listed in Table 3-3. A 1-ton air conditioner offsets 12,000 BTUs of heat. The MCPA operates within the temperature environment specified in Chapter 5.
Fan speed is dependent on MCPA operating temperature. The fans remain off until the MCPAs exceed +43°C base plate temperature. Once enabled, the fan remains on until all MCPA base plate temperatures are below +41°C.
Installation Instructions
Install the PAF frame, DC and RF connections, alarms, and MCPAs as described in the following paragraphs.
PAF
To install the PAF frame, perform the instructions in Table 3-4.
CAUTION: The PAF frame, as factory shipped, weighs approximately 250 lbs (113 kg) to 428 lbs (194 kg) depending on configuration (MCPAs not included). During unpacking and installation, be careful with the semi-rigid cables. Protect the cables from damage by avoiding contact with doorways or other equipment. Do not use the cables as handles for moving the components or the frame.
NOTE
Reuse shipping pallet washers to secure PAF to installation site floor.
3-2 044-05298 Rev A
PAF-19XX-EX-XXX Installation Instructions
Table 3-2 PAF Frame Installation Procedure
Step Action
1. Set PAF frame in planned location
2. Mark floor drill holes on floor where lag bolts will be installed. Move frame to side. Refer to lag bolt manufacturer’s instructions for hole depth and diameter
3. Move frame back over drilled holes
4. Use a level to ensure frame is not leaning. Insert shims between frame base and floor to level frame. Shims should wrap around lag bolts as shown in Figure 3-2
5. Secure frame in place with red eye lag bolts and appropriate washers
Lag Bolt
Lock Washer
Flat Washer
Cabinet
Shim
Lag Anchor
Concrete
Figure 3-1 Frame Installation
Seismic Brace (Optional)
The PAF system meets GR-63-CORE, Section 4.4.1, Zone 4 compliance. If additional bracing is required, Powerwave offers an optional seismic brace kit for those circumstances. Please contact a Powerwave sales representative for additional information and assistance.
DC Connections
Connect and verify DC power cables between the BTS power plant and the PAF system circuit breaker panel and PAF return bus located at the top of the PAF as instructed in Table 3-5. Required power is +27 VBC, and each power input is directly connected through the circuit breaker in the front of the panel to the power output directly below it in the panel.
WARNING: Turn off external DC power before connecting DC power cables.
044-05298 Rev A 3-3
Installation Instructions PAF-19XX-EX-XXX
Table 3-3 DC Power Installation Procedure
Step Action
1. Remove circuit breaker panel top protective cover
2. Connect fourteen individual red power cables, one to each input on the upper row of connections. (designated Row A Figure 3-2)
3. Attach opposite ends of red MCM 250 powr cables to power plant’s main DC bus bar after main shunt.
4. Insert fourteen individual black power cables into front of yellow and green ground connections as shown in Figure 3-3 and tighten screws
5. Attach opposite ends of black power cables to power plant's main DC return bus bar
6. Connect PAF frame to halo grounding system at frame top (four locations) using green 6 AWG cable as shown in Figure 3-4
7. Reinstall circuit breaker panel top protective cover.
8. Affix supplied ground sticker directly beneath one utilized frame grounding points shown in Figure 3-4
Row A
Row B
Figure 3-2 Power Connections
Ground Return Connections
Figure 3-3 Return Bus connection
3-4 044-05298 Rev A
PAF-19XX-EX-XXX Installation Instructions
NOTE
DO NOT remove metallic tape at frame top when connecting to Halo ground system. Removing tape voids PAF frame warranty.
To Halo Ground
To Halo
Ground
Metallic Tape
Ground
Sticker
Figure 3-4 Frame to Halo Ground Connection Example
RS-485 Alarm Interface
The RS-485 alarm interface provides the BTS controller with system status via a 1 byte protocol. The baud rate is fixed at 15.6 K. Table 3-6 lists the available alarm states.
Table 3-4 RS-485 Alarm States
AlarmState Definition
No Alarm
Minor Alarm Any or all fans fail
Major Alarm Any one MCPA module disabled
Critical All MCPA modules disabled
MCPA
Install the MCPAs as instructed in Table 3-7.
CAUTION: Slowly insert MCPA into subrack. Forcing MCPA into subrack may cause pins on
the MCPA D-sub connector to become recessed or broken.
044-05298 Rev A 3-5
Initial Start-Up and Power Setting Procedures PAF-19XX-EX-XXX
Table 3-5 MCPA Installation Procedure
Step Action
1. Inspect MCPA 21-pin connector. Verify all pins are straight, no pins are recessed, and alignment shield is not bent
2. Set MCPA power OFF/ON/RESET switch to OFF
3. Rotate MCPA quarter-turn fasteners counter-clockwise to unlock position shown in Figure 3-8
4. Install MCPA(s) into subrack. To secure each MCPA, rotate quarter-turn fasteners clockwise to lock position as shown in Figure 3-8
Quarter-Turn Fasteners
Alcatel Lucent
Locked
ON
OFF
LED Status Indicator
RF Switch:
RESET ON OFF
Unlocked
Alcatel Lucent
ON
OFF
Figure 3-5 MCPA Front Panel Features
Initial Start-Up and Power Setting Procedures
The following paragraphs provide initial startup, and power setting procedures.
Initial Start Up
To complete initial startup, perform the instructions listed in Table 3-8.
CAUTION: Excessive input power may damage MCPA. Before applying power, ensure MCPA inputs and outputs are properly terminated at 50 ohms. Do not operate MCPA without a load attached. Refer to Chapter 5 for input power requirements.
Table 3-6 Initial Startup Procedure
Step Action
1. Verify all input and output cables are properly connected
2. Turn on +27 VDC supply to MCPA
3. Set all MCPA front panel OFF/ON/RESET switches to ON (middle) position
4. Allow MCPAs to warm up for at least two minutes before taking power readings
3-6 044-05298 Rev A
Loading...