Powerwave Technologies and the Powerwave logo are registered trademarks.
Powerwave Technologies Inc. reserves the right to make changes to documentation and equipment, including
but not limited to component substitution and circuitry changes. Changes that impact this document may be
subsequently incorporated in a later revision of this document.
This Powerwave product is designed to operate within the Normal Operating (typical operating) ranges or conditions specified in this document. Operation of this equipment beyond the specified ranges in this document
may cause (1) spurious emissions that violate regulatory requirements; (2) the equipment to be automatically
removed from service when maximum thresholds are exceeded; or (3) the equipment to not perform in accordance with its specifications. It is the Operator's responsibility to ensure this equipment is properly installed and
operated within Powerwave operating specifications to obtain proper performance from the equipment and to
comply with regulatory requirements.
The rated output power of a WRH-V it is for multiple carriers. As long as the composite power does not exceed
the rated power (20W for North America), derating is not required for multiple carriers. For situations where
regulatory requirements require reduced interference to adjacent band users, the rating would have to be
reduced by 3 dB. This power reduction is to be by means of input power or gain reduction and not by an attenuator at the output of the device. Input power is rated at 115/230VAC, 50/60Hz, and should be protected based
on the power and fuse specifications in Chapter 5 of this manual. Power strips should, at a minimum, conform
to this requirement to prevent equipment damage and possible overload.
Federal Communications Commission (FCC)
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
CRF47 part 15 of the FCC rules. This equipment is also certified to CRF47 part 22 (cellular), part 24 (PCS) and
part 90 (iDEN800 and iDEN900) of the FCC Rules depending on the band of operation. Changes or modifications not expressly approved by Powerwave Technologies, Inc. for compliance could void the user’s authority
to operate this equipment. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may
cause harmful interference to radio communications. Operation of this equipment in a residential area is likely
to cause harmful interference in which case the user will be required to correct the interference at his own
expense.
Industry Canadian Requirements
All Powerwave apparatus introduced in the Canadian market meet all requirements of the Canadian Interference-Causing Equipment Regulations. The -20dB bandwidth at 1900 MHz band is 80 MHz. The -20dB bandwidth at the 850 MHz is 34 MHz. The output impedance of the unit referenced in this document is 50 Ohms.
The -20dB bandwidth at IDEN 800MHz band is 26 MHz.
The input signal is optical so input impedance requirements are not applicable.
European Requirements
The Powerwave WRH-V apparatus introduced in EU markets are certified to ESTI EN 300 609-4 (GSM900 and
DCS1800) and ESTI EN 301 908-11 (WCDMA).
Powerwave Technologies Inc., 1801 East St. Andrew Place, CA 92705 Santa Ana, USA.
Phone +1 714 466 1000 – Fax +1 714 466 5800 – Internet www.powerwave.com
High Power Wideband Radio Head (WRH-V)Warnings, Cautions, and Notes
Warnings, Cautions, and Notes
Warnings, Cautions, and Notes are found throughout this manual where applicable. The associated
icons in warnings and cautions are used to quickly identify a potential condition that could result in the
consequences described below if precautions are not taken. Notes clarify and provide additional
information to assist the user.
WARNING: The warning symbol means danger. You are in a situation that could cause
bodily injury or death. Before you work on any equipment, be aware of the hazards
involved with electrical and RF circuitry and be familiar with standard practices for
preventing accidents.
CAUTION: The caution symbol means the potential exists for equipment damage or loss
of data.
NOTE
Notes contain helpful suggestions or references to material not covered in the document.
044-05251 Rev Ai
Revision RecordHigh Power Wideband Radio Head (WRH-V)
High Power Wideband Radio Head (WRH-V)Abbreviations
Abbreviations
The following list of abbreviations are used throughout this manual, the software, and the repeater:
AGCAutomatic Gain Control
ALIAlarm Interface
AMPSAdvanced Mobile Phone Service
BABooster Amplifier
BeOBeryllium Oxide
BMUBase Station Master Unit
BSBase Station, BS antenna = towards the base station
BSABand Selective Amplifier
BSelBand Selective
BTSBase Transceiver Station
CDMACode Division Multiple Access
CHEChannel Amplifier for GSM and EDGE
CMBCombiner
CSAChannel Selective Amplifier
CSelChannel Selective
CUControl Unit
CWContinuous Wave
DAMPSDigital Advanced Mobile Phone Service
DCDirectional Coupler
DCSDigital Communication System (same as PCN)
DIADistribution Interface
DLDownlink signal direction (from base station via repeater to mobile station)
DPXDuplex filter
EDGEEnhanced Data rates for GSM Evolution
EEPROMElectrical Erasable Programmable Read Only Memory
EGSMExtended Global System for Mobile communication
ESDElectrostatic Discharge
ETACSExtended Total Access Communication System
ETSIEuropean Telecommunications Standard Institute
FLIFiber Link Interface
FONFiber Optic Node
FORFiber Optic Repeater
FOUFiber Optic Unit
GSMGlobal System for Mobile communication
HWHardware
ICNIRPInternational Commission on Non-Ionizing Radiation Protection
LEDLight Emitting Diode
LNALow Noise Amplifier
MCPAMulti-Carrier Power Amplifier
MSMobile Station, MS antenna = towards the mobile station
044-05251 Rev Avii
AbbreviationsHigh Power Wideband Radio Head (WRH-V)
MSCMobile Switching Center
NEMANational Electrical Manufacturers Association
NiCdNickel Cadmium
NMTNordic Mobile Telephone system
NOCNetwork Operations Center
OCMOptical Converter Module
OMSOperation and Maintenance System
PCNPersonal Communication Network (same as DCS)
PCSPersonal Communication System
POIPoint of Interconnect
PSMPower Supply Module
PTFEPolytetrafluoro Ethylene (Teflon)
R2RRepeater-to-Repeater
RCIRemote Control Interface
RCURemote Control Unit
RCMRF Converter Module
RFRadio Frequency
RIARepeater-to-Repeater Adapter
RMURemote Master Unit
RSSIReceived Signal Strength Indication
RTCReal Time Clock
SWSoftware
TACSTotal Access Communication System
TDMATime Division Multiple Access
ULUplink signal direction (from mobile station via repeater to base station)
UPSUninterruptible Power Supply
WHOWorld Health Organization
WLIWire Link Interface
WRHWideband Radio Head
viii044-05251 Rev A
Chapter 1
Product Description
Introduction
This manual contains information and procedures for installation, operation, and maintenance of a High Power
Wideband Radio Head (WRH-V). The manual is organized into chapters as follows:
❑
Chapter 1 - Product Description
❑
Chapter 2 - Controls and Indicators
❑
Chapter 3 - Installation
❑
Chapter 4 - Maintenance
❑
Chapter 5 - Specifications
Scope of Manual
This manual is intended for use by service technicians familiar with similar types of equipment. It contains
service information required for the equipment described and is current as of the printing date. Changes which
occur after the printing date may be incorporated by a complete manual revision or alternatively as additions.
Safety
It is necessary that any personnel involved in installation, operation, or service of units included in a Powerwave
Distributed Antenna System (DAS) understand and follow the below points.
❑Powerwave WRH-Vs are designed to receive and amplify signals from one or more
base stations and retransmit the signals to one or more mobile stations. And, also to
act the other way round, that is to receive signals from one or more mobile stations,
amplify and retransmit the signals to the base stations. Powerwave WRH-V systems
must be used exclusively for this purpose and nothing else.
❑Units supplied from the mains must be connected to grounded outlets and in conformity
with the local prescriptions.
❑Power supply units supplied from the mains contain dangerous voltage that can cause
electric shock. Disconnect the mains prior to any work in such a unit. Local regulations
are to be followed when servicing such units. Authorized service personnel only are
allowed to service units while the mains is connected.
❑The WRH-V cover must be secured in opened position, for instance by tying it up.
Otherwise, the cover can be closed by the wind and cause your fingers getting pinched
or your head being hit.
❑When working on a WRH-V on high ground, for instance on a mast or pole, be careful
not to drop parts or the entire WRH. Falling parts can cause serious personal injury.
❑All RF transmitting units, including WRHs, will generate radio signals and thereby give
rise to electromagnetic fields that may be hazardous to the health of any person who is
extensively exposed close to an antenna.
❑A lithium battery is permanently mounted on the CU and FON PCBAs. Due to the risk
of explosion, this battery must only be removed from the board by an Powerwave
authorized service technician.
❑NiCd batteries are mounted on the FON PCBA. These batteries contain environmental
poisonous substances. If replaced, the old batteries should be taken care of as stated
in the local prescriptions.
044-05251 Rev A1-1
SafetyHigh Power Wideband Radio Head (WRH-V)
❑The FON unit contains a class IIIb laser transmitter that emits 2 – 4mW invisible laser
radiation during operation. Avoid direct exposure from unconnected laser transmitter or
fiber cord.
❑Do not power up the FON unit if a fiber cable is not attached to the fiber output UL port,
neither if a fiber cable is attached to the port but unattached in the other end.
❑Never look in the end of a fiber cable. The 1310nm and 1550nm laser light is not
visible, so no signal identification can be made anyway. Use always an instrument,
such as a power meter to detect signaling.
❑Never use any kind of magnifying devices that can focus the laser light to an
unaided eye.
Human Exposure of RF Radiation
Safe distances must be kept when working around antennas. The following paragraphs describe the cautions
to be aware of during the installation and maintenance of antenna systems and how to calculate safety
distances needed for RF radiation at different antenna power and frequencies.
Antennas
To be able to receive and transmit signals, a WRH-V is connected to a donor antenna directed towards the
base station and a service antenna directed towards the coverage area. A fiber optic cable from the base
station might, however, be substituted for the donor antenna.
Installation and Maintenance of Antenna Systems
Installation and maintenance of all antenna systems must be performed with respect to the radiation exposure
limits for public areas. The antenna radiation level is affected by WRH-V output power, antenna gain, and
transmission devices such as cables, connectors, splitters and feeders. Also have in mind the system minimum
coupling loss, typically between 25dB and 35dB, is determined by a standard with the purpose to protect base
stations from noise and other performance dropping effects.
Radiation Exposure
The World Health Organization (WHO) and International Commission on Non-Ionising Radiation Protection
(ICNIRP) have determined recommendations for radiation exposure. ICNIRP recommends not to exceed the
following radiation power for public exposure:
For antennas larger than 20cm the maximum radiation power can be calculated by using the following formula:
S = Radiation power in W/m²
P = Output power in W
r = Distance between antenna and human in meters
S= P/(4
πr
2
)
Electrostatic Discharge (ESD)
ESD can severly damage essential parts of the equipment if not handled carefully. Parts on
printed circuit board assemblies (PCBA) as well as other parts in the equipment are sensitive
to ESD. Never touch the PCBA or uninsulated conductor surfaces unless absolutely
necessary.
If you must handle the PCBAs or uninsulated conductor surfaces, use ESD protective
equipment or first touch the chassis with your hand. Never let your clothes touch PCBAs or
uninsulated conductor surfaces and always store PCBAs in ESD-safe bags.
1-2044-05251 Rev A
High Power Wideband Radio Head (WRH-V)Overview
Overview
Figure 1-1 Powerwave Wideband Radio Head (WRH)
Powerwave WRH-Vs work as bi-directional on-frequency amplifiers used to extend coverage into uncovered
areas in wireless mobile systems such as base station fringe areas, tunnels, convention centers, airports and
buildings. It receives, amplifies, and transmits signals to/from a base transceiver station (BTS) to/from mobile
stations (MS) with both directions being served simultaneously. Connections to the WRH-V are made with Ntype or 7/16" male connectors.
WRH-Vs are microprocessor controlled with alarm and operational status LEDs visible on the front cover.
Cooling is provided through convection heat dissipation. Operational parameters, such as gain and power
levels are set using a PC running Powerwave OM-Online software which communicates with the WRH-Vs
either locally or remotely via modem. Remote operation can be performed via PSTN or a GSM net. The
Operation and Maintenance System (OMS) provides for Network Operations Center (NOC) configuration and
alarm monitoring.
WRH-Vs can be configured in many combinations depending on the wireless system, single or double system
operation, and output power. The following paragraphs provide a description of the different models of WRHVs available.
The WRH-V is a fiber fed system designed to provide a high output power level and comes equipped with a
MCPA in the downlink path. The MCPA restricts the number of bands to one in the cabinet and one additional
band if a high cover is used. The MCPA is located in the cabinet and is supplied from the existing PSU.
Chassis Design
The WRH-V is housed in a cast aluminium waterproof chassis, class NEMA4 / IP65, approved for outdoor use
but is also suited for indoor installations. The chassis consists of a cabinet and a cover attached with hinges.
The cabinet contains the WRH-V circuitry. The cover comes as either a low or high version. The high cover can
be used as an empty cover or be equipped as a part of the WRH-V or an independent WRH-V unit. A WRH-V
with a high cover that is equipped as two independent units can, for example, be equipped for channel selective
operation in the cabinet and band selective operation in the cover.
Inside the WRH, a number of amplifier PCBAs are individually shielded and located under a metal cover that
can be opened outward. These PCBAs are of different types depending on the supported system.
044-05251 Rev A1-3
OverviewHigh Power Wideband Radio Head (WRH-V)
Sub Unit Overview
A number of amplifier PCBAs are individually shielded and located under a metal cover inside the WRH-V. This
cover can be opened outward for access. These amplifier PCBAs are of different types depending on the
supported system. All of the WRH-Vs are built up with a number of sub units which are described in the
following sections.
Wideband Amplifier PCBA (WBA)
WRH-Vs can handle multiple carriers over a wide band. Each band requires one WBA for the uplink and
downlink, and one associated PA or MCPA for the downlink. The cabinet can be equipped with up to two WBAs
along with two PAs supporting two bands or one MCPA supporting one band. Positions 1 and 3, shown in
Figure 1-6, are assigned for a WBA.
Multi-Carrier Power Amplifier PCBA (MCPA)
The MCPA is used to amplify the output signal from the WBA. Each MCPA can handle one band in the downlink
direction. It requires an extra heat sink element on the outside of the cabinet or high cover to dissipate the heat
generated. The MCPA occupies positions 2 through 4 in the cabinet and 6 through 8 in a high cover, as shown
in Figure 1-6.
Distribution PCBA (DIA)
The DIA is the core distribution PCBA to which all other PCBAs and units connect in the cabinet with the
exception of the PA. Figure 1-2 shows a DIA PCBA. A shielded metal frame on the DIA provides the mounting
location for the CU, ALI and RCIs, if used.
P11P12P13V1P14P22P29P34V2P36
XOB
XOA
P26
P28
P23
V6B
P27
1
1
M
>
S
15 16
2
1
UP-LINK
8
1
X
U
A
W5
1
2
16
P11
5
6
3
2
P
1
X0A
P34
X0B
89
3
P28
DOOR
1
8
15
P26
1
6
P23
LNA
9
P32
MODEM
P27
W6B 10
9
5
ALLGON INNOVATION
SWEDEN M105 R6
PARKING
FOR W5
c
b
a
1
P33
ALARM
P32
1
V2
1
P6
c
b
a
1
P5
c
b
a
1
P4
16
P12P13
16
16
16
P4P5P6P2P3 P31 P21 P35 P33
1
1P232
c
b
a
16
1
b
a
1
16P3
1
V1
16
P14
LED
P22
4
1
1
S
P25
>
-
6
M
15
9
15216
1
P25
P29
6
P31
PC
5
10
P21
PSU
1
6
5
1
P35
4
8
P24
2
P24
1
1
LNA
DOWN-LINK
6V6
V6
7
GND
GND
Figure 1-2 DIA PCBA
Control Unit PCBA (CU)
Figure 1-3 shows the CU, which is the core microprocessor controller in the WRH-V and is connected to P2 on
the DIA. The CU contains a microprocessor, main memory, flash memory for the CU software, EEPROM
memory for parameters, memory for the event log and statistics, a REFO reference oscillator, ports for local
and remote communication, a battery powered real-time clock, and a MAC identity circuit. It supervises and
controls operational parameters such as gain control and channel handling, alarms, the event log, the
password and the logon. The CU is also a control interface for OM-Online and OMS. Software for the CU can
be downloaded from OM-Online, either locally or remotely. It is located in the lower right part of the shielded DIA
frame.
1-4044-05251 Rev A
High Power Wideband Radio Head (WRH-V)Overview
Figure 1-3 CU PCBA
Low Noise Amplifier (LNA)
LNAs are used on the uplink and are located at the top of the cabinet and the high cover, if equipped. An
example of an LNA is illustrated in Figure 1-4. All of the coaxial connectors are SMA-type. Signals from the DPX
output are fed to the LNA input connector (IN). The OUT1 and OUT2 outputs feed the WBAs in the UL direction.
The signal level at these connectors is +20dB referenced to the antenna input. The other output, OUT LOW, is
an expansion output for an additional LNA if the WRH-V is equipped with a unit in the cover part of the chassis.
The gain to this connector is +2dB. The +7V input is used for +7V supply from the DIA PCBA and the ATT
connection is for the control signal for a controllable attenuator in the LNA.
Figure 1-4 LNA
Duplex Filter (DPX)
DPXs are located on the metal cover sheet in the upper part of the cabinet.
Fiber Optic Unit (FOU)
The FOU is a metal plate mounted on top of the cover plate in the upper part of the WRH. The FON and fiber
optic connectors are mounted on the FOU. Figure 1-5 illustrates an FOU with the FON and fiber optic
connectors mounted on the plate. It can also be configured with combiners, splitters, and Wave Division
Multiplexers (WDMs) to obtain a desired combination of several branches with double or single fiber.
DPX
FON
Figure 1-5 FOU in WRH-V
044-05251 Rev A1-5
OverviewHigh Power Wideband Radio Head (WRH-V)
Fiber Optic Node (FON)
The FON is the main part of the FOU. It is a bi-directional electrical/optical signal converter and a node in a fiber
network. In addition, the FON has all the functionality included in the CU PCBA and contains battery backup.
It has also functionality for:
• Electrical and optical signal supervision
• Internal and external alarm handling
• RS232 interface for local PC control via an O&M software (OM-Online)
• Remote control via an O&M software (OM-Online or OMS)
• Interfaces for RCU and FLI
• Battery backup with charger
There are two versions of the FON; one with three SMA ports (UL, DL and RX Mon) and the other with four SMA
ports (UL, DL, RX Mon and TX Mon). The FON also has two optical ports for DL and UL fiber connections.
Power Supply Unit (PSU)
The PSU supplies DC power to all of the components in the WRH-V.
Remote Control Unit (RCU)
The RCU is an optional communication unit for remote control of WRH-Vs via PSTN or RF modems. RCU types
and details are described in Chapter 4.
Alarm Interface PCBA (ALI) and Remote Control Interface PCBA (RCI)
The ALI handles alarms and alarm communication. It is replace with an RCI if an RCU is used and provides an
interface between the CU and an RCU for remote communication via modem. The RCI also handles alarms
and alarm communication. Either unit is located in the lower left part of the shielded DIA frame.
Sub Unit Locations
The MCPA is located at positions 3 and 4 in the cabinet. A WRH-V is equipped for one band in the cabinet and,
if required, an additional band in a high cover. PCBA positions are illustrated in Figure 1-6 and a block diagram
is located in Appendix A.
LNA - UL
1234
WBA
DL/UL
DPX
MCPA DL
FONFON
FOU
CUALI/RCI
PSU
(RCU)
5678
WBA
DL/UL
DPX
MCPA DL
FOU
CUALI/RCI
PSU
(RCU)
Figure 1-6 WRH-V Sub Unit Locations
1-6044-05251 Rev A
High Power Wideband Radio Head (WRH-V)Overview
Fiber Optic Distribution Networks
Fiber optic networks are setup identically to data networks. WRH-Vs are connected in a star configuration as
illustrated in Figure 1-7. In this example, a Base Station Master Unit (BMU) is fed by a BTS via an RF cable. An
Optical Converter Module (OCM) could also be used depending on the system configuration. The BMU or OCM
contain three FONs and provide continuity to the FONs in the four WRHs. By using WDMs and Optical Splitters
(OSPs) in the WRHs, the distribution net can be built up with a combination of star and daisy-chain connections
using double or single fiber.
BMUWRH
BTS
RF
WRH
WRH
WRH
Figure 1-7 Fiber Optic Star Configuration
Multi-Operator Configurations
Multi-operator systems require the use of Point of Interconnect (POI) units and OCMs as illustrated in Figure
1-8. In this simple example, two operators have two sectors each. Each sector is connected to a POI and then
to a RCM. The RCM is interconnected with an OCM via coaxial cables. The combined DL and UL signals are
converted to optical signals in the OCM and then distributed to the WRHs-V.
OCM
Operator 1
Sector 1
Sector 2
Operator 2
Sector 1
BTS-POI
BTS-POI
BTS-POI
BTS-POI
OCM-POI
OCM-POI
Sector 2
Figure 1-8 Multi-operator System
044-05251 Rev A1-7
OverviewHigh Power Wideband Radio Head (WRH-V)
This page intentionally left blank
1-8044-05251 Rev A
Controls, Indicators and Connectors
Introduction
This chapter contains descriptions of the controls, indicators and connectors for the WRH.
Front Cover Indicators
Chapter 2
Amber
Red
Figure 2-1 External Indicators
Two LEDs, shown in Figure 2-1, are located on the front cover to provide easy identification of a fault in the
system. The amber operation LED lights up approximately 15 seconds after the main power is switched on.
When the LED is steady, the WRH-V is ready for operation. The red alarm LED indicates a system error alarm
when flashing and a critical alarm when steady.
Cabinet Indicators
OPER
FAULT
2
16
1
V2
1
P6
cba
P34
1
P5
cb
8
a
1
16P4
cba
1
P33
ALARM
POWER SUPPLY UNIT
WLI / R2R
SV
POWER
ALARM
16
P12P13
16
16
1P232
cba
BOOT
1
DATA
16
ba
FAULT
1
OPER
1
6
16P3
1
P29
1
16
V1
P14
LEDP22
4
2
1
1
S>
-M
15
9
16
15
P25
2
6
P24
1
1
LNA
DOWN-LINK
DC
6V6P31PC
DPX
5
10
7
TEST
P21
GND
PSU
-30 dB
1
6
MS
5
1
-20 dB
P35
4
8
ANT
CU
ALI
RCI
POWER
10V
or
1
P11
5
63
1
2
P
1
X0A
M>
X0B
-S
893
P28DOOR
1
1516
15
P26
2
1
1
6
P23
DC
LNA
UP-LINK
9
9
5
DPX
P32
MODEM
TEST
P27
W6B10
8
-30 dB
1XUA
MS
W5
ALLGON INNOVATION
-20 dB
SWEDEN M105 R6
1
PARKINGFOR W5
ANT
Figure 2-2 Cabinet Internal Indicators
044-05251 Rev A2-1
PCBA IndicatorsHigh Power Wideband Radio Head (WRH-V)
Figure 2-2 shows the LED indicators located on the ALI or RCI, the CU PCBAs, the 115/220V main power
switch (S) in the cabinet, and the voltage indicator (V). These indicators are described in further detail in the
following sections.
PCBA Indicators
This following paragraphs describe the LED indicators on the main PCBAs inside the WRH.
CU PCBA
Figure 2-3 shows the location of the LEDs on the CU and Table 2-1 lists their indications.
WLIDATAPOWERBOOTFAULTOPER
Figure 2-3 CU PCBA Indicators
Table 2-1 CU PCBA LED Indicators
LEDDescription
WLIWire Line Interface. A flashing green LED indicates the unit is receiving
data over the subcarrier. A steady green LED indicates: the unit is
currently not receiving any data, is currently not a control station or there
is no other node in the network
DATABlue LED indicating data transmission in the W-net
POWERYellow LED indicating present power and remains steady after power is
switched on
BOOTSteady red LED when the CU boots (10 – 15 seconds after main power is
switched on), then flashing red (5 – 10 seconds), then off if no error is
detected. If an error is detected LED will stay on
FAULTFlashing red LED for 15 – 20 seconds after main power is switched on.
Flashes for less serious alarms (Error) and is on solid for fatal alarms
(Critical)
OPERSteady green LED indicates WRH-V is ready for operation
WARNING: A lithium battery is permanently mounted on the CU PCBA. Due to risk of
explosion, this battery must not be removed. In case of battery malfunction, replace the
CU PCB.
2-2044-05251 Rev A
High Power Wideband Radio Head (WRH-V)PCBA Connections
FON PCBA
The FON is shown in Figure 2-4 and the LED indicators are listed in Table 2-2.
P117
Figure 2-4 FON LED Indicators
Table 2-2 FON LED Indications
LEDDescription
FLI or
F2F
OPERGreen LED. Lights up for approximately 5 seconds after the power is switched on.
FAULTRed LED. Flashes for 15 – 20 seconds after the mains is switched on. Will flash for
POWERYellow LED. Indicates power is present
BOOTRed LED. Steady LED when the control unit boots up (10 – 15 seconds after the
WLIGreen LED. Wire Line Interface. Flashing LED indicates unit is receiving data over
DATABlue LED. Indicates data transmission in the W-net
BATTGreen LED. Steady LED indicates battery pack is currently used as power source
CHARGEYellow LED. Steady LED indicates battery charging
Green LED. Fiber Line Interface (FLI). Flashing LED indicates the unit is receiving
data over the sub carrier. A steady LED indicates the unit has detected an FLI subcarrier, but is not carrying any data
The LED is dark during the boot process and when it is steadily lit again, it indicates
the unit is ready for operation
less serious alarms and be steady for fatal alarms
mains is switched on). Next enters a flashing state for 5 – 10 seconds. If no error is
detected, the LED turns off. If an error occurs, the LED remains on
the subcarrier. A steady LED indicates one of the following: The unit is not currently
receiving any data, the unit is not currently a control station or there is no other node
in the network
PCBA Connections
The following tables list the connections from the main PCBAs to replaceable units inside the WRH-V. Table
2-3 lists the connections for a WRH-V configured for PCS both with and without diversity and Table 2-4 lists
the connections for Cellular with and without diversity.
044-05251 Rev A2-3
PCBA ConnectionsHigh Power Wideband Radio Head (WRH-V)
V
V
Table 2-3 WRH-V Base Unit Connections
FromToCable NumberNon-DiversityDiversity
WBA P2401M FON P101VE007 06/3UsedUsed
WBA P3401D FON P101700-16639-001Not UsedUsed
WBA P1101M FON P102VE007 20/2UsedUsed
PSUDIA P21, P35VE007 98/1UsedUsed
M FON P108DIA P29VE007 66/1UsedUsed
D FON P108M FON P116VE007 66/1Not UsedUsed
M FON P111DIA P36VE008 05/1UsedUsed
D FON P111DIA P112VE008 05/1Not UsedUsed
Table 2-4 WRH-V Cover Unit Connections
FromToCable NumberNon-DiversityDiversity
Cover DIA P36M FON P112VE008 05/1UsedNot Used
Cover DIA P36D FON P112VE008 05/1Not UsedUsed
PSUDIA P21, P35VE007 98/1UsedUsed
DX DL CM FON P102700-14508-401UsedUsed
DX UL1 C (M)M FON P101700-14508-401UsedUsed
DX UL2 C (D)M FON P101VE007 52/2Not UsedUsed
DIA PCBA
Figure 2-5 shows and Table 2-5 lists the connections on the DIA PCBA. The DIA provides most of the internal
connection between the sub units and external ports. Connectors involved are also located on the DIA.
P11P12P13V1P14P22P29P34V2P36
P11P12P13V1P14P22P29P34V2P36
XOB
XOB
XOA
XOA
P26
P26
P28
P28
P23
P23
P37
P37
6B
6B
P27
P27
1
1
1
1
>M
>M
-
S
S
1516
15 16
P23
P23
UL LNA ATTN
UL LNA ATTN
W5
W5
P11
P11
5
5
P36
P36
2
2
1
1X0A
X0A
89
89
3
3
1
1
P26
P26
2
2
1
1
6
6
2
2
1
1
9
9
DIV
DIV
MODEM
MODEM
P27
P27
W6B10
W6B 10
8
8
AUX1
AUX1
1
1
P28
P28
DOOR
DOOR
P32
P32
ALLGON INNOVATION
ALLGON INNOVATION
SWEDENM105 R6
SWEDEN M105 R6
PARKING
PARKING
FOR W5
FOR W5
P34
P34
X0B
X0B
15
15
1
1
9
9
5
5
ALARM
ALARM
P32
P32
2
2
1
16
16
8
8
1
1
P33
P33
1
V2
V2
1
1
P6
P6
c
c
b
b
a
a
1
1
P5
P5
c
c
b
b
a
a
1
1
P4
P4
c
c
b
b
a
a
P4P5P6P2P3P31P21P35P33
P4P5P6P2P3P31 P21 P35 P33
16
16
P12P13
P12P13
16
16
16
16
16
16
1
1
16
16
1
1
b
b
a
1P232
1P232
c
c
b
b
a
a
a
1
1
16P3
16P3
Figure 2-5 DIA PCBA Connectors and Testpoints
The External Alarm Port P33 is used for external alarm sensors and alarm equipment. The four alarm inputs
are low-level inputs with common ground (AIC). Use an insulated switch or relay to initiate alarms (open
switches in normal operating mode, closed switches cause alarm). The alarm switch connection can be
toggled between active open and active closed. The alarm input voltage ratings, related to ground (AIC), are:
Vinmax= 5.5V, Vinmin= –0.5V.
The four alarm inputs are connected to the following pins:
Pin 14 AI1 External alarm input 1 - EAL1
Pin 15 AI2 External alarm input 2 - EAL2
Pin 7 AI3 External alarm input 3 - EAL3
Pin 8 AI4 External alarm input 4 - EAL4
2-4044-05251 Rev A
1
1
V1
V1
16
16
P14
P14
LED
LED
P22
P22
4
4
2
2
1
1
1
1
S
S
>
>
P25
P25
-
-
6
6
M
M
15
15
9
9
16
16
15
15
1
1
P25
P25
P29
P29
6
6
P31
P31
PC
PC
5
5
10
10
P21
P21
PSU
PSU
1
1
6
6
5
5
1
1
P35
P35
4
4
8
8
P24
P24
2
2
P24
P24
1
1
1
1
UL LNA ATTN
UL LNA ATTN
V6
V6
6V6
6V6
2
2
P38
P38
1
1
DIV
DIV
P38
P38
7
7
GND
GND
GND
GND
High Power Wideband Radio Head (WRH-V)PCBA Connections
Pin 6 AIC Ground.
Two alarm outputs are 1 pole closing and 1 pole opening relay outputs insolated from each other. Maximum
ratings, related to ground or any other alarm terminal, are 50 VAC / 60 VDC. The alarm outputs are defined as
follows:
Pin 9 and 1 AO1 and AO8 Closed when operating, otherwise open.
Pin 10 and 2 AO6 and AO7 Open when operating, otherwise closed.
Pin 11 and 3 AO2 and AO5 Closed at alarm state, otherwise open.
Pin 12 and 4 AO3 and AO4 Open at alarm state, otherwise closed.
Table 2-5 DIA PCBA Connections
PortConnected to
P2CU PCBA
P3, 5, 6Not Used
P4ALI or RCI PCBA
P11 - 14Channel PCBA positions 1 through 4
P21PSU, connector 1
P22LED PCBA in cover
P23LNA/UL
P24LNA/DL
P25Expansion output port to cover circuitry. Only in cabinets
P26Expansion input port to cover circuitry. Used in equipped high covers
P27Auxiliary Port (8-pin male) - Pins 2 and 3 must always be interconnected to
provide the CU and ALI/RCI PCBAs with voltage. If there is no cable
connected, pins 2 and 3 must be interconnected with a jumper
P28Door switch port - Normally, alarm input AI4 is used for door opening alarm
EAL4 which is arranged using an optional door switch. Signal AI4 and AIC
are thus available also in the P28 connector, to which the door switch is
connected. The EAL4 door switch alarm is activated 10 – 30 seconds after
the cover has been opened
P29Power to FON
P31RS-232 PC Port (9-pin D-sub female) - Used for local PC communication
P32RS-232 Modem port (9-pin D-sub male)
P33External Alarm Port (15-pin D-sub female) - Used for external alarm sensors
and alarm equipment. Four alarm inputs, EAL1 – EAL4, and two alarm
outputs
P34Not used
P35PSU, connector 2
P36IP or R2R connection between CU and FON
P37LNA Diversity DL
P38LNA Diversity UL
LNA
Figure 2-6 shows the front of the LNA and Table 2-6 lists the connections.
044-05251 Rev A2-5
PCBA ConnectionsHigh Power Wideband Radio Head (WRH-V)
Figure 2-6 LNA
Table 2-6 LNA Connections
LNA Port Connected to
OUT LOWIN on the LNA/UL in the cover, if equipped
INLO on the service DPX duplex filter
ATT +7VP23 on the DIA PCBA
OUT1P2101 on the WBA PCBA
OUT2Diversity LNA connected to P3101 on WBA PCBA
FON
Figure 2-7 shows the locations of the connectors on the FON and Table 2-7 lists the port numbers, connector
types, and port usage.
P117
Figure 2-7 FON Connector Locations
Table 2-7 FON Connectors
PortDescription
P101SMA, electrical RF input port (to the optical TX port)
P102SMA, electrical RF output port (from the optical RX port)
P103SMA, electrical RF output port (15dB below the P102 port)
RXDIN/APC, optical input port (to the P102 and P103 RF ports)
TXDIN/APC, optical output port (from the P101 RF port)
P104Used only for development and debugging
P1054-pin male, door LED indicators. Used for the yellow and red LED indicators located
on the front cabinet door
P1069-pin D-sub female, RS-232 used for local PC communication
P108/1166-pin male, parallel connected power ports for the FON
P1097-pin male, used for external alarm sensors
2-6044-05251 Rev A
High Power Wideband Radio Head (WRH-V)PCBA Connections
Table 2-7 FON Connectors (Continued)
PortDescription
P110W-link jumper, used to terminate units in a W-link. It has to be set in the parking
state for all units except for the first and last units in a W-link. The Parking state (P)
has the jumper between the center and bottom pins. The opposite state, with the
jumper between the tip and center pins, terminates(T) the W-link
P111/1125-pin male, WLI ports used for interconnecting nodes in WLI-nets (IP or R2R
networks). They are identical and connected in parallel. One of the connectors is
intended to be used from the previous node and the other connector to the next
node in the network. Either can be used for the first and the last unit in the net chain
P1132-pin male, used for the on-PCBA backup batteries
P114Backup power output jumper, sets the backup power output state. The OFF state
has jumper between the center and left pins. This jumper has to be in the OFF state
when used in an OCM. Otherwise, it shall be in the ON state
P1153-pin male, intended for future use
P117SMA, electrical RF output port (15dB below the P101 port)
P13034-pin, 2-line male, RCU port used for connecting an RCU. The connector contains
both the modem connection and RCU power supply
PSU
The PSU is located in the bottom middle of the cabinet or in an equipped high cover. The PSU has all the
voltages required for the WRH. It has capacity for the radio circuitry, fiber optics, and modem. Multi-band
WRH-Vs always require a second PSU. There are two PSU types with different input voltages:
1. 115/230V 50/60Hz, 300W input max.
2. 21- 60V DC, 300W input max.
The PSU is connected to the DIA at P21 and P35, and voltage is tested at V1 (test point for P35) and V2 (test
point for P21).
AC
1
1
1
1
1
1
M
M
M
>
>
>
-
-
S
S
S
1516
15 16
15 16
W5
W5
W5
AC
Power
Power
2
2
2
1
1
16
16
16
P11
P11
P11
5
5
5
6
6
6
3
3
3
P
P
P
2
2
2
1
1
1
X0A
X0A
X0A
P34
P34
P34
X0B
X0B
X0B
89
89
89
3
3
3
P28
P28
P28
DOOR
DOOR
DOOR
1
1
1
8
8
8
15
15
15
P26
P26
P26
2
2
2
1
1
1
1
1
1
6
6
6
P23
P23
P23
LNA
LNA
LNA
UP-LINK
UP-LINK
UP-LINK
9
9
9
9
9
9
5
5
5
1
1
1
P32
P32
P32
P33
P33
P33
MODEM
MODEM
MODEM
ALARM
ALARM
ALARM
P27
P27
P27
W6B10
W6B 10
W6B 10
8
8
8
1
1
1
X
X
X
U
U
U
A
A
A
ALLGON INNOVATION
ALLGON INNOVATION
ALLGON INNOVATIONSWEDEN M105 R6
SWEDEN M105 R6
SWEDEN M105 R61
1
1
PARKING
PARKING
PARKINGFOR W5
FOR W5
FOR W5
1V2
V2
V2
1
1
1
P6
P6
P6
c
c
c
b
b
b
a
a
a
1
1
1
P5
P5
P5
c
c
c
b
b
b
a
a
a
1
1
1
P4
P4
P4
c
c
cb
b
ba
a
a
POWER SUPPLY UNIT
POWER SUPPLY UNITPOWER SUPPLY UNIT
16
16
16
P12P13
P12P13
P12P13
16
16
16
16
16
16
16
16
16
1
1
1
16
16
16
1
1
1
b
b
b
a
a
1P232
1P232
1P232
c
c
c
b
b
b
a
a
a
a
1
1
1
16P3
16P3
16P3
V1V2
V1V2
1
1
1
16
V1
16
V1
16
V1
P14
P14
P14
LED
LED
LED
P22
P22
P22
4
4
4
2
2
2
1
1
1
1
1
1
S
S
S
>
>
>
-
-
-
6
6
6
M
M
M
15
15
15
9
9
9
16
16
16
15
15
15
1
1
1
P25
P25
P25
P29
P29
P29
6
2
6
2
6
2
P24
P24
P24
1
1
1
1
1
1
LNA
LNA
LNA
DOWN-LINK
DOWN-LINK
DOWN-LINK
DC
DC
DC
6V6
6V6
6V6
P31
P31
P31
PC
PC
PC
DPX
DPX
5
5
5
1
1
1
5
5
5
8
8
8
DPX
10
10
10
7
7
7
P21
P21
P21
TEST
TEST
TEST
GND
GND
GNDPSU
PSU
PSU
-30 dB
-30 dB
-30 dB
6
6
6
1
1
1
P35
P35
P35
4
4
4
-20 dB
-20 dB
-20 dB
MS
MS
MS
ANT
ANT
ANT
P21
P21
P35
P35
Figure 2-8 PSU Location
044-05251 Rev A2-7
Software and Hardware CompatibilityHigh Power Wideband Radio Head (WRH-V)
Software and Hardware Compatibility
There are different versions of CU PCBA software which can be combined with PCBAs of various revisions.
These have unique part numbers and revision information. Table 2-8 lists the software currently available in
combination with CU PCBA revisions.
Table 2-8 Hardware / Software Compatibility
CU PCBA part numberCU Software part number
500-13817-001 (previously K103/3)D631-18072-001
D631-18072-003
This information is accurate as of 06/31/2007. As new versions of hardware and software are released without
prior notice, contact your Powerwave sales representative for information on the latest revision.
For detailed information, refer to the release notes for the CU software to be downloaded (normally found in
the readme.txt file provided with the program files).
2-8044-05251 Rev A
Chapter 3
Installation
Introduction
This chapter contains unpacking, inspection and installation instructions for installing and powering up the
WRH.
Site Survey
Powerwave recommends that a site survey be performed prior to equipment ordering or installation.
Performing a detailed site survey reduces or eliminates installation and turn-up delays. Pay particular
attention to power plant capacity, cooling needs, floor space, and RF/DC cabling/breaker requirements.
Cabinet dimensions and weights are listed in Chapter 5.
Unpacking and Inspection
This equipment has been operated, tested, and calibrated at the factory. Carefully open containers to remove
equipment. Retain all packing material that can be reassembled in the event unit must be returned to the
factory. Perform the following steps:
❑ Visually inspect equipment for damage that may have occurred during shipment. If possible, in the
presence of the delivery person.
❑ Check for evidence of water damage, bent or warped chassis, loose screws or nuts, or extraneous
packing material in connectors.
If equipment is damaged, file a claim with the carrier once the extent of any damage is assessed.
If equipment must be returned to factory, please contact factory for a Return Material Authorization (RMA),
see Chapter 4.
WRH-V Location
The WRH-V is designed with a weather proof outdoor cabinet that can be mounted without any kind of shelter
from rain, snow or hail. The same unit can be installed indoors. A preferable site for the WRH-V is a location
free of obstructions, easily accessible and allows for proper air-flow and ventilation.
If a WRH-V is installed outdoors and can be exposed to direct sunshine, it is essential that air circulates
around the WRH-V with no obstacles. The operating temperature must not exceed 131°F (55°C). A shelter
can be used to shade the WRH-V from direct sunshine.
Never open a WRH-V when rain, snow, hail, high humidity or high winds are present unless some kind of
temporary shelter can be erected.
Mounting
The WRH-V is easy to mount using the provided mounting bracket, which has 9/16-inch (14mm) holes for 3/8inch (10mm) or 1/2-inch (12mm) fixing screws. Clamps with C-C measurements of 3.5-inch (90mm), 5.3-inch
(135mm), 5.7-inch (144mm), 8.1-inch (205mm), 9.8-inch (250mm), and 11.8-inch (300mm) can be used as
well. The vertical C-C measurement for these is 16.2-inch (411mm). There is a 9/16-inch (14mm) single hole
in the middle of the mounting bracket, marked ‘A’ in the figure, which is intended for a locking screw to lock the
bracket into place.
044-05251 Rev A3-1
MountingHigh Power Wideband Radio Head (WRH-V)
A
411
Ø14
90
135
144
205
250
300
Figure 3-1 Mounting Bracket
Normally, the WRH-V is mounted on a wall, pole, or mast. Figure 3-2 illustrates the installation of the
mounting bracket on a wall using four fixing screws and a locking screw.
Figure 3-2 Mounting Bracket Installation on Wall
Figure 3-3 illustrates the installation of the mounting bracket on a pole using two 5.7-inch (144mm) U-shaped
clamps and a locking screw.
3-2044-05251 Rev A
High Power Wideband Radio Head (WRH-V)Mounting
Figure 3-3 Attaching the Bracket to a Pole
Figure 3-4 illustrates a mast installation using two 11.8-inch (300mm) bar-shaped clamps and no locking
screw.
Figure 3-4 Attaching the Bracket to a Mast
After installing the mounting bracket, hang the WRH-V on the upper supports, as illustrated in Figure 3-5.
Tighten the upper and lower mounting screws to secure it into place using the 6mm hex socket wrench.
Locking cylinders, used to prevent unauthorized removal of the repeater, can be inserted and locked with a
044-05251 Rev A3-3
ConnectionsHigh Power Wideband Radio Head (WRH-V)
key after the lower screws have been tightened. Make sure the donor antenna, directed towards the BTS
antenna, and the service antenna, directed towards the area to be covered by the WRH, are mounted and
installed properly.
Figure 3-5 Attaching the WRH-V to the Bracket
Connections
This section describes general examples of how to connect the input and output ports on the WRH.
Main Power and Grounding
Local regulations need to be followed for the main power connection. WRH-Vs are approved in accordance
with EN and UL/cUL regulations. This is, however, only valid if a classified power cord is used. For the WRHV to meet these regulations you must select one of the following classified and approved cord types:
❑ EN – H 05 W5 - F HMR
❑ UL – AWM Style 2587
❑ CSA– AWM 1 A/B 11 A/B
For outdoor use, the power cord should meet at least IP65 encapsulation requirements. Do not turn the main
power on until you are ready to commission the WRH.
WARNING: For WRH-Vs supplied from the main power source, the main outlet must be
grounded.
Fiber Optic and RF Connections
Fiber optic and RF cable connections should be verified both internally and externally before powering up the
equipment. This section illustrates the general internal connections of the WRH-V. Verify these connections
with the as-built drawings and documents for your specific system configuration. Table 3-1 lists the steps to
add the external connections to the WRH-V.
3-4044-05251 Rev A
High Power Wideband Radio Head (WRH-V)Connections
Table 3-1 Cable Connection Procedure
StepAction
1Connect service antenna coaxial cable to left-outside DIN connection on cabinet
2Connect fiber optic cable from OCM or BMU to fiber optic cable demark on FOU
3Connect station ground to appropriate ground point in cabinet
4Mount main power plug to main power cord and insert into PSU
WRH-V
Figure 3-6 illustrates the cables and connections for the WRH-V.
Service Antenna
Connection
1550
1310
Fiber Optic
Connection
Power connection
Ground Points
Figure 3-6 WRH-V Cable Connections
044-05251 Rev A3-5
Optional ConnectionsHigh Power Wideband Radio Head (WRH-V)
Optional Connections
Alarms
Alarm signals from external sensors are received by an ALI or RCI which forwards them to the CU. The RCI is
used if the WRH-V has an RCU, otherwise the ALI is used. The software on the CU can activate acoustic or
visual alarms or direct the alarm to the P33 alarm port for forwarding via an RCU through OM-Online. Alarms
can also be handled by the FON. Alarms are configured through OM-Online.
External Alarm
Burglary, fire or other external alarms can be handled by the WRH-V. External alarm sensors and alarm
signals are connected to the P33 alarm port located to the left in the cabinet, as illustrated in Figure 3-7. The
P33 alarm port is described in Chapter 2. The cable for this installation is taken through a strain relief bushing
at the bottom of the WRH-V cabinet.
Door Open Alarm
A door open alarm can be configured and installed in the WRH. This is arranged with a door switch connected
to pin 8 (AI4) on P28, as described in chapter 2. The location of P28 is shown in Figure 3-7.
P28P33
1
1
M>
-S
1516
21
DC
UP-LINK
DPX
TEST
8
-30 dB
1XUA
MS
W5
-20 dB
1
ANT
2
16
1
V2
P11
5
63P
2
1
X0A
P34
X0B
89
3
P28DOOR
c
1
b
8
15
a
P26
1
6
P23LNA
cb
9
9
a
5
1
P32
P33
MODEM
ALARM
P27
W6B10
ALLGON INNOVATIONSWEDEN M105 R6
PARKINGFOR W5
1
P6
cba
1
P5
1
P4
P12P13
16
16
16
1
16
1P232
c
b
a
16
1
ba
1
1
16
V1
P14
LEDP22
4
1
1
S>
-
6
M
16P3
15
9
15216
1
P25
P29
6
2
P24
1
1
LNA
DOWN-LINK
DC
6V6
P31PC
DPX
5
10
7
TEST
P21
GND
PSU
-30 dB
1
6
5
8
MS
1
-20 dB
P35
4
ANT
POWER SUPPLY UNIT
Figure 3-7 External Alarm Connection
Main Power Breakdown Relay
To be able to distinguish PSU faults from power failures, a main power breakdown relay can be used. This
relay is not included in the WRH. It has to be mounted outside the WRH-V cabinet. The relay intended for this
purpose must fulfil the following specifications:
Closing time:Max. 30 milliseconds
Insulation coil/contact:Min. 4KV
A main power connected relay must also be in compliance with valid local regulations. To install a main power
breakdown relay connection, follow the steps listed in Table 3-2.
3-6044-05251 Rev A
High Power Wideband Radio Head (WRH-V)Commissioning
Table 3-2 Main Power Breakdown Relay Connection
StepAction
1Connect a currentless closed relay contact to pin AI1 and AIC on P33 alarm connector, as shown in
Figure 3-8. Alarm is initiated when pins AI1 and AIC are shorted
2Connect relay coil. Coil must be supplied from same fuse as WRH
3After commissioning, select Mains Breakdown in alarm configuration window in OM-Online. For
details on setting alarm configuration see OM-Online User Manual.
P33
P11
5
63P
1
X0A
3
1
6
9
MODEM
W6B10
89
P32
PARKINGFOR W5
P34
X0B
P28DOOR
15
1
9
5
ALARM
ALLGON INNOVATIONSWEDEN M105 R6
2
16
8
1
P33
1
V2
1
cba
1
P5
cba
1
P4
cba
16
P12P13
16
P6
16
16
1
16
1
b
1P232
cba
a
1
16P3
1
1
2
M>
-S
1516
P26
21
P23
LNA
DC
UP-LINK
DPX
TEST
P27
8
-30 dB
1XUA
MS
W5
-20 dB
1
ANT
1
16
V1
P14
LEDP22
4
1
2
1
S>
-
6
M
15
9
16
15
1
P25
P29
2
6
P24
1
1
LNA
DOWN-LINK
6V6
P31PC
5
10
7
P21
GND
PSU
1
6
5
1
P35
4
8
POWER SUPPLY UNIT
P33:AICP33:AI1
Figure 3-8 Main Power Breakdown Relay Connection
21-60 Volt DC PSU Installation
See the Field Replaceable Units, PSU section in Chapter 4 for details on replacing a 115/230 VAC PSU with
a 21 to 60 Volt DC PSU.
Commissioning
Before proceeding, carefully read the Safety section and check all connections made during the installation.
To fulfill the IP65 weather protective requirements, ensure cable strain relief bushings are properly tightened.
Also, ensure gaskets at cable inlets and on the cabinet are properly fitted and not damaged.
044-05251 Rev A3-7
CommissioningHigh Power Wideband Radio Head (WRH-V)
A WRH-V can be configured locally with OM-Online by connecting a standard serial cable from the COM port
on the PC to the P31 PC port (RS-232) located to the right in the cabinet as shown in Figure 3-9. The P31 PC
port is described in Chapter 2. Details on using OM-Online are described in the OM-Online User Manual.
P31
1
16
V1
P14
LEDP22
4
2
1
1
S>
-
6
M
15
9
16
15
1
P25
P29
6
2
P24
1
1
LNA
DOWN-LINK
6V6
P31PC
5
10
7
P21
GND
PSU
1
6
5
1
P35
4
8
X0B
P28DOOR
P32
ALLGON INNOVATIONSWEDEN M105 R6
PARKINGFOR W5
2
16
P34
8
15
1
9
5
1
P33
ALARM
1
V2
1
P6
cba
1
P5
cba
1
cba
16
P12P13
16
16
16P4
1
16
1
b
1P232
cba
a
1
16P3
1
P11
5
63
1
2
P
1
X0A
M>
-S
893
1
1516
P26
21
6
P23LNA
DC
UP-LINK
9
DPX
MODEM
TEST
P27
W6B10
8
-30 dB
1XUA
MS
W5
-20 dB
1
ANT
POWER SUPPLY UNIT
Figure 3-9 Connecting a PC for Local Access
Initial Startup
To complete the inital start-up of the WRH-V, follow the steps listed in Table 3-3.
Table 3-3 Initial Statup Procedure
StepAction
1Turn main power on
2Check Yellow LED on power supply unit. Steadily lit = functioning correctly
3Check the four CU PCBA LEDs. Refer to CU PCBA section in Chapter 2 for correct power up
indications
4Check the three ALI PCBA LEDs or corresponding LEDs on RCI PCBA. Refer to ALI or RCI PCBA
section in Chapter 2 for correct power up indications
3-8044-05251 Rev A
High Power Wideband Radio Head (WRH-V)Commissioning
(
Passive Intermodulation (PIM) Testing
PIM is the non-linear effect of passive RF components in a desired RF transmission band. As higher percarrier transmit power levels are applied to duplexed passive RF networks, PIM becomes an increasingly
significant factor in potential receiver desensitization. A PIM tester may be used on the RF network prior to
turn-on and commissioning of the unit, but if a PIM tester is not available, the following may be used:
The following equipment is required to test for PIM:
❑ Anritsu Site eMaster or equivilent RF Spectrum Analyzer
❑ Agilent ESG4432B or equivilent Multi-Signal Generator (or commissioned BTS)
❑ Guarateed/calibrated PIM load capable of handling 20W composite power
❑ Low-PIM RF cable adaptors such as N-N female, Din male to N femaile, DIN-DIN, SMA-SMA
female, and N male to SMA female
❑ Installed and operational WRH-V unit
❑ Installed passive RF network under test
❑ Torque wrenches for DIN and N connectors
Two different types of setup are available, depeding on equipment availability and testing methods.
Figure 3-10 shows PIM testing with two carriers over one WRH-V, and Figure 3-11 shows PIM testing with
one carrier over each of two WRH-Vs.
E4432B
SIG Gen
or BTS)
E4432B
SIG Gen
(or BTS)
Σ
OCM
E4402B
Spec. An.
WRH-V
Load /
DAS
Figure 3-10 PIM testing two carriers and one WRH-V
E4432B
Sig Gen /
BTS 1
E4432B
Sig Gen /
BTS 2
OCM
OCM
WRH-V
WRH-V
Under Test
E4402B
Spec. An.
Hybrid
Load /
DAS
Figure 3-11 PIM testing one carrier over each of two WRH-Vs
The following PIM test uses the receive sensitivity and gain of the WRH-V under test to verify that the receive
path is free of PIM noise. For PIM to be a problem at a particular site, TX signals must exist such that their
products fall into the RX band using the formulae:
3rd order product = (2 * f1) - f
2
and
3rd order product = (2 * f2) - f
1
044-05251 Rev A3-9
CommissioningHigh Power Wideband Radio Head (WRH-V)
Where f1 and f2 are two TX signals entering a WRH-V. The specification for the maximum allowed PIM is -115
dBm per 100 kHz resolution bandwidth at rated output power. To test for PIM follow the steps listed in
Table 3-4.
Table 3-4 PIM Testing Procedure
StepAction
1If BTS signals are present, continue with step 2. Otherwise, connect two signal generators to OCM
and set frequencies such that products are in relevent receive band (see equations above)
2Set WRH-V UL gain to 60 dB and DL gain such that desired per carrier power is presented at output
port
3Set Spectrum Analyzer to 100 kHz resolution bandwidth and view RX band at 3rd order product
frequency calculated in step 1
4 Loosen fastening screw in each corner on front cover of WRH-V under test, and open cover
5Verify the noise floor specification for the Spectrum Analyzer. If the noise floor is higher than or equal
to -85 dBm/100 kHz, locate FON, disconnect UL cable from port P101 and connect
SpectrumAnalyzer to the cable using an SMA female - female connector (noise limit becomes -115
dBm + 60 dB = -55 dBm). Continue with step 7.
6If noise floor is lower than -85 dBm/100 kHz, locate the FON card and connect the Spectrum Analyzer
to P117 (noise limit becomes -115 dBm + 60 dB - 30 dB = -85 dBm). If the FON only has three RF
ports on the left side, port P117 will not be available, so follow instructions listed in step 5.
7Enable WRH-V TX signal. For details on using OM-Online, see OM-Online user manual
8Using Spectrum Analyzer, measure noise level. If no noise exists above calculated limit in step 5
(-55 dBm) or step 6 (-85 dBm) above, as appropriate, then test is passed and no other action is
necessary
9If a higher level of noise exists, disable the WRH-V TX signal and disconnect cable to DAS at bottom-
left outside corner
10Connect low PIM load onto WRH-V Service antenna connector at bottom-left outside corner. Tighten
11Remeasure noise level. If no noise exists above calculated limit in step 5 (-55 dBm) or step 6 (-85
12Otherwise, if noise is higher than limit, WRH-V is defective and must be replaced. See Chapter 4 for
connectors securely
dBm) as appropriate, then DAS has a PIM issue. Tighen all connections in DAS with torque
wrenches, replace any cripmed or severely bent cables, and retest. Repeat until all issues are solved
Replacement procedures
3-10044-05251 Rev A
Chapter 4
Maintenance
Introduction
This chapter contains periodic maintenance and performance test procedures for the WRH.
Periodic Maintenance
Periodic maintenance requirements are listed in Table 4-1, as well as the intervals at which the tasks should
be performed.
Table 4-1 Recommended Periodic Maintenance
TaskIntervalAction
Inspection of cables
and connectors
Clean equipmentClean as required depending on operating environment
12 monthsInspect power, RF and Fiber cables for signs of damage or wear
(frayed insulation, cracks, punctures, etc.) Check connections to be
sure they are tight
OptionalPerform cable sweeps
Troubleshooting
The sections that follow contain a list of problems that could occur and a few suggested actions that might
correct each problem. If the suggested corrective action does not eliminate the problem, please contact your
Powerwave field representative or help line for further instruction.
Clearing Alarm Faults
Table 4-2 lists the alarms that can be generated in the WRH. Critical, Error and Warning alarms are sent
automatically from a WRH-V to OM-Online, stored and then viewed in the Alarm window.
Table 4-2 Alarm Troubleshooting
IDAlarm TextAlarm UnitAlarmDescription
1PowerPSUCriticalPSU1 in the cabinet does not work properly. A sum signal from
the PSU1 indicates that at least one voltage output has dropped. If
no mains breakdown relay is used, then the alarm will also be sent
at mains breakdown
CeasingPSU1 in the cabinet works properly again. Ceasing is sent if the
PSU1 works at start-up, and there is a corresponding critical
PSU1 alarm logged in the Events log. The WRH-V will restart
when the power is back and this alarm will be sent
PSUCriticalPSU2 in the cover does not work properly. A sum signal from the
PSU2 indicates that at least one voltage output has dropped. If no
mains breakdown relay is used, then the alarm will also be sent at
mains breakdown
044-05251 Rev A4-1
TroubleshootingHigh Power Wideband Radio Head (WRH-V)
Table 4-2 Alarm Troubleshooting (Continued)
IDAlarm TextAlarm UnitAlarmDescription
CeasingPSU2 in the cover works properly again. Ceasing is sent if the
PSU2 works at start-up, and there is a corresponding critical
PSU2 alarm logged in the Events Log. The WRH-V will restart
when the power is back and this alarm will be sent
PowerFONErrorThe FON 10 Volt charger voltage is below limit. Suggested
remedy: Replace the FON
CeasingThe cause of the alarm has ceased
2WRH-V
restart
3Mains
breakdown
4Alarm resetCUNoneAlarm reset by the user. All alarms are reset. The cause of the
5Local bus
error
6Main bkd w
backup
CUNonePower on start, or user ordered reboot. Logged to indicate a
normal power up, or a restart ordered by the operator
WarningSoftware error restart, 1st – 7th time. Restart 1st to 7th time during
a 14 day period. The counter is reset every 14th day, counted
from power up
ErrorSoftware error restart 8th – 10th time. Restart 8th to 10th time
during the 14 day period. At the 11th time, the SW bank will be
blocked and not used anymore until a user ordered reset is
performed, or power is switched off/on
ExternalCriticalThe mains power is gone. Used with an external relay indicating
mains breakdown. The external relay should be connected to
External Alarm 1 and the WRH-V configured to indicate this alarm.
If no relay is used, a mains breakdown will be reported as a PSU
fault
CeasingThe mains power is back. Sent if there is a corresponding critical
mains breakdown alarm logged in the Events Log. The WRH-V
will restart when the power is back
alarm will be re-evaluated and reported, if still active
WBA #,
MCPA#
ExternalErrorUsed to indicate that the mains is no longer available. WRH-V is
ErrorError when communicating on the bus. The CU has no contact
with the WBA, or MCPA PCBA, which is taken out of service
powered by external battery backup unit. Suggested remedy:
Check the mains power
CeasingThe cause of the alarm has ceased
7Err in AD-
converter
8New unit
detected
9Inst. unit lostErrorCompared to the last power on, the CU lacks at least one
10EEPROM
error
11Log memory
fault
CUErrorEEP read or write fail. Data cannot be written or read from the
WarningThe analog-to-digital converter on the CU PCBA does not give
reliable values
NoneCompared to the last power on, the CU has recognized at least
one additional hardware unit
hardware unit
EEPROM on the CU PCBA. User parameters are stored in the
EEPROM
ErrorLog memory fault. Indicates that the log memory on the CU PCBA
is faulty. The WRH-V will not work. Not available in all CU
software versions
4-2044-05251 Rev A
High Power Wideband Radio Head (WRH-V)Troubleshooting
Table 4-2 Alarm Troubleshooting (Continued)
IDAlarm TextAlarm UnitAlarmDescription
12High tempCUWarningThe CU PCBA temperature is higher than 90°C
CeasingThe CU PCBA temperature has fallen below 90°C
13REFO errorErrorSignificant REFO drift or error detected by CU
14Ext REFO
error
15CU battery
fault
16SW load errorCUErrorSoftware load error. An error has occurred during a software load
17Log clearedCUNoneLog memory has been cleared. The check sum in the Events Log
18RTC restartedCUNoneThe time is changed by the operator (logged to keep track of
19RTC errorErrorRTC does not operate. The CU has detected an error in the RTC
CUWarningCU RAM battery fault. The battery for the RAM on the CU PCBA
WarningSuggested remedy: Check the reference source and the cables
has a voltage outside the normal 2.7 to 3.5 Volt. An alarm may be
initiated at start-up if the WRH-V has been stored out of power for
a long time. Suggested remedy: Ensure jumper P3 on the CU
PCBA is mounted to charge the battery
CeasingThe cause of the alarm has ceased
process. The flash memory does not contain a proper software.
Suggested remedy: Check the CU software using the OM-Online
SW Manager. Do NOT restart the WRH
memory is faulty. The log is cleared. Can be caused of a bad RAM
battery backup or low voltage to the RAM
changes made to the RTC)
WarningTime reset to 1994-01-01. The RTC was unable to keep track of
the time and did a reset. Suggested remedy: Ensure jumper P3 on
the CU PCBA is mounted to charge the battery
operation which makes the time unreliable. Suggested remedy:
Replace the CU PCBA
20Door open
alarm
21External
alarm 1
22External
alarm 2
23External
alarm 3
24External
alarm 4
ExternalConfigThe door has been open 30 seconds without disabling the alarm
CeasingThe door has been closed 30 seconds, or the alarm is disabled
ExternalConfigExternal alarm input EA1 active more than 1 second
CeasingExternal alarm input EA1 no longer active
ExternalConfigExternal alarm input EA2 active more than 1 second
CeasingExternal alarm input EA2 no longer active
ExternalConfigExternal alarm input EA3 active more than 1 second
CeasingExternal alarm input EA3 no longer active
ExternalConfigExternal alarm input EA4 active more than 1 second
CeasingExternal alarm input EA4 no longer active
044-05251 Rev A4-3
TroubleshootingHigh Power Wideband Radio Head (WRH-V)
Table 4-2 Alarm Troubleshooting (Continued)
IDAlarm TextAlarm UnitAlarmDescription
30No modem
found
33No
connection
34Login failedNoneInvalid WRH-V password
35Remote
connection
36Modem init
failed
37Remote
timeout
38PIN code
failed
Remote ctrlNoneNo modem found, that is no answer is returned on a poll string to
the modem
Remote ctrlNoneNo connection at callback. The WRH-V has tried to call as many
times as stated in the alarm call settings. No connection was
established.
WarningNo connection at alarm call. The WRH-V has tried to call as many
times as stated in the alarm call settings. No connection was
established. This alarm does not generate a new attempt to report
alarm by alarm call.
Remote ctrlNoneModem connection to OM-Online opened. Not logged on CU2.
Login Registry gives the same function and more information
about CU2
Remote ctrlNoneInitiation string to modem not OK. The initiation string sent to the
modem is not OK. The string may contain commands not
recognized by the modem. An alarm might be sent anyway.
Suggested remedy: Check the modem using the OM-Online or
OMS modem debugger
Remote ctrlWarningThe time limit of 20 minutes is exceeded without extending the
timer. The modem connection is terminated by the WRH
Remote ctrlWarningThe PIN code sent to MS is incorrect. To unlock the MS/SIM card,
the PUK code will probably be needed
39No phone
detected
40Battery faultRCU, FON
42Antenna
isolation
48Battery
backup fault
Remote ctrlWarningWhen using a PC-card together with the MS, the alarm indicates
charger
WBA #,
Channel #,
UL/DL
ExternalErrorIf a battery backup unit alarm is connected to external alarm 2,
CeasingThe cause of the alarm has ceased
contact with the PC-card, but MS is not present or turned off.
Note: A Nokia MS does not power-up after power failure.
Suggested remedy: Ensure the cellular phone is connected
CeasingThe cause of the alarm has ceased
ErrorThe backup battery on the RCU or the FON PCBA does not work
properly. Suggested remedy: Check cables or replace battery
CeasingThe cause of the alarm has ceased
WarningLow antenna isolation. The antenna isolation is lower than the
gain set. Gain is reduced by 10dB – 13dB below the oscillation
point. Suggested remedy: Decrease gain or increase antenna
isolation
ErrorLow antenna isolation at lowest gain. The gain has been reduced
as much as possible but the oscillation still remains. The amplifier
is turned off. Suggested remedy: Decrease gain or increase
antenna isolation
CeasingNormal operation again, that is no oscillation can be detected
13dB above the gain set
then the operator can configure the WRH-V to display this alarm
when the battery backup unit indicates alarm
4-4044-05251 Rev A
High Power Wideband Radio Head (WRH-V)Field Replaceable Units
Table 4-2 Alarm Troubleshooting (Continued)
IDAlarm TextAlarm UnitAlarmDescription
CeasingThe cause of the alarm has ceased
50Fiberoptical
error
70Bad table
alarm
71Table not
found
72Table
database
error
80Antenna
SWR alarm
90FON power
alarm
91FON
TxStable
alarm
FOT fiber
optics
CUErrorRequested table contains incorrect information (SW error)
CUErrorRequested table not found in the database (SW or calibration
CUErrorTable database not found (calibration error)
Donor
antenna
service
antenna
FON RFErrorA DC voltage on a FON PCBA is out of range. Suggested remedy:
FON RFErrorLaser transmitter control loop voltage out of range. Suggested
Configur
able
CeasingThe cause of the alarm has ceased
ErrorToo low antenna return loss, caused either by cables, connectors,
CeasingThe cause of the alarm has ceased
CeasingThe cause of the alarm has ceased
If a fiber unit alarm is connected to external alarm 3, then the
operator can configure the WRH-V to display this alarm when the
fiber optical unit indicates alarm
error)
or antenna problems.
Suggested remedy: Check antenna and cables
Replace the FON PCBA.
remedy: Replace the FON PCBA
CeasingThe cause of the alarm has ceased
92FON RxLevel
alarm
93FON SPI
alarm
245Not In
Allowed Area
FONWarningReceived optical level is below any of the two limits (one for
Warning and one for Error). Suggested remedy: Check optical
cables
ErrorReceived optical level is below any of the two limits (one for
Warning and one for Error). Suggested remedy: Check optical
cables
CeasingThe cause of the alarm has ceased
FON F2FErrorThe SPI bus connection to the RF modem does not work properly.
Suggested remedy: Replace the FON PCBA
CUNoneWRH-V is moved from the operating area and the RF HW is
switched on or off
Remarks:
The Door Open alarm requires an optional door switch described in the Door Open Alarm section of Chapter
3.
The Main power breakdown alarm requires an optional relay described in the Main Power Breakdown Relay
section of Chapter 3.
Field Replaceable Units
044-05251 Rev A4-5
Field Replaceable UnitsHigh Power Wideband Radio Head (WRH-V)
The following units can be replaced in the field on-site by a qualified technician with experience maintaining
RF equipment:
❑ FON
❑ PSU
❑ WRH
FON
To replace a FON PCBA, follow the steps listed in Table 4-3. For details on cables and connectors, see
Chapter 2.
CAUTION: Do not look into the end of any fiber optic cable. Be sure to cap fiber optic
cables to protect the connecting end from damage
NOTE
Verify ‘Fiberoptical’ classmark in the FON Status window is checked, otherwise FON will not be operational.
Classmarks are described in the OM-Online User Manual.
Table 4-3 FON Replacement Procedure
StepAction
1Loosen all four locking screws on front of cabinet
2Open WRH-V door and secure
3Locate power connector on FON and remove connector from PCBA
4Verify all cables on FON are labeled before disconnecting, then disconnect all cables.
5Remove screws securing FON PCBA to FOU and remove PCBA
6Replace FON PCBA in reverse order and apply power
7Connect PC to OM Online port, login to FON and verify configuration and IP address.
8Close WRH-V door and secure
PSU
To replace a PSU, follow the steps listed in Table 4-4. For details on cables and connectors, see Chapter 2.
4
5
6
Figure 4-1 PSU Cable, Switch and Lable locations
4-6044-05251 Rev A
High Power Wideband Radio Head (WRH-V)Field Replaceable Units
Table 4-4 PSU Replacement Procedure
StepAction
1Loosen all four locking screws on front of cabinet
2Open WRH-V door and secure
3Disconnect main power plug from PSU(Location 1 shown in Figure 4-1)
4Disconnect power cable bundle from PSU(Location 2 shown in Figure 4-1)
5Loosen but do not remove screws securing PSU using a 5mm Allen key and remove PSU (Location 3
shown in Figure 4-1)
6On new AC power supply, if used, set input voltage switch on PSU to correct input voltage -- 115 VAC
or 230 VAC (Location 4 shown in Figure 4-1)
7On new DC power supply, if used, verify that the supply voltage is 24 VDC or 48 VDC as stated on
label on PSU (Location 5 shown in Figure 4-1)
8Set new PSU to correct output supply voltage (27 VDC) by moving wire connection plug as illustrated
on label on PSU (Location 6 shown in Figure 4-1)
9Mount new PSU with all four fixing screws (Location 3 shown in Figure 4-1)
10Connect PSU to DIA PCBA (Location 2 shown in Figure 3-9) with cable marked VE007 98/1. This
cable must be used in all situations. If only one connection is available on DIA PCBA, the second
connector may be tied out of the way with a cable tie
11Insert power cord (AC power supply) or connect DC power cable brown wire to positive (+) pole and
blue wire to negative (-) pole (DC power supply)
12Close WRH-V door and secure with four locking screws on front of cabinet
WRH-V
To replace a WRH-V, follow the steps listed in the Table 4-5.
WARNING: A fully loaded WRH-V can weigh 96lbs. Lifting of the WRH-V should be done
by two people. Do not attempt to carry the WRH-V up a ladder.
044-05251 Rev A4-7
Remote Control Unit (RCU)High Power Wideband Radio Head (WRH-V)
.
Table 4-5 WRH-V Replacement Procedure
StepAction
1Loosen all four locking screws on front of cabinet
2Open WRH-V door and secure
3Disconnect main power plug from PSU
4Verify all external cables connected to WRH-V are labeled before disconnecting, then disconnect all
external cables
5Remove mounting screws from bottom legs of WRH-V and loosen mounting screws in top legs
6Close and secure door
7Lift the WRH-V off of mount hinges
8Replace WRH-V in reverse order
9Connect PC to OM Online port and verify configuration. For Fiber Optic installations, verify IP
address
10Close WRH-V door and secure
Remote Control Unit (RCU)
The RCU provides remote control of Powerwave WRHs. It contains an integrated mobile phone, modem and
power supply backup. The RCU is installed in the bottom front of the cabinet, on top of the PSU as illustrated
in Figure 4-2.
The RCU is connected to P130 on either an RCI or FON. A jumper is required between pins 1 and 2 on the
RCI if the P130 cable connector is disconnected. If a main power failure occurs, the unit has a battery with
enough capacity for sending a number of alarms.
1
16
V1
P14
LEDP22
4
2
1
1
S>
-
6
M
15
9
16
15
1
P25
P29
6
2
P24
1
1
LNA
DOWN-LINK
DC
6V6
P31
PC
5
10
1
6
5
1
P35
4
8
DPX
7
P21
TEST
GND
PSU
-30 dB
MS
-20 dB
ANT
X0B
P28DOOR
P32
ALLGON INNOVATIONSWEDEN M105 R6
PARKINGFOR W5
2
16
P34
8
15
1
9
5
1
P33
ALARM
1
V2
1
P6
cba
1
P5
cba
1
P4
cba
16
P12P13
16
16
16
1
16
b
1P232
cba
a
1
16P3
1
1
P11
5
63
1
2
P
1
X0A
M>
-S
89
3
1
1516
P26
21
6
P23
LNA
DC
UP-LINK
9
DPX
MODEM
P27
TEST
W6B10
8
-30 dB
1XUA
MS
W5
-20 dB
1
ANT
POWER SUPPLY UNIT
RCU
Figure 4-2 RCU in the WRH-V cabinet
4-8044-05251 Rev A
High Power Wideband Radio Head (WRH-V)Return For Service Procedures
RCU for Radio Communication
The RCU antenna for a radio modem is connected to the BS antenna via the uplink DC, provided the RCU
and the WRH-V operate in the same cell system. Otherwise, the modem must have a separate antenna. Data
is transferred between the WRH-V and the RCU via the P130 modem port on the RCI or FON. The RCU is
also powered via the same port and has a battery with enough capacity to send a number of alarms if a main
power failure occurs.
RCU for Telephone Line Communication
The land line version uses a telephone line connected to a terminal block on the RCU. A free strain relief
bushing at the bottom of the WRH-V is used for the external telephone line cable.
Return For Service Procedures
When returning products to Powerwave, the following procedures will ensure optimum response.
Obtaining an RMA
A Return Material Authorization (RMA) number must be obtained prior to returning equipment to the factory
for service. Pease contact our Repair Department at +1-714-466-1000 to obtain this number, or FAX your
request to +1-714-466-5800. Failure to obtain this RMA number may result in delays in receiving repair
service.
Repackaging for Shipment
To ensure safe shipment of the unit, it is recommended that the original package designed for shipping the
unit be reused. If it is not available, contact Powerwave’s Customer Service Department at 1-800-797-9283,
+1-714-466-100 or by e-mail at support@pwav.com for packing material.
044-05251 Rev A4-9
Return For Service ProceduresHigh Power Wideband Radio Head (WRH-V)
This page intentionally left blank
4-10044-05251 Rev A
Introduction
This chapter provides specifications for the WRH-V.
Table 5-1 WRH-V Specifications
Electrical
Frequency band UL824 to 849 MHz (Cellular)
806 to 824 MHz (800 iDEN)
880 to 915 MHz (GSM 900)
896 to 901 MHz (900 iDEN)
1710 to 1785 MHz (GSM 1800)
1850 to 1910 MHz (PCS)
1920 to 1980 MHz (UMTS)
1710 to 1755 MHz (AWS 2100)
Frequency band DL869 to 894 MHz (Cellular)
851 to 869 MHz (800 iDEN)
935 to 940 MHz (GSM 900)
925 to 960 MHz (900 iDEN)
1805 to 1880 MHz (GSM 1800)
1930 to 1990 MHz (PCS)
2110to 2170 MHz (UMTS)
2110 to 2155 MHz (AWS 2100)
Chapter 5
Specifications
Max absolute delay<300 ns
Gain adjustment range (in 1 dB steps)30 dB
Gain
Uplink
Downlink
Variation
Instantaneous bandwidth25 MHz (Cellular)
Uplink AGC limit0 dBm at FON input
Downlink AGC limit43 dBm at antenna port
Return Loss11 dB
35 to 60 dB typical - Excluding fiber link
45 to 70 dB typical - Excluding fiber link
± 1.5 dB versus temperature including fiber link
± 1.5 dB versus DL frequency including fiber link
± 0.5 dB versus DL output power including fiber link
± 0.5 dB versus input voltage including fiber link
± 2.0 dB versus UL frequency including fiber link
Power consumption210 W typical, 300 W max (Single band)
Impedance
Input
Output
Mechanical
Dimensions (W x H x D in inches)465 x 530 x 195 mm (18.3 x 20.9 x 8.3 in) incl. hinges (low cover)
Weight<25 kg (55 lbs) low cover
Service Antenna port connector7/16 DIN Female
Donor Optical port connectorFC/APC
Environmental
Operating Temperature Range-25 °C to +55 °C (-13°F to +131°F)
Altitude-142 m to 4000 m (-466 ft. to 13100 ft.
Casing classNEMA4/IP65
20 A for AC voltage
40 A for DC voltage
420 W typical, 600 W max (Dual band)
Not Applicable - Optical input
50 Ω
465 x 530 x 310 mm (18.3 x 20.9 x 12.3 in) incl hinges (high cover)
<44 kg (96 lbs) high cover
Fiber Optic Node (FON)
Bandwidth @ 3dB800 – 2200 MHz
Power Consumption, total<5 W
5-2044-05251 Rev A
High Power Wideband Radio Head (WRH-V)Introduction
Table 5-1 WRH-V Specifications (Continued)
WavelengthTX: DFB 1310 or 1550 nm
RX: 1250 – 1600 nm
Transmit
Max continuous RF input
Optical output power, two levels
RF attenuation settable by SW in 1dB steps
Receive
Max optic power input
RF attenuation settable by SW in 1dB steps
Alarm threshold level, settable warning
Alarm threshold level, settable error
+36dBm
+3 or 0dBm
0-20dB
+5dBm
4-24dB
0-40dBm
0-40dBm
044-05251 Rev A5-3
IntroductionHigh Power Wideband Radio Head (WRH-V)
This page intentionally left blank
5-4044-05251 Rev A
Appendix A
Block Diagrams
Introduction
This appendix describes the main signals paths for the WRH.
Non-Diversity
Figure A-2 shows the non-diversity block diagram configuration of the WRH-V. The WRH-V is always fed by a
BTS via either a BMU or an OCM. The TX signal from the BTS is converted to an optical signal in a BMU or
OCM and fed to the WRH-V via a fiber optic cable. The optical signal is then received by the FON and
converted to an RF signal. The FON supervises the signaling and reports errors via the RCU connected to the
CU.
The RF signal enters the WBA, is amplified, and further amplified in amplifier stages followed by controllable
attenuators. The signal exits the WBA and enters the MCPA where it is amplified and fed to the DPX. The
amplified output signal passes the DPX before it is fed to the service antenna.
The uplink signal path is located on the same WBA but goes through an LNA before entering the WBA.
To/From
OCM or
BMU
WDM
PSU
WBA
DL
FOU
DX
FON
DX
RCU
RCI
UL
LNA
WBA
DL
UL
LNA
CU
Figure A-1 WRH-V Block Diagram - Non-Diversity
MCPA
MCPA
DPX
DPX
ALI
850 MHz
TX0/RX0
1900 MHz
TX0/RX0
To
External
alarms
044-05251 Rev AA-1
DiversityHigh Power Wideband Radio Head (WRH-V)
Diversity
Figure A-2 illustrates the diversity block diagram configuration of the WRH-V. With diversity installed, there
are two paths on the UL instead of one. This requires an additional FON for the added receive path signal.
Signal flow is identical to the non-diversity version with the MCPA on the DL and LNAs on the UL providing
the additional amplification out of and into the WBA.
To/From
OCM or
BMU
WDM
PSU
RCU
RCI
FOU
FON
FON
DX
DX
DX
WBA
DL
UL
UL
WBA
DL
UL
UL
CU
LNA
LNA
LNA
LNA
MCPA
MCPA
DPX
DPX
DPX
DPX
ALI
850 MHz
TX0/RX0
850 MHz
RX1
1900 MHz
TX0/RX0
1900 MHz
RX1
To
External
alarms
Figure A-2 WRH-V Block Diagram - Diversity
A-2044-05251 Rev A
P
owerw
ave
I
nstallation a
nd
S
ervice
M
anua
l
Corporate Headquarters
Powerwave Technologies, Inc.
1801 East St. Andrew Place
Santa Ana, CA 92705 USA