PowerWalker VFI 6000 CG PF1 operation manual

PowerWalker
VFI 6000 CG PF1
VFI 10000 CG PF1
User Manual
EN / DE
Please comply with all warnings and operating
instructions in this manual strictly. Save this
manual properly and read careful ly the following
instructions before installing the unit. Do not
operate this unit before reading through all
safety information and operating instructions
carefully.
Table of Contents
1. SAFETY AND EMC INSTRUCTIONS ......................................................................................................................... 1
1-1. TRANSPORTATION AND STORAGE ................................................................................................................................... 1
1-2. PREPARATION ................................................................................................................................................................ 1
1-3. INSTALLATION ............................................................................................................................................................... 1
1-4. CONNECTION WARNINGS ................................................................................................................................... 2
1-5. OPERATION ................................................................................................................................................................... 3
1-6. STANDARDS ................................................................................................................................................................... 3
2. INSTALLATION AND OPERATION ........................................................................................................................... 4
2-1. UNPACKING AND INSPECTION ......................................................................................................................................... 4
2-2. REAR PANEL VIEW ........................................................................................................................................................ 4
2-3. SINGLE UPS INSTALLATION ........................................................................................................................................... 5
2-4. UPS INSTALLATION FOR PARALLEL SYSTEM .................................................................................................................... 6
2-5. SOFTWARE INSTALLATION .............................................................................................................................................. 7
3. OPERATIONS .................................................................................................................................................................. 8
3-1. BUTTON OPERATION ...................................................................................................................................................... 8
3-2. LED INDICATORS AND LCD PANEL ................................................................................................................................. 8
3-3. AUDIBLE ALARM .......................................................................................................................................................... 10
3-4. SINGLE UPS OPERATION ............................................................................................................................................. 10
3-5. PARALLEL OPERATION .................................................................................................................................................. 14
3-6. ABBREVIATION MEANING IN LCD DISPLAY ................................................................................................................... 15
3-7. LCD SETTING ............................................................................................................................................................. 16
3-8. OPERATING MODE/STATUS DESCRIPTION .................................................................................................................... 20
3-9. FAULT CODE ............................................................................................................................................................... 22
3-10. WARNING INDICATOR ............................................................................................................................................... 22
3-11 WARNING CODE ......................................................................................................................................................... 23
4. TROUBLE SHOOTING ................................................................................................................................................ 24
5. STORAGE AND MAINTENANCE .............................................................................................................................. 25
5-1. STORAGE .................................................................................................................................................................... 25
5-2. MAINTENANCE ............................................................................................................................................................. 25
6. SPECIFICATIONS........................................................................................................................................................ 26

1. Safety and EMC instructions

Please read carefully the f ollowing us er manual a nd the safet y instruc tions befor e installing the unit or usi ng the unit!

1-1. Transportation and Storage

Please transport the UPS system only in the original package to protect against shock and
impact.
The UPS must be stored in the room where it is ventilated and dry.

1-2. Preparation

Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or nearby heater.
Do not block ventilation holes in the UPS housing.

1-3. Installation

Do not connect appliances or devices which would overload the UPS (e.g. big motor-type equipment)) to the UPS output sockets or terminal.
Place cables in such a way that no one can step on or trip over them.
Do not block air vents in the housing of UPS . T he UPS m ust be ins talled i n a l ocation wi th goo d ventilation. Ensure enough space on each side for ventilation.
UPS has provided earthed terminal, in the final installed system configuration, equipotential earth bonding to the external UPS battery cabinets.
The UPS can be installed only by qualified maintenance personnel.
An appropriate disconnect device as short-circuit backup protection should be provided in the building wiring installation.
An integral single emergency switching device which prevents f ur ther supply to the load by the UPS in any mode of operation should be provided in the building wiring installation.
Connect the earth before connecting to the building wiring terminal.
Installation and Wiring must be performed in accordance with the local electrical laws and regulations.
1

1-4. Connection Warnings

Before working on this circuit
There is no standard backfeed protection inside of the UPS. Please isolate the UPS before working according to Diagram 1. The isolation device must be able to carry the UPS input current.
Diagram 1: External backfeed protection wiring
This UPS should be connected with TN earthing system.
The power supply for this uni t must be single-phase rated in accordance wi th the equipment nameplate.
It also must be suitably grounded.
Use of this equipment in life support applications where failure of this equipment can reasonably be
expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
Connect your UPS power module’s grounding terminal to a grounding electrode conductor.
The UPS is connected to a DC energy source (battery). The out p ut terminals may be live when the UPS
is not connected to an AC supply.
- Isolate Uninterruptible Power System (UPS)
- Then check for Hazardous Voltage between all terminals including the protective earth.
Risk of Voltage Backfeed
2

1-5. Operation

* Safety
IEC/EN 62040-1
* EMI
Conducted Emission...............................:IEC/EN 62040-2
Category C3
Radiated Emission..................................:IEC/EN 62040-2
Category C3
*EMS
ESD.........................................................:IEC/EN 61000-4-2
Level 4
RS........................................................ ...:IEC/EN 61000-4-3
Level 3
EFT......................................................... :IEC/EN 61000-4-4
Level 4
SURGE................................................... :IEC/EN 61000-4-5
Level 4
CS........................................................... :IEC/EN 61000-4-6
Level 3
Power-frequency Magnetic field.............. :IEC/EN 61000-4-8
Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
tion in the
installation restrictions or additional measures may be
needed to prevent disturbances.
Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any
time since this would cancel the protective earth of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the “OFF” button and then disconnect the mains.
Ensure that no liquid or other foreign objects can enter into the UPS system.
The UPS can be operated by any individuals with no previous experience.

1-6. Standards

Warning: This is a product for commercial and industrial applica
second environment-
3

2. Installation and Operation

Model
Type
Model
Type
6K
6KL
10K
10KL
Emergency power off function connector (EPO
There are two different types of online UPS: standard and long-run models. Please refer to the following model table.
standard model
Parallel function is also available for these two types and related installation and operation of Parallel function will be described in detail in the following content.
Long-run model

2-1. Unpacking and Inspection

Unpack the package and check the package contents. The shipping package contains:
One UPS
One user manual
● One monitoring software CD
One RS-232 cable (option)
One USB cable
One parallel cable (only available for parallel model)
One share current cable (only available for parallel model)
● One battery cable (option)
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged during transportation. Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts. Please keep the original package in a safe place for future use.

2-2. Rear Panel View

Diagram 1: 6K/10K Diagram 2: 6KL/10KL
Rear Panel Rear Panel
1) Share current port (only available for parallel model)
2) Parallel port (only available for parallel model)
3) External battery connector
4) Intelligent slot
5) RS-232 communication port
6) USB communication port
7) connector)
8) Maintenance bypass switch
9) Cooling fan
10) Input cir cui t breaker
11) Output terminals
12) Ground
13) Input terminals
4

2-3. Single UPS Installation

Wiring spec (AWG)
Input
Output
Battery
Ground
6K
10
10 10
6KL
10
10
10
10
10K 8 8 8
10KL 8 8 8 8
Input Neutral
Input Line
Ground
Output Line
Output Neutral
Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the following instructions by professional personnel.
1) Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
2) Switch off the mains switch in the building before installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare wires based on the following table:
Model
NOTE 1: The cable for 6K/6KL should be able to withstand over 40A current. It is recommended to use 10AWG or thicker wire for safety and efficiency.
NOTE 2: The cable for 10K/10KL should be able to withstand over 63A current. It is recommended to use 8AWG or thicker wire for safety and efficiency.
NOTE 3: The selections for color of wires should be followed by the local electrical laws and regulations.
5) Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the following terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect the earth wire last when making wire disconnection!)
Terminal Block wiring diagram
NOTE 1: Make sure that the wires are connected tightly with the terminals. NOTE 2: Please install the output breaker between the output terminal and the load, and the breaker
should be qualified with leakage current protective function if necessary.
6) Put the terminal block cover back to the rear panel of the UPS.
5
Warning: (Only for standard model)
● Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring connection.
● Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the standard internal battery to the e xtern al ba ttery . T he b attery ty pe a nd volta ge m ay be di ffer ent. If yo u connect them together, it maybe causes the hazard of electric shock or fire!
Warning: (Only for long-run model)
● Make sure a DC breaker or other protection device between UPS and external battery pack is installed. If
not, please install it carefully. Switch off the battery breaker before installation.
Warning:
For standard battery pack, there is one DC breaker to disconnect the battery pack and the UP S . But for other external battery pack, make sure a DC breaker or other protection device between UPS and external battery pack is installed. If not, please install it carefully. Switch off the battery breaker before installation.
NOTE: Set the battery pack breaker in “OFF” position and then install the battery pack.
● Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the numbers of the battery pack, please make sure you modify the setting simultaneously. The connection with wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the battery pack is correct.
● Pay highly attention to the polarity marking on external battery terminal block, and make sure the correct battery polarity is connected. Wrong connection may cause permanent damage of the UPS.
● Make sure the protective earth ground wiring is correct. The wire current spec, color, position, connection and conductance reliability should be checked carefully.
● Make sure the utility input & output wiring is correct. The wire current spec, color, position, connection
and conductance reliability should be checked carefully. Make sure the L/N site is correct, not reverse and short-circuited.

2-4. UPS Installation for Parallel System

If the UPS is only available for single operation, you may skip this section to the next.
1) Install and wires the UPSs according to the section 2-3.
2) Connect the output wires of each UPS t o an output breaker.
3) Connect all output breakers to a major output breaker. Then this major output breaker will directly connect to the loads.
4) Each UPS is connected to an independent battery pack.
5) Remove the cover of parallel share current cable port on the UP S, connect each UPS one by one with the parallel cable and share current cable, and then screw the cover back again.
NOTE: The parallel system can not use one battery pack. Otherwise, it will cause system permanent failure.
6
6) Refer to the following wiring diagram:
Diagram 1: Power cable connection
Diagram2: Wiring diagram of parallel system

2-5. Software Installation

For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
7

3. Operations

Turn on the UPS: Press and hold the button more than 0.5s to turn on the UPS.
Turn off the UPS: Press and hold the button more than 0.5s to turn off the UPS.
Battery test: Press and hold the button more than 0.5s to test the battery while
UP key: Press this button to display next selection in setting menu.
Mute the alarm: Press and hold the button more than 0.5s to mute the buzzer.
Test/Up +
Mute/Down Button
Press and hold the two buttons simultaneous more than 1s to e nter/escape the
setting menu.
UPS Startup
● ● ●
No Output mode
○ ○ ○
Bypass mode
AC mode
○ ● ○
Battery mode
○ ● ○
○ ● ○
Battery Test
ECO mode
Fault

3-1. Button Operation

Button Function
ON/Enter Button
OFF/ESC Button
Test/Up Button
Mute/Down Button
* CVCF mode means converter mode.
 Enter Key: Press this button to confirm the selection in setting menu.
Esc key: Press this button to return to last menu in setting menu.
in AC mode, or CVCF mode.
Please refer to section 3-4-9 for details.
 Down key: Press this button to display previous selection in setting menu.

3-2. LED Indicators and LCD Panel

LCD panel
LED indicators
There are 4 LEDs on front panel to show the UPS working status: Mode LED Bypass Line Battery Fault
CVCF mode
Note: ● means LED is lighting, and ○ means LED is faded.
8
LCD Panel:
Display
Function
Backup time information
Indicates battery discharge time in numbers.
H: hours, M: minutes, S: seconds
Fault information
Indicates that the warning and fault occurs.
Indicates the fault codes, and the codes are listed in details in section 3-9.
Mute operation
Indicates that the UPS alarm is disabled.
Output & Battery voltage information
Indicates the output voltage, frequency or battery voltage.
Load information
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates the load or the output is short.
Mode operation information
Indicates the UPS connects to the mains.
Indicates the battery is working.
Indicates the bypass circuit is working.
Indicates the ECO mode is enabled.
Indicates the Inverter circuit is working.
Indicates the output is working.
Vac: output voltage, Vdc: battery voltage, Hz: frequency
9
Battery information
Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the battery is not conne cted.
Indicates low battery level and low battery voltage.
Input & Battery voltage information
Indicates the input voltage or frequency or battery voltage. Vac: Input voltage, Vdc: battery voltage, Hz: input frequency

3-3. Audible Alarm

Description
Buzzer status
Muted
UPS status
Bypass mode
Beeping once every 2 minutes
Battery mode
Beeping once every 4 seconds
Fault mode
Beeping continuously
Warning
Overload
Beeping twice every second
Others
Beeping once every second
Fault
Yes
Yes
Yes
All Beeping continuously

3-4. Single UPS Operation

3-4-1. Turn on the UPS with utility power supply (in AC mode)

1) After power supply is connected correctly, set the breaker of the battery pack at “ON” position (the step only available for long-run model). Then set the input breaker at “ON” position. At this time the fan is running and the UPS enter to power on mode f or initialization, several seconds later, UPS operates in Bypass mode and supplies power to the loads via the bypass.
NOTE: When UPS is in Bypass mode, the output voltage will directly power from utility after you switch on the input breaker. In Bypass mode, the load is not protected by UPS. To protect your precious devices, you should turn on the UPS. Refer to next step.
2) Press and hold the “ON” button for 0.5s to turn on the UPS and the buzzer will beep once.
3) A few seconds later, the UPS will enter to AC mode. If the utility power is abnormal, the UPS will operate in Battery mode without interruption.
NOTE: When the UPS is running out battery , it will shut down automatically at Battery mode. When the utility power is restored, the UPS will auto restart in AC mode.

3-4-2. Turn on the UPS without utility power supply (in Battery mode)

1) Make sure that the breaker of the battery pack is at “ON” position (only for long-run model).
2) Press the “ON” button to set up the pow er supply for the UPS, UPS will enter to power on mode. After initialization UPS will enter to No Output mode, then Press and hold the “ON” button for 0.5s to turn on the UPS, and the buzzer will beep once.
3) A few seconds later, the UPS will be turned on and enter to Battery mode.
10

3-4-3. Connect devices to UPS

After the UPS is turned on, you can connect devices to the UPS.
1) Turn on the UPS f irst and then switch on the devices one by one, the LCD panel will display total load level.
2) If it is necessary to connect the inductive loads such as a printer, the in-rush current should be calculated carefully to see if it meets the capacity of the UPS, because the power consumption of this kind of loads is too big.
3) If the UPS is overload, the buzzer will beep twice every second.
4) When the UPS is overload, please remove some loads immediately. It is recommended to have the total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload for system safety.
5) If the overload time is longer than acceptable time listed in spec at AC mode, the UPS will automatically transfer to Bypass mode. After the overload is removed, it will return to AC mode. If the overload time is longer than acceptable time listed in spec at Battery mode, the UPS will become fault status. At this time, if bypass is enabled and the voltage and frequency in the r ange of it is set value, the UPS will power to the load via bypass. If bypass function is disabled or the input power is not within bypass acceptable range, it will cut off output directly.

3-4-4. Charge the batteries

1) After the UPS is connected to the utility power and working on the AC mode, the charger will charge the batteries automatically except in Battery mode or during battery self-test.
2) Suggest to charge batteries at least 10 hours before use. Otherwise, the backup time may be shorter than expected time.
3) Make sure the battery numbers setting on the control board (Please refer to the section 3-4-12 for detailed setting) is consistent to real connection.

3-4-5. Battery mode operation

1) When the UPS is in Battery mode, the b uzzer will beep according to dif ferent battery c apacity . If the battery capacity is more than 25%, the buzzer will beep once every 4 seconds; If the battery voltage drops to the alarm level, the buzzer will beep quickly ( once every sec) to remind users that the battery is at low level and the UPS will shut down automatically soon. Users could switch off some non-critical loads to disable the shutdown alarm and prolong the backup time. If there is no more load to be switched off at that time, you have to shut down all loads as soon as possible to protect the devices or save data. Otherwise, there is a risk of data loss or load failure.
2) In Battery mode, if buzzer sound annoys, users can press the Mute button to disable the buzzer.
3) The backup time of the long-run model depends on the external battery capacity.
4) The backup time may vary from different environment temperature and load type.
5) When setting backup time for 16.5 hours (990min in LCD setting menu 09), after discharging 16.5 hours, UPS will shut down automatically to protect the battery. This battery discharge protection can be enabled or disabled through LCD panel control. (Refer to 3-7 LCD setting section)

3-4-6. Test the batteries

1) If you need to check the battery status when the UPS is running in AC mode/CVCF mode/ECO mode, you could press the “Test” button to let the UPS do battery self-test.
2) T o keep the system reliable, the UPS can perform the battery self-test periodically while connect the
11
monitoring software.
3) Users also can set battery self-test through monitoring software.
4) If the UPS is at battery self-test, the LCD display and buzzer indication will be the same as at Battery mode except that the battery LED is flashing.

3-4-7. Turn off the UPS with utility power supply in AC mode

1) Turn off the inverter of the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once. The UPS will turn into Bypass mode.
NOTE 1: If the UPS has been set to enable the bypass output, it will bypass voltage from utility power to output terminal even though you have turned off the UPS (inverter).
NOTE 2: After turning off the UPS, please be aware that the UPS is working at Bypa ss mode and there is risk of power loss for connected devices.
2) In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off the input breaker. A few seconds later, there is no display shown on the display panel and UPS is complete off.

3-4-8. Turn off the UPS without utility power supply in Battery mode

1) Turn off the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once.
2) Then UPS will cut of f power to output and there is no display shown on the display panel.

3-4-9. Mute the buzzer

1) To mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after t he buzzer is muted, the buzzer will beep again.
2) Some warning alarms can’ t be muted unless the error is f ixed. Please refer to section 3-3 for the details.

3-4-10. Operation in warning status

1) When Fault LED flashes and the buzzer beeps once every second, it means that there are some problems for UPS operation. Users can get the warning code from LCD panel. Please check the 3-11 warning code table and the trouble shooting table in chapter 4 for details.
2) Some warning alarms can’t be muted unless the error is f ixed. Please refer to section 3-3 for the details.

3-4-11. Operation in Fault mode

1) When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error in the UPS. Users can get the fault code from display panel. Please check the 3-9 fault code table and the trouble shooting table in chapter 4 for details.
2) Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try to turn on the UPS again bef ore solving the proble ms. If the problems can’t be fixed, please contact the distributor or service people immediately.
3) For emergency case, please cut off the connection from utility, external battery, and output immediately to avoid more risk or danger.

3-4-12. Operation of changing battery numbers

1) This operation is only available for professional or qualified technicians.
2) Turn off the UPS. If the load couldn’t be cut off, you should remove the cover of maintenance
12
bypass switch on the rear panel and turn the maintenance switch to “BPS” position first.
JP1
pin1 & pin2
pin3 & pin4
Pin5 & pin6
pin7 & pin8
Pin9 & pin10
16 X X 1 0 0 17 X X 0 1 1 18 X X 0 1 0 19 X X 0 0 1 20 X X 0 0
0
in series
voltage (V)
16
218
0 0 0 1 0
17
232
0 0 1 0 0
18
245
0 1 0 0 0
19
259
1 0 0 0 0
20
273
0 0 0 0 0
Charge current (A)
1A
0 0 1
3A
1 0 0
3) Switch off the input br eaker, and switch off the battery breaker (only ava ilable for long-run model).
4) Remove the cabinet cover and disconnect battery wire for standard model. Then, modify the jumper on the control board to set the battery numbers as below table.
Battery Number
in series
Note: 0 = no jumper; 1 = connect with jumper; x = the pins are for other functions.
5) Modify the battery pack to meet the setting number in control board carefully.
6) Modify charger voltage according to below table to meet the setting number in control boar d. There are 5 jumpers on the charger board. Please refer to the below table to modify charger voltage.
Battery Number
Charge
JP01 JP02 JP03 JP04 JP05
Note: 0 = no jumper; 1 = connect with jumper.
7) After complete the above steps, put the cover back, switch on the battery breaker for long-run model and switch on the input breaker. Then, the UPS will enter Byp ass mode. If the UPS is in maintenance Bypass mode, turn the maintenance switch to “UPS” position and then turn on the UPS.

3-4-13. Operation of changing charging current:

1) This operation is only available for professional or qualified technicians.
2) Turn off the UPS. If the load couldn’t be cut off, you should remove the cover of maintenance bypass switch on the rear panel and turn the maintenance switch to “BPS” position first.
3) Switch off the input breaker, and switch off the battery breaker (only available f or long-run model).
4) Remove the cabinet cover, and disconnect battery wire for standard model. Then modify the jumpers on the charger board to set the charging current (refer to table below). Be careful that the maximum charge current should not exceed the battery accepted charging current.
JP06 JP07 JP08
2A 0 1 0
4A 0 0 0
Note: 0 = no jumper; 1 = connect with jumper.
13

3-5. Parallel Operation

3-5-1. Parallel system initial startup

First of all, please make sure all of the UPSs are parallel models and have the same configuration.
1) Turn on each UPS to AC mode respectively (Refer to section 3-4-1). Then, measure the output voltage of each UPS to check if the voltage difference between actual output and setting value is less than 1.5V (typical 1V) with multimeter. If the difference is more than 1.5V, please calibrate the voltage by configuring inverter voltage adjustment (Refer to Program 15, section 3-7) in LCD setting. If voltage difference remains more than 1.5V after calibration, please contact your local distributor or service center for help.
2) Calibrate the output voltage measurement by configuring output voltage calibration (Refer t o Program 16, section 3-7) in LCD setting to make sure the error between real output voltage and detected value of UPS is less than 1V.
3) Turn off each UPS (Refer to section 3-4-7.). Then, follow the wiring procedure in section 2-4.
4) Remove the cover of parallel share current cable port on the UPS, connect each UPS one by one with the parallel cable and share current cable, and then screw the cover back.

3-5-2. Turn on the parallel system in AC mode

1) Turn on the input breaker of each UPS. After all UPSs enter to bypass mode, measure the voltage between output L1 of each UPS with multimeter. If the voltage difference is less than 1V, that means all connections are correct. Otherwise, please check if the wirings are connected correctly.
2) Turn on the output breaker of each UPS. Before turning on each UPS in turns, check if PARXXX is displayed in each UPS sequentially. If no “PARXXX” exists in any UPS, please check if the parallel cables are connected correctly.
3) Turn on each UPS in turns. After a while, the UPSs will enter to AC mode synchronously and then, the parallel system is completed.

3-5-3. Turn on the parallel system in Battery mode

1) Turn on the battery breaker (only available in long-run model) and output breaker of each UPS . NOTE: It’s not allowed to share one battery pack for long-run UPSs in parallel system. Each UPS
should be connected to its battery pack.
2) Turn on any UPS. A few seconds later, the UPS will enter to battery mode.
3) Press the “ON” button to set up the power supply for another UPS, check if PARXXX is displayed. If not, please check if the parallel cables are connected correctly. Then Turn on another UPS. A few seconds later, the UPS will enter to battery mode and add to the parallel system.
4) If you have the third UP S, follow the same procedure of 3). Then, the parallel system is complete.

3-5-4. Add one new unit into the parallel system

1) Yo u can not add one new unit into t he par allel system whe n whole sy stem is runni ng. You must cut off the load and shutdown the system.
2) Make sure all of the UPS are the parallel models, and follow the wiring refer to section 2-4.
3) Install the new parallel system refers to the previous section.

3-5-5. Remove one unit from the parallel system

There are two methods to remove one unit from the parallel system: First method:
1) Press the “OFF” key twice and each time should last for more than 0.5s. Then, the UPS will enter
into bypass mode without output.
2) Turn off the output breaker of this unit, and then turn off the input breaker of this unit.
14
3) After it shuts down, you can turn off the battery breaker (for long-run model) and remove the
BAT
Battery
parallel cable and share current cable. Then, remove the unit from the parallel system.
Second method:
1) If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the load and shut down the system.
2) Make sure the bypass setting is enabled in each UPS and then turn of f the running syste m. All UPSs will transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintena nce switches from “UPS” to “BPS”. Turn off the input breakers and battery breakers.
3) Remove the UPS that you want.
4) Turn on the input breaker of the remaining UPSs and the system will transfer to Bypass mode.
5) Set the maintenance switches from “BPS” to “UPS and put the ma intenance bypass covers back. Turn on the remaining UPSs and finish the parallel system connection.
Warning: (Only for the parallel system)
● Before turning on the parallel system to activate inverter, make sure that all unit’s maintenance switch
at the same position.
● When parallel system is turned on to work through inverter, please do not operate the maintenance
switch of any unit.

3-6. Abbreviation Meaning in LCD Display

Abbreviation Display content Meaning
ENA DIS ATO
NCF CF SUB ADD ON OFF FBD OPN
Enable Disable Auto
Normal mode (not CVCF mode) CVCF mode Subtract Add On Off Not allowed
Allow RES OP.V PAR
Reserved
Output voltage
Parallel
15
Loading...
+ 42 hidden pages