PowerWalker VFI 6000 CG PF1 Product Information

Online UPS
BlueWalker GmbH | Hellersbergstrasse 6, 41460 Neuss, Germany | Tel.: +49 2131 206 17 59
110-300 VAC @ 0-60% load
176-300 VAC @ 80-100% load
≤4% @ 100% load
≤6% @ 50% load
≤1% Full Linear Load
≤4% Non-Linear Load
The PowerWalker VFI 6000-10000 CG PF1 is a professional series for
PowerWalker VFI 6000-10000 CG PF1 Series
Unity Power Factor (PF 1.0 means 10kVA = 10kW of the output!)
Professional solution for commercial application
Programmable output voltage and frequency
Generator-compatible and very low Total Harmonic Distortion on output voltage
EPO Function (Emergency Power Off)
commercial applications featuring unity Power Factor (PF=1.0), very
low harmonic distortions (<1%) and high efficiency (up to 94%). The
wide input voltage and frequency ranges allow operation in unstable
networks and provide generator support.
Multiple accessories, including battery packs and communication
cards, enhance the functionality of the UPS and allow a greater
backup time. The system can be monitored locally via an LCD panel or remotely via the PowerWalker ViewPower software.
TECHNICAL SPECIFICATION
2016 PREMIERE
MODEL VFI 6000 CG PF1 VFI 10000 CG PF1
Item Number 10122048 10122049 Power Power Factor
Input Voltage Range
Input PF ≥ 0.99 at full load Max THDi Frequency Range 46Hz - 54Hz or 56Hz - 64Hz
Nominal Output Voltage 208/220/230/240 VAC Voltage Regulation ±1%
THDv Frequency (Synchronized Range) 46Hz - 54Hz or 56Hz - 64Hz
Frequency (Battery Mode) ±0,1Hz
Overload Capacity
Batteries 16 x 9Ah/12V 20 x 9Ah/12V Charger 1A Recharge Time 9h to 90% Full Load Backup Time 3.7min 2.8min Half Load Backup Time 11.2min 8.4min Battery Connection Yes, for external battery pack
6000VA / 6000W 10000VA / 10000W
Unity Power Factor (PF=1.0)
INPUT
140-300 VAC @ 60-80% load
OUTPUT
Line: 10min @100%-110%; 1min @110%-130%; 1s @>130%
BAT: 30s @100%-110%; 10s @110%-130%; 1s @>130%
BATTERIES
Online UPS
BlueWalker GmbH | Hellersbergstrasse 6, 41460 Neuss, Germany | Tel.: +49 2131 206 17 59
COMMUNICATION
ENVIRONMENT
Name
Picture
Name
Picture
SNMP Manager
EMD for SNMP Manager
AS400 Card
Modbus Card 2
SNMP Box
MBS/PDU 19in 6-10KVA
BP A192T-16x9Ah
BPH A240T-20
BP A192T-32x9Ah
BPH A240T-40
MODEL VFI 6000 CG PF1 VFI 10000 CG PF1
TECHNICAL DETAILS
Transfer Time [Inverter to Bypass] 0ms Transfer Time [AC to Battery] 0ms Load Crest Ratio 3:1 Fan Logic Always on, automatic speed control LINE mode full Load 94% BATTERY mode full Load 91%
Communication USB port, RS-232 port, EPO, Intelligent Slot Software PowerWalker ViewPower
Noise Level < 55dB < 58dB Temperature 0°C – 40°C Humidity 20% - 95% RH (non-condensing)
ACCESSORIES
Network Management Item Number: 10120505 EAN: 4260 074974 03 4
Environment M od ul e Item Number: 10120544 EAN: 4260 074974 96 6
BACK VIEW
Dry Contacts Item Number: 10120515 EAN: 4260 074974 30 0
Network M an agemen t Item Number: 10131000 EAN: 4260 074977 42 4
16x9Ah, 192VDC Item Number: 10134026
32x9Ah, 192VDC Item Number: 10134027 EAN: 4260 074978 12 4
Modbus Protocol Item Number: 10120565 EAN: 4260 074975 70 3
Maintenance Bypass Switch (Power Distribution Unit) Item Number: 10120584 EAN: 4260 074976 25 0
for 20 bat, 24 0VD C Item Number: 10134024 EAN: 4260 074977 80 6
for 40 bat, 24 0VD C Item Number: 10134025 EAN: 4260 074977 81 3
01/08/2016