PowerWalker VFI 30K CPG 3/3, VFI 40K CPG 3/3 User Manual

Page 1
User Manual PowerWalker VFI 30K CPG 3/3 PowerWalker VFI 40K CPG 3/3
EN
Uninterruptible Power Supply System
Page 2
Please comply with all warnings and operating
instructions in this manual strictly. Save this
manual properly and read carefully the following
instructions before installing the unit. Do not
operate this unit before reading through all
safety information and operating instructions
carefully.
Page 3
Table of Contents
1. SAFETY AND EMC INSTRUCTIONS ......................................................................................................................... 1
1-1. TRANSPORTATION AND STORAGE ................................................................................................................................... 1
1-2. PREPARATION ................................................................................................................................................................ 1
1-3. INSTALLATION ............................................................................................................................................................... 1
1-4. OPERATION ................................................................................................................................................................... 2
1-5. STANDARDS ................................................................................................................................................................... 3
2. INSTALLATION AND OPERATION ........................................................................................................................... 4
2-1. UNPACKING AND INSPECTION......................................................................................................................................... 4
2-2. REAR PANEL VIEW ......................................................................................................................................................... 5
2-3. SINGLE UPS INSTALLATION ........................................................................................................................................... 7
2-4. UPS INSTALLATION FOR PARALLEL SYSTEM .................................................................................................................... 9
2-5. SOFTWARE INSTALLATION .............................................................................................................................................. 9
3. OPERATIONS................................................................................................................................................................ 10
3-1. BUTTON OPERATION .................................................................................................................................................... 10
3-2. LED INDICATORS AND LCD PANEL ............................................................................................................................... 10
3-3. AUDIBLE ALARM .......................................................................................................................................................... 12
3-4. SINGLE UPS OPERATION ............................................................................................................................................. 12
3-5. PARALLEL OPERATION .................................................................................................................................................. 15
3-6. ABBREVIATION MEANING IN LCD DISPLAY ................................................................................................................... 16
3-7. LCD SETTING ............................................................................................................................................................. 17
3-8. OPERATING MODE/STATUS DESCRIPTION .................................................................................................................... 22
3-9. FAULT CODE ............................................................................................................................................................... 28
3-10.WARNING INDICATOR ................................................................................................................................................ 28
3-11.WARNING CODE ......................................................................................................................................................... 29
4. TROUBLE SHOOTING ................................................................................................................................................ 30
5. STORAGE AND MAINTENANCE .............................................................................................................................. 32
5-1. STORAGE .................................................................................................................................................................... 32
5-2. MAINTENANCE ............................................................................................................................................................. 32
6. SPECIFICATIONS........................................................................................................................................................ 33
Page 4
1
1. Safety and EMC instructions
Please read carefully the f ollowing user manual and the sa fety inst ructions before i nstalling the unit or u sing the unit!
1-1. Transportation and Storage
Please transport the UPS system only in the original package to protect against shock and
impact.
The UPS must be stored in the room where it is ventilated and dry.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or nearby heater.
Do not block ventilation holes in the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS (e.g. big motor-type equipment)) to the UPS output sockets or terminal.
Place cables in such a way that no one can step on or trip over them.
Do not block air vents in the housing of UPS. The UPS must be i ns tal led in a location with good ventilation. Ensure enough space on each side for ventilation.
UPS has provided earthed terminal, in the final installed system configuration, equipotential earth bonding to the external UPS battery cabinets.
The UPS can be installed only by qualified maintenance personnel.
An appropriate disconn ect d e v ice as short-circuit backup protection should be provided in the building wiring installation.
An integral single emergency switching device which prevents further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation.
Connect the earth before connecting to the building wiring terminal.
Installation and Wiring must be performed in accordance with the local electrical laws and regulations.
Page 5
2
1-4. Connection Warnings
• This UPS should be connected with TN earthing system.
• The power supply for this unit must be si ngle-phase rat ed in accordance with the equipment name plate. It also must be suitably grounded.
• Use of this equipment in life support applications where failure of this equipment can reasona bly be expected to cause the failure of the life support equipment or to signif ic antly affect its safety or effectiveness is not re commended. Do not use this e quipment in the presence of a flammable anest hetic mixture with air, oxygen or nitrous oxide.
• Connect your UPS power module’s grounding terminal to a grounding electrode conductor.
Page 6
3
1-5. Operation
Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any
time since this would cancel the protective earth of the UPS system and of al l c onnected lo ads.
The UPS system features its own, internal current source (batteries). The UPS output so ckets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the “OFF” button an d then disconne ct the mains.
Ensure that no liquid or other foreign objects can enter into the UPS system.
The UPS can be operated by any individuals with no previous experience.
1-6. Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission...............................:IEC/EN 62040-2
Category C3
Radiated Emission..................................:IEC/EN 62040-2
Category C3
*EMS
ESD...................................................... ...:IEC/EN 61000-4-2
Level 4
RS........................................................ ...:IE C/EN 61000-4-3
Level 3
EFT......................................................... :IEC/EN 61000-4-4
Level 4
SURGE................................................... :IEC/EN 61000-4-5
Level 4
CS........................................................... :IEC/EN 61000-4-6
Level 3
Power-frequency Magnetic field.............. :IEC/EN 61000-4-8
Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
Warning:
This is a product for commercial and industrial application in the
second environment-
installation restrictions or additional measures may be
needed to prevent disturbances.
Page 7
4
2. Installation and Operation
There are two different types of online UPS: standard and long-run models. Please refer to the following model table.
Model
Type
Model
Type
30K
Standard
model
30KL
Long-run
model
40K
40KL
We also offer optional parallel function for these two types by request. The UPS with parall el function is called as “Parallel model”. We have described detailed installation and operation of Parallel Model in the following chapter.
2-1. Unpacking and Inspection
Unpack the package and check the package contents. The shipping package contains:
One UPS
One user manual
● One monitoring software CD
One RS-232 cable (option)
One USB cable
One parallel cable (only available for parallel model)
One share current cable (only available for parallel model)
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged during transportation. Do not turn on the unit and notify the carrier and dealer immediately if there is any damage o r lacking of some parts. Please keep the original packaging in a safe place for future use. It is advisable to keep each equipment and battery set, inside their original packaging because they have been designed to assure the maximum protection during transport ant storage.
Page 8
5
2-2. Rear Panel View
Diagram 1: 40K Rear Panel Diagram 2: 30K Rear Panel
Page 9
6
Diagram 3: 40KL Rear Panel Diagram 4: 30KL Rear Panel
Diagram 5: 30K(L)/ 40K(L) Input/Output Terminal
1.RS-232 communication port
2.USB communication port
3.Emergency power off function connector (EPO connector)
4.Share current port (only available for parall el mod el)
5.Parallel port (only available for parallel model)
6.Intelligent slot
Page 10
7
7. External battery terminal(Only available for long-run model)
8.Line Input circuit breaker (40K(L))
9.Maintenance bypass switch
10.Input/Output terminal
11.Power stage fan
12.Line Input circuit breaker (30K(L))
13.Output Grounding terminal
14.Output terminal: connect to mission-critical loads
15.Line input terminal
16.Input Grounding terminal
2-3. Single UPS Installation
Installation and wiring must be performed in a ccordance with the local electric laws/regulations and execute the following instructions by professional personnel.
1) Make sur e the mains w ire and breakers in the building are enough for the rated capacity o f UPS to avoid the hazards of electric shock or fire.
NOTE: Do not use t he wall re ceptacle as the input power source for the UPS, a s its rated current is le ss than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
2) Switch off the mains switch in the building before installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare wires based on the following table:
Model
Wiring spec (AWG)
Input(Ph)
Output(Ph)
Neutral
Battery
Ground
30K 8 8 4
4
30KL 8 8 4 4 4
40K 7 7 4
4
40KL 7 7 4 4
4
NOTE 1: The cable for 30K/30KL should be able to w ithstand over 63A current. It is recommended to use AWG 8 or thicker wire for Phase and AWG 4 or thicker wire for Neutral fo r safety and efficiency.
NOTE 2: The cable for 40K/40KL should be able to w ithstand over 80A current. It is recommended to use AWG 7 or thicker wire for Phase and AWG 4 or thicker wire for Neutral for safety and efficiency.
NOTE 3: The selections for color of wires should be followed by the local electrical laws and regulations.
5) Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the following terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect the earth wire last when making wire disconnection!)
Page 11
8
Terminal Block wiring diagram of 30K(L)/40K(L)
NOTE 1: Make sure that the wires are connected tightly with the terminals. NOTE 2: Please install the output breaker between the output terminal and the load, and the breaker
should be qualified with leakage current protective function if necessary.
6) Put the terminal block cover back to the rear panel of the UPS.
Warning: (Only for standard model)
● Make sure the UPS is not turned on before installation. The UPS should not be turn ed on during wi ring connection.
● Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the standard internal battery to the external battery. The battery type and voltage may be different. If you connect them together, it maybe causes the hazard of electric shock or fire!
Warning: (Only for long-run model)
● Make sure a DC breaker or other protection device between UPS and external battery pack is installed. If not, please install it carefully. Switch off the battery breaker before installation.
NOTE: Set the battery pack breaker in “OFF” position and then install the battery pack.
● Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the numbers of the battery pack, please make sure you modify the setting simultaneously. The connection with wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the battery pack is correct.
● Pay highly attention to the polarity marking on external battery terminal block, and make sure the
correct battery polarity is connected. Wrong connection may cause permanent damage of the UPS.
● Make sure the protective earth ground wiring is correct. The wire current spec, color, position, connection and conductance reliability should be checked carefully.
● Make sure the utility input & output wiring is correct. The wire current spec, color, position, connection
and conductance reliability should be checked carefully. Make sure the L/N site is correct, not reverse and short-circuited.
Page 12
9
2-4. UPS Installation for Parallel System
If the UPS is only available for single operation, you may skip th is section to the next.
1) Install and wires the UPSs according to the section 2-3.
2) Connect the output wires of each UPS to an output breaker.
3) Connect all output breakers to a major output breaker. Then this major output breaker will directly connect to the loads.
4) Both sharing battery cabinet and independent battery cabinet for each UPS are allowed.
5) Refer to the following wiring diagram:
Wiring diagram of parallel s ystem for 30K(L)/40K(L)
2-5. Software Installation
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
Page 13
10
3. Operations
3-1. Button Operation
Button Function
ON/Enter Button
Turn on the UPS: Pres s and h ol d the button more than 0.5s to turn on the UPS.
Enter Key: Press this button to confirm the selection in setting menu.
OFF/ESC Button
Turn off the UPS: Press and hold the button more th an 0.5s to turn off the UPS.
Esc key: Press this button to return to last menu in setting menu.
Test/Up Button
Battery test: Press and hold the button more than 0.5s to test the battery while
in AC mode and CVCF* mode.
UP key: Press this button to display next selection in setting menu.
Mute/Down Button
Mute the alarm: Press and hold the button more than 0.5s to mute the buzzer.
Please refer to section 3-4-9 for details.
Down key: Press this button to display previous selection in setting menu.
Test/Up +
Mute/Down Button
Press and hold the two buttons simultaneous more than 1s to enter/escape the
setting menu.
* CVCF means Constant Voltage and Constant Frequency.
3-2. LED Indicators and LCD Panel
LED Indicators:
There are 4 LEDs on front panel to show the UPS working status:
Mode LED
Bypass
Line
Battery
Fault
UPS On
● ● ●
No Output mode
○ ○ ○
Bypass mode
AC mode
○ ● ○
Battery mode
○ ● ○
CVCF mode
○ ● ○
Battery Test
ECO mode
Fault
Note: ● means LED is lighting, and ○ means LED is faded.
LCD panel
LED indicators
Page 14
11
LCD Panel:
Display
Function
Backup time information
Indicates the battery discharge time in numbers H: hours, M: minutes, S: seconds
Fault inform at io n
Indicates that the warning and fault occurs.
Indicates the fault codes, and the codes are listed in details in section 3-9.
Mute operation
Indicates that the UPS alarm is disabled.
Output & Battery voltage information
Indicates the output voltage, frequency or battery voltag e . Vac: output voltage, Vdc: battery voltage, Hz: frequency
Load information
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates the load or the output is short.
Mode operation information
Indicates the UPS connects to the mains.
Indicates the battery is working.
Indicates the bypass circuit is working. Indicates the ECO mode is enabled. Indicates the Inverter circuit is working.
Indicates the output is working.
Page 15
12
Battery information
Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the battery is not connected.
Indicates low battery level and low battery voltage.
Input & Battery voltage information
Indicates the input voltage or frequency or battery voltage. Vac: Input voltage, Vdc: battery voltage, Hz: input frequency
3-3. Audible Alarm
Description
Buzzer status
Muted
UPS status
Bypass mode
Beeping once every 2 minutes
Yes
Battery mode
Beeping once every 4 seconds
Fault mode
Beeping continuously
Warning
Overload
Beeping twice every secon d
No
Others
Beeping once eve ry second
Fault
All
Beeping continuously
Yes
3-4. Single UPS Operation
1. Turn on the UPS with utility power supply (in AC mode)
1) After power supply is connected correctly, set the breaker of the battery pack at “ON” position (the step only available for long-run model). Then set the line input breaker at “ON” position (for dual input unit, also set the bypass input breaker at “ON”). At this time the fan is running and the UPS enter to power on mode for initialization, several seconds later, UPS operates in Bypass mode and supplies power to the loads via the bypass.
NOTE: When UPS is in Bypass mode, the output voltage will directly power from utility after you switch on th e input breaker. In Bypass mode, the load is not protected by UPS. To protec t your precious devices, you should turn on the UPS. Refer to next step.
2) Press and hold the “ON” button for 0.5s to turn on t h e UPS and the buzzer will beep once.
3) A few seconds later, the UPS will enter to AC mode. If the utility power is abnormal, the UPS will operate in Battery mode without interruption.
NOTE: When the UPS is running out battery, it will shut down automatically at Battery mode. When the utility power is restored, the UPS will auto restart in AC mode.
2. Turn on the UPS without utility power supply (i n Battery mode)
1) Make sure that the two groups battery are connected correctly as ”+,GND,-” order and the breaker of the battery pack is at “ON” position (only for long-run model).
2) Press the “ON” button to set up the power supp ly for th e UP S, UPS will enter to power on mode. After initialization UPS will enter t o N o Output mode, then Press and hold the “ ON” but ton fo r 0.5s to turn on the UPS , and the buzzer will beep once.
3) A few seconds later, the UPS will be turned on and enter to Battery mode.
Page 16
13
3. Connect devices to UPS
After the UPS is turned on, you can connect devices to the UPS.
1) Turn on the UPS f ir st and the n switch on the devices one by one, the LCD panel will display total load level.
2) If it is necessary to connect the inductive loads such as a printer, the in-rush current of the load should be calculated carefully to see if it meets the overload capability of the UPS.
We str on gly
recommend that 200% overload is less than 0.2s, 150% overload is less than 0.5s.
3) If the UPS is overload, the buzzer will beep twice every second.
4) When the UPS is overload, please remove some loads immediately. It is recommended to have the total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload for system safety.
5) If the overload time is over acceptable time listed in spec at AC mode, the UPS will automatically transfer to Bypas s mod e. After the overload is removed, it will return to AC mode. If the overload time is over acceptable time listed in spec at Battery mode, the UPS will become fault status. At this time, if bypass is enabled, the UPS will power to the load via bypass. If bypass functio n is disabled or the input power is not within bypass acceptable range, it will cut off output directly.
4. Charge the batteries
1) After the UPS is connected to the utility power and be turned on to AC mode, the charger will charge the batteries automatically except in Battery mode, dur ing battery self-test ,overload or battery voltage is high.
2) Suggest to charge batteries at least 10 hours before use. Otherwise, the backup time may be shorter than expected time.
3) Make sure the battery numbers setting on the control board (Please refer to the section 3-4-12 for detailed setting) is consistent to real connection.
5. Battery mode operation
1) When the UPS is in Bat tery mode, the buzzer w ill beep according to different bat tery capacity. If the battery capacity is more than 25%, the buzzer will beep once every 4 seconds; If the battery voltage drops to the alarm level, the buz zer will beep quickly (once every sec) to remind users that the battery is at low level and the UPS will shut down automatically soon. Users could switch off some non-critical loads to disable the shutdown alarm and prolong the backup time. If there is no more load to be switched off at that time, you have to shut down all loads as soon as possible to protect the devices or save data. Otherwise, there is a risk of data loss or load failure.
2) In Battery mode, if buzzer sound annoys, users can press the Mute button to disable the buzzer.
3) The backup time of the long-run model depends on the external battery capacity.
4) The backup time may vary from different environment temperature and load type.
5) When setting backup time for 16.5 hours (default value from LCD panel), after discharging 16.5 hours, UPS will shut down automatically to protect the battery. This battery discharge protection can be enabled or disabled through LCD panel control. (Refer to 3-7 LCD sett ing section)
6. Test the batteries
1) If you nee d to check t he battery status when th e UPS is running in AC mode/CVCF mode, you could press the “Test” button to let the UPS do battery self-test.
2) Users also can set battery self-test through monitoring software.
7. Turn off the UPS with utility power supply in AC mode
1) Turn off the inverter o f the U PS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once. The UPS will turn into Bypass mode.
NOTE 1: If the UPS has been set to enable the bypass output, it will bypass voltage from utility power to output terminal even though you have turned off the UPS (in verter).
NOTE 2: After turning off the UPS, please be aware that the UPS is working at Bypass mode and
Page 17
14
there is risk of power loss for connected devices.
2) In Bypass mode, output voltage of the UPS is still present. In or der t o c ut of f the output, switch off the line input breaker(for dual input unit, also switch off the bypass line breaker). A few seconds later, there is no display shown on the display panel and UPS is complete off .
8. Turn off the UPS without utility power supply in Battery m o d e
1) Turn off th e UPS by pressing “OFF” button for at least 0.5s, and th e n t h e buzzer will beep once.
2) Then UPS will cut off power to output and there is no display shown on the display panel.
9. Mute the buzzer
1) To mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after the buzzer is muted, the buzzer will beep again.
2) Some warning alarms c an’ t be m uted un less the error is f ixed. Please refer to section 3-3 fo r t he details.
10. Operation in warning status
1) When Fault LED flashes and the buzzer beeps once every second, it means that there are some problems for UPS operation. Users can get the warning indicator from LCD panel. Please check t he trouble shooting table in chapter 4 for details.
2) Some warning alarms can’ t be m uted un less the error is f ixed. Please refer to section 3-3 fo r t he details.
11. Operation in Fault mode
1) When Fault LED illumi nates and the buzzer beeps continu ously, it means that there is a fatal er ror in the UPS. Users can get the fault code f rom displa y panel. Please check t he t r ouble sh ooting table in chapter 4 for details.
2) Please check the loads, wiring, ventilation , utility, battery and so on after the fault occurs. Don’t try to turn on the UPS again before sol ving the problems . If the problems can’t be fixed, please contact the distributor or service people immediately.
3) For emergency case, please cut off the connection from utility, external battery, and output immediately to avoid more risk or danger.
12. Operation of changing battery numbers
1) This operation is only available for professional or qualified technicians.
2) Turn off the UPS. If the l oad couldn’t be cut off, you should remove the cover of maintenance bypass switch on the rear panel and turn the maintenance switch to “BPS” position first.
3) Switch off the line input breaker (for dual input unit, also switch of f the by pass input breaker), and switch off the battery breaker (only available for long-run model).
4) Remove the cabinet cover, and disconnect battery wire for standard model. Then modify the jumper of JS4 & JS5 on the control board to set the battery numbers as following table.
Battery Number in series
JS5 JS4
16
0 0
18
0 1
19
1 0
20
1 1
Note:1 = connect with jumper; 0 = no jumper; x = the pins are for other functions.
5) Modify the battery pack for the setting number carefully. After complete it, put the cover back, switch on the battery breaker for long-run model.
6) Switch on the line input breaker (for dual input unit, also s witch on t he bypass input breaker) and
Page 18
15
the UPS will enter Bypass mode. If the UPS is in maintenance Bypass mode, turn the maintenance switch to “UPS” position and then turn on the UPS.
3-5. Parallel Operation
1. Parallel system initial startup
First of all, please make sure all of the UPSs are parallel models and have the same configuration.
1) Turn on e ach UPS to AC mod e re spectively (Refer to section 3-4(1)). Then, measure the inverter output voltage of each phase for each UPS to check if the inverter voltage difference between actual output and setting value is less than 1.5V (typical 1V) with multimeter. If the difference is more than 1.5V, please calibrate the voltage by conf iguring inverter voltage adjustment (Refer to Program 15, 16 and 17, section 3-7) in LCD setting. If voltage difference remains more than 1.5V after calibration, please contact your local distributor or service center fo r help .
2) Calibrate the output voltage measurement by configuring output voltage calibration (Refer to Program 18, 19, and 20, section 3-7) in LCD setting to make sure the difference between real output voltage and detected value of UPS is less than 1V.
3) Turn off each UPS (Refer to section 3-4(7.)). Then, follow the wiring procedure in section 2-4.
4) Remove the cover of parallel share current cable port on the UPS, connect each UPS one by one with the parallel cable and share current cable, and then screw t he cover back.
5) Turn on the parallel system in AC mode: a) Turn on the line input br eaker of each UP S( for dual input, also turn on bypass input breaker).
After all UPSs enter to bypass mode, measure the output voltage b e tween two UPS for the same phase to make sure the phase sequence is corre ct . If these two voltage differences are near to zero, that means all connections are correct. Otherwise, please check if the wirings ar e
connected correctly. b) Turn on the output breaker of each UPS. c) Turn on eac h UPS in turns. After a while, the UPSs will enter to AC mode synchronously and
then, the parallel system is completed.
6) Turn on the parallel syste m in B at te ry mode: a) Turn on the battery breaker (only available in long-run model) and output break er of each UPS.
b) Turn on any UPS. A few seconds later, the UPS will enter to battery mode.
c) Then, turn on another UPS. A f ew seconds later, the UPS will enter to battery mode and add to the
parallel system.
d) If you have the third U PS, f ollow the sam e pr oce du re of c). Then, the parallel system is complete.
If more detailed information is needed, please contact supplier or service center for parallel operation instruction.
2. Add one new unit into the parallel system
1) You can not add one ne w unit into the pa rallel s ystem w hen whole system is runnin g. You must cut
off the load and shutdown the system.
2) Make sure all of the UPS are the parallel models, and follow the wiring refer to section 2-4.
3) Install the new parallel system refers to the previous section.
3. Remove one unit from the parallel system
There are two methods to remove one unit from the parallel system: First method:
1) Press the “OFF” key twice and each time should be lasted for more than 0.5s. Then, the UPS will
enter into byp a s s mode or no output mode without output.
2) Turn off the output breaker of this unit, and then turn off the input breaker of this unit.
3) After it shuts down, you can turn off the battery breaker (for long-run model ) and remov e the
Page 19
16
parallel and share current cables. And then remove the unit from the parallel system.
Second method:
1) If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the
load and shut down the system first.
2) Make sure the bypass setting is enabled in each UPS and then turn off the running s ystem. All UPSs
will transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintenance switches from “UPS” to “ BPS”. Turn of f all the input breakers and battery break ers in paralle l system.
3) T urn off the output breake r and remo ve the parallel cable and sha re current cable of the U PS which
you want to remove. Then, remove it from parallel sy stem.
4) Turn on the input breaker of the remaining UPS and the system will transfer to Bypass mode. Set
the maintenance switches from “BPS” to “UPS and put the maintenance bypass covers back.
5) Turn on the remaining UPS according to the previous section.
Warning: (Only for the parallel system)
● Before turning on the parallel syst em to activate inverter, make sure that all unit’s maintenance switch at the same position.
● When parallel system is turned on to work through inverter, please do not operate the maintenance switch of any unit.
Do not support ECO mode, please do not set any unit ECO enable.
3-6. Abbreviation Meaning in LCD Display
Abbreviation Display content Meaning
ENA
Enable
DIS
Disable
ATO
Auto
BAT
Battery
NCF
Normal mode (not CVCF mode)
CF
CVCF mode
SUB
Subtract
ADD
Add
ON
On
OFF
Off
FBD
Not allowed
OPN
Allow
RES
Reserved
N.L
Neutral line loss
CHE
Check
OP.V
Output voltage
PAR
Parallel, 001 means the first UPS
AN
The first phase
BN
The second phase
Page 20
17
CN
The third phase
AB
The first line
BC
The second line
CA
The third line
HS.H
Hot Standby
3-7. LCD Setting
There are three parameters to set up the UPS. Refer to following diag r am.
Parameter 1: It’s for program alternatives. Refer to below tables for the programs to set up.
Parameter 2 and parameter 3 are the setting options or values for each program.
Note: Please select “Up” or “Down” button to change the programs or parameters.
Programs available list for parameter 1:
Code Description
Bypass /
No Output mode
AC
mode
ECO
mode
CVCF
mode
Battery
mode
Battery
Test
01
Output voltage
Y*
02 Output frequency Y
03
Voltage range f or bypass
Y
04 Frequency range for bypass Y
05
ECO mode enable/disable
Y
06 Voltage range for ECO mode Y
07
Frequency range for ECO mode
Y
08 Bypass mode setting Y Y
09
Maximum battery discharge time
setting
Y Y Y Y Y Y
10 Reserved Reserved for future options
11
Hot Standby Function Setting
Y
12 Neutral loss detection Y Y Y Y Y Y
13
Battery voltage calibration
Y
Y Y Y Y Y
14 Charger voltage adjustment Y Y Y Y Y Y
15
Inverter A voltage adjustment
Y Y Y
16 Inverter B voltage adjustment Y Y Y
17
Inverter C voltage adjustment
Y Y Y
Parameter 1
Parameter 2 Parameter 3
Page 21
18
18
Output A voltage calibration
Y Y Y
19
Output B voltage calibration
Y Y Y
20
Output C voltage calibration
Y Y Y
*Y means that this program can be set in this mode. Note: All parameter settings will be saved only when UPS s huts down normally with internal or external battery connection. (Normal UPS shutdown mea ns turning off input breaker in bypass/no output mode).
01: Output voltage
Interface
Setting
Parameter 3 : O utput voltage
You may choose the following output voltage in parameter 3:
208: Presents output voltage is 208Vac 220: Presents output voltage is 220Vac 230: Presents output voltage is 230Vac 240: Presents output voltage is 240Vac
02: Output frequency
Interface
Setting
60 Hz, CVCF mode
50 Hz, Normal mode
ATO
Parameter 2: Output Frequency
Setting the output frequency. You may choose following three options in parameter 2:
50.0Hz: The output frequency is setting for 50.0Hz.
60.0Hz: The output frequency is setting for 60.0Hz. ATO: If selected, output frequency will be decided according to
the latest normal utility frequency. If it is from 46Hz to 54Hz, the output frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the output frequency will be 60.0Hz. ATO is default setting.
Parameter 3: Frequency mode
Setting output frequency at CVCF mode or not CVCF mode. You may choose following two options in parameter 3: CF: Setting UPS to CVCF mode. If selected, the output frequency will be fixed at 50Hz or 60Hz according to setting in parameter 2. The input frequency could be from 46Hz to 64Hz. NCF: Setting UPS to normal mode (not CVCF mode). If selected, the output frequency will synchronize with the input frequency within 46~54 Hz at 50Hz or within 56~64 Hz at 60Hz according t o setting in parameter 2. If 50 Hz selected in parameter 2, UPS will transfer to battery mode when input frequency is not within 46~54 Hz. If 60Hz selected in parameter 2, UPS will transfer to battery mode when input frequency is not within 56~64 Hz. *If Parameter 2 is ATO, the Parameter 3 will show the current
frequency.
03: Voltage range for bypass
Interface
Setting
Parameter 2: Set the acceptable low voltage for bypass. Setting
range is from 176V to 209V and the default value is 176V. Parameter 3: Set the ac ceptable high voltage for bypass. Setting range is from 231V to 276V and the default value is 264V.
Page 22
19
04: Frequency range for bypass
Interface
Setting
Parameter 2: Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz. 60 Hz system: Setting range is from 56.0Hz t o 5 9.0Hz. The default value is 46.0Hz/56.0Hz. Parameter 3: Set the acceptable high frequency for bypass. 50 Hz: Setting range is from 51.0Hz to 54.0 Hz. 60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
05: ECO mode enable/disable
Interface
Setting
Parameter 3: Enable or disable ECO function. You may choose
following two options:
DIS: disable ECO function ENA: enable ECO function
If ECO function is disabled , voltage range and f requency ra nge for ECO mode still can be set, but it is meaningless unless the ECO
function is enabled.
06: Voltage range for ECO mode
Interface
Setting
Parameter 2: Low voltage point in ECO mo de. The s etting range
is from -5% to -10% of the nominal voltage. Parameter 3: High voltage point in ECO m ode. The sett ing range is from +5% to +10% of the nominal voltage.
07: Frequency range for ECO mode
Interface
Setting
Parameter 2: Set low voltage point for ECO mode.
50 Hz system: Setting range is from 46.0Hz to 48.0Hz. 60 Hz system: Setting range is from 56.0Hz t o 5 8.0Hz. The default value is 48.0Hz/58.0Hz. Parameter 3: Set high voltage point for ECO mode. 50 Hz: Setting range is from 52.0Hz to 5 4.0 Hz. 60 Hz: Setting range is from 62.0Hz to 6 4.0Hz.
The default value is 52.0Hz/62.0Hz.
08: Bypass mode setting
Interface
Setting
Parameter 2:
OPN: Bypass allowed. When selected, UPS will run at Bypass
mode depending on bypass enabled/disabled setting. FBD: Bypass not allowed. When selected, it’s not allowed for running in Bypass mode under any situations.
Parameter 3: ENA: Bypass enabled. When selected, Bypass mode is activated. DIS: Bypa ss disabled. When selected, automatic bypass is
acceptable, but manual bypass is not allowed. Manual bypass means users manually operate UPS for Bypass mode. For example , p ressing OFF but ton in AC mod e to turn into Bypass
mode.
Page 23
20
09: Maximum battery discharge time setting
Interface
Setting
Parameter 3:
000~999: Set the maximum discharge time from 0 min to 999
min. UPS will shut down to protect battery if the discharge time arrives before the battery is under voltage. The default value is 990 min. DIS: Disable battery discha rge protection and backup time wi ll
depend on battery capacity.
10: Reserved
Interface
Setting
Reserve for future options.
11: Hot Standby Function Setting
Interface
Setting
Parameter 2:
HS.H: Indicates Hot standby function. Parameter 3: Enable or disable hot standby function. YES: Hot standby function is enabled. It means that the current
UPS is set to host of the hot standby function, and it will restart After AC recovery even without battery connected. NO: Hot standby function is disabled. The UPS is running at
Normal mode and can’t restart without battery.
12: Neutral loss detection
Interface
Setting
Parameter 2:
N.L: Indicates neutral loss detection function. Parameter 3: DIS: Disable the neutral loss detection function. The UPS will not
detect the neutral loss or not. ATO: The UPS will automa tically detect the neutr al is lost o r not. If neutral loss is detected, an alarm will be generated. If the UPS is turned on, it will transfer to battery mode. When neutral is restored and detected, the alarm will be muted automatically and the UPS will go back to normal mode automatically. CHE: The UPS will autom atically detect the neut ral l oss. If neut ral loss is detected, an alarm will be generated. If the UPS is turned on, it will transfer to battery mode. When neutral is restored, the alarm will NOT be muted automatically and the UPS will NOT go back to normal mode automatically. Here, you must mute the alarm and make the UPS go back to normal mode manually. The operation is: Firstly, enter this menu and press the “Enter” key to make the “CHE” flash. Secondly , press the “Enter” key again to activate the neutral detection (check). If neutral is detected, the alarm will be muted and the UPS will go back to normal mode. If neutral is not detected, the UPS will continue alarming and stay on t he latest status until the neutral is detected well at next manual checking operation.
CHE is default setting.
Page 24
21
13: Battery voltage calibration
Interface
Setting
Parameter 2: Select “Add” or “Sub” function to adjust battery
voltage to real figure. Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V.
14: Charger voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust charger
voltage Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all batteries first to get the accurate charger vol tage.
* Any modification should be suitable to battery specifications.
15: Inverter A voltage adjustment
Interface Setting
Parameter 2: you may choose Add or Sub to adjust inverter A
voltage. Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V. * Add or Sub is according to the output voltage what you set.
16: Inverter B voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter B
voltage*. Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V.
*It will display number 1 under
or to represent
inverter B voltage.
17: Inverter C voltage adjustment
Interface Setting
Parameter 2: you may choose Add or Sub to adjust inverter C
voltage*. Parameter 3: the voltage range is from 0V to 9.9V, the default value is 0V.
*It will display number 2 under
or to represent
inverter C voltage.
Page 25
22
18: Output A voltage calibration
Interface
Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurem
ent value of the
output A voltage, and you can calibrate it by pressing Up or Down
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing Enter
. The
calibration range is limited within +/-9V. This function is normally
used for parallel operation.
19: Output B voltage calibration
Interface
Setting
Parameter 2: it always shows OP.V as output voltage*.
Parameter 3:
it shows the internal measurement value of the
output B voltage, and you can calibrate it by pressing Up or Down
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing Enter
. The
calibration range is limited within +/-9V. This function is normally used for parallel operation.
*It will display number 1 under to represent the output B
voltage.
20: Output C voltage calibration
Interface
Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3:
it shows the internal measurement value of the
output C voltage, and you can calibrate it by pressing Up or Down
according to the measurement from an external voltage
meter. The calibration result will be effective by pressing Enter. The calibration range is limited within +/-
9V. This function is
normally used for parallel operation. *It will display number 2 under to represent the output C
voltage.
3-8. Operating Mode/Status Description
Following table shows LCD display for operating modes and status. (1) If the UPS is in n ormal operation, it will show seven screens one by one, which represents 3 phase input voltages (An, bn, Cn), 3 line input voltages (Ab, bC, CA) and frequency in turns. (2) If parallel UPS systems are successfully set up, it will show one more screen with “PAR” in parameter 2 and assigned number in parameter 3 as below parallel screen diagram. The master UPS will be default assigned as “001” and slave UPSs will be a ssigned as either “002” or “003”. The assigned num bers may be changed dynamically in the operation;
Parallel screen
Page 26
23
Operating mode/status
UPS Power On Description When UPS is powered on, it will enter into this mode for a few seconds as
initializing the CPU and system.
LCD display
No-output mode
description When bypass voltage/frequency
is out of acceptable range or bypass is
disabled (or forbidden), UPS will enter into no-output mode if powering on or turning off the UPS. It means the UPS has no output. Alarm beeps every
two minutes.
LCD display
AC mode Description When the input voltage is within acceptable range, UPS will provide pure
and stable AC power to output. The UPS will also charge the battery at AC
mode.
LCD display
Page 27
24
ECO mode Description When the input voltage is within voltage regulation range and ECO mode is
enabled, UPS will bypass voltage to output for energy saving.
LCD display
Page 28
25
CVCF mode Description When the output frequency is set to “CF”, the inverter will output constant
frequency (50 Hz or 60 Hz). At this mode, the UPS will hav
e no bypass
output but still charge battery.
LCD display
Battery mode Description When the input v oltage/frequency is beyond the acceptable range or power
failure, UPS will backup power from battery and alarm will beep every 4 seconds.
LCD display
Page 29
26
Bypass mode Description When input voltage is within acceptable range and bypass is enabled, turn
off the UPS a nd it will enter Bypass mode. Alarm beeps every two minutes.
LCD display
Battery Test Description When UPS is in AC mode or CVCF mode, press “Test” key for more than 0.5s.
Then, the UPS will beep once and start “Battery Test”. The line between I/P and inverter icons will blin k to re mind use rs. This operation is used to c heck
the battery status.
LCD display
Page 30
27
Warning status
Description If some errors occur in the UPS (but it is still running normally), it will show
one more screen to represent the warning situation. In the warning screen, the icon
will be flashing, and it can show up to 3 er ror c od es a nd each
code indicates one error. You can find the code
meaning in the warning
code table.
LCD display
Fault status Description When UPS has fault happened, the inverter will be blocked. It will display
fault code in screen, and the icon
will light up. You can find the code
meaning in the fault code table.
LCD display
Page 31
28
3-9. Fault Code
Fault code
Fault event
Icon
Fault code
Fault event
Icon
01
Bus start failure
None
36
Parallel output current unbalance
None
02
Bus over
None
41
Over temperature
None
03
Bus under
None
42
DSP communication failure
None
04
Bus unbalance
None
43
Overload 06
Converter over current
None
46
Incorrect UPS setting
None
11
Inverter soft start failure
None
47
MCU communication failure
None
12
High inverter voltage
None
48
Two DSP firmware versions are incompatible.
None
13
Low inverter voltage
None
49
Input and output phases are incompatible
None
14
Inverter A output(line to neutral) short circuited
51
Battery wiring fault
None
15
Inverter B output(line to neutral) short circuited
60
Inverter Over curre nt
circuited
None
16
Inverter C output(line to neutral) short circuited
61
Bypass STS Short circuited
None
17
Inverter A-B output (line to line) short circuited
62
Bypass STS open circuited
None
18
Inverter B-C output (line to line) short circuited
63
Inverter A voltage wave abnormal
None
19
Inverter C-A output (line to line) short circuited
64
Inverter B voltage wave abnormal
None
1A
Inverter A negative power fault
None
65
Inverter C voltage wave abnormal
None
1B
Inverter B negative power fault
None
66
Inverter current sample abnormal
None
1C
Inverter C negative power fault
None
67
Bypass line to neutral short circuited
None
21
Battery SCR short circuited
None
68
Bypass line to line short circuited
None
24
Inverter relay sh ort circuited
None
69
Inverter SCR short circuited
None
25
Line wiring fault
None
6A
Bus Voltage Vary
circuited
None
31
Parallel communication failure
None
6B
PFC_INV Over Current
circuited
None
3-10.Warning Indicator
Warning Icon (flashing) Alarm
Battery low
Beeping every second
Overload
Beeping twice every second
Battery unconnected
Beeping every second
Page 32
29
Over charge
Beeping every second
EPO enable
Beeping every second
Fan failu re/Over temperature
Beeping every second
Charger failure
Beeping every second
I/P fuse broken
Beeping every second
Other warnings(refer to 3-11)
Beeping every second
3-11.Warning Code
Warning code
Warning event
Warning code
Warning event
01 Battery unconnected 21
Line situations are dif ferent in parallel system
02 IP Neutral loss 22
Bypass situations are different in parallel system
04 IP phase abnormal 33
Locked in bypass aft e r overload 3 times in 30 minutes
05
Bypass phase abnormal
34
Converter current unbalance
07
Over charge
3A
Cover of maintain switch is open
08
Low battery
3C
Utility extremely unbalanced
09 Overload
3D Bypass unstable
0A
Fan failure
3E
Battery Voltage too High
0B
EPO enable
3F
Battery Voltage unbalanced
0D Over temperature
40
Charger Short
0E
Charger failure
Page 33
30
4. Trouble Shooting
If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom
Possible cause
Remedy
No indication and alarm in the front
display panel e ven th ough the mains is
normal.
The AC input power is not
connected well.
Check if input cable firmly connected to the mains.
The icon
and the warning code
flash on LCD display and alarm
beeps every second.
EPO function is activated. At
this time, the EPO switch is in “OFF”
status or the jumper is
open.
Set the circuit in closed position to disable the EPO function.
The icon and
flash on
LCD display and alarm beeps every
second.
The
external or internal
battery is incorrectly
connected.
Check if all batteries are
connected well.
The icon and
flash on
LCD display and alarm beeps twice
every second.
UPS is overload.
Remove excess loads from UPS output.
UPS is overloaded. Devices connected to the UPS are fed directly by the electrical network via the Bypass.
Remove excess loads from UPS output.
After repetitive overloads, the UPS is locked in the Bypass
mode. Connected devices are
fed directly by the mains.
Remove excess loads from UPS
output first. Then shut down
the UPS and restart it.
Fault code is shown as 43. The icon
lights on LCD display and
alarm beeps continuously.
UPS is overload too long and
becomes fault. Then UPS shut down automatically.
Remove excess loads from UPS output and restart it.
Fault code is shown as 14,15,16,17,18 or 19, the ic o n
lights on LCD
display, and alarm beeps continuously.
The UPS shut down
automatically be
cause short circuit occurs on the UPS output.
Check output wiring and if
connected devices are in short circuit status.
Other fault codes are
shown on LCD
display and alarm beeps continuously.
A UPS internal fault has
occurred.
Contact your dealer
Batte
ry backup time is shorter than
nominal value
Batteries are not fully charged
Charge the batteries for at
least 7
hours and then check capacity. If the problem still persists, consult your dealer.
Batteries defect
Contact your dealer to replace the battery.
The icon and
flash on LCD
display an d ala rm bee ps every second.
Fan is locked or not working;
or the UPS temperature is too
high.
Check fans and notify dealer.
Page 34
31
Symptom
Possible cause
Remedy
The warning code 02 is shown, the
icon flashes on LCD display, and alarm beeps every second.
The input neutral wire is
disconnected.
Check and correct the input neutral connection. If the
connection is ok and the alarm
is still displaying, please refer
to the LCD setting section, to
enter the neutral loss check
menu, to see if the parameter3 is “CHE”, if it is, please press the “Enter” key firstly to make the “CHE” flash and press the
“Enter” key secondly to make
the UPS clear the alarm. If the
warning still exists, please
check input fuses of L2 and L3 .
The L2 or L3 input fuse is broken.
Replace the fuse.
Page 35
32
5. Storage and Maintenance
5-1. Storage
Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
5-2. Maintenance
The UPS system operates with hazardous voltages . R epairs may be carried out only by qualified
maintenance personnel.
Even after the unit is disconnected from the mains, components inside the UPS system are still
connected to the battery packs which are potentially dangerous.
Before carrying out an y kind of ser vice and/or maint enance, disconnect the batteries and v erify that no current is present and no hazardous voltage e xis t s in the terminals of high capa bility capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Verify that no voltage between the battery te rminals and the ground is present be fore maintena nce or repair. In this product, t he battery circuit is not isolated from the input voltag e. Hazardous voltages may occur between the battery terminals and the ground.
Batteries may cause electric shock and have a high short-circuit current. Please remove all wristwatches, rings and other metal personal objects before maintenance or repair, and only use tools with insulated grips and handles for maintaining or repairing.
When replace the batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The batteries must be rightly deposed according to local regulation.
Do not open or destroy bat teries. Escaping electrolyte can cause injury to the ski n and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
Do not disassemble the UPS system.
Page 36
33
6. Specifications
MODEL
30K
30KL
40K
40KL
CAPACITY*
30KVA / 27KW
40KVA / 36KW
INPUT
Voltage Range
Low Line Loss
110 VAC(Ph-N) ± 3 % at 50% Load
176 VAC(Ph-N) ± 3 % at 100% Load
Low Line Comeback
Low Line Loss Voltage + 10V
High Line Loss
300 VAC(L-N) ± 3 % at 50% Load
276 VAC(L-N) ± 3 % at 100% Load
High Line Comeback
High Line Loss Voltage - 10V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system 56Hz ~ 64 Hz @ 60Hz system
Phase
3 Phase with Neutral
Power Factor
0.99 at 100% Load
OUTPUT
Phase
3 Phase with Neutral
Output voltage
208*/220/230/240VAC(Ph-N)
AC Voltage Regulation
± 1%
Frequency Range (Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system 56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mode
100%~110%: 10min
110%~130%: 1min
>130% : 1sec
Battery mode
100%~110%: 30sec
110%~130%: 10sec
>130% : 1sec
Current Crest Ratio
3:1 max
Harmonic Distortion
2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load
Transfer Time
Line Battery
0 ms
Inverter Bypass
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
Inverter ECO
<10 ms
EFFICIENCY
AC mode
94%
94%
Battery Mode
92%
92%
BATTERY
Standard Model
Type
12 V / 7 Ah
12 V / 9 Ah
Numbers
(16+16)pcs * 2strings
(16+16)pcs * 2strings
Recharge Time
9 hours recover to 90% capacity
Charging Current
2.0 A ± 10% (max.)
2.0 A ± 10% (max.)
Charging Voltage
218 VDC ± 1%
Long-run Model
Type
Depending on applications
Numbers
16 - 20
Charging Current
4.0 A ± 10% (max.)
4.0 A ± 10% (max.)
Charging Voltage
13.65 VDC * N ± 1% (N = 16~20)
PHYSICAL
Outline
Dimension, D X W X H mm
815×300 ×1000 592×250×576 815×300 ×1000 592×250×576
Net Weight (kgs)
225
43
250
45
Packaging
Dimension, D X W X H mm
920 × 430×1205 690×370×670 920 × 430×1205 690× 370× 670
Net Weight (kgs)
241
46
266
48
ENVIRONMENT
Operation Temperature
0 ~ 40°C (the battery life will down when > 25°C)
Operation Humidity
<95 % and non-condensing
Operation Altitude**
<1000m**
Acoustic Noise Level
Less than 60dB @
1 Meter
Less than 60dB @
1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Derate capacity to to 90% when the output voltage is adjusted to 208VAC. **If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated 1% per 100m. ***Product specifications are subject to change without further notice.
Loading...