176-300 VAC or 80-285 VAC in bypass mode
Frequency (Synchronized Range)
45Hz - 55Hz or 54Hz - 66Hz
≤2% Full Linear Load; ≤5% Non-Linear Load
Voltage Regulation (Bat. Mod.)
Transfer Time [AC to Battery]
Transfer Time [Inverter to Bypass]
External Battery Connec tion
Available in VFI TGS version
COMMUNICATION AND CONNECTIONS
The PowerWalker VFI 1000-3000 TG and its
The models are either
available with internal batteries (TG) or
alternatively with stronger charger for
security level systems, where additional
PowerWalker VFI 1000-3000 TG(S) Series
• Online technology with Power Factor 0.9
• HID support (Human Interface Device)
• Wide Input Range 100-300VAC for all environments
• Available with integrated batteries or with
stronger charger for external batteries
long-run version VFI 1000-3000 TGS offer
a professional solution for home and office
environment.
external batteries (TGS).
All VFI TG(S) series are detected as HID
Power Device by the internal O/S drivers and
can be manag
software.
It finds its appl
systems for kiosks, ATMs as well as in high
software is not allowed (i.e. banking).
2016 PREMIERE
ACCESSORIES
SERIES
constant @100%-105%
1min @105%-130%; 10s @130%-150%
300ms @>150%; bypass at higher
Low speed: bypass/ECO or line mode with load below 70%
High speed: Battery mode or line mode with load above 70%
VFI 1000-3000 TG & TGS
Battery Mode:
10s @100%-150%
cut-off at higher
10120599 - Mini NMC Card
10120545 - EMD for NMC Card
10120592 - Mini Modbus Card 3
10120597 - Mini AS400 Card 4

BlueWalker GmbH | Hellersbergstrasse 6, 41460 Neuss, Germany | Tel.: +49 2131 206 17 59
Not included, compatible with 5-120Ah
VFI TG Series
VFI TGS Series
VFI 1000 TG VFI 2000 TG VFI 3000 TG
MODEL VFI 1000 TG VFI 2000 TG VFI 3000 TG VFI 1000 TGS VFI 2000 TGS VFI 3000 TGS
VFI 1000 TGS VFI 2000 TGS VFI 3000 TGS
Battery related
BATTERY PACKS AND BACKUP TABLE
MODEL
VFI 1000 TG 3.7 10.5 56.8 28.6 17.4 11.6 8.9 5.2
VFI 2000 TG 3.8 11.0 90.6 60.7 38.9 29.0 21.4 13.3 9.3 5.3
VFI 3000 TG 3.9 11.7 105.7 88.7 60.7 46.0 44.8 23.8 17.0 9.7 6.6
VFI 1000 TGS
+ 1 x BP S24T-6x9Ah 18.1 49.3 174.9 104.7 72.4 52.1 43.4 23.8
+ 2 x BP S24T-6x9Ah 50.6 100.8 407.4 215.2 132.0 104.7 92.1 59.4
+ 3 x BP S24T-6x9Ah 80.8 144.7 604.0 352.1 215.2 154.1 124.0 94.3
+ 4 x BP S24T-6x9Ah 102.8 201.8 908.1 470.2 296.4 215.2 175.9 115.5
VFI 2000 TGS
+ 1 x BP S48T-12x9Ah 18.4 50.6 280.3 184.0 81.0 105.7 90.9 56.5 44.8 24.3
+ 2 x BP S48T-12x9Ah 51.3 102.8 596.1 426.6 262.2 218.6 169.6 111.3 94.3 59.9
+ 3 x BP S48T-12x9Ah 81.9 128.2 1000.6 660.1 426.6 358.5 273.8 169.6 129.2 95.3
+ 4 x BP S48T-12x9Ah 103.7 208.5 >1200 950.2 564.4 475.0 393.4 237.4 179.8 116.3
VFI 3000 TGS
+ 1 x BP S72T-12x9Ah 10.1 28.8 218.6 164.1 116.5 95.6 73.9 42.7 44.8 25.2 16.4
+ 2 x BP S72T-12x9Ah 28.8 73.1 475.0 378.6 262.2 184.0 179.5 115.5 94.3 62.3 46.9
+ 3 x BP S72T-12x9Ah 52.5 105.5 801.2 566.5 426.6 296.9 292.5 179.8 129.2 97.3 74.3
+ 4 x BP S72T-12x9Ah 68.7 134.1 1056.0 845.2 564.4 426.6 420.4 257.3 179.8 117.8 97.3
100W 200W 300W 400W 500W 750W 1000W 1500W 2000W
3x2x9Ah for 1000VA
3x4x9Ah for 2000VA
2x6x9Ah for 3000VA