Indicates the remaining backup time in pie chart.
Indicates the remaining backup time in numbers.
H: hours, M: minute, S: second
Indicates that the warning and fault occurs.
Indicates the warning and fault codes, and the codes are listed in
details in 3-5 section.
Indicates that the UPS alarm is disabled.
Indicates the output voltage, frequency or battery voltage.
Vac: output voltage, Vdc: battery voltage, Hz: frequency
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the load or the UPS output is short circuit.
Indicates the UPS connects to the mains.
Indicates the battery is working.
Indicates the bypass circuit is working.
I. LCD Panel
PowerWalker VFI 1000-3000 C LCD
Quick Guide

Indicates the ECO mode is enabled.
Indicates the Inverter circuit is working.
Indicates the output is working.
Indicates the Battery level by 0-25%, 26-50%, 51-75%, and 76100%.
Indicates the battery is fault.
Indicates low battery level and low battery voltage.
Indicates the input voltage or frequency or battery voltage.
Vac: Input voltage, Vdc: battery voltage, Hz: input frequency
5.SNMP intelligent slot (option)
7.Output terminal (only 3kVA unit)
4.RS-232 communication port
II. Rear panel view
III. Communication connection
Apart from standard USB Port, the UPS is equipped with RS-232. Those two ports do not work
at the same time.

Sounding every 10
seconds
Sounding twice every
second
Out of bypass voltage
range
Bypass frequency
unstable
Fault Continuously sounding
IV. Modes and warnings
V. Frequency Converter Mode
VI. Button operation
ON/Mute Button
Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.
When the UPS is on battery mode, press and hold this button for at least 5 seconds to
When input frequency is within 40 Hz to 70 Hz, the UPS can
be set at a constant output frequency, 50 Hz or 60 Hz. The
UPS will still charge battery under this mode. Frequency
Converter requires de-rating of the UPS Power to 80%.

Enable or Disable (default)
Converter Mode setting (if
enabled)
Enable or Disable (default)
ECO voltage
range setting
Upper Limit for Input Voltage
Bottom Limit for Input
Voltage
Enable or Disable (default) bypass
mode
Bypass Input
Voltage setting
Upper Limit for Input Voltage
Bottom Limit for Input
Voltage
Autonomy
Limitation
setting
Backup time limit in minutes. 0
actually means 10s and 999
means disabled
disable or enable the alarm system. But it’s not applied to the situations when warnings
or errors occur.
Press this button to display previous selection in UPS setting mode (up key)
Press and hold ON/Mute button for 5 seconds to enter UPS self-testing while in AC
mode, ECO mode, or converter mode.
OFF/Enter Button
Press and hold this button at least 2 seconds to turn off the UPS. UPS will be in standby
mode under power normal or transfer to Bypass mode if the Bypass enable setting by
pressing this button.
Press this button to confirm selection in UPS setting mode.
Select Button
Press this button to change the LCD message for input voltage, input frequency, battery
voltage, output voltage and output frequency. It will return back to default display when
pausing for 10 seconds.
Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in
standby mode or bypass mode.
Press this button to display next selection in UPS setting mode. (down key)
ON/Mute + Select Button
When the main power is normal, press ON/Mute and Select buttons simultaneously for 5
seconds. Then UPS will enter to bypass mode. This action will be ineffective when the
input voltage is out of acceptable range.
VII. UPS Setting

110-160VAC±5%
Depending on the load level (gradually from 100% to 0%)
125-175VAC± 5 %
Depending on the load level (gradually from 100% to 0%)
> 0.99 @ nominal voltage (input voltage)
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range (Batt.
Mode)
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
Ambient Temp.<350C
105%~110%: 10 min; 110%~130%: 1min; >130%:3s
UPS transfers immediately to bypass when the utility is normal
< 3 % THD (linear load); < 6 % THD (non-linear load)
4 hours recover to 90% Power (Typical)
Dimension, D x W x H
(mm)
20-90 % RH @ 0- 35 degC (non-condensing)
Less than 50dBA @ 1 Meter
Power management from SNMP manager and web browser
VIII. Technical Specification