IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the equipment
and save this manual for future reference.
CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS
Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute
procédure d'installation et de maintenance des batteries et de l'onduleur. Veuillez consulter
entièrement ces instructions avant de faire fonctionner l'équipement et conserver ce manuel afin
de pouvoir vous y reporter ultérieurement
The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts)
unless permission granted. Every care has been taken to ensure the accuracy of the information
contained in this manual, but no liability can be accepted for any errors or omission. The right to make
design modifications is reserved.
Figure 3-1. UPS Cabinet Dimensions (VFI 20000TAP 3/3 BE/BI Front and Right Side Views) .
Figure 3-2. UPS Cabinet Dimensions (VFI 30000TAP 3/3 BE/BI Front and Right Side Vies) ..
Figure 3-3. UPS Cabinet Dimensions (VFI 40000TAP 3/3 BE/BI Front and Right Side Views) .
Figure 3-4. UPS Cabinet Dimensions (VFI 60000-80000TAP 3/3 BX Front and Right Side Views). ..
Figure 3-5. UPS Cabinet Dimensions (Top and Bottom Views) .............................................3-9
Figure 3-6. UPS Cabinet Centre of Gravity (VFI 20000TAP 3/3 BE/BI) .
Figure 3-7. UPS Cabinet Centre of Gravity (VFI 30000TAP 3/3 BE/BI) ......
Figure 3-8. UPS Cabinet Centre of Gravity (VFI 40000TAP 3/3 BE/BI) .
Figure 3-9. UPS Cabinet Centre of Gravity (VFI 60000TAP 3/3 BX) ..... .............. ............. ........
Figure 3-10. UPS Cabinet Centre of Gravity (VFI 80000TAP 3/3 BX) .. ... . ..... .............. ..............
The PowerWalker VFI 3/3 Series VFI 20000-80000TAP 3/3 BE/BI uninterruptible power supply (UPS) is a
true online, continuous-duty, transformer-free, double-conversion, solid-state, three-phase system,
providing conditioned and uninterruptible AC power to protect the customer's load from power failures.
The PowerWalker VFI 3/3 Series VFI 20000-80000TAP 3/3 BE/BI online power protection system is used to
prevent loss of valuable electronic information, minimise equipment downtime, and minimise the adverse
effect on production equipment due to unexpected power problems.
The PowerWalker VFI 3/3 Series VFI 20000-80000TAP 3/3 BE/BI UPS continually monitors incoming
electrical power and removes the surges, spikes, sags, and other irregularities that are inherent in
commercial utility power. Working with a building's electrical system, the UPS system supplies clean,
consistent power that sensitive electronic equipment requires for reliable operation. During brownouts,
blackouts, and other power interruptions, batteries provide emergency power to safeguard operation.
The UPS is housed in a single free-standing cabinet, with safety shields behind the door for hazardous voltage
protection.
This manual is
Figure 1-1 shows the PowerWalker VFI 3/3 series UPS.
for PowerWalker VFI 3/3 series UPS, refer to Table 9-1 for product models.
NOTE 1
NOTE 2
Startup may be performed by the customer’s qualified electrical contractor for single (not
parallel) UPS installations without any accessory cabinets.
Startup and operational checks for parallel systems or installations with accessory
cabinets must be performed by an authorised Customer Service Engineer, or the
warranty terms may become void. This service is offered as part of the sales contract
for the UPS. Contact an service representative in advance (usually a two-week notice is
required) to reserve a preferred startup date.
Figure 1-1. PowerWalker VFI 3/3 series UPS (VFI 20000-80000TAP)
1-1
Page 14
1.1 UPS Standard Features
The UPS has many standard features that provide cost-effective and consistently reliable power protection.
The descriptions in this section provide a brief overview of the UPS standard features.
1.1.1 Installation Features
Power wiring can be routed to the bottom or rear of the cabinet with connections made to easily accessible
terminals. Some models (VFI 20000TAP 3/3 BI
access. Details in 4.4 section of user manual.
1.1.2 Control Panel
The control panel, located on the front of the UPS, contains a liquid crystal display (LCD) and pushbutton
switches to control the operation of the UPS and to display the status of the UPS system. See Chapter 6,
“UPS Operating Instructions,” for additional information.
1.1.3 Customer Interface
•Building Alarm Monitoring – Up to three inputs in the UPS are available to connect the facility's alarm
system contacts. Some system configurations may limit the number of inputs available. The UPS uses
these inputs to monitor the building alarms in addition to the UPS status. See Chapter 7,
“Communication,” for additional information.
•Mini-Slot Communication Bays – Two communication bays are standard equipment. One to two optional
Mini-Slot connectivity cards can be installed in the UPS module at any time. Mini-Slot cards are quickly
installed at the front (behind door) of the UPS and are hot-pluggable. See Chapter 7, “Communication,” for
additional information.
/ VFI 30000TAP 3/3 BI / VFI 40000TAP 3/3 BI) provide rear-only cable
1.1.4 High-Efciency Mode
The PowerWalker VFI 3/3 Series UPS offers a High-Efficiency (HE) normal mode with double-conversion
on demand that allows the UPS to operate in standby bypass mode. This mode allows the PowerWalker VFI 3/3 Series UPS to achieve
Operating Instructions,” for additional information. On setting the UPS to work in High Efficiency mode.
98% efficiency while still protecting the load. See Chapter 6, “UPS
1.1.5 Intelligent Charging Management
A three-stage charging system increases battery service life by optimising recharge time, and protects
batteries from damage due to high current charging and inverter ripple currents. Charging at high currents can
overheat and damage batteries.
1.1.6 Maintenance Bypass
The internal Maintenance Bypass for VFI 20000-80000TAP 3/3 BE/BI models consists of input, output and
bypass input (Dual feeds) switches used to control the AC input to the UPS the inverter output, and a
Maintenance Bypass switch used to partially isolate the UPS so that a limited number of components can be
serviced without interrupting power to critical systems.
1-2
Page 15
1.2 Options and Accessories
Contact an sales representative for information about the following options.
1.2.1 External Battery Cabinet
Battery backup protection is provide by equipping the UPS system with up to four External Battery Cabinets
(EBCs) containing sealed lead-acid, maintenance-free batteries. The EBCs are housed in single, free-standing
cabinets designed for line-up-and-match installation, but may be installed separate from the UPS cabinet.
1.2.2 Parallel System
A parallel UPS system with up to four UPSs can be installed to provide a parallel capacity and/or redundant
system. This load sharing system provides more capacity than a single UPS, and can provide backup,
depending on the load and configuration. In addition, when one UPS is taken out of service for maintenance or
is not operating properly, a redundant UPS continues to supply uninterrupted power to the critical load. A
Controller Area Network (CAN) Bridge provides connectivity for system metering and operational mode
control.
1.2.3 Monitoring and Communication
Mini-Slot Cards – Optional Mini-Slot cards support several protocols, such as WEB/SNMP, RELAY / RS232 and
Modbus. See Chapter 7, “Communication,“ for additional information on monitoring and communication
features.
1.2.4 Dual Input
Dual feed models are available for PowerWalker VFI 3/3 Series UPS.
a separated bypass input to UPS.
Connectors on dual feed models provide
1-3
Page 16
1.3 Battery System
Depending on UPS model, the battery system may be internal or external. The battery system provides
emergency short-term backup power to safeguard operation during brownouts, blackouts, and other power
interruptions. The battery system is equipped with lead-acid batteries.
1.4 Basic System Congurations
The following basic UPS system configurations are possible (model dependant):
•Single UPS (internal battery).
•Single UPS with external battery.
•Single UPS with external batteries and accessory cabinets
The UPS system configuration can be enhanced by adding optional accessories such as a
Remote Emergency Power-off (REPO) control or Mini-Slot communication cards.
1.5 Using This Manual
This manual describes how to install and operate the PowerWalker VFI 3/3 Series VFI 20000-80000TAP
3/3 BE/BI/BX. Read and understand the procedures described in this manual to ensure trouble-free
installation and operation. In particular, be thoroughly familiar with the REPO procedure (see paragraph
6.3.13).
The information in this manual is divided into sections and chapters. The system, options, and accessories
being installed dictate which parts of this manual should be read. At a minimum, Chapters 1 through 4
and Chapter 6 should be examined.
Read through each procedure before beginning the procedure. Perform only those procedures that apply to
the UPS system being installed or operated.
1.6 Conventions Used in This Manual
This manual uses these type conventions:
•Bold type highlights important concepts in discussions, key terms in procedures, and menu options, or
represents a command or option that you type or enter at a prompt.
•Italic type highlights notes and new terms where they are defined.
•Screen type represents information that appears on the screen or LCD.
IconDescription
NoteInformation notes call attention to important features or instructions.
[Keys]Brackets are used when referring to a specific key, such as [Enter] or [Ctrl].
In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system
refers to the entire power protection system – the UPS cabinet, an external battery system, and options or
accessories installed.
1-4
Page 17
1.7 Symbols, Controls, and Indicators
The following are examples of symbols used on the UPS or accessories to alert you to important information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric
shock symbol.
CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for
additional information, such as important operating and maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries in
the trash. This product contains sealed, lead-acid batteries and must be disposed of
properly. For more information, contact your local recycling/reuse or hazardous waste
centre.
This symbol indicates that you should not discard waste electrical or electronic
equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse
or hazardous waste centre.
1.8 For More Information
Refer to the External Battery Cabinet Installation Manual for the following additional information:
• Installation instructions, including site preparation, planning for installation, wiring and safety information,
1.9 Getting Help
If help is needed with any of the following:
• Scheduling initial startup
• Regional locations and telephone numbers
• A question about any of the information in this manual
• A question this manual does not answer
Please call your local service representative.
and detailed illustrations of cabinets with dimensional and connection point drawings
1-5
Page 18
1-6
This page intentionally left blank.
Page 19
Chapter 2 Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and
maintenance of the UPS and batteries. Read all instructions before operating the equipment and
save this manual for future reference.
The UPS is designed for industrial or computer room applications, and contains safety shields
behind the door and front panels. However, the UPS is a sophisticated power system and should be
handled with appropriate care.
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORISED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the
UPS.
• The UPS is suitable for mounting on concrete or other non-combustible surfaces only.
• The UPS is powered by its own energy source (batteries). The output terminals may carry live
voltage even when the UPS is disconnected from an AC source.
DANGER
WARNING
• To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature must not
exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum). The
system is not intended for outdoor use.
• As a result of the connected loads high leakage current is possible. Connection to earth ground is
required for safety and proper product operation. Do not check UPS operation by any action that
includes removal of the earth (ground) connection with loads attached.
• Ensure all power is disconnected before performing installation or service.
• Batteries can present a risk of electrical shock or burn from high short-circuits current. The
following precautions should be observed: 1) Remove watches, rings, or other metal objects;
2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries; 4) Wear
rubber gloves and boots.
• ELECTRIC ENERGY HAZARD. Do not attempt to alter any UPS or battery wiring or connectors.
Attempting to alter wiring can cause injury.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be
toxic.
• The UPS unit is not suitable for IT or corner-earthed power distribution systems.
CAUTION
• Installation or servicing should be performed by qualified service personnel knowledgeable of
UPS and battery systems, and required precautions. Keep unauthorised personnel away from
equipment. Consider all warnings, cautions, and notes before installing or servicing equipment.
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
2-1
Page 20
• See installation instructions before connecting to the supply.
• Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according
to the instructions.
• Replace batteries with the same number and type of batteries as originally installed with the
UPS.
• Disconnect the charging source prior to connecting or disconnecting terminals.
• Determine if the battery is inadvertently grounded. If it is, remove the source of the ground.
Contacting any part of a grounded battery can cause a risk of electric shock. An electric shock is
less likely if you disconnect the grounding connection before you work on the batteries.
• Proper disposal of batteries is required. Refer to local codes for disposal requirements.
• Do not dispose of batteries in a fire. Batteries may explode when exposed to flame.
• Keep the UPS door closed and front panels installed to ensure proper cooling airflow and to
protect personnel from dangerous voltages inside the unit.
• Do not install or operate the UPS system close to gas or electric heat sources.
• The operating environment should be maintained within the parameters stated in this manual.
• Keep surroundings uncluttered, clean, and free from excess moisture.
• Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the
equipment.
AVERTISSEMENT!
• Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des courts–
circuits de haute intensité. Prendre les précautions nécessaires.
• Pour le replacement, utiliser le même nombre et modéle des batteries.
ATTENTION!
• Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en
vigueur dans votre localité.
• Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire exploser.
CE marking
The product has the CE marking in compliance with the following European directives:
LVD Directive (Safety)2006/95/EEC
EMC Directive2004/108/EEC
CAUTION
This product is designed for commercial and industrial applications. In a residential environment, the
product may cause radio interference, in which the user may be required to take additional measures.
2-2
Page 21
Section 1
Installation
Page 22
Page 23
Chapter 3 UPS Installation Plan and Unpacking
Use the following basic sequence of steps to install the UPS:
1.Create an installation plan for the UPS system (Chapter 3).
2.Prepare your site for the UPS system (Chapter 3).
3.Inspect and unpack the UPS cabinet (Chapter 3).
4.Unload and install the UPS cabinet, and wire the system (Chapter 4).
5.Install features, accessories, or options, as applicable (Chapter 4).
6.Complete the Installation Checklist (Chapter 4).
7.Have authorised service personnel perform preliminary operational checks and start up the system.
NOTE
It must be ensured that no line input source can accidentally be connected to the UPS during installation.
•Installation may only be carried out by qualified technicians and in conformity with the applicable
safety standards.
•The UPS unit is not suitable for IT or corner-earthed power distribution systems.
Startup and operational checks for parallel systems or installations with accessory
cabinets must be performed by an authorised Service Engineer, or the warranty terms
may become void. This service is offered as part of the sales contract for the UPS.
Contact an service representative in advance (usually a two-week notice is required) to
reserve a preferred startup date.
3.1 Creating an Installation Plan
Before installing the UPS system, read and understand how this manual applies to the system being installed.
Use the procedures and illustrations in paragraph 3.2 and Chapter 4 to create a logical plan for installing the
system.
3.2 Preparing the Site
CAUTION
WARNING
For the UPS system to operate at peak efficiency, the installation site should meet the environmental
parameters outlined in this manual. If the UPS is to be operated at an altitude higher than 1000m (3300 ft),
contact an service representative for important information about high altitude operation. The operating
environment must meet the weight, clearance, and environmental requirements specified.
3.2.1 Environmental and Installation Considerations
The UPS system installation must meet the following guidelines:
• The system must be installed on a level floor suitable for computer or electronic equipment.
• Suitable for mounting on concrete or other non-combustible surfaces only.
• The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
3-1
Page 24
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements shown in Table 3-1 and the
size requirements shown in Figure 3-1 through Figure 3-5. Dimensions are in millimetres (inches).
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the back of the cabinet. Allow clearance in front of and in back of the cabinet
for proper air circulation. The clearances required around the UPS cabinet are shown in Table 3-2.
Table 3-2. UPS Cabinet Clearances
From Top of Cabinet300 mm (12") working space
From Front of Cabinet900 mm (36") working space
From Back of CabinetSee Table No: 3-3
From Right Side of Cabinet See Table No: 3-3
From Left Side of CabinetSee Table No: 3-3
The basic environmental requirements for operation of the UPS are:
• L2- clearance between the adjacent paralleled UPS or UPS and adjacent PDU. Parallel UPS should be as
close as possible.
• Some models that feature rear connections also require additional rear clearance to enable installation and
connection.
3-3
Page 26
CAUTION
If battery systems are located in the same room as the UPS, the battery manufacturer's
environmental requirements should be followed if they are more stringent than the UPS
requirements. Operating temperatures above the recommended range will result in decreased
battery life and performance, and may reduce or void the battery warranty.
The UPS ventilation requirements are shown in Table 3-4.
Table 3-4. Air Conditioning or Ventilation Requirements During Full Load Operation
ModelModel
VFI 20000TAP 3/3 BI20000 VA
VFI 20000TAP 3/3 BE20000 VA
VFI 30000TAP 3/3 BI 30000 VA
VFI 30000TAP 3/3 BE 30000 VA
VFI 40000TAP 3/3 BI40000 VA
VFI 40000TAP 3/3 BE 40000 VA
VFI 60000TAP 3/3 BX60000 VA
VFI 80000TAP 3/3 BX 80000 VA
Input / Output Voltage
380/380 400/400 415/4151149
380/380 400/400 415/4151149
380/380 400/400 415/4151723
380/380 400/400 415/4151723
380/380 400/400 415/4152298
380/380 400/400 415/4152298
380/380 400/400 415/4153447
380/380 400/400 415/4154596
Heat Rejection
BTU/hr x1000 (kg-cal/hr)
3-4
Page 27
706 (27.8)
500 (19.69)
960 (37.8)
FRONT VIEWREAR VIEW
RIGHT VIEW
VFI 20000TAP 3/3 BI / VFI 20000TAP 3/3 BE
Figure 3-1. UPS Cabinet Dimensions (VFI 20000 TAP 3/3 BE/BI Front and Right Side Views)
Dimensions are in millimetres [inches]
3-5
Page 28
500 (19.69)
706 (27.8)
1230 (48.43)
FRONT VIEW
RIGHT VIEW
REAR VIEW
VFI 30000TAP 3/3 BI / VFI 30000TAP 3/3 BE
Figure 3-2. UPS Cabinet Dimensions (VFI 30000TAP 3/3 BE/BI Front and Right Side Views)
Dimensions are in millimetres [inches]
3-6
Page 29
706 (27.8)
500 (19.69)
1500 (59.06)
FRONT VIEWREAR VIEWRIGHT VIEW
VFI 40000TAP 3/3 BI / VFI 40000TAP 3/3 BE
Figure 3-3. UPS Cabinet Dimensions (VFI 40000TAP 3/3 BE/BIFront and Right Side Views)
Dimensions are in millimetres [inches]
3-7
Page 30
600 (23.62)
796 (31.34)
1876 (73.9)
600 (23.62)
796 (31.34)
1876 (73.9)
VFI 60000TAP 3/3 BX
FRONT VIEW
RIGHT VIEW
REAR VIEW
VFI 80000TAP 3/3 BX
FRONT VIEW
Figure 3-4. UPS Cabinet Dimensions (VFI 60000-80000TAP 3/3 BX Front and Right Side Views)
3-8
RIGHT VIEW
REAR VIEW
Dimensions are in millimetres [inches]
Page 31
500 (19.69)
706 (27.8)
600 (23.62)
500(19.69)
706(27.8)
796 (31.34)
FRONT
FRONT
TOP VIEW
BOTTOM VIEW
VFI 20000TAP 3/3 BI / VFI 20000TAP 3/3 BE / VFI 40000TAP 3/3 BI / VFI 40000TAP 3/3 BE
FRONT
FRONT
TOP VIEW
VFI 60000TAP 3/3 BX / VFI 80000TAP 3/3 BX
Figure 3-5. UPS Cabinet Dimensions (Top and Bottom Views)
BOTTOM VIEW
Dimensions are in millimetres [inches]
3-9
Page 32
960 (37.8)
361.5 (14.23)
250 (9.84)
500 (19.69)
361.5 (14.23)
FRONT VIEWRIGHT VIEW
VFI 20000TAP 3/3 BI / VFI 20000TAP 3/3 BE
Figure 3-6. UPS Cabinet Centre of Gravity (VFI 20000 TAP 3/3 BE/BI)
353 (13.9)
706 (27.8)
Dimensions are in millimetres [inches]
3-10
Page 33
1230 (48.43)
445 (17.52)
500
250 (9.84)
500 (19.69)
445 (17.52)
353 (13.9)
FRONT VIEW
VFI 30000TAP 3/3 BI / VFI 30000TAP 3/3 BE
Figure 3-7. UPS Cabinet Centre of Gravity (VFI 30000TAP 3/3 BE/BI)
706 (27.8)
RIGHT VIEW
Dimensions are in millimetres [inches]
3-11
Page 34
1500 (59.06)
550 (21.65)
250 (9.84)
500 (19.69)
FRONT VIEW
550 (21.65)
353 (13.9)
RIGHT VIEW
VFI 40000TAP 3/3 BI / VFI 40000TAP 3/3 BE
Figure 3-8. UPS Cabinet Centre of Gravity (VFI 40000TAP 3/3 BE/BI)
706 (27.8)
Dimensions are in millimetres [inches]
3-12
Page 35
1876 (73.9)
300 (11.81)
920 (36.22)
970 (38.19)
600 (23.62)
970 (38.19)
796 (31.34)
FRONT VIEWRIGHT VIEW
VFI 60000TAP 3/3 BX
Figure 3-9. UPS Cabinet Centre of Gravity (VFI 60000TAP 3/3 BX)
Dimensions are in millimetres [inches]
3-13
Page 36
1876 (73.9)
1020 (40.16)
600
300 (11.81)
600 (23.62)
1020 (40.16)
300 (11.81)
796 (31.34)
FRONT VIEWRIGHT VIEW
VFI 80000TAP 3/3 BX
Figure 3-10. UPS Cabinet Centre of Gravity (VFI 80000TAP 3/3 BX)
Dimensions are in millimetres [inches]
3-14
Page 37
3.2.2 UPS System Power Wiring Preparation
CAPACITORS INSIDE
REQUIRE 5 MINUTES
TO DISCHARGE
TO A SAFE LEVEL
AFTER ALL POWER
IS REMOVED.
SEE HANDBOOK
FOR INSTRUCTIONS.
The UPS system installation must meet the following guidelines:
• The system must be installed on a level floor suitable for computer or electronic equipment.
• The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements shown in Table 3-1 and the
size requirements shown in Figure 3-1. Dimensions are in millimetres (inches).
WARNING
•HIGH TOUCH CURRENT EARTH CONNECTION ESSENTIAL BEFORE CONNECTING SUPPLY.
As a result of the connected loads high leakage current is possible. Connection of the earth
(ground) is required for proper product operation. Do not check UPS operation by removal of
the Earth (ground) connection.
•The UPS unit is not suitable for IT and corner-earthed power distribution systems.
WARNING
•RISK OF ELECTRIC SHOCK. This ups receives power from more than one source disconnection of the AC and the DC source is required to de - energise this unit before
servicing. After disconnecting the utility power and the DC power, authorised service
personnel should wait at least five minutes for capacitor bleedoff before attempting internal
access to the UPS module.
•Backfeed protection is an internally fitted option on this device. If this option, or an externally
fitted backfeed contactor are not installed. Select backfeed contactor are shown in Table 3-7
and Table 3-8.
•The below label should be applied on all primary power isolators installed remote from the
UPS area and on external access points.
• Refer to national and local electrical codes for acceptable external wiring practices.
• To allow for future kVA upgrades, consider installing a derated UPS using wiring and external overcurrent
protection breakers sized for a fully rated UPS.
• For external wiring, use 90°C copper wire. Wire sizes listed in Table 3-5 are for copper wiring only. If wire is
run in an ambient temperature greater than 30°C, higher temperature wire and/or larger size wire may be
necessary. Wire sizes are based on using the specified breakers.
• Material and labour for external wiring requirements are to be supplied by designated personnel.
• If installing an external maintenance bypass, all feeds to the UPS including the Rectifier Input Breaker (RIB)
(if installed) must have a service disconnect independent of the maintenance bypass power path. Most
maintenance bypass solutions provide UPS input feeds derived from but isolated from the maintenance
bypass power path. If the maintenance bypass solution being installed does not provide such functionality,
DO NOT use a single feeder breaker to supply both the UPS and the maintenance bypass.
3-15
Page 38
• The bypass feed into this equipment uses four wires (three line conductors and neutral conductor), plus
grounding conductor (protective earthing conductor) . The rectifier feed into this equipment uses four wires
(three line conductors and neutral conductor), plus grounding conductor (protective earthing conductor). The
phases must be symmetrical about ground (from a Wye/Star source) for proper equipment operation.
• Parallel UPS input wiring size requirements and output wiring size requirements from the UPSs to the Tie
Cabinet are the sames as those for single systems.
• Install a proper three-pole overcurrent disconnect device before connecting to the UPS, the disconnect
device shall disconnect simultaneously all line conductors of the AC MAINS SUPPLY.
MBS (Maintenance bypass switch) is installed inside the UPS. When maintaining, open neutral switch and
•
MBS to isolation the UPS internal parts from the utility. Do not open neutral switch in any other cases
because the
neutral is required for UPS operation. For some VFI 60000-80000TAP 3/3 BX model without
internal neutral switch, external neutral switch shall be installed in site for maintenance.
• If a disconnect device interrupts the neutral conductor, it shall simultaneously interrupt all line conductors.
• When single-phase current exceeds 100A, switches of protective atmosphere should be equipped with
arc-control device.
• The UPS requires an input neutral connection. Ensure that an input neutral is connected prior to energising
the UPS. If a 4 pole Automatic Transfer Switch is installed upstream of the UPS it must work with a break
before make transition with a minimum transfer time of 50ms.
Figure 4-4 and Figure 4-5 show the location of the UPS power cable terminals.
93E60-80K
L1 L2 L3 N
Input
Input switchOutput switch
MBS
Suggested
External Neutral
Switch for
Maintenance
L1 L2 L3 N
Output
Figure 3-11. VFI 60000-80000TAP 3/3 BX N Switch connection (Recommended)
3-16
Page 39
Table 3-5. Input / Output Ratings and External Wiring Requirements for the VFI 20000-80000TAP
Basic Unit Rating
Input and Output Voltage
A: AC Input to UPS Rectier (0.99 Minimum PF)
Full load current plus battery recharge current
(3) Phases
Conductor Size (Phase A, B, C )
B: AC Input to UPS Bypass (Five Wire, Dual-Feed)
Full Load Current
(3) Phases
Conductor Size (Phase A, B, C )
C: DC Input from External Battery (432 Vdc)
(1) Positive, (1) Negative
Conductor Size
D: AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases
Conductor Size (Phase A, B,C )
Grounding
Neutral (N) (Mains/Load):( Non-linear load )
Backfeed protection device
cross-sections
Refer the IEC
62040-1
minmm
maxmm
minmm
maxmm
minmm
maxmm
minmm
maxmm
Units
kVA
kW
Volts
15
13.5
20
18
400/400 400/400400/400 400/400400/400 400/400
Rating 50/60 Hz
30
27
40
36
60
54
80
72
Amps2331466192123
2
6×16×16×116×116×125×1
2
6×110×125×125×150×170×1
Amps2229435887115
2
6×16×16×116×116×125×1
2
6×110×125×125×150×170×1
Total Amps34466992137183
2
6×16×110×116×135×150×1
2
16×125×135×150×150×270×2
Amps2229435887115
2
6×16×16×116×116×125×1
2
6×110×125×125×150×170×1
1.0times
1.7times
Clearance distance:≧2.0mm
Break time:
≦15s
NOTE
Callout letters A, B, C, and D map to Figure 5-5.
External overcurrent protection is not provided by this product, but is required by codes. Refer to
table 3-5 for wiring requirements. If an input/output lockable disconnect is required, it is to be
supplied by the user.
CAUTION
3-17
Page 40
Table 3-6. UPS External Power Cable Terminations for the VFI 20000-80000TAP
To reduce the risk of fire, connect only to a circuit provided with maximum input
circuit breaker current ratings from Table 3-7 in accordance with local regulations.
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values
for AC output to critical load shown in Table 3-5. The recommended line-to-line load unbalance is 50% or less.
Readily accessible disconnect devices (Bypass and output overcurrent protection and bypass and output
disconnect switches) are to be supplied by the customer. Table 3-8 lists the Recommended Bypass Circuit
Breaker, Output Circuit Breaker and Bypass Fuse Ratings.
There is no DC disconnect device within the UPS. A battery disconnect switch is recommended, And may be
required by local codes when batteries are remotely located. The battery disconnect switch should be installed
between the battery and the UPS
External DC input overcurrent protection and disconnect switch for the remote battery location is to be
provided by the user. Table 3-9 lists the maximum rating for continuous-duty rated circuit breakers satisfying the
criteria for both.
Table 3-9. Recommended DC input circuit breaker rating
Circuit Breaker Rating
UPS ModelLoad Derating
VFI 20000TAP
VFI 30000TAP
VFI 40000TAP
VFI 60000TAP
VFI 80000TAP
80% Derated
100% Rating
80% Derated
100% Rating
80% Derated
100% Rating
80% Derated
100% Rating
80% Derated
100% Rating183A
Rated battery voltage (DC 432V) Rated battery voltage(DC 384V)
57A64A
46A52A
86A97A
69A77A
114A129A
92A103A
172A193A
137A155A
229A258A
206A
Battery voltage is computed at 2 volts per cell. Rated battery current is computed at 2 volts per cell. The battery
wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC
voltage at rated battery current. If the conductors used for DC input from the battery cabinets to the UPS are
those provided by the UPS manufacturer, and the UPS and battery cabinets are manufactured by the same
supplier, then it is acceptable if they do not meet the noted minimum conductor sizes.
3-20
Page 43
3.2.3 UPS System Interface Wiring Preparation
Control wiring for features and options should be connected at the customer interface terminal blocks located
inside the UPS.
WARNING
Do not directly connect contactor contacts to the mains related circuits. Reinforced insulation is
required before connecting to the mains.
Read and understand the following notes while planning and performing the installation:
• Interface wiring should be rated for 24V, 1A minimum.
• For interface wiring from 30V to 600V, the wire should be rated for 600V, 1A minimum.
• Because of the REPO and building alarm wiring route in the UPS cabinet, the wire should be rated for a
minimum of 300V.
• Use twisted-pair wires for each input and return or common.
• All interface wiring and conduit is to be supplied by the customer.
• When installing external interface wiring between a REPO or building alarm and the UPS interface terminals,
conduit must be installed between each device and the UPS cabinet.
• If using the power terminal wiring channel, keep interface wiring separate from power wiring or use shielded
wire.
• If using conduit, install the interface wiring in separate conduit from the power wiring.
• All building alarm inputs require an isolated normally-open contact or switch (rated at 24 Vdc, 20 mA
minimum) connected between the alarm input and common terminal. All control wiring and switch contacts
are customer-supplied.
• LAN and telephone drops for use with Mini-Slot connectivity cards must be supplied by the customer.
• The REPO feature opens all contactors in the UPS cabinet and isolates power from your critical load. Local
electrical codes may also require tripping upstream protective devices to the UPS.
• The REPO switch must be a latching-type switch not tied to any other circuits.
• A jumper wire must be connected between pins 3 and 4 on the REPO terminal block if using a normallyclosed REPO switch.
• REPO wiring should be a minimum of 0.5~2.0 mm
2
.
• The REPO switch wiring must be in accordance with local regulations.
• The maximum distance between the REPO and the UPS cannot exceed 150 metres (500 feet).
3-21
Page 44
3.3 Inspecting and Unpacking the UPS Cabinets
The cabinet is shipped bolted to a wooden pallet and protected with an outer wood container.
The UPS cabinet is heavy (see Table 3-1). If unpacking and unloading instructions are not closely
followed, the cabinet may tip and cause serious injury.
1.Carefully inspect the outer packaging for evidence of damage during transit.
Do not install a damaged cabinet. Report any damage to the carrier and contact an service
representative immediately.
WARNING
CAUTION
NOTE
2.Use a forklift or pallet jack to move the packaged cabinet to the installation site, or as close as possible,
before unpacking. If possible, move the cabinets using the pallet. Insert the forklift or pallet jack forks
between the supports on the bottom of the pallet (see Figure 3-6 through Figure 3-10 for the UPS cabinet
centre of gravity measurements).
For the following step, verify that the forklift or pallet jack is rated to handle the weight of
the cabinet (see Table 3-1 for cabinet weight).
CAUTION
Do not tilt the UPS cabinets more than 10° from vertical or the cabinets may tip over.
3.Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft) on each side for
removing the cabinet from the pallet.
4.Remove the inner protective packaging. Retain the ramp brackets.
5.Recycle the remainder of the outer shipping container and the inner protective packaging in a responsible
manner.
6.Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading.
If damage has occurred or shortages are evident, contact an service representative immediately to
determine the extent of the damage and its impact on further installation.
3-22
Page 45
NOTE
While waiting for installation, protect the unpacked cabinet from moisture, dust, and
other harmful contaminants. Failure to store and protect the UPS properly may void
your warranty.
Figure 3-12. UPS Cabinet as Shipped on Pallet
3-23
Page 46
This page intentionally left blank.
3-24
Page 47
Chapter 4 UPS System Installation
4.1 Preliminary Installation Information
Installation should be performed only by qualified personnel. See installation instructions before
connecting to the supply.
Refer to the following while installing the UPS system:
• Chapter 3 for cabinet dimensions, equipment weight, wiring and terminal data, and installation notes.
WARNING
• Do not tilt the cabinets more than
• If perforated floor tiles are required for ventilation, place them in front of the UPS.
• The UPS unit is not suitable for IT or corner-earthed power distribution systems.
• Suitable for mounting on concrete or other non-combustible surfaces only
4.2 Unloading the UPS Cabinetfrom the Pallet
The UPS Cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet:
The UPS cabinet is heavy (see Table 3-1). If unpacking and unloading instructions are not closely followed,
the cabinet may tip and cause serious injury.
• Do not tilt cabinet more than 10° from vertical.
• Lift the cabinets only with a forklift or damage may occur.
NOTE
1.If not already accomplished, use a forklift or pallet jack to move the UPS cabinet to the installation area, or
as close as possible, before unloading from the pallet. Insert the forklift or pallet jack forks between the
supports on the bottom of the pallet (see Figure 3-6 through Figure 3-10for the UPS cabinet centre of
gravity measurements).
For the following steps, verify that the forklift or pallet jack is rated to handle the weight of
the cabinet (see Table 3-1 for cabinet weight).
±10° during installation.
WARNING
CAUTION
2.Remove four bolts securing the front shipping bracket to the cabinet and four bolts securing the bracket to
the pallet (see Figure 4-1). If installing the cabinet permanently, retain the shipping bracket and securing
hardware for later use.
3.Attach the ramp to the front of the pallet (see Figure 4-2):
4.If the leveling feet are not fully retracted, turn the leveling feet until they are retracted.
5.Remove four bolts securing the rear shipping bracket to the cabinet and four bolts securing the bracket to
the pallet (see Figure 4-1). If installing the cabinet permanently, retain the shipping bracket and securing
hardware for later use.
4-1
Page 48
Front Door
Shipping Bracket Bolts
Pallet
Shipping Bracket
Figure 4-1. Removing the Shipping Bracket
WARNING
Do not stand directly in front of the pallet while unloading the cabinet. If unloading instructions are
not closely followed, the cabinet may cause serious injury.
6.Slowly roll the cabinet toward the front of the pallet. Continue rolling the cabinet down the ramp until the
cabinet is clear of the ramp (see Figure 4-3).
7.Roll the cabinet to the final installation location.
8.If installing the cabinet permanently, retain the shipping brackets and hardware; otherwise, recycle the
pallet, ramp, and shipping brackets in a responsible manner.
4-2
9.Secure the UPS cabinet in position by lowering the leveling feet until the cabinet is not resting on the
casters and the cabinet is level.
10. If permanently mounting the system, proceed to Step 11;
11. Using the retained hardware, reinstall the shipping brackets removed in Step 2 and Step 5 to the front and
rear of the UPS cabinet with the angle facing outward (see Figure 4-1).
12. Secure the cabinet to the floor with customer-supplied hardware.
Page 49
Pallet
UPS System Installation
Ramp
Figure 4-2. Attaching the Ramp to the Pallet
UPS Cabinet
Figure 4-3. Rolling the Cabinet Down the Ramp
4-3
Page 50
4.3 External Battery Cabinet Installation
Before connecting the external battery, please read the notice and warning label on the battery cabinet.
•In the event of malfunction, the battery cabinet chassis or battery cabinet frames may become
live!
•Special care should be taken when working with the battery cabinet associated with the
equipment. Ensure the battery number is suited to the setting of the battery charging voltage
before installing the battery. When the battery cabinet is connected the overall voltage exceeds
nominal voltage. It is very important to ensure that the batteries are installed separately, in a
dedicated battery cabinet.
•Battery back-up time do not exceed one hour, if the battery setting shall be exceeded one hour,
consult to the professional personnel.
• The most common battery type used in UPS installations is the valve regulated battery. Valve
regulated cells are not sealed. The amount of gas given off is less than for flooded cells, but
when planning the battery installation, allowance must be made for adequate ventilation and
heat dissipation. Valve regulated cells are not completely maintenace- free. They must be kept
clean and their connections checked periodically to ensure they are tight, and that there is no
evidence of corrosion. It is inevitable that the batteries will lose charge during transportation and
storage; before attempting to carry out an autonomy test, ensure that the batteries are fully
charged as this may take several hours. Cell performance typically improves after a few
discharge/recharge cycles.
• The requirements of the EC directives are satisfied when battery cabinet are used with original
accessories. If alternative batteries are used, you must ensure that the applicable EC directives
are met and declare conformity.
WARNING
CAUTION
4-4
Connect the battery cabinet as follows:
1.Turn off the UPS.
2.Check all the external battery breakers are open.
3.Connect PE first.
4.Connect the battery cabinet(s) with cables sized according to cable cross section and protective device.
5.Specification to terminals + (positive pole) and - (negative pole).
Refer to instructions provided with the battery cabinet or by vendor.
WARNING
ENSURE CORRECT POLARITY!
Page 51
4.4 External Power Wiring Installation
NOTE
To install wiring:
1.Route the wiring to the UPS terminal blocks in the UPS. Figure 4-4 and Figure 4-5 for wiring access
information and terminal locations.
2.Ground the UPS according to local and/or national electrical wiring codes by routing and connecting the
ground wire to the input ground lug.
3.Connect phase A, B and C rectifier input power wiring from the utility source to the rectifier input, See
paragraph 3.2.2 for wiring and termination requirements.
4.Bypass input power wiring from the utility source to the bypass input terminals and neutral terminals. See
paragraph 3.2.2 for wiring and termination requirements.
5.Connect phase A, B and C power wiring from output terminals to the critical load. See paragraph 3.2.2 for
wiring and termination requirements.
6.Mains input N , Output N and Bypass input N are connected together inside UPS.
7.If wiring interface connections, proceed to paragraph 4.5.
Without accessory cabinets, conduit and wiring enter from the bottom of the UPS
conduit landing plate. With accessory cabinets, wiring can be installed between the
UPS and accessory cabinets by using conduit or by routing wiring through the
power terminal cover base wiring channels.
WARNING
•HIGH TOUCH CURRENT. EARTH CONNECTION ESSENTIAL BEFORE CONNECTING
SUPPLY. As a result of the connected loads high leakage current is possible. Connection of the
earth (ground) is required for proper product operation. Do not check UPS operation by
removal of the Earth (ground) connection.
•BAT+/BAT- are terminals connected to the battery cabinet, Battery+ polarity should use red
cable, battery - polarity should use black or blue cable.
•This device may not be fitted with an optional internal mains disconnection device. If not
fitted, it is essential that the customer install such a device at the installation site near the
UPS.
•Input neutral line should be directly connected to input “N” terminal of UPS wire connection
terminal bay without AC input idle-run.
•There are protective earthing terminals within the UPS for mains supply, load supply and
battery. The battery cabinet earth protection can be connected either to the UPS or to a
common earthing terminal outside the UPS.
4-5
Page 52
External Battery +
External Battery -
Neutral (N)
Phase C (L3)
Phase B (L2)
Phase A (L1)
AC Input to UPS Bypass
Ground Terminals
AC Output to Critical Load
Note: Connection terminals for these models are accessible from the rear of the UPS cabinet.
Phase C (L3)
Phase B (L2)
Phase A (L1)
Phase A (L1)
Phase B (L2)
Phase C (L3)
REAR VIEW
AC Input to UPS Rectifier
VFI 20000-40000TAP 3/3 BE/BI
Figure 4-4. Power Terminal Locations VFI 20000-40000TAP 3/3 BE/BI/
4-6
Page 53
Ground Terminals
AC Input to
UPS Bypass
Phase C (L3)
Phase B (L2)
Phase A (L1)
External Battery -
External Battery +
Neutral (N)
RIGHT VIEW
AC Input to
UPS Rectifier
Phase A (L1)
Phase B (L2)
Phase C (L3)
FRONT VIEW
Phase C (L3)
Phase B (L2)
Phase A (L1)
AC Output to
Critical Load
VFI 60000-80000TAP 3/3 BX
Note: Connection terminals for these models are accessible from the front of the UPS cabinet.
Figure 4-5. Power Terminal Locations VFI 60000-80000TAP 3/3 BX
4-7
Page 54
4.5 Installing Interface Connections
4.5.1 Installing Building Alarm Connections
To install wiring:
1.Verify the UPS system is turned off and all power sources are removed. See Chapter 6, “UPS Operating
Instructions", for shutdown instructions.
2.To locate the appropriate terminals and review the wiring and termination requirements, see
paragraph 3.2.3, Table 4-1, Figure 4-6 and Figure 4-7.
3.Interface cables can enter the UPS via right side panel or a knockout in the top of the cabinet, see Figure
4-9.
4.Connect the building alarm interface wiring as shown in Table 4-1 and Figure 4-8.
6.If wiring parallel connections, proceed to paragraph 4.5.2; if wiring Mini-Slot connections, proceed to
paragraph 4.5.3;
FRONT MIDDLE
COVER PLATE
Mini-Slot Communication Bays
(See Figure 4-7 for detail)
Interface Terminals
(See Figure 4-7 for detail)
FRONT VIEW
VFI 20000-40000TAP 3/3 BE/BI
FRONT MIDDLE
COVER PLATE
Mini-Slot Communication Bays
(See Figure 4-7 for detail)
Figure 4-8. Building Alarm Terminal Block Connector Assignments
Parallel CAN Output (RJ45)
Parallel CAN Input (RJ45)
Pull chain Terminals
REPO Terminals (See Figure 4-13 for Detail)
Building Alarm (See Figure 4-8 for Detail)
Building Alarm Terminal NameDescription
1Building Alarm 1 +
2Building Alarm 1 –
3Building Alarm 2 +
4Building Alarm 2 –
5Building Alarm 3 +
6Building Alarm 3 –
Input: Programmable UPS alarm, activated by a remote dry contact closure.
Input: Programmable UPS alarm, activated by a remote dry contact closure.
Input: Programmable UPS alarm, activated by a remote dry contact closure.
4-9
Page 56
FRONT VIEW
Wiring Access
VFI 20000-40000TAP 3/3 BE/BI
Wiring Aaccess 1
FRONT VIEW
4-10
Wiring Aaccess 2
VFI 60000-80000TAP 3/3 BX
Figure 4-9. Interface Wiring Access
Page 57
4.5.2 Installing Parallel Pull Chain and CAN Control Wiring and Connections
NOTE
RJ-45 Controller Area Network (CAN) must be supplied by the customer.
To install wiring:
1.Verify the UPS system is turned off and all power sources are removed. See Chapter 6, “UPS Operating
Instructions", for shutdown instructions.
2.Installing Parallel system, see Figure 4-10 and Figure 4-12.
CAUTION
• Parallel system combined input and output cable length should be in accordance with the
following rule. It should be designed to ensure that wiring impedance from point of supply to
UPS input and from UPS output to load connection for each UPS module in a multi-module
system is equal, or within a tolerance of approximately ±10%. This is to ensure approximately
equal current sharing when in static bypass mode and restrain input/output high frequency loop
current of parallel system. Suggest that parallel system combined input and output cable length
no less than 10m, 5m for input and 5m for output.
Total length of 1A =2A=3A=4A
1B=2B=3B=4B
1C=2C=3C=4C
• If installing only two UPS modules (redundant), this requirement is no longer required as each
UPS is capable of supporting the full bypass requirement. However, this would preclude future
expansion.
• Ensure that each UPS static bypass is fed from a single common source, as is an external
bypass switch if installed. If each UPS is fed with a separate rectifier source, please consult for
advice on compatibility.
3.To locate the appropriate terminals and review the wiring and termination requirements, see
paragraph 3.2.3, Table 4-2, Figure 4-7, Figure 4-9, and Figure 4-10.
4.Remove the small parts from the knockout in the right side plate.
5.Route and install RJ-45 Controller Area Network (CAN) cables between the UPS cabinets. See Figure 4-7,
Figure 4-11 and Figure 4-12 for wiring information.
6.Route and install pull chain wiring (Twisted Wires 0.5-2.0 mm2) between the UPS cabinets and cabinet
MOBs. See Figure 4-7, Figure 4-10 and Figure 4-11 for wiring information.
7.If wiring Mini-Slot connections, proceed to paragraph 4.5.3;
4.5.3 Installing Mini-Slot Interface Connections
NOTE
LAN drop for connection to UPS communications card is to be supplied by
customer.
For installation and setup of an Mini-Slot card, contact an service representative (see paragraph 1.8)
To install wiring:
1.If not already installed, install the LAN drop.
2.Route and install the LAN and other cables to the appropriate Mini-Slot cards. See Figure 4-6 and Figure 4-7
for Mini-Slot communication bay locations.
3.Refer to the manual supplied with the Mini-Slot card for operator instructions.
4.Install the power terminal cover using the provided hardware.
4-12
Page 59
TERMINATING
JUMPER
INOUTINOUTINOUTINOUT
CN3CN6CN3CN6CN3CN6CN3CN 6
CAN BUSCAN BUSCAN BUSCAN BUS
RJ-45 CABLERJ-45 CABLERJ-45 CABLE
UPS1UPS 2UPS 3UPS 4
BUILDING
PULLCHAIN
ALARM CN9
CUSTOMER
TERMINAL
BLOCK
CONNECTIONS
3 24 259 810 2615 1416 2721 2022 28
165712
NO NC
COM
CN4
121212121212121212
NO NC
M
O
COM
B
1
BUILDING
ALARM CN9
NO NC
COM
M
O
B
2
PULLCHAIN
CN4
NO NC
COM
11
BUILDING
ALARM CN9
1318
NO NC
M
O
COM
B
3
PULLCHAIN
CN4
NO NC
COM
17
TIE CABINET
Figure 4-11. Parallel UPS Control Wiring
BUILDING
ALARM CN9
TWISTED
PAIRS
1924
NO NC
M
O
COM
B
4
TERMINATING
JUMPER
PULLCHAIN
CN4
NO NC
COM
23
Bypass inputs
to UPSs
UPS 1
1A
2A
3A
Battery
UPS 2
4A
Battery
REC inputs
to UPSs
1C
2C
3C
4C
UPS 3
Outputs from
UPSs
1B
Battery
UPS 4
2B
3B
4B
Battery
Battery
Battery
Battery
Battery
UPS 1
UPS 2
UPS 3
UPS 4
Outputs from
UPSs
1C
2C
3C
4C
Figure 4-12. Parallel UPS system connections
4-13
Page 60
4.6 Installing a REPO Switch
Normally Open
UPS
A latching-type Remote Emergency Power-off (REPO) switch can be used in an emergency to shut down the
UPS and remove power to the critical load from a location away from where the UPS is installed. Shows a
REPO switch.
NOTE 1
Before installing a REPO switch, verify that the UPS was installed according to the
instructions in paragraphs 4.2 through 4.5.
NOTE 2
When installing the REPO switch, you must install conduit between the device and
the UPS cabinet for wiring the switch.
NOTE 3
The REPO switch must be a normally-open or normally-closed latching-type switch
not tied into any other circuits.
NOTE 4
The REPO switch wiring must be in accordance with local regulations.
To Install a REPO switch:
1.Verify the UPS system is turned off and all power sources are removed. See Chapter 6, “UPS Operating
Instructions,“ for shutdown instructions.
2.Securely mount the REPO switch. Recommended locations include operator's consoles or near exit doors.
3.To locate the appropriate terminals and review the wiring and termination requirements, see
paragraph 3.2.3, Table 4-3, Figure 4-6, Figure 4-7, and Figure 4-13.
UPS
4-14
Table 4-3. REPO Connections
REPO Terminal Description
4.Normally-Open REPO Switch Wiring see Table 4-4 and Figure 4-14,Normally-Closed REPO Switch Wiring
seeTable 4-5 and Figure 4-15 .
Input: normally-closed dry contact used to activate UPS EPO from a remote switch.
Input: normally-open dry contact used to activate UPS EPO from a remote switch.
Page 61
5.Connect the wiring as shown in Table 4-4 and Figure 4-14 for a normally-open REPO or Table 4-5 and
Figure 4-15 for a normally-closed REPO.
6.If using a normally-closed REPO switch, connect a jumper wire between pins 3 and 4 on the REPO
terminal block.
7.If you are installing multiple REPO switches, wire additional switches in parallel with the first REPO.
8.If required, install wiring from the REPO switch to the trip circuitry of the upstream protective devices. A
second contact block is provided on the REPO switch for this function . The REPO switch wiring must be in
accordance with local regulations.
Table 4-4. REPO Connections
From REPO Station(s)
Switch Contact Block
(Either Block)
3,4 NOSee Figure 4-14 for wiringTwisted Wires (2)
To REPO Terminal Block
on Back of UPS CabinetWire SizeTightening Torque
7 lb in
(0.8 Nm)
(0.5 -2.0 mm
1
2
)
REPRO
Switch
(No)
2
REPO TB
3
Twisted
Wires
4
3
4
Figure 4-14. Normally-Open REPO Switch Wiring
4-15
Page 62
Table 4-5. REPO Connections
From REPO Station(s)
Switch Contact Block
(Either Block)
1,2,3,4 NCSee Figure 4-15 for wiringTwisted Wires (2)
To REPO Terminal Block
on Back of UPS CabinetWire SizeTightening Torque
7 lb in
(0.8 Nm)
(0.5 -2.0mm
2
)
4.7 Initial Startup
Startup may be performed by the customer’s qualified electrical contractor for single (not parallel) UPS
installations without any accessory cabinets.
Startup and operational checks for parallel systems or installations with accessory cabinets must be performed
by an authorised Service Engineer, or the warranty terms may become void. Contact an service representative
in advance (usually a two-week notice is required) to reserve a preferred startup date.
REPRO
Switch
(NC)
1
Twisted
Wires
2
Figure 4-15. Normally-Closed REPO Switch Wiring
1
2
3
4
REPO TB
4.8 Completing the Installation Checklist
The final step in installing the UPS system is completing the following Installation Checklist. This checklist
ensures that you have completely installed all hardware, cables, and other equipment. Complete all items listed
on the checklist to ensure a smooth installation. Make a copy of the Installation Checklist before filling it out,
and retain the original.
After the installation is complete, an Service Engineer must verify the operation of the UPS system and
commission it to support the critical load. The service representative cannot perform any installation tasks
other than verifying software and operating setup parameters. Service personnel may request a copy of the
completed Installation Checklist to verify all applicable equipment installations have been completed.
NOTE
4-16
The Installation Checklist MUST be completed prior to starting the UPS system for
the first time.
Page 63
Installation Checklist
All packing materials and restraints have been removed from each cabinet.
The UPS cabinet is placed in its installed location.
All conduits and cables are properly routed to the UPS and any ancillary cabinets.
All power cables are properly sized and terminated.
Neutral conductors are installed.
A ground conductor is properly installed.
Building alarms are wired appropriately. (Optional)
LAN drops are installed. (Optional)
LAN connections have been completed. (Optional)
The REPO device is mounted in its installed location and its wiring is terminated inside the UPS cabinet. (Optional)
A jumper wire is connected between pins 3 and 4 on the REPO terminal block if using a normally-closed REPO switch.
(Optional)
All terminal cover plates are installed.
Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (Optional)
Air conditioning equipment is installed and operating correctly.
The area around the installed UPS system is clean and dust-free. (Recommends that the UPS be installed on a level
floor suitable for computer or electronic equipment.)
Adequate workspace exists around the UPS and other cabinets.
Adequate lighting is provided around all UPS equipment.
A 230 Vac service outlet is located within 7.5 metres (25 feet) of the UPS equipment.
Startup and operational checks are performed by an authorised Service Engineer, for parallel systems or installations
with accessory cabinets.
Parallel System Installation Checklist
Each cabinet in the parallel system is placed in its installed location.
All conduits and cables are properly routed to the UPSs and to the parallel tie cabinet.
All power cables are properly sized and terminated.
Neutral conductors are installed between cabinets as required.
Ground conductors are properly installed.
CAN wiring between the UPSs is properly installed.
Pull chain wiring between the UPSs is properly installed.
Adequate workspace exists around the UPSs, parallel tie cabinet, and other cabinets.
Startup and operational checks are performed by an authorised Service Engineer, for parallel systems.
4-17
Page 64
Notes
4-18
Page 65
Section 2
Operation
Page 66
Page 67
Chapter 5 Understanding UPS Operation
5.1 UPS System Overview
The VFI 20000-80000TAP 3/3 BE/BI/BX UPS is a continuous-duty, solid-state, three-phase, true online system
that provides conditioned and uninterruptible AC power to the UPS system's output and critical load.
The basic system consists of a rectifier, battery converter, inverter, monitoring/operation control panel, integrated
communication server, and digital signal processor (DSP) logic. Figure 5-1 shows the main elements of the UPS
system.
If utility power is interrupted or falls outside the parameters specified in Chapter 9, “Product Specifications,” the
UPS uses a backup battery supply to maintain power to the critical load for a specified period of time or until the
utility power returns. For extended power outages, the UPS allows you to either transfer to an alternative power
system (such as a generator) or shut down your critical load in an orderly manner.
External Battery cabinet
Battery
Relay
Battery
Converter
AC Input to
Rectifier/
Charger
AC Input to
Bypass
Input
Switch
(Optional Dual Input)
Bypass Input Switch
Input
Relay
(Optional)
Backfeed Contactor
Digital Metering
Static
Switch
UPS Cabinet
Output
Relay
InverterRectifier
Power Module
Output switch
AC Output to
Critical Load
Maintenance Bypass Switch
Figure 5-1. Main Elements of the UPS System
The emergency bypass consists of a continuous static switch, and an optional backfeed protection contactor. The
backfeed protection contactor (if fitted) is located in series with the static switch. The static switch is armed and
ready during normal operation.
5-1
Page 68
5.2 Single UPS
A single UPS operates independently to support an applied load from the inverter, providing conditioned and
uninterruptible AC power to the critical load from the output of the module. During an outage, the inverter
continues to operate, supporting power to the load from the battery supply. If the unit requires service, applied
loads are transferred to the internal bypass either automatically or manually. With the exception of an optional
external battery cabinet, no other cabinets or equipment are required for the single UPS to successfully support
its applied loads.
5.2.1 Modes
The VFI 20000-80000TAP 3/3 BE/BI/BX UPS supports a critical load in four different modes of operation:
•In Standard Normal mode, the critical load is supplied by the inverter, which derives its power from rectified
•In High-Efficiency (HE) mode, commercial AC power is supplied directly to the critical load through the
•In Bypass mode, the critical load is directly supported by utility power.
•In Battery mode, the battery provides DC power, which maintains inverter operation. The battery supports
The following paragraphs describe the differences in the UPS operating modes, using block diagrams to show
the power flow during each mode of operation.
utility AC power. In this mode, the battery charger also provides charging current for the battery, if needed,
Standard mode is the standard normal operating mode.
internal bypass and transfers automatically to Standard Normal mode (double-conversion on demand) if an
abnormal condition is detected.
the critical load.
5.2.2 Standard Normal Mode
During Standard Normal mode, power for the system is derived from a utility input source through the rectifier
input contactor. Three-phase AC input power is converted to DC using IGBT devices to produce a regulated DC
voltage to the inverter. When the battery contactor is closed the battery is charged directly from the regulated
rectifier output through a buck or boost DC converter, depending on the system voltage and the size of the
battery string attached to the unit.
Figure 5-2 shows the path of electrical power through the UPS system when the UPS is operating in Normal
mode.
The battery converter derives its input from the regulated DC output of the rectifier and provides either a
boosted or bucked regulated DC voltage charge current to the battery. The battery is always connected to the
UPS and ready to support the inverter should the utility input become unavailable.
The inverter produces a three-phase AC output to a customer's load without the use of a transformer. The
inverter derives regulated DC from the rectifier and uses IGBT devices and pulse-width modulation (PWM) to
produce a regulated and filtered AC output. The AC output of the inverter is delivered to the system output
through the output contactor.
If the utility AC power is interrupted or is out of specification, the UPS automatically switches to Battery mode
to support the critical load without interruption. When utility power returns, the UPS returns to Normal mode.
5-2
Page 69
Bypass Input
Rectifier
Input
Bypass Switch (Optional Dual Input)
Input Switch
Input
Relay
Rectifier
Static
Switch
Output
Inverter
Output
Relay
Battery
Converter
Main Power Flow
Trickle Current
Energised
De-Energised
Switch
Relay
Battery
Relay
Closed
Open
Battery
Figure 5-2. Path of Current Through the UPS in standard Normal Mode
If the UPS becomes overloaded or unavailable, the UPS switches to Bypass mode. The UPS automatically
returns to Normal mode when the overload condition is cleared and system operation is restored within
specified limits.
If the UPS suffers an internal failure, it switches automatically to Bypass mode and remains in that mode until
the failure is corrected and the UPS is back in service.
5.2.3 High-Efciency Mode
When the UPS is operating in HE mode, commercial AC power is supplied directly to the critical load through the
internal bypass with the power module in a standby state. If a commercial power brownout, blackout, overvoltage,
undervoltage, or out-of-tolerance frequency condition occurs the system forward transfers to normal mode
(double-conversion on demand) or battery mode. When the input line returns to normal operating range, the UPS
returns to HE operation. For charging batteries in HE mode, the UPS will revert to normal mode to charge the
batteries, then return to HE mode when charge cycle is complete.
HE mode, if selected, is a normal operating mode, and not an alarm condition. While the UPS is in this mode,
the NORMAL light on the front display will illuminate.
5-3
Page 70
5.2.4 Bypass Mode
CAUTION
The critical load is not protected from voltage or frequency fluctuations or power outages while
the UPS is in Bypass mode.
The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The
UPS can also be transferred from Normal mode to Bypass mode manually. The bypass source supplies the
commercial AC power to the load directly. Figure 5-3 shows the path of electrical power through the UPS
system when operating in Bypass mode.
In Bypass mode, the output of the system is provided with three-phase AC power directly from the system
input. While in this mode, the output of the system is not protected from voltage or frequency fluctuations or
power outages from the source. Some power line filtering and spike protection is provided to the load but no
active power conditioning or battery support is available to the output of the system in the Bypass mode of
operation.
The internal bypass is comprised of a solid-state, silicon-controlled rectifier (SCR) continuous static switch, and
an optional backfeed protection contactor. The static switch is used instantaneously anytime the inverter is
unable to support the applied load. The continuous static switch is wired in series with the backfeed protection
contactor (if fitted), and together they are wired in parallel with the rectifier and inverter.
The static switch, being an electronically-controlled device, can be turned on immediately to pick up the load
from the inverter while inverter output contactor opens to isolate the inverter. The backfeed protection
contactor (if fitted) is normally closed, ready to support the static switch unless the bypass input source
becomes unavailable.
If the UPS transfers to Bypass mode from Normal mode due to any reason other than operator intervention,
the UPS automatically attempts to transfer back to Normal mode (up to three times within a ten minute
period). The fourth transfer locks the critical load to the bypass source and requires operator intervention to
transfer.
Bypass Input
Rectifier
Input
Bypass Switch (Optional Dual Input)
Input Switch
Input
Relay
Switch
Relay
Rectifier
Closed
Open
Static
Switch
Battery
Converter
Battery
Battery
Relay
Inverter
Output
Output
Relay
Main Power Flow
Trickle Current
Energised
De-Energised
5-4
Figure 5-3. Path of Current Through the UPS in standard Bypass Mode
Page 71
5.2.5 Battery Mode
The UPS automatically transfers to Battery mode if a utility power outage occurs, or if the utility power does
not conform to specified parameters. In Battery mode, the battery provides emergency DC power that the
inverter converts to AC power.
Figure 5-4 shows the path of electrical power through the UPS system when operating in Battery mode.
Bypass Input
Rectifier
Input
Bypass Switch (Optional Dual Input)
Input Switch
Input
Relay
Switch
Relay
Rectifier
Closed
Open
Static
Switch
Battery
Converter
Battery
Battery
Relay
Inverter
Output
Output
Relay
Main Power Flow
Trickle Current
Energised
De-Energised
Figure 5-4. Path of Current Through the UPS in standard Battery Mode
During a utility power failure, the rectifier no longer has an AC utility source from which to supply the DC
output voltage required to support the inverter. The input contactor opens and the battery instantaneously
supplies energy to the battery converter. The converter boosts the voltage so that the inverter can support the
customer's load without interruption. If bypass is common with the rectifier input, the backfeed protection
contactor also opens. The opening of the input and the optional backfeed protection contactors prevent
system voltages from bleeding backwards through the static switch and rectifier snubber components to the
utility source.
If the input power fails to return or is not within the acceptance windows required for normal operation, the
battery continues discharging until a DC voltage level is reached where the inverter output can no longer
support the connected loads. When this event occurs, the UPS issues another set of audible and visual alarms
indicating SHUTDOWN IMMINENT. Unless the rectifier has a valid AC input soon, the output can be supported
for only two minutes before the output of the system shuts down. If the bypass source is available, the UPS
transfers to bypass instead of shutting down.
If at any time during the battery discharge the input power becomes available again, the input and the backfeed
protection contactors close and the rectifier begins to supply DC current to the converter and inverter. At this
point, the unit returns to Normal mode. Depending on the total load and the duration of the battery discharge,
battery current limit alarms may be seen for a short time due to the current required to recharge the battery.
5-5
Page 72
5.3 Single UPS Unit System Oneline Congurations
The system oneline drawings in this section show the simplified internal structure of the UPS, battery supply,
and basic maintenance bypass.
Oneline Drawing
See Figure 5-5See Tab 9-1 for
UPS ModelInputOutputSystem Type
Model
Voltage
380/400/415380/400/415Single Reverse Transfer UPS with External Battery
5-6
Page 73
L1, L2,
L3, N
Input Switch
AC Input to
UPS Rectifier
4 Wire A-B-C
Rotation
AB
AC Input to
Bypass 4 Wire
A-B-C Rotation
L1, L2,
L3, N
Bypass Input Switch
(Optional Dual Input)
(Optional)
Backfeed Contactor
Pull Chain
Remote EPO
Parallel CAN
Mini-Slot
Interface
Interface Board
Static
Switch
Fuse
Input
relay
Rectifier
NOTE Callout letters A,B,C, and D map to Table 3-5.
(OPTIONAL)
INTERNAL BATTERY
Fuse
disconnector
Inverter
Output
relay
Fuse
Battery
relay
Battery reay
C
Battery
Breaker
EXTERNAL BATTERY
CABINET
MBS
Output Switch
UPS
CABINET
L1, L2,
L3, N
AC Output to
Critical Load
D
Figure 5-5. UPS System Oneline (Dual Input)
5-7
Page 74
AC Input to
UPS Rectifier
4 Wire A-B-C
Rotation
A,B
Pull Chain
Remote EPO
Parallel CAN
Mini-Slot
Interface
L1, L2,
L3, N
Input Switch
(Optional)
Backfeed Contactor
Static
Switch
Battery
relay
Fuse
Input
relay
Rectifier
Inverter
Output
relay
Fuse
Interface Board
Output Switch
MBS
L1, L2,
L3, N
AC Output to
Critical Load
D
NOTE Callout letters A,B,C, and D map to Table 3-5.
Figure 5-6. UPS System Oneline (Single Input)
5-8
(OPTIONAL)
INTERNAL BATTERY
Fuse
disconnector
Battery reay
Fuse
UPS
CABINET
C
Battery
Breaker
EXTERNAL BATTERY
CABINET
Page 75
Chapter 6 UPS Operating Instructions
This section describes how to operate the UPS.
NOTE 1
NOTE 2
6.1 UPS Controls and Indicators
The controls and indicators identified and described in this section are used to control and monitor UPS
operation. Figure 6-1 shows the controls and indicators and Figure 6-2 shows the UPS switches.
Before starting the UPS, ensure all installation tasks are complete and a preliminary
startup has been performed by authorised service personnel. The preliminary
startup verifies all electrical interconnections to ensure the installation was
successful and the system operates properly.
Read this section of the manual and have thorough knowledge of UPS operation before
attempting to operate any of the controls.
Control Panel
Door Latch
Figure 6-1. UPS Controls and Indicators
6-1
Page 76
Input Switch
Bypass Switch (Optional)
DC Fuse Connector
Neutral Switch
Output Switch
Maintenance
Bypass Switch
Input Switch
Maintenance
Bypass Switch
DC Fuse Connector
Neutral Switch
Output Switch
Input Switch
Bypass Switch (Optional)
VFI 20000-40000TAP 3/3 BE/BI
Dual Input (Example for 30000 VA)
Output Switch
Maintenance
Bypass Switch
VFI 20000-40000TAP 3/3 BE/BI
Single Input (Example for 30000 VA)
Input Switch
Bypass Switch
(Optional)
Output Switch
Maintenance
Bypass Switch
VFI 60000TAP 3/3 BX
6.1.1 Control Panel
The control panel is used to set up and control the UPS, and to monitor UPS operation. For a description of the
UPS control panel functions, see paragraph 6.2.
6-2
VFI 80000TAP 3/3 BX
Figure 6-2. UPS Switches
Page 77
6.2 Using the Control Panel
UPS Operating
Instructions
singthe Control Panel
The fo
llowing paragraphs describe the UPS control panel, including controls andindicators, and how to monitor
UPS operation. The controlpanel (see Figure6-3) is locatedon the front door of the UPS.
Figure 6-3. UPS Control Panel
The control panel consists of:
l
A l
iquid crystal display (LCD) (1)
l
Menu na
vigation pushbutton switches (2)
l
A
v
erticalcolumn of status indicators (3). See paragraph6.2.1.
The following paragraphs describe using the UPS control panelto monitor the UPS. See paragraph6.3 for useof the operational controls.
When the unit powers up, the screen displays the Eaton logo as shown in Figure6-3. To advance to the Main Menu and Mimic screen, press any control panel pushbutton once.
6.2.1S
tatus Indicators
The four symbo
ls on the right side of the control panel are status indicators. These colored lightemitting diode
(LED) lamps work with the alarm horn to let you know the operating status of the UPS.
Table6-1 describes the status indicators.
2
13
le 6-1. Status Indicators
Indicato
rStatusDescription
OnThe UPS is in Normal mode. The power moduleis supplying power to the critical load.
UPS Operating
Instructions
The fo
llowing paragraphs describe the UPS control panel, including controls andindicators, and how to monitor
UPS operation. The controlpanel (see Figure6-3) is locatedon the front door of the UPS.
Figure 6-3. UPS Control Panel
The control panel consists of:
l
A l
iquid crystal display (LCD) (1)
l
Menu na
vigation pushbutton switches (2)
l
A v
erticalcolumn of status indicators (3). See paragraph6.2.1.
The following paragraphs describe using the UPS control panelto monitor the UPS. See paragraph6.3 for useof the operational controls.
When the unit powers up, the screen displays the Eaton logo as shown in Figure6-3. To advance to the Main Menu and Mimic screen, press any control panel pushbutton once.
6.2.1S
tatus Indicators
The four symbo
ls on the right side of the control panel are status indicators. These colored lightemitting diode
(LED) lamps work with the alarm horn to let you know the operating status of the UPS.
Table6-1 describes the status indicators.
2
13
le 6-1. Status Indicators
Indicato
rStatusDescription
OnThe UPS is in Normal mode. The power moduleis supplying power to the critical load.
OffThe UPS is turned off.
OnThe UPS is in Battery mode. Because Battery modeis a normal condition of the UPS, the Normal indicator also
remains illuminated.
OnThe UPS is in Bypass mode. The critical load is supported by the bypass source. The Normal indicator is not
illuminated when the system is in Bypass mode.
OnThe UPS has an active alarm and requires immediateattention. The LCD shows the highest priority active alarms.
All alarms are accompanied by an audible horn. To silence the horn, pressany control panel pushbutton once. The Alarm indicator may be illuminated alongwith other indicators.
Gree
n
Yellow
Yellow
UPS Operating
Instructions
singthe Control Panel
The fo
llowing paragraphs describe the UPS control panel, including controls andindicators, and how to monitor
UPS operation. The controlpanel (see Figure6-3) is locatedon the front door of the UPS.
Figure 6-3. UPS Control Panel
The control panel consists of:
l
A l
iquid crystal display (LCD) (1)
l
Menu na
vigation pushbutton switches (2)
l
A v
erticalcolumn of status indicators (3). See paragraph6.2.1.
The following paragraphs describe using the UPS control panelto monitor the UPS. See paragraph6.3 for useof the operational controls.
When the unit powers up, the screen displays the Eaton logo as shown in Figure6-3. To advance to the Main Menu and Mimic screen, press any control panel pushbutton once.
6.2.1S
tatus Indicators
The four symbo
ls on the right side of the control panel are status indicators. These colored lightemitting diode
(LED) lamps work with the alarm horn to let you know the operating status of the UPS.
Table6-1 describes the status indicators.
2
13
le 6-1. Status Indicators
Indicato
rStatusDescription
OnThe UPS is in Normal mode. The power moduleis supplying power to the critical load.
OffThe UPS is turned off.
OnThe UPS is in Battery mode. Because Battery modeis a normal condition of the UPS, the Normal indicator also
remains illuminated.
OnThe UPS is in Bypass mode. The critical load is supported by the bypass source. The Normal indicator is not
illuminated when the system is in Bypass mode.
Gree
n
Yellow
UPS Operating
Instructions
singthe Control Panel
The fo
llowing paragraphs describe the UPS control panel, including controls andindicators, and how to monitor
UPS operation. The controlpanel (see Figure6-3) is locatedon the front door of the UPS.
Figure 6-3. UPS Control Panel
The control panel consists of:
l
A l
iquid crystal display (LCD) (1)
l
Menu na
vigation pushbutton switches (2)
l
A v
erticalcolumn of status indicators (3). See paragraph6.2.1.
The following paragraphs describe using the UPS control panelto monitor the UPS. See paragraph6.3 for useof the operational controls.
When the unit powers up, the screen displays the Eaton logo as shown in Figure6-3. To advance to the Main Menu and Mimic screen, press any control panel pushbutton once.
6.2.1S
tatus Indicators
The four symbols on the right side of the control panel are status indicators. These colored lightemitting diode (LED) lamps work with the alarm horn to let you know the operating status of the UPS.
Table6-1 describes the status indicators.
2
13
le 6-1. Status Indicators
Indicato
rStatusDescription
OnThe UPS is in Normal mode. The power moduleis supplying power to the critical load.
OffThe UPS is turned off.
OnThe UPS is in Battery mode. Because Battery modeis a normal condition of the UPS, the Normal indicator also
remains illuminated.
Gree
n
following paragraphs describe the UPS control panel, including controls and indicators, and how to monitor
The
UPS operation. The control panel (see Figure 6-3) is located on the front door of the UPS.
Table 6-1. Status Indicators
IndicatorStatusDescription
Green
Yellow
Yellow
Red
The control panel consists of:
• A liquid crystal display (LCD) (1)
• Menu navigation pushbutton switches (2)
• A vertical column of status indicators (3). See paragraph 6.2.1.
The following paragraphs describe using the UPS control panel to monitor the UPS. See paragraph 6.3 for use
of the operational controls.
When the unit powers up, the screen displays as shown in Figure 6-3. To advance to the Main Menu and Mimic
screen, press any control panel pushbutton once.
6.2.1 Status Indicators
four symbols on the right side of the control panel are status indicators. These colored light emitting diode
The
(LED) lamps work with the alarm horn to let you know the operating status of the UPS.
Table 6-1 describes the status indicators.
OnThe UPS
OffThe UPS is turned off.
OnThe UPS is in Battery mode. Because Battery mode is a normal condition of the UPS, the Normal indicator also
OnThe UPS is in Bypass mode. The critical load is supported by the bypass source. The Normal indicator is not
OnThe UPS has an active alarm and requires immediate attention. The LCD shows the highest priority active alarms. All
FlashingThere is a new UPS alarm condition. The indicator flashes until acknowledged by pressing any control panel
Figure 6-3. UPS Control Panel
is in Normal mode. The power module is supplying power to the critical load.
remains illuminated.
illuminated when the system is in Bypass mode.
alarms are accompanied by an audible horn. To silence the horn, press any control panel pushbutton once. The Alarm
indicator may be illuminated along with other indicators.
pushbutton once.
6-3
Page 78
6.2.2 System Events
When the UPS system is running in Normal mode, it continually monitors itself and the incoming utility power.
In Battery or Bypass modes, the UPS may issue alarms to let you know exactly what event caused the change
from Normal mode. System events on the UPS can be indicated by horns, lights, messages, or all three.
Select the EVENTS symbol from the menu bar on the main menu screen to display the active events screen.
This screen shows any currently active alarms, notices, or commands. This screen shows any currently active
alarms, notices, or commands. For more information on using the events screen, see paragraph 6.2.6.
• System Event Horns – The system event horn beeps to alert an operator that an event needing attention is
taking place. The horn cycles at a half-second rate.
• System Event Indicators – The status indicators on the UPS control panel work with the event horn to let the
operator know when the UPS is operating in any mode other than normal. Only the Normal mode indicator is
illuminated during normal UPS system operation. The other indicators illuminate to indicate alarms or events.
When an alarm occurs, first check these indicators to see what type of event has taken place. For
descriptions of the status indicators, see paragraph 6.2.1.
• System Event Messages – When a system event occurs, a message appears on the LCD in the UPS status
area. This message is also written to the Events Log and may be added to the History Log. The messages are
divided into four categories: alarms, notices, status, and commands.
6-4
Page 79
6.2.3 Using the LCD and Pushbuttons
The LCD on the control panel provides an operator interface with the UPS system. Figure 6-4 identifies the
display areas discussed in the following sections.
Alarm:
A
Alarm: Output
Alarm:Alarm:
Output AC
OutputOutput
AC Under
ACAC
Under Voltage
Voltage
UnderUnder
VoltageVoltage
B
C
MeterEventsHistoryControlsSetup
Figure 6-4. Parts of the LCD
A
The UPS status area automatically scrolls between the model number, current date and time, active
alarms, UPS status, load percent, and battery runtime for the UPS. The top line of display blinks while
scrolling when the system needs attention. Some notices and alarms may be accompanied by an audible
horn. To silence the horn, press any control panel pushbutton once. Shown is a typical alarm message. For
more information about alarms and notices, see paragraph 6.2.2.
The information area contains data about UPS status and operations.
B
The menu bar shows the symbols of the available screens. To select a screen, highlight the screen symbol
C
using the navigation pushbuttons and then press the RETURN pushbutton.
The navigation pushbuttons function depending on the screen displayed. Use the Up, Down, Left, and
D
Right pushbuttons to scroll through available screens and the Esc and Enter pushbuttons to select menu
screens and functions.
D
You can use the LCD and the pushbuttons to:
• Look at a log of UPS events (alarms, notices, and commands) (see paragraph 6.2.6)
• Monitor UPS operation (see paragraph 6.2.6)
• Set UPS parameters (see paragraph 6.2.6)
• Control UPS operation (see paragraphs 6.2.6 and 6.2.7)
After approximately 10 minutes, the display screen darkens. To restore the screen, press any pushbutton once.
6-5
Page 80
6.2.4 Using the Menu
The UPS menu bar allows you to display data in the information area to help you monitor and control UPS
operation. Table 6-2 shows the basic menu structure.
Table 6-2. Display Function Menu Map
Menu Option Description
METERSDisplays performance meters for the system or critical load.
EVENTSDisplays the list of Active System Events.
HISTORYDisplays a historical log of system events.
CONTROLSDisplays the System Control screen.
SETUPAllows you to set the date and time for the time stamp, set the display language, the unit name, and
meter subscripts, change the password, and view the firmware version numbers.
ESCReturns to Main Menu and Mimic screen from the Meters, Events, History, Controls, or Setup
screens. Returns to the main System Setup Level screen from a setup submenu.
Return arrow acknowledges or executes a command, or saves a setting.
Up and down arrows scroll through screens and lists or highlight settings.
Left and right arrows select or adjust settings displayed on the screen.
6.2.5 Mimic Screen
Figure 6-5 shows the Main Menu and Mimic screen. To select the Mimic screen from the Meters, Events,
History, Controls, or Setup screens, press the ESC pushbutton on the current menu bar.
The Mimic screen shows the internal components of the UPS cabinet and a real-time graphical representation
of the operating status of the system.
Figure 6-5. Main Menu and Mimic Screen
6-6
Page 81
6.2.6 Display Menu Operation
Table 6-3 describes the menu functions and how to use them.
Table 6-3. Display Menu Operation
FunctionSubfunctionOperation
Meters – UPSThe Meter screens show the UPS meter readings for the unit. The default voltage displayed on these
screens is phase-to-neutral. These can be changed to display the voltage phase-to-phase (AB, B-C, C-A). Use the LEFT or RIGHT arrow pushbuttons to select the METER symbol on the main menu
bar, to display the Meter screens. To scroll through the meter screens, press the UP or DOWN arrow
pushbutton. The current UPS readings are displayed in the information area of the screen.
Output – UPS
Input – UPS
Bypass
Battery – UPSThe Battery screen displays the battery voltage (Vdc) and the battery current (Idc).
EventsUse the LEFT or RIGHT arrow pushbuttons to select the EVENTS symbol on the main menu bar to display
HistoryUse the LEFT or RIGHT arrow pushbuttons to select the HISTORY symbol on the main menu bar to
Setup – UserFunction SelectionThis screen can be used to display user information and show the firmware versions installed. Use the
User InfoThe User Info screen provides the model, CTO and serial numbers of the UPS, the Output voltage,
AboutThe About screen provides the firmware version numbers installed on the UPS. Use the LEFT or RIGHT
Setup – Config
(System Level 1 Setup)
PasswordTo enter a password if required, use the LEFT or RIGHT arrow pushbutton to select the password
Function SelectionThis screen can be used to set the date and time, change the display language, enter a unit name,
ClockThe Clock Setup screen allows the selection of either month/day/year or day/month/year formats and
The Output screen shows output voltage (phase to neutral), output current (each phase), and frequency
being supplied by the UPS, as well as the kVA, kW, and power factor measurements.
The Input screen shows input voltage (phase to neutral), input current (each phase), and frequency of
the incoming utility source, as well as the kVA, kW, and power factor measurements.
The Bypass screen shows the bypass input voltage (phase to neutral), input current (each phase), and
frequency of the incoming utility source, as well as the kVA, kW, and power factor measurements.
the Events screens. A listing of all system events that are currently active is displayed. The most recent
event is listed first. As events clear, they are removed from the Events listing. To scroll through the
events, press the UP or DOWN arrow pushbutton.
display the History screen. The history Log lists up to 512 events in chronological order, with the most
recent event listed last (once 512 is reached, the earliest event is overwritten). The end of the log (the
most recent events) is displayed first; scroll upward to view older event listings. To scroll through the
events, press the UP or DOWN arrow pushbutton.
LEFT or RIGHT arrow pushbuttons to select the SETUP symbol on the main menu bar to display the
Setup screen. Use the UP or DOWN arrow pushbutton to highlight the function desired, then press the
RETURN pushbutton to display the function screen. See Figure 6-6 for a typical screen display.
frequency, and kVA rating, the input voltage rating, and the battery run time rating. Use the LEFT or
RIGHT arrow pushbuttons to select USER on the Setup menu bar. Use the UP or DOWN arrow
pushbutton. to select Info, then press the RETURN pushbutton to display the function screen. To return
to the System Setup screen, press the ESC pushbutton.
arrow pushbuttons to select USER on the Setup menu bar. Use the UP or DOWN arrow pushbutton. to
select About. To return to the System Setup screen, press the ESC pushbutton.
character position. Use the UP or DOWN arrow pushbutton to change the password character. Once the
password is entered, select DONE
menu screen is displayed. The default System Setup Level 1 password is 0101.
change the meter style, perform lamp test, clear the history log, and enter a password to access Level 1
functions. Use the LEFT or RIGHT arrow pushbuttons to select the SETUP symbol on the main menu bar
to display the Setup screen. Use the LEFT or RIGHT arrow pushbutton to
menu bar.
daylight savings time for display on the screen and for logging events in the Event and History Logs. Use
the UP or DOWN arrow pushbutton to select CLOCK to display the Clock screen. Use the UP or DOWN
arrow pushbutton to highlight the desired format, then press the RETURN pushbutton to display the Set
Date and Time screen. To return to the System Setup screen, press the ESC pushbutton.
Enter a password if required.
and then press the RETURN pushbutton. The System Setup Level 1
select CONFIG on the Setup
6-7
Page 82
Table 6-3. Display Menu Operation
FunctionSubfunctionOperation
Setup – Config
(System Level 1 Setup)
(continued)
Set Date and Time
MM/DD/YYYY
The Set Date and Time MM/DD/YYYY screen allows the internal date and time of the UPS to be set in
the month/day/year format. The date and time information is used for display on the screen and for
logging events in the Event and History Logs. Use the LEFT or RIGHT arrow pushbutton to highlight the
setting to be changed. Use the UP or DOWN arrow pushbutton to make the change. When finished
making changes, use the LEFT or RIGHT arrow pushbutton to highlight SAVE and the UP or DOWN
arrow pushbutton to select YES. To complete the save function and return to the System Setup screen,
select the RETURN arrow pushbutton.
Set Date and Time
DD/MM/YYYY
The Set Date and Time DD/MM/YYYY screen allows the internal date and time of the UPS to be set in
the day/month/year format. The date and time information is used for display on the screen and for
logging events in the Event and History Logs. Use the LEFT or RIGHT arrow pushbutton to highlight the
setting to be changed. Use the UP or DOWN arrow pushbutton to make the change. When finished
making changes, use the LEFT or RIGHT arrow pushbutton to highlight SAVE and the UP or DOWN
arrow pushbutton to select YES. To complete the save function and return to the System Setup screen,
select the RETURN arrow pushbutton.
LanguageThe Language Setup screen allows the display menu language to be selected. Use the UP or DOWN
arrow pushbutton to highlight Language, then press the RETURN pushbutton to display the Language
screen. Use the UP or DOWN arrow pushbutton to highlight the desired language, then press the
RETURN pushbutton. To return to the System Setup screen, press the ESC pushbutton.
Unit NameThe Unit Name Setup screen allows a unit name to be entered. Use the UP or DOWN arrow pushbutton
to highlight Unit Name, then press the RETURN pushbutton to display the Unit Name screen. Use the
LEFT or RIGHT arrow pushbutton to highlight the character to be changed. Use the UP or DOWN arrow
pushbutton to make the change. When finished making changes, use the LEFT or RIGHT arrow
pushbutton to highlight SAVE and the UP or DOWN arrow pushbutton to select YES. To complete the
save function and return to the System Setup screen, select the RETURN arrow pushbutton. To return to
the System Setup screen, press the ESC pushbutton.
MetersThe Meters Setup screen allows the Meters Screen display style to be selected. Use the UP or DOWN
arrow pushbutton to highlight Meters, then press the RETURN pushbutton to display the Meters
screen. Use the UP or DOWN arrow pushbutton. to highlight the desired style, then press the RETURN
pushbutton. To return to the System Setup screen, press the ESC pushbutton.
Lamp TestThe Lamp Test screen allows the control panel status lamps to be tested. Use the UP or DOWN arrow
pushbutton to highlight Lamp Test, then press the RETURN pushbutton to illuminate the status lamps.
To return to the System Setup screen, press the ESC pushbutton.
Clear LogThe Clear Log screen allows the history log to be cleared. Use the UP or DOWN arrow pushbutton to
highlight Clear Log, then press the RETURN pushbutton to clear the log. To return to the System Setup
screen, press the ESC pushbutton.
P/WThe P/W screen is used to change the System Setup Level 1 password. Use the UP or DOWN arrow
pushbutton to highlight P/W, then press the RETURN pushbutton to display the P/W screen. Use the
LEFT or RIGHT arrow pushbutton to select the password character position. Use the UP or DOWN arrow
pushbutton to change the password character. Once the password is entered, select CHANGE
press the RETURN pushbutton
.
and then
ControlsSee paragraph 6.2.7 for details.
6-8
Page 83
Status:
Status:Load
Status:Status:
Load Off
Off
LoadLoad
OffOff
Load
Load Off
Off
LoadLoad
OffOff
Load
Load Off
Off
LoadLoad
OffOff
UPS
UPSBattery
UPSUPS
BatteryUPM
BatteryBattery
Normal
Normal
NormalNormal
Bypass
Bypass
BypassBypass
UPM
UPMUPM
Figure 6-6. Typical Initial Setup Screen
6.2.7 System Controls
Select the CONTROLS symbol on the main menu bar, then press the RETURN pushbutton to display the
Controls screen. Normal operation, transfer to bypass, load off, and charger control commands are controlled
through this screen. In addition, the screen displays the current status of the UPS. Figure 6-7 shows the
System Control screen.
Use the or pushbutton to highlight the command screen desired, then press the RETURN pushbutton to
display the command menu screen.
Use the or pushbutton to highlight the command desired.
Table 6-4 describes the control functions and provides instructions to access and use the command menu
screens.
Table 6-5 lists the typical System Status Screen Messages that are displayed during UPS operation.
For detailed information about using the System Controls, see paragraph 6.3.
6-9
Page 84
Status:
LoadLoad
LoadOff
OffOff
Off
Load
LoadLoad
LoadOff
OffOff
Off
Normal
NormalNormal
Normal
Status:Load
Status:Status:
Table 6-4. Command Menu Operation
FunctionSubfunctionOperation
UPS Control
Commands
Normal ModeStarts the UPS in Standarad Normal mode or transfers the UPS to Standard Normal mode
Bypass ModeStarts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.
High-Efficiency (HE) ModeTransfers the UPS from Standard Normal mode to HE mode.
Battery Control
Commands
ChargerTurns the battery charger on.
RestingTurns the battery charger off.
Load Off
Off
LoadLoad
OffOff
Load
Load Off
Off
LoadLoad
OffOff
Load
Load Off
Off
LoadLoad
OffOff
HE:EnableDisable
Load
Load Off
Off
LoadLoad
OffOff
UPS
UPSBattery
UPSUPS
BatteryUPM
BatteryBattery
Normal
Normal
NormalNormal
Bypass
Bypass
BypassBypass
Bypass
Bypass
BypassBypass
Figure 6-7. Typical System Control Screen
Use the up or down arrow pushbutton to highlight the command function desired, then
press the RETURN pushbutton to execute the command or proceed to further command
screens.
from Bypass mode.
Transfers the UPS from HE mode to Standard Normal mode.
Use the up or down arrow pushbutton to highlight the command function desired, then
press the RETURN pushbutton to execute the command.
UPM
UPMUPM
Table 6-5. Typical System Status Messages
FunctionMessage
UPSLoad Off; Bypass; Online, HE
BypassOff; On; Available
ChargerCharger Resting; Charger
6-10
Page 85
6.3 Single UPS Operation
NOTE
•Note switch operation nomenclature: Open = O = Off, Closed = I = On.
•Refer to the
breaker location.
•The neutral switch here means the external neutral switch installed by user
(VFI 60000-80000TAP 3/3 BX
External Battery Cabinet Installation Manual
).
for EBC battery
6.3.1 Starting the UPS in Standard Normal Mode (Default Mode)
To start the UPS system:
1.Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (see Figure 6-1).
2.Verify that the input and output switches are open.
3.Verify the bypass input switch is open (Dual Input).
4.Verify that the maintenance bypass switch is open and the Neutral Switch is closed.
5.Close the UPS input feeder circuit breaker.
6.If the UPSs are wired for dual input, close the UPS Bypass input feeder circuit breaker.
7.Close the input switch.
8.If the UPSs are wired for dual input, close the bypass input switch.
9.If the UPS contains an output switch, close the output switch.
10. Make sure MBS cover is installed.
11. Close the door and secure the latch.
12. Close the external battery breakers.
13. Observe the UPS control panel display becoming active, indicating logic power.
14. Verify no alarms are active.
15. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
16. If not already selected, select UPS on the System Control screen.
1 7.On the UPS System Control screen, select the LOAD OFF NORMAL command, then press the
RETURN pushbutton.
18. If requested, enter the Level 1 password. Default password is 1111.
After entering password, UPS will transfer to bypass first and the Bypass LED will illuminate.
The rectifier and inverter turn on. The inverter continues to ramp up to full voltage.
Once the inverter reaches full voltage, the UPS output contactor closes and the static switch turns off.
Power is now supplied to the critical load in Standard Normal mode. It takes approximately one minute for
the UPS to achieve Standard Normal mode.
The Normal status indicator is illuminated.
6-11
Page 86
6.3.2 Starting the UPS in Bypass Mode
If the inverter output of the UPS is not available and the critical load needs to be energised:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
To start the UPS system:
1.Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (Figure 6-1).
2.Verify that the input and output switches are open.
3.Verify that the bypass input switch is open (Dual Input). .
4.Verify that the bypass switch is open and the Neutral Switch is closed.
5.Close the UPS input feeder circuit breaker.
6.If the UPSs are wired for dual input, close the UPS Bypass input feeder circuit breaker.
7.Close the input switch.
8.If the UPS contains two input sources, close the bypass input switch.
9.Close the output switch.
10. Make sure MBS cover is installed.
11. Close the door and secure the latch.
12. Close the external battery breakers.
13. Observe the UPS control panel display becoming active, indicating logic power.
14. Verify no alarms are active.
15. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
16. If not already selected, select UPS on the System Control screen.
1 7.On the UPS System Control screen, select the LOAD OFF BYPASS command, then press the RETURN
pushbutton.
6.3.3 Transfer from Normal to Bypass Mode
To transfer the critical load to Bypass mode:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1.Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2.If not already selected, select UPS on the System Control screen.
3.On the UPS System Control screen, select the NORMAL BYPASS command, then press the RETURN
pushbutton.
The UPS transfers to Bypass mode.
The BYPASS status indicator is illuminated. The power module remains on.
6-12
Page 87
WARNING
Power is present inside the UPS cabinet.
6.3.4 Transfer from Bypass to Normal Mode
To transfer the critical load to Normal mode:
1.Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2.If not already selected, select UPS on the System Control screen.
3.On the UPS System Control screen, select the BYPASS NORMAL command, then press the RETURN
pushbutton.
The UPS transfers to Normal mode. If the power module is not available, the system remains on bypass
and an alarm sounds.
The NORMAL status indicator is illuminated.
6.3.5 Transfer from Standard Normal Mode to HE mode
To transfer the load to HE mode:
1.Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2.If not already selected, select UPS on the System Control screen.
3.On the UPS System Control screen, select the HE: DISABLE ENABLE command, then press the
RETURN pushbutton.
After battery is fully charged, the UPS transfers to HE mode if no abnormal power conditions are detected.
If abnormal power conditions are detected, the UPS will wait and transfer to HE mode when conditions are
cleared.
The NORMAL status indicator is illuminated.
6.3.6 Transfer from HE Mode to Standard Normal Mode
To transfer the load to Standard Normal mode:
1.Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2.If not already selected, select UPS on the System Control screen.
3.On the UPS System Control screen, select the HE: ENABLE DISABLE command, then press the
RETURN pushbutton.
The UPS transfers to Standard Normal mode.
The NORMAL status indicator is illuminated.
6-13
Page 88
6.3.7 Transfer from Normal Mode to Internal Maintenance Bypass
To transfer the load to maintenance bypass:
1.On the UPS System Control screen, select the NORMAL BYPASS command, then press the RETURN
pushbutton.
2.Loosen the screws that fix the cover over the maintenance bypass switch. This action will signal the UPS
to transfer to static bypass. Refer to Figure 6-2 for switch arrangement.
3.Verify that the LCD/LED display indicates the UPS is in Bypass mode.
4.Close the Maintenance Bypass switch.
5.Open the Bypass Input and Output switches separately (Dual Input).
6.Open the Neutral switch.
NOTE
•The Neutral Switch should remain closed unless operated by a service technician.
•Maintenance Bypass operate must be performed by an authorized Service Engineer.
WARNING
Power is present inside the UPS cabinet.
6.3.8 Transfer from Internal Maintenance Bypass to Normal Mode
To transfer the load to Normal mode:
1.Close the Neutral switch, slide the cover plate right and tighten the screws.
2.Close the Input and Bypass input switches.
3.Command the UPS to run in Bypass mode via the Control panel.
4.Verify that the LCD/LED display indicates the UPS is in Bypass mode.
5.Close the Output switch.
6.Open the Maintenance Bypass switch, slide the cover plate left and tighten the screws.
7.Command the UPS to transfer to Normal mode via the control panel.
6-14
Page 89
6.3.9 UPS and Critical Load Shutdown
To perform maintenance or service on the critical load, shut down power to the load:
1.Turn off all equipment that is being powered by the UPS.
2.Perform the LOAD OFF procedure in paragraph 6.3.12.
The output and bypass backfeed relay (if fitted) open, and the power module is turned off.
3.Perform the battery charger off procedure in paragraph 6.3.10.
The input and battery relay open.
WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.
4.Open the UPS Input switch.
5.If the UPSs are wired for dual input, open the Bypass input switch.
6.Open the Maintenance Bypass switch.
7.Open the UPS input and bypass feeder circuit breakers.
8.Open all external battery breakers.
6.3.10 Charger Control
To turn the battery charger on:
1.Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2.Select Battery on the System Control screen.
3.On the Battery System Control screen, select the RESTING CHARGING command, then press the
RETURN pushbutton.
To turn the battery charger off:
1.Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2.Select Battery on the System Control screen.
3.On the Battery System Control screen, select the CHARGING RESTING command, then press the
RETURN pushbutton.
6-15
Page 90
6.3.11 Battery Test
NOTE 1
NOTE 2
To start the battery test:
1.Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2.Select Battery on the System Control screen.
3.On the Battery System Control screen, select the RESTING TESTING command, then press the
RETURN pushbutton.
This UPS has a user initiated battery test intended to determine if the batteries are
able to support the load.
The battery test is only able to be initiated when the battery is fully charged. This
normally occurs within 72 hours of the start of a charging cycle. The command will
not be shown if the test is not able to be run.
6.3.12 Using the UPS LOAD OFF Command
A UPS Load Off is initiated by the Load Off command on the UPS Control screen. The UPS LOAD OFF controls
the UPS output by powering down the UPS and de-energising the critical load.
The UPS (including Bypass) remains off until restarted.
To use the LOAD OFF command:
1.Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2.Select UPS on the System Control screen.
3.On the UPS System Control screen, select the NORMAL LOAD OFF or BYPASS LOAD OFF
command depending on the UPS mode, then press the RETURN pushbutton.
The Verify Action screen is displayed, providing a choice to proceed or abort the shutdown.
CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You
should use this feature only when you want to de-energise the critical load.
4.Select Yes or No, then press the RETURN pushbutton.
Selecting Yes will immediately shut down the UPS and de-energising the critical load. Selecting No will
abort the shutdown.
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
5.To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure in paragraph 6.3.1 or
6.3.2.
WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.
6-16
Page 91
6.3.13 Using the Remote Emergency Power-off Switch
A UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this
switch to control the UPS output. The REPO switch de-energises the critical load and powers down the UPS
immediately, without asking for verification.
The UPS, including Bypass, remains off until restarted.
CAUTION
All power to the critical load is lost when the REPO switch is activated in the following step. You
should use this feature only when you want to de-energise the critical load.
NOTE
The REPO switch is to be supplied by the user. refer to the operating instructions
provided with the switch.
CAUTION
Do not attempt to restart the system after the REPO until the cause of the shutdown has been
identified and cleared.
1.Restart the UPS by following the procedure in paragraph 6.3.1 or 6.3.2.
6-17
Page 92
6.4 Multiple UPS Parallel Operation
The paragraphs in this section provide operating instructions for a UPS system containing multiple UPSs.
NOTE 1
NOTE 2
Refer to the
EBC battery breaker location.
Start and control system wide function from UPS 1.
External Battery Cabinet Installation Manual
listed in paragraph 1.8 for
6.4.1 Starting the Parallel UPS in Standard Normal Mode (Default Mode)
To start the UPS system:
1.Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (see Figure 6-1).
2.Verify that all input breakers are open.
3.Verify that the maintenance bypass breakers are open.
4.Close all Module Output Breakers (MOBs).
5.Close all UPS input feeder circuit breakers.
6.If the UPSs are wired for dual input, close all of the UPSs Bypass input feeder circuit breakers.
7.Close all input breakers.
8.If the UPSs are wired for dual input, close all bypass input switches.
9.Make sure MBS cover is installed.
10. Close the door and secure the latch.
11. Close all external battery breakers.
12. Observe the UPS control panel display becoming active, indicating logic power.
13. Verify no alarms are active.
14. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
15. If not already selected, select UPS on the System Control screen.
16. On the UPS System Control screen, select the LOAD OFF NORMAL command, then press the
RETURN pushbutton.
1 7.If requested, enter the Level 1 password. Default password is 1111.
After entering password, UPS will transfer to bypass first and the Bypass LED will illuminate.
All rectifiers and inverters turn on. The inverters continue to ramp up to full voltage.
Once all inverters reach full voltage, the UPS output contactor closes and the static switch turns off. Power
is now supplied to the critical load in Standard Normal mode. It takes approximately one minute for the
UPS to achieve Standard Normal mode.
The Normal status indicator is illuminated.
6-18
Page 93
6.4.2 Starting the Parallel UPS in Bypass Mode
If the inverter output of the parallel UPS is not available and the critical load needs to be energised:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1.Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (Figure 6-1).
2.Verify that all input breaker are open.
3.Verify that the Maintenance bypass switches are open.
4.Close all Module Output Breakers (MOBs).
5.Close all UPS input feeder circuit breakers.
6.If the UPSs are wired for dual input, close all of the UPS Bypass input feeder circuit breakers.
7.Close all input breakers.
8.If the UPSs are wired for dual input, close all of the bypass input switches.
9.Make sure MBS cover is installed.
10. Close the door and secure the latch.
11. Close the external battery breakers.
11. Observe the UPS control panel display becoming active, indicating logic power.
12. Verify no alarms are active.
13. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
14. If not already selected, select UPS on the System Control screen.
15. On the UPS System Control screen, select the LOAD OFF BYPASS command, then press the RETURN
pushbutton.
The critical load is immediately supplied by the bypass source, in Bypass mode from all UPSs.
The BYPASS status indicator is illuminated.
6-19
Page 94
6.4.3 Transfer from Normal to Bypass Mode
To transfer the critical load to Bypass mode:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1.Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2.If not already selected, select UPS on the System Control screen.
3.On the UPS System Control screen, select the NORMAL BYPASS command, then press the RETURN
pushbutton.
All of the UPSs transfer to Bypass mode.
The BYPASS status indicator is illuminated. The power module remains on.
WARNING
Power is present inside the UPS cabinet.
6.4.4 Transfer from Bypass to Normal Mode
To transfer the critical load to Normal mode:
1.Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2.If not already selected, select UPS on the System Control screen.
3.On the UPS System Control screen, select the BYPASS NORMAL command, then press the RETURN
pushbutton.
All of the UPSs transfer to Normal mode. If the power module is not available, the system remains on
bypass and an alarm sounds.
The NORMAL status indicator is illuminated.
WARNING
Power is present inside the UPS cabinet.
6-20
Page 95
6.4.5 Single UPS Shutdown
To shut down the UPS:
1.Open the MOB for the UPS being shut down.
2.Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
3.If not already selected, select UPS on the System Control screen.
4.On the UPS System Control screen, select the NORMAL UPS OFF command, then press the RETURN
pushbutton.
The output and bypass backfeed relay open, and the power module is turned off on the UPS being shut
down.
Logic power remains on.
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
5.Open the UPS input and the bypass feeder circuit breakers for the UPS being shut down.
6.If EBCs are installed, open all battery breakers
The UPS is now completely shut down.
6.4.6 Single UPS Restart
To restart a single UPS from a shutdown state:
1.Close the MOB for the UPS being restarted.
2.Close the UPS input and bypass feeder circuit breakers for the UPS being restarted.
3.Close the input switch.
4.If the UPSs are wired for dual input, close the bypass input switch.
5.Close the output switch.
6.Close the external battery breakers.
7.On the UPS being restarted, observe the UPS control panel display becoming active, indicating logic
power.
8.Verify no alarms are active on the UPS being restarted.
9.On the UPS being restarted, select the CONTROLS symbol on the main menu bar. The System Control
screen is displayed.
10. If not already selected, select UPS on the System Control screen.
11. On the UPS System Control screen, select the UPS OFF NORMAL command, then press the RETURN
pushbutton.
12. If requested, enter the Level 1 password. Default password is 1111.
The rectifier and inverter turn on. The inverter continues to ramp up to full voltage.
Once the inverter reaches full voltage, the UPS output contactor closes and the static switch turns off.
Power is now supplied to the critical load in Standard Normal mode along with the other UPSs online. It
takes approximately one minute for the UPS to achieve Standard Normal mode.
The Normal status indicator is illuminated.
6-21
Page 96
6.4.7 UPS and Critical Load Shutdown
To perform maintenance or service on the critical load, shut down power to the load:
1.Turn off all equipment that is being powered by the UPS parallel system.
2.Transfer the UPSs to bypass by performing the procedure in paragraph 6.4.3.
3.Perform the LOAD OFF procedure in paragraph 6.4.10.
The output and bypass backfeed contactors open, and the power module is turned off.
4.Perform the battery charger off procedure in paragraph 6.4.8 for each UPS.
The input and battery relay open.
WARNING
Power is present inside the UPS cabinets after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.
5.Open all input switches.
6.Open all of the maintenance bypass switches.
7.Open the output switch.
8.Open all of the MOBs.
9.Open all of the UPSs input and bypass feeder circuit breakers.
10. Open all external battery breakers
6.4.8 Charger Control
To turn an individual UPS battery charger on:
1.Select the CONTROLS symbol on the main menu bar on the UPS requiring the charger to be turned on. The
System Control screen is displayed.
2.Select Battery on the System Control screen
3.On the Battery System Control screen, select the RESTING CHARGING command, then press the
RETURN pushbutton.
To turn an individual UPS battery charger off:
1.Select the CONTROLS symbol on the main menu bar on the UPS requiring the charger to be turned off. The
System Control screen is displayed.
2.Select Battery on the System Control screen.
3.On the Battery System Control screen, select the CHARGING RESTING command, then press the
RETURN pushbutton.
6-22
Page 97
6.4.9 Battery Test
NOTE 1
NOTE 2
To start an individual UPS battery test:
1.Select the CONTROLS symbol on the main menu bar on the UPS to be tested. The System Control screen
is displayed.
2.Select Battery on the System Control screen.
3.On the Battery System Control screen, select the RESTING TESTING command, then press the
RETURN pushbutton.
This UPS has a user initiated battery test intended to determine if the batteries are
able to support the load.
The battery test is only able to be initiated when the battery is fully charged. This
normally occurs within 72 hours of the start of a charging cycle. The command will
not be shown if the test is not able to be run.
6.4.10 Using the UPS LOAD OFF Command
A UPS Load Off is initiated by the Load Off command on the UPS Control screen. The UPS LOAD OFF controls
the UPSs output by powering down the UPS and de-energising the critical load.
The UPSs (including Bypass) remains off until restarted.
To use the LOAD OFF command:
1.Select the CONTROLS symbol on the main menu bar on the UPS to be shut down. The System Control
screen is displayed.
2.Select UPS on the System Control screen.
3.On the UPS System Control screen, select the NORMAL LOAD OFF or BYPASS LOAD OFF
command depending on the UPS mode, then press the RETURN pushbutton.
The Verify Action screen is displayed, providing a choice to proceed or abort the shutdown.
CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You
should use this feature only when you want to de-energise the critical load.
4.Select Yes or no, then press the RETURN pushbutton.
Selecting Yes will immediately shut down the UPS and de-energising the critical load. Selecting No will
abort the shutdown.
5.If another UPS is to be shut down, proceed to that UPS and repeat Step 1 through Step 4.
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
6.To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure in paragraph 6.4.1 or
6.4.2.
6-23
Page 98
WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.
6.4.11 Using the Remote Emergency Power-off Switch
A UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this
switch to control the UPS output. The REPO switch de-energises the critical load and powers down the UPS
immediately, without asking for verification.
The UPSs, including Bypass, remains off until restarted.
CAUTION
All power to the critical load is lost when the REPO switch is activated in the following step. You
should use this feature only when you want to de-energise the critical load.
NOTE
The REPO switch is to be supplied by the user. refer to the operating instructions
provided with the switch.
CAUTION
Do not attempt to restart the system after the REPO until the cause of the shutdown has been
identified and cleared.
1.Restart the UPS by following the procedure in paragraph 6.4.1 or 6.4.2.
WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.
6-24
Page 99
Chapter 7 Communication
Network ManagementCard
This chapter describes the communication features of the VFI 20000-80000TAP 3/3 BE/BI/BX UPS.
wiring information, see paragraph 3.2.3 and paragraph 4.4. For location of the customer interface panel and
terminals, see Figure 4-6 and Figure 4-7.
7.1 Mini-Slot Cards
The VFI 20000-80000TAP 3/3 BE/BI/BX UPS has two standard, factory-installed Mini-Slot communication bays.
See Figure 4-7 for bay locations. The UPS is compatible with the following Mini-Slot cards (see Figure 7-1):
• Network Management Card and Modbus/Jbus – provides remote monitoring through a Web browser
interface, e-mail, and a network management system (NMS) using SNMP and connects to a twisted-pair
Ethernet (10/100BaseT) network. The card also provides direct integration of UPS information (meters and
status) to a Building Management System (BMS) using the Modbus RTU protocol.
• Network Management Card – provides remote monitoring through a Web browser interface, e-mail, and a
network management system (NMS) using SNMP and connects to a twisted-pair Ethernet (10/100BaseT)
network.
• Management Card Contact and RS232 / Serial – two types of interfaces via a DB9 connector are available
with this card. Dry contact mode provides a simple way to transmit UPS information to an alarm system,
PLC, or computer system via dry relay contacts. The transmitted information is load powered, load on bypass,
load on battery, load on utility, battery fault, and low battery. RS232 mode provides an RS232 interface for
connection to a PC or to a UPS Control display unit. Jumpers are used to select the interface (contacts or
RS232).
LAN and telephone drops for use with Mini-Slot connectivity cards must be supplied by facility planners or the
customer.
For terminal
For installation and setup of a Mini-Slot card, contact an service representative (see paragraph 1.8). Refer to the
manual supplied with the Mini-Slot card for user instructions.
Management Card Contact and
RS232/Serial
7.2 Building Alarm Monitoring
This standard feature lets you connect the UPS to your building alarms, such as smoke detectors or
overtemperature alarms. The customer interface terminals for external connections are located inside the UPS.
Use twisted-pair wires for each alarm input and common.
The building alarms can be programmed to display the alarm functional name.
Network Management Card
Network Management Card and
Modbus/Jbus
Figure 7-1. Optional Mini-Slot Cards
7-1
Page 100
This page intentionally left blank.
7-2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.