4-1. Warning status ........................................................................................................................................... 35
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and
read carefully the following instructions before installing the unit. Do not operate this unit before reading through
all safety information and operating instructions carefully.
1-1. Transportation and Storage
⚠ Please transport the UPS system only in the original package to protect against shock and impact.
⚠ The UPS must be stored in the room where it is ventilated and dry.
1-2. Preparation
⚠ Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS
system must be absolutely dry before being installed. Please allow at least two hours for the UPS system
to acclimate the environment.
⚠ Do not install the UPS system near water or in moist environments.
⚠ Do not install the UPS system where it would be exposed to direct sunlight or nearby heater.
⚠ Do not block ventilation holes in the UPS housing.
⚠ Do not operate unit in dusted environment.
1-3. Installation
⚠ Do not connect appliances or devices which would overload the UPS (e.g. big motor-type equipment)).
⚠ Place cables in such a way that no one can step on or trip over them.
⚠ Do not block air vents in the housing of UPS. The UPS must be installed in a location with good
ventilation. Ensure enough space on each side for ventilation.
⚠ UPS has provided earthed terminal, in the final installed system configuration, equipotential earth
bonding to the external UPS battery cabinets.
⚠ The UPS can be installed only by qualified maintenance personnel.
⚠ An appropriate disconnect device as short-circuit backup protection should be provided in the building
wiring installation.
⚠ An integral single emergency switching device which prevents further supply to the load by the UPS in
any mode of operation should be provided in the building wiring installation.
⚠ Connect the earth before connecting to the building wiring terminal.
⚠ Installation and Wiring must be performed in accordance with the local electrical laws and regulations.
1-4. Connection Warnings
2
Page 4
•There is no standard backfeed protection inside, please isolate the UPS before working according to this
* Safety
* EMI
*EMS
dditional measures may be needed to
prevent disturbances.
Before working on this circuit
Risk of Voltage Backfeed
circuit. The isolation device must be able to carry the UPS input current.
• This UPS should be connected with TN grounding system.
• The input power supply rating must be in accordance with your equipment (i.e., 3-phase or single-phase.) It
also must be suitably grounded.
•Use of this equipment in life support applications where failure of this equipment can reasonably be expected
to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not
recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen
or nitrous oxide.
• Connect your UPS power module’s grounding terminal to a grounding electrode conductor.
• The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not
connected to an AC supply.
• Isolate Uninterruptible Power System (UPS)
• Then check for Hazardous Voltage between all
terminals including the protective earth.
1-5. Operation
⚠ Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time
since this would cancel the protective earth of the UPS system and of all connected loads.
⚠ If the external battery cabinet is connected, the UPS output Anderson connector may be electrically live
even if the UPS system is not connected to the building wiring outlet.
⚠ In order to fully disconnect the UPS system, first press the “OFF” button and then disconnect the mains.
⚠ Ensure that no liquid or other foreign objects can enter into the UPS system.
⚠ The UPS can be operated by any individuals with no previous experience.
Power-frequency Magnetic field.............. :IEC/EN 61000-4-8 Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the second
environment-installation restrictions or a
3
Page 5
2. Installation
Model
Type
VFI 10K CPH 3/3
3-phase in/3-phase out 400V online UPS
VFI 10K CPH 3/1
3-phase in/single phase out online UPS
Battery serial PCB, Brass
Fixing nut X 8, M6 screw X 10,
Parallel cable
sharing cable
Tower stands
Fixing nut X 8, M6 screw X 10,
M3 screw X 2
13pcs for 3-1 10K
There are two types of models in this series:
VFI CPH Series can be used as stand-alone rack unit (fits 19” cabinet), it is then connected with terminal input and
output on the back of the unit. It might also be used as parallel system with hot-swappable modularity up to
100kW (10 modules/units). This manual covers but type of installations.
2-1. Unpacking and Inspection
Content of the UPS box:
UPS Manual USB cable RS-232 cable Mounting ears
Slides
and Current
Content of the Battery Pack box:
including feet and
short extensions
Parallel busbars
10pcs for 2-2 6K;
12pcs for 3-3 10K;
M6 stud X 2, M4 screw X 4,
Battery pack Manual Mounting ears
Slides
4 long extensions Parallel busbars
spacer, Insulator paper,
Long busbars
(Not apply for the model
with BP 192V
battery pack)
M6 stud X 2, M4 screw X 4,
M3 screw X 2
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged during
transportation. Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or
lacking of some parts. Please keep the original package in a safe place for future use.
4
Page 6
2-2. Rear Panel View
6-2
6-3
6
-4
6-1
Input/ Output Terminal
7-1
7-2
7-3
7-4
7-5
7-6
7-7
7-8
7-9
3-3 10K
I/P-R
I/P-N
I/P-S
I/P-T
PE
OP-L1
OP-L2
OP-L3
OP-N
3-1 10K
I/P-R
I/P-N
I/P-S
I/P-T
PE
OP-L
OP-L
OP-N
OP-N
agram 1: rear panel
Di
agram 2: Battery pack rear panel
Di
1.EPO (Emergency Power Off) connector
2.USB communication port
3.Intelligent card
4.Parallel port (for parallel function)
5.Current sharing port (for parallel function)
6.Battery terminal
1.BAT + (positive polarity)
2.BAT N (neutral polarity – middle of the DC string)
3.BAT – (negative polarity)
4.R – bypass (only for VFI 10K CPH 3/1 version)
7.Input/ Output terminal
Model
2-3. Rack/Tower Installation
2-3-1. Tower (vertical) Installation
The UPS module is shipped with two sets of feet and 2 short extensions that can be used to install the UPS
vertically. Battery pack is shipped with 4 long extensions that can be used to install UPS module and one battery
pack.
5
Page 7
Installing UPS module
Assemble two feet and one short extension as
one tower stand shown in step 1. Align the two
Installing UPS module and one battery pack or
Assemble two feet and two long extensions as
If two battery packs are installed with UPS
s for
Step 1 Step 2
stands approximately 35cm apart in step 2. Then,
put UPS module in the stands as shown in step 3.
NOTE: Make sure the connector box is firmly
attached to UPS back panel with screws.
Step 1 Step 2
Step 3
two battery packs
one tower stand shown in step 1. Align the two
stands approximately 35cm apart in step 2. Then,
put UPS module and battery pack in the stands as
shown in step 3.
together, please use three long extension
each tower stand. Then, put UPS module and two
battery packs in the stands as shown in step 4.
Step 3 Step 4
6
Page 8
2-3-2. Rack Installation
M4 screws
Slide-bone
Please follow below steps to mount UPS/battery pack into 19” rack or rack enclosure.
Step 1: Insert 8 pieces of fixing nuts into the following locations to fix rail sliders and UPS.
Step 2: Use 4 pieces of M6 screws to mount rail sliders into front of the chassis.
Step 3: Adjust the distance of rail sliders by pulling the other end. It should be the same depth of rack chassis. For
example, if depth of rack chassis is 900mm, please pull the length of rail sliders in 900mm. Then, use 2
pieces of M6 screws and 2 pieces of M6 studs to the mount rail sliders into the back of the chassis.
Step 4: Fixing the slide-bone into the middle of two sliders with 4 pieces of M4 screws. See chart below.
Step 5: Disassemble the connector box from UPS by removing 4 screws.
Step 6: Fixing the connector box with slide-bone by 2 pieces of M3 screws. See chart below.
7
Page 9
Connector box
Step 7: Attach mounting ears to the side mounting holes of UPS module by using the screws provided and the
ears should face forward as following picture show.
Step 8: Put the UPS module on the sliders and push it toward connector box. Please make sure hot-swappable
connectors on connector box are firmly plugged into the UPS module. Fasten the UPS module to the
chassis with screws on the mounting ears.
Step 9: Install the battery pack with the same procedure as UPS module.
2-4. Single UPS Installation
Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the
following instructions by professional personnel.
1) Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the
hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the
8
Page 10
UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
Input
Output
Battery
Ground
12 AWG
12 AWG
12 AWG
12 AWG
Input/ Output terminal
Parallel cable
Parallel busbars
Current sharing cable
Parallel port
Current sharing port
Battery terminal
2) Switch off the mains switch in the building before installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare wires based on the following table:
NOTE 1: The cable for 10K should be able to withstand over 30A current. It is recommended to use 12AWG
or thicker wire for safety and efficiency.
NOTE 2: The selections for color of wires should be followed by the local electrical laws and regulations.
Warning:
● For external battery pack, make sure a DC breaker or other protection device between UPS and external
battery pack is installed. If not, please install it carefully. Switch off the battery breaker before installation.
NOTE: Set the battery pack breaker in “OFF” position and then install the battery pack.
● Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the
numbers of the battery pack, please make sure you modify the setting simultaneously. The connection with
wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the battery pack is
correct.
● Pay highly attention to the polarity marking on external battery connector and make sure the correct battery
polarity is connected. Wrong connection may cause permanent damage of the UPS.
● Make sure the protective earth ground wiring is correct. The wire current spec, color, position, connection
and conductance reliability should be checked carefully.
● Make sure the utility input & output wiring is correct. The wire current spec, color, position, connection and
conductance reliability should be checked carefully. Make sure the L/N site is correct, not reverse and
short-circuited.
2-5. Parallel UPS Installation
For parallel UPS system installation, please follow Section 2-3-2 Rack Installation to install required UPS modules
into 19” rack or rack enclosure first. Then, connect the parallel busbars (with black sleeve), parallel cable and
current sharing cable on the connector box of the top two UPSs as below chart. Apply the same connection way if
more parallel modules are required.
NOTE: For the detailed connection for parallel busbars in each terminal, please refer to the terminal
configurations on 2-2.
2-6. Battery Pack Installation
There are three types of battery pack. Please refer to the following configuration for each UPS model.
9
Page 11
Model Battery voltage
Battery
quantity
Applicable battery
capacity
Minimum required QTY
per UPS module
Battery terminal
UPS
Battery Pack
M6 screw
Battery serial PCB
Back PCB
BP H240R-20x9Ah 120V 20 7Ah/9Ah/10Ah 2*
BP H240R-32x5Ah ±192V 32 5Ah
1
* installed in pairs – positive and negative half-string
2-6-1 Single Battery Pack Connection
Connect the battery terminals of battery pack and UPS module with parallel busbars as below chart.
2-6-2 Serial Connection for Battery Packs
Before wiring connection, please follow Section 2-3-2 Rack Installation to install required battery packs into 19”
rack or rack enclosure first. For the serial connection for multiple battery packs, please follow below steps.
Step 1: Fix the battery serial PCB to the back PCB of battery packs with 6 screws.
Step 2: Remove 3 pieces of original screws on battery terminals of UPS and fix brass spacer instead. Insert
insulator papers to each battery terminal. Then, screw one end of the long busbars to the brass spacer on the UPS
module and the other end to terminal of serial PCB on battery pack as below chart.
10
Page 12
UPS
Battery Pack
Battery Pack
Brass spacer
Battery serial PCB
Insulator paper
Long busbars
Back PCB
Back PCB
Back PCB
The wiring connection for parallel UPS system with serial connection of battery packs is shown as below.
UPS
Battery Pack
Battery Pack
Brass spacer
Battery serial PCB
Insulator paper
Long busbars
Back PCB
Back PCB
Back PCB
UPS
Back PCB
NOTE: For the detailed connection for parallel busbars in each terminal, please refer to the terminal
configurations on 2-2.
11
Page 13
3. Operations
3-1. Operation Mode
This modular UPS is on-line, double-conversion and reverse-transfer UPS that permits operation in the following
modes:
Power On Mode
Standby Mode
Bypass Mode
Line Mode
Battery Mode
Battery Test Mode
Fault Mode
CVCF Mode
ECO Mode
Shutdown Mode
3-1-1. Power On Mode
Upon connecting to utility input power or UPS cold start, the UPS is in Power On mode. The load is not powered
under this mode.
Power On Mode Diagram
3-1-2. Standby Mode
Upon connecting to utility input power, the UPS is in Standby mode before UPS is turned on (if BYPASS enable
setting is Disabled), and charger function will be active when the battery is present. The load is not powered
under this mode.
Standby Mode Diagram
12
Page 14
3-1-3. Bypass Mode
Upon connecting to utility input power, the UPS is in Bypass mode before UPS is turned on (if BYPASS enable
setting is Enabled), and charger function will be active when battery is present.
After UPS has been turned on, if the UPS encounters abnormal situations (over-temperature, overload …, etc.),
UPS will perform the load from the inverter to the bypass source with no interruption. If the transference is
caused by a recoverable reason, the UPS will turn back to line mode when abnormal situation is solved.
Bypass Mode Diagram
3-1-4. Line Mode
In Line Mode, the rectifier derives power from the utility power, supplies DC power to the inverter and the
charger charges the battery. The inverter filters the DC power and converts it into pure and stable AC power to
the load.
Line Mode Diagram
3-1-5. Battery Mode
The UPS automatically transfers to battery mode if the utility power fails. There is no interruption in power to the
critical load upon failure.
In battery mode, the rectifier derives power from the battery and supplies DC power to the inverter. The inverter
filters the DC power and converts it into pure and stable AC power to the load.
13
Page 15
Battery Mode Diagram
3-1-6. Battery Test M o de
Users can manually operate UPS to battery test mode. There is no interruption in power to the load. If the test is
completed or battery fails, the UPS will return to Line mode or CVCF mode (if CVCF mode is enabled).
In battery test mode, the rectifier derives power from the battery and supplies DC power to the inverter. The
inverter filters the DC power and converts it into pure and stable AC power to the load.
Battery Test Mode Diagram
3-1-7. Fault Mode
The UPS transfers to fault mode if the UPS fails.
In fault mode, the charger function will be off and the load is not powered under this mode.
Fault Mode Diagram
14
Page 16
3-1-8. CVCF Mode
The CVCF mode is enabled through the LCD setting menu. The output frequency will be fixed at 50Hz or 60Hz
according to setting of “Freq”. In CVCF mode, the rectifier derives power from the utility power, supplies DC
power to the inverter and the charger charges the battery. The inverter filters the DC power and converts it into
pure and stable AC power to the load.
CVCF Mode Diagram
3-1-9. ECO Mode
The ECO mode is enabled through the LCD setting menu. In ECO mode, the load is powered by bypass when the
bypass voltage and frequency are within the acceptable ranges. If the bypass voltage or frequency is out of range,
the UPS will transfer the power source of load from bypass to inverter. In order to shorten the transfer time, the
rectifier and inverter are working when the UPS is in ECO mode.
ECO Mode Diagram
3-1-10. Shutdown Mode
When the UPS is in the off state and the utility power source is absent, the UPS will enter into shutdown mode.
When the UPS enters this mode, it is going to shut off the control power of UPS. The rectifier, charger and
inverter are all in off state.
15
Page 17
Shutdown Mode Diagram
No.
Item
Description
The UPS module uses forced convection cooling by these fans. Cooling air enters the
the rear of the module. Please do not block the ventilation area.
2
Battery Start Button
When AC input is not present, use this button to start battery power for UPS.
There is LCD display on the UPS module. It can show the UPS information and the
slave UPS information when operating in parallel.
There are four function keys in the UPS module. They can control and monitor the
single UPS module. Please refer to function key table for the details.
There are four LED indicators to show UPS working status. Please refer to LED
indicator table for the details.
3-2. UPS Module Introduction
3-2-1. UPS Module
The capacity of each UPS module is 10kVA/10kW. All models contain a power factor correction rectifier, a battery
charger, an inverter, an bypass circuit and control circuit.
1 Fan
module through ventilation grills and exhalation exhausts through grills located at
3 LCD display
4 Function Keys
5 LED indicators
16
Page 18
3-2-2. Button Operation
LED Indicators
BY PASS
LINE
BATTERY
ALARM
UP
DOWN
OFF/ESC
ON/ENTER
LCD Display
Function Keys
Control Key
Description
Press this button to turn on the UPS.
Press this button to turn off the UPS.
Press this button to select the previous item in the menu.
Press this button to select the next item in the menu.
To allow LCD display to rotate 90 automatically, press these two buttons at the
LED
Bypass mode
● ○ ○
○
Line mode / CVCF mode
○ ● ○
○
Battery mode
○ ○ ●
○
Fault mode ○ ○ ○ ●
There are four buttons on the front panel.
ON/ENTER
Or press it to confirm the selection in the menu.
OFF/ESC
UP
Or press it to return to the last menu.
Or press this button to jump to previous page in the screen.
Or press this button to increase the number in the setting.
DOWN
Or press this button to jump to next page in the screen.
Or press this button to decrease the number in the setting.
UP + DOWN
same time. This operation is used to configure the UPS in rack or tower display.
3-2-3. LED Indicators
There are 4 LEDs on front panel to show the UPS working status:
Mode
BYPASS LINE BATT ERY ALARM
UPS Power On ●●●●
Standby mode ○○○○
Battery Test mode ○●●○
ECO mode ●●○○
Note: ● means LED is lighting, and ○ means LED is faded.
3-3-1. Turn on the UPS with utility power supply (to Line mode)
1) Make sure mains input and battery are connected well, and the Battery pack breaker is at “ON” position;
Set the external mains input breaker to “ON” position, then the fan will be running and the UPS supplies
power to the loads via bypass; (The UPS is operating in Bypass mode.)
NOTE: When UPS is in Bypass mode, the output voltage comes directly from utility, so the load is not
protected by UPS. To protect the precious load, the UPS should be turned on to Line mode.
2) When LCD is on home page, press the “ON/ENTER” button, LCD will show a prompt page of “Turn On”;
Move the arrow to “Yes” by up or down button, then press “ON/ENTER”, the UPS will be starting up with
beeping once. You could also enter the “control menu” to select the instruction “Turn On” to startup the
UPS. Please refer to the section of “LCD operation ”.
3) A few seconds later, the UPS will enter into Line mode; “Line mode” will be displayed on LCD. (In line
mode, if the utility power is abnormal, the UPS will transfer to Battery mode without interruption.)
3-3-2. Turn on the UPS without utility power supply (to Battery mode)
1) Make sure the battery is connected well and the Battery pack breaker is at “ON” position;
2) Press the “ON/ENTER” button to start up the internal power, the UPS will enter into bypass mode
without output;
3) When LCD is on home page, press the “ON/ENTER” button, LCD will show a prompt page of “Turn On”;
Move the arrow to “Yes” by up or down button, then press “ON/ENTER”, the UPS will be starting up with
beeping once. You could also enter the “control menu” to select the instruction “Turn On” to startup the
UPS. Please refer to the section of “LCD operation”.
4) A few seconds later, the UPS will enter into Battery mode; “Battery mode” will be displayed on LCD (In
Battery mode, it will shutdown automatically when battery is depleted. If the utility power is restored, it will
auto restart to Line mode.)
3-3-3. Connect devices to UPS
After the UPS is turned on, you can connect devices (load) to the UPS.
1) Turn on the UPS first and then switch on the devices one by one, the LCD panel will display total load
level;
2) If inductive loads needed to be connected, such as a printer, the in-rush current should be calculated
carefully to see if capacity of the UPS can cover due to the huge starting power consumption of this kind
of load;
3) If the UPS is overload, the buzzer will beep twice every second;
4) When the UPS is overload, please remove some loads immediately. It is recommended to have the total
loads connected to the UPS less than 80% of its nominal power capacity for system safety;
18
Page 20
5) If the overload time is over duration listed in spec at Line mode, the UPS will automatically transfer to
Bypass mode. After the overload is removed, it will return to Line mode. If the overload time is over
duration listed in spec at Battery mode, the UPS will become fault status. At this time, if bypass is
enabled, the UPS will power to the load via bypass. If bypass function is disabled or the input power is
not within bypass acceptable range, it will cut off output directly.
3-3-4. Charge the batteries
1) After the UPS is connected to the utility power, the charger will charge the batteries automatically except
in Battery mode or during battery test;
2) Suggest to charge batteries at least 10 hours before use. Otherwise, the backup time may be shorter than
expected;
3) Make sure the battery numbers setting on the LCD Panel (Please refer to the section of changing battery
quantity) is consistent with actual connection.
3-3-5. Battery mode operation
1) When the UPS is in Battery mode, the buzzer will beep according to different battery capacity. Normally,
the buzzer will beep once every 4 seconds in battery mode, but when the battery voltage drops to the
alarm level, the buzzer will beep once per second and the UPS will shut down automatically soon. Users
could switch off some non-critical loads to disable the shutdown alarm and prolong the backup time. If
there is no more load to be taken off at that time, you have to shut down all loads as soon as possible to
protect the devices or save data. Otherwise, there is a risk of data loss or load failure.
2) In Battery mode, if buzzer sounds annoying, you could enter ”Control->Mute” on LCD to silence it.
Please refer to the section of “LCD operation”.
3) The backup time of the long-run model depends on the external battery capacity.
4) The backup time may change under different environment temperature and load type.
5) The maximum backup time is limited by default 16.5 hours (After discharging 16.5 hours, UPS will shut
down automatically to protect the battery). The time could be modified through LCD panel or
communication port.
3-3-6. Test the batteries
1) If you need to check the battery status or performance when the UPS is running in Line / Converter (CVCF)
/ ECO mode, you could enter ”Control->Bat Test” to instruct the UPS to do battery test. Please refer to the
section of “LCD operation”;
2) Users also can set battery test through monitoring software;
3) If the UPS is in battery testing, “Battery test mode” will be displayed on LCD, the buzzer indication will be
the same as Battery mode, but both line LED and battery LED will be lit.
3-3-7. Turn off the UPS with utility power supply in Line mode
1) When LCD is on home page, press the “OFF/ESC” button, LCD will show a prompt page of “Turn Off”;
Move the arrow to “Yes” by up or down button, then press “ON/ENTER”, the UPS will be turning off to
bypass mode with beeping once. You could also enter the “control menu” to select the instruction “Turn
Off” to turn off the UPS. Please refer to the section of “LCD operation”;
NOTE: Here, “Turn Off” means that UPS is not working on line / converter / ECO / battery / battery test
mode. So even though the UPS is turned off, if input or bypass voltage is normal, the internal power
supply will be still working; and if bypass status has been set to “enable”, the output voltage of the UPS
will be still exist;
2) If you need to fully cut off the output, please switch off the external input breaker. A few seconds later,
there is no display shown on the panel and UPS is completely off.
19
Page 21
3-3-8. Turn off the UPS without utility power supply in Battery mode
1) When LCD is on home page, press the “OFF/ESC” button, LCD will show a prompt page of “Turn Off”;
Move the arrow to “Yes” by up or down button, then press “ON/ENTER”, the UPS will be turning off to
bypass mode with beeping once. You could also enter the “control menu” to select the instruction “Turn
Off” to turn off the UPS. Please refer to the section of “LCD operation”;
2) If there is no bypass input voltage, the UPS will cut off all power supply and there is no display shown on
the panel.
3-3-9. Operation of changing battery quantity (number)
The default battery (12V) quantity of this UPS system is 16 (for one series), but 17, 18, 19, 20 could also be
applied in this system. Changing the battery quantity setting, can setup from UPS LCD panel.
NOTE: This operation should be done by professional technicians, please contact the dealer for support
3-4. LCD Operation on UPS Module
3-4-1. LCD Structure
The entire LCD structure is demonstrated as diagram below.
After initialization, the main screen will display as below chart.
Main screen (Home Page)
1) UPS Mode: Current operation mode.
2) It will display the UPS running status mode and parallel information as below table.
3) Input and output information.
4) Battery capacity, load level and backup time/warning or fault codes. When alarms happen, the warning or
fault information will display. When UPS is operated in Battery mode or Battery Test mode, the backup time
will display.
When the front panel is not operated for 2 minutes, the display page will return back to home page. Press the
“UP” or “DOWN” button to enter the operation menu (Refer to 4.2.3).
When it displays home page in LCD, if UPS is in bypass or standby, you could press the “ON/ENTER” button to turn
on the UPS to line / CVCF / ECO / battery mode according to the setting and input status.
When UPS is turned on, you could press the “OFF/ESC” button to allow UPS to bypass mode or standby.
Set system shutdown time (0.2~99min)
0.2 min (Default)
Set system restore time (0~9999min)
1 min (Default)
Control:
Bat Test
Turn to Bps
SR Off
Charger Off
Turn Off
SR Off ?
Yes
No
Bypass Mode M
IP1:230.0V/
50.0Hz
IP2:
230.0V/50.0Hz
IP3:230.0V/50.0Hz
OP1:230.0V/50
.0Hz
OP2:230.
0V/50.0Hz
OP3:
230.0V/50.0Hz
Bat:192.0V/192.0V
Load: 0/ 0/ 0%
a) On Line/Battery/Battery Test/CVCF/ECO mode, it will display “SR On” in control menu. If it is selected
and confirmed, shutdown and restore time can be setting. Please refer to setting range table for
shutdown and restore time.
When “Shutdown Time” countdown ends, the UPS will turn off. Then, the “Restore Time” will start to
count. When countdown ends, the UPS will be turned on and back to current mode.
→→→
Table: Setting range for Shutdown & Restore Time
SR On/SR Off
b) On Standby/Bypass/Fault mode, it will display “SR Off” in control menu. If it is selected and confirmed,
the screen will return back to home page and system will back to current mode.
If “SR On” is selected and confirmed, When UPS in Line/Battery/Battery Test/CVCF/ECO mode, it will
display “SR Off” in control menu. If it is selected and confirmed, the screen will return back to home
page and system will cancel this function.
Shutdown Time
Restore Time
→
→
→
26
Page 28
5) Charger Off / Charger On
Control
Measurement
Setting
Information
Events
Measurement:
System
Master
Slave1
Local
Slave2
Slave3
Slave4
>>>
Measurement:
Slave6
Slave7
Slave8
Slave9
<<<
Slave5
a) This selection will be displayed under all UPS modes when charger is working. If it is selected and
confirmed, the screen will return back to home page. And charger will stop charging the battery.
→
b) This selection will be displayed under all UPS modes when charger is turned off. If it is selected and
confirmed, the screen will return back to home page. And charger will charging the battery.
3-4-3-3. Measurement
Measurement displays the measurement value of the parameters such as voltage / current / frequency / power /
capacity / time etc. Each UPS could display the measured value of the whole system. Press “” or “” button
to explore the pages.
“Local” means the current UPS module. “System” means all UPS modules. “Master” and “Slave<n>” means the
other UPS module in this parallel system.
→
→
27
→
Page 29
Measurement
:
Output
Bypass
Load
Input
Bat
→
Input:
Volt1:
Volt
2
:
Volt3:
Freq
:
Phase
:
230.0V
230.0V
230
.
0V
50
.0
Hz
120
Output:
Volt
1
:
Volt2:
Volt3:
Freq:
230.0V
230.0V
230.0V
50.0Hz
Inv1:
Inv2:
Inv3:
230.0V
230.0V
230.0V
>>>
Output:
Curr1:
Curr2:
Curr3:
15.0A
15.0A
15.0A
<<<
Bypass:
Volt
1
:
Volt
2
:
Volt
3
:
Freq
:
Phase
:
230
.0
V
230.
0V
230
.
0
V
50.0
Hz
120
Load:
Sout
1:
3300VA
Sout
2:
Sout3:
Pout1:
Pout2:
Pout3
:
>>>
3300
VA
3300VA
3300W
3300W
3300
W
Load
:
Load1
:
100
%
Load2
:
Load3
:
<<<
100
%
100
%
→
→
→
→
→
3-4-3-4. Setting
This page is used to configure the parameter settings. It’s necessary to enter password to enter submenus. The
default password is 0729. There are submenus under the Setting, including Bypass, ECO, Output, SystemTime,
Others and Battery, as shown below.
→→
NOTE: Some settings will be only available in some operation modes. If the setting is not available in current
mode, the LCD will show prompt message with “Item can’t be set in this mode”. Press any button or just wait for
several seconds until this message fades.
28
Page 30
1) Bypass setting (only available or effective on bypass mode and standby mode)
Interface
Description
Bypass
:
Status:
HighLoss V:
Open
Disable
240V
LowLoss V:
HighLoss F:
LowLoss F:
110
V
54Hz
46
Hz
1. Status
The default value is 46Hz/56Hz.
Interface
Description
ECO:
Status
:
HighLoss V:
Disable
240V
LowLoss V:
HighLoss F:
LowLoss F:
218V
52Hz
48Hz
1. Status
Interface
Description
1.1 Open/Forbid:
Open: Bypass allowed. When selected, UPS will run at Bypass mode depending on bypass enabled/disabled setting.
Forbid: Bypass not allowed. When selected, it’s not allowed for running
in Bypass mode under any situations.
The default setting is Open.
1.2 Enable/Disable
This option appears only when Bypass status is set to “Open”.
Enable: Bypass enabled. When selected, Bypass mode is activated.
Disable: Bypass disabled. When selected, automatic bypass is
acceptable, but “manual bypass” is not available. “Manual bypass”
means users manually operate UPS to Bypass mode (for example, in AC
mode turning off the UPS to Bypass mode). Then, the UPS will go to
bypass mode but without output if it is turned off in AC mode.
The default setting is Enable.
NOTE: The following items are only available in bypass mode.
2. HighLoss V: Set the acceptable high voltage for bypass. Setting range is from (Rated Output Volt +11V) to 276V and the default value is 264V.
3. LowLoss V: Set the acceptable low voltage for bypass. Setting range is
from 110V to (Rated Output Volt - 11V) and the default value is 110V.
4. HighLoss F: Set the acceptable high frequency for bypass.
50 Hz system: Setting range is from 51Hz to 54 Hz.
60 Hz system: Setting range is from 61Hz to 64Hz.
The default value is 54.0Hz/64.0Hz.
5. LowLoss F: Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
2) ECO setting (only available or effective on bypass mode, standby mode, Line mode and ECO mode)
Enable: ECO function enabled
Disable: ECO function disabled
If ECO function is disabled, voltage range and frequency range for
ECO mode still can be set, but it is meaningless unless the ECO
function is enabled. The default setting is Disable.
2. HighLoss V: High voltage point in ECO mode. The setting range is from
(Rated Output Volt +11V) to (Rated Output Volt +24V) and the default
setting is (Rated Output Volt +11V).
3.LowLoss V: Low voltage point in ECO mode. The setting range is from
(Rated Output Volt -24V) to (Rated Output Volt-11V) and the default
setting is (Rated Output Volt -11V).
4.HighLoss F: Set High frequency point for ECO mode.
50 Hz system: Setting range is from 52Hz to 54Hz.
60 Hz system: Setting range is from 62Hz to 64Hz.
3) Output setting (only available or effective on bypass mode and standby mode)
The default value is 52Hz/62Hz.
5.LowLoss F: Set Low frequency point for ECO mode.
50 Hz system: Setting range is from 46Hz to 48Hz.
60 Hz system: Setting range is from 56Hz to 58Hz.
The default value is 48Hz/58Hz.
29
Page 31
Output:
Volt:
Freq:
CVCF:
230V
60Hz
Enable
1. Volt:
208: Presenting the rated output voltage with 208Vac
56Hz to 64Hz, the output
The output frequency will synchronize with the input
The default setting is Disable.
Interface
Description
SystemTime:
Interface
Description
Others:
Hot Standby:
Audible Mute:
Disable
Disable
Language:
English
>>>
1. Hot standby(only available or effective on bypass mode and
Enable: It is to mute the buzzer when UPS is in battery mode.
220: Presenting the rated output voltage with 220Vac
230: Presenting the rated output voltage with 230Vac
240: Presenting the rated output voltage with 240Vac
The default value is 230Vac.
2. Freq:
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
NOTE: CVCF should be enabled first to modify this item.
If CVCF is disabled, output frequency will be decided according to the
latest normal utility frequency. If it is within 46Hz and 54Hz, the output
frequency will be 50.0Hz. If it is within
frequency will be 60.0Hz.
3. CVCF:
Enable or disable CVCF (converter) mode.
Enable: The output frequency will be fixed at 50Hz or 60Hz according
to setting of “Freq”. The input frequency could be from 46Hz to 64Hz.
Disable:
frequency within 46~54 Hz for 50Hz system or within 56~64 Hz for
60Hz system.
NOTE: CVCF means Constant Voltage and Constant Frequency. It
represents converter mode.
4) SystemT ime setting (available or effective on all mode)
Date, time and calendar date can be modified via this interface. Input the
actual time, the unit will automatically adjust timer after “
pressed.
5) Others setting
standby mode):
Enable: Hot standby function is enabled. It means that the current UPS is
set to be host of hot standby system, and it will automatically restart
after AC recovery even without battery connected.
Disable: Hot standby function is disabled. The UPS is running at normal
mode and can’t restart without battery.
The default setting is Disable.
2. Audible Mute(available or effective for all mode):
Enable: It is to mute the buzzer.
Disable: It is to enable the buzzer when UPS have alarms or UPS is
working in bypass mode or battery mode.
The default setting is Disable.
3. Language (available or effective for all mode):
English: All interface will show in English
4. Bat Mute(available or effective on all mode):
” button is
30
Page 32
Others:
Bat Mute:
Disable
Fault Mute:
Bypass Mute:
>>>
Disable
Disable
Others:
Redundancy:
Standard Mode:
00
Enable
Factory Reset
<<<
Total Power:
02
Disable: It is to enable the buzzer when UPS is in battery mode.
The default setting is Disable.
Interface
Description
Bat:
BatNum:
ChgCur:
BatGroups:
BatCap:
Factor:
16
04A
01
9AH
1.
0
<<<
1. Dischg Protect: Enable or disable battery discharge protection.
5. Fault Mute(available or effective on all mode):
Enable: It is to mute the buzzer when UPS is in fault mode.
Disable: It is to enable the buzzer when UPS is in fault mode. The default setting is Disable.
6. Bypass Mute(available or effective on all mode):
Enable: It is to mute the buzzer when UPS is in bypass mode.
Disable: It is to enable the buzzer when UPS is in bypass mode. The default setting is Disable.
7. Redundancy (available or effective on all mode):
of redundant UPS module. The setting range is 0~9. The setting
quantity must be less than the total number of UPS modules in the
system. The default value is 0.
8. Total Power (available or effective on all mode): It is to set parallel
number of power modules for whole system.
9. Standard Mode(only available or effective on bypass mode and
standby mode):
Enable: It is a compatible mode for dynamo.
Disable: It is a normal mode.
The default setting is Enable.
10. Factory Reset(only available or effective on bypass mode and standby
mode): Restore to factory default setting.
It is to set the quantity
6) Battery
Enable: Battery discharge protection function is enabled. When UPS have
Disable: Battery discharge protection function is disabled.
Backup Time: When discharge protection is enabled, this setting time can be counted.
1~990: The maximum discharge time can be set from 1 to 990 minutes.
2. Cold Start:
Enable: UPS could be turned on without mains.
Disable: UPS could not be turned on without mains.
3. Charger Test:
Test the battery charger even without battery. After entering this item, it
will pop up a screen showing “Yes” and “No”. If selecting “Yes”, the UPS will
execute charger test. After test, the LCD screen will return to main scree
(home page) and show battery voltages on BAT+ and BAT-.
4. Low Volt:
Set battery low warning voltage. The setting range is from 10.5~11.5V per
piece and the default value is 11.2V.
5. Under Volt:
Set battery low cut off voltage. The setting range is from 9.6~10.7V per
piece and the default value is 9.6V.
6. Periodic Test:
Enable: UPS will test the battery periodically;
Disable: UPS will not test the battery periodically.
7. Periodic Time:
When periodic test is enabled, please set up battery test interval. The
setting range is from 7 days to 99 days. The default value is 30-day.
been continuously working in “battery/battery test mode”, the
UPS will automaticallyshut down when the backup time set next
is achieved.
UPS will shut down to protect battery after backup time arrives
when the “Dischg Protect” is enabled. If “Dischg protect” is
disabled, then this setting does not make sense whatever the
value is. The default value for this setting is 990 minutes.
31
Page 33
8. BatNum:
Set battery number in the system. The setting range is from 16 to 20 pieces.
Item 10~12 are used for the battery backup time calculation.
Information:
Identification
System
Bat
Identification:
Module Name:
Arena 3
-3
Serial NO:
*********
*********
Display Ver:
00.21
>>>
Identification:
Control Ver:
00.00
Main Ver:
MiniLcd Ver:
02.36
<<<
30.01
30.01
Information:
Identification
System
Bat
System: Bypass
Status:
HighLoss V:
Open
Disable
240V
LowLoss V:
HighLoss F:
LowLoss F:
110V
54Hz
46Hz
>>>
System: ECO
Status:
HighLoss V
:
Disable
240V
LowLoss V:
HighLoss F
:
LowLoss F:
218V
52Hz
48Hz
>>>
The default value is 16.
9. Chg Curr:
Set maximum charge current. The setting range is from (0~ 4A) x N. N
represents the parallel unit number. The default value is 4A. If parallel unit
number is 10, the maximum setting value can be 40A.
10. Bat Groups: Set the number of battery group ranging from 1 to 10. The
default value is 1 group.
11. Bat Cap: Set the battery capacity such as 7AH, 9AH, 10AH, 12AH, 17AH,
26AH, 40AH, 65AH, 100AH and so on. The default value is 9AH.
12. Factor: Calibrate the displayed backup time by adjusting this multiplier
factor. The formulation is listed below:
Displayed backup time=Original calculated backup time x Multiplier factor
The value of default factor is 1.0. The setting range is from 0.5 to 2.
3-4-3-5. Information
In Information page, you can check the serial number, firmware versions, system configuration and settings of the
UPS. There are submenus under the Information, including Identification, System and Battery, as shown below.
Information displays all parameter setting value and status.
1) Identification item shows the UPS Module name, serial no, UPS display version, controller module version,
CPU version and system LCD version.
→
2) System shows the UPS configuration.
→
32
→
→
→
Page 34
Output:
Volt:
Freq:
CVCF:
230V
Auto
Disable
>>>
→
System: TimeTemp
System Time:
2018-05-23
20:26:30
Wednesday
Temperature:
28C
>>>
System:
Others
Hot Standby
:
Disable
Audible Mute:
Language
:
English
>>>
Disable
System: Others
Bat Mute:
Disable
Fault Mute:
Bypass Mute:
>>>
Disable
Disable
System: Others
Redunduancy
:
00
Standard Mode:
<<<
Enable
Parallel:02+01
Bat:
BatNum:
ChgCur:
BatGroups:
BatCap:
Factor:
16
04A
01
9AH
1.0
<<<
→
→
3) Battery shows the battery configuration.
→→→
→
33
Page 35
3-4-3-6. Events
Events:
Current Events
History Events
Reset Events
Current Events:
Fault Events:
Warning Events:
No Fault
01:BatLow
02:BatOpen
Events:
Current Events
History Events
Reset Events
History Events:
Fault:
Warning:
10/160
01:Bus Start Fail
02:BatOpen
01:BatLow
Bypass Mode
2018-04-20
11:16:33
In Event pages, you can check the current events, history events and reset events.
1) Currents Events
When an event occurs, it will display alarm code in Current Events page. If events exceed more than one
page, press “
2) History Events
The detailed event information is saved in history events. It can save up to 160 pages in history events. When
a warning occurs, it will display alarm code, alarm time and UPS mode. When a fault event occurs, it will
display fault code, alarm time/date and UPS operation mode. (Refer to Chapter 4 Troubleshooting)
” or “” button to read other events.
→
3) Reset Events
It’s necessary to enter Maintainer password to enter Reset Events page as shown below. Then, press “
“
” button to choose “Yes” to clear all history events or “No” to cancel the reset action.The default
maintainer password is 0729.
→
→→
34
” or
Page 36
3-5. Parallel UPS Operation
LCD Message
Explanation
Solution
The rectifiers could not start within
Turn off UPS and then restart the UPS.
DC-bus voltage exceeds the maximum
DC-bus voltage is lower than the
Fault 04:Bus Unbalance
DC-bus voltage is not balanced
Contact service personnel.
Fault 05:Bus Volt Vary
DC-bus voltage changes too fast.
Contact service personnel.
PFC current is higher than the maximum
Check if the ambient temperature is over
Fault 08:Batt SCR Short
Battery SCR is short circuited.
Contact service personnel.
Fault 11:Inv Start Fail
Inverter voltage cannot reach desired
Turn off UPS and then restart it. If it fails
You can add one new UPS into the parallel system when whole system is running at any mode. The additional UPS
will automatically match with the Master UPS. Then, fasten the UPS through the screw of mounting ears.
NOTE:
• Before parallel operation, please make sure all the connections are correctly (refer to Section 2-5).
• The maximum parallel quantity is 10.
• Be sure the load is less than the maximum capacity of whole UPS system. Otherwise, the UPS will overload
fault.
4. Trouble Shooting
4-1. Warning status
When Fault LED flashes and the buzzer beeps once every second, it means that there are some
problems with UPS. Users can see the warning code from LCD panel and refer to the trouble shooting
table to check what problem probably happen.
4-2. Fault mode
1) When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error about
UPS. Users can get the fault code from LCD panel. Please refer to the trouble shooting table to check
what problems probably happen.
2) Don’t try to turn on the UPS again before the problem is clear. If the problems can’t be fixed, please
contact the distributor or service people immediately.
3) For emergency case, please cut off the connection from utility, external battery, and output immediately
to avoid more risk or danger.
4-3. Trouble shooting table
Most of the fault and warnings need to be released by authorized service personnel. Few of them can be solved
by users themselves.
Fault 01:Bus Start Fail
Fault 02:Bus Over Volt
specified time due to low DC-bus voltage.
voltage.
If it fails again, contact service personnel.
Contact service personnel.
Fault 03:Bus Under Volt
Fault 06:PFC Over Curr
Fault 07:Over Temperature
minimum value.
current.
The temperature in UPS is higher than
85°C. At this time, the UPS is off.
35
Contact service personnel.
Contact service personnel.
specification.
Or contact service personnel.
Page 37
voltage within specified time.
again, contact service personnel.
Fault 12:Inv Volt High
Inverter voltage is too high.
Contact service personnel.
Fault 13:Inv Volt Low
Inverter voltage is too low.
Contact service personnel.
Fault 14:Inv Short R
R phase inverter output is short circuited
Contact service personnel.
Fault 15:Inv Short S
S phase inverter output is short circuited
Contact service personnel.
Fault 16:Inv Short T
T phase inverter output is short circuited
Contact service personnel.
Fault 17:Inv Short RS
R-S inverter output is short circuited
Contact service personnel.
Fault 18:Inv Short ST
S-T inverter output is short circuited
Contact service personnel.
Fault 19:Inv Short TR
T-R inverter output is short circuited
Contact service personnel.
Fault 1A:Nega Power R
R phase inverter output negative power is
S phase inverter Output Negative Power
T phase inverter Output Negative Power
Fault 21:Inv STS Open
Inverter relay or STS is open.
Contact service personnel.
Fault 22:Inv STS Short
Inverter relay or STS is short circuited.
Contact service personnel.
Fault 23:Op STS Open
Output relay or STS is open.
Contact service personnel.
Fault 24:Op STS Short
Output relay or STS is short circuited.
Contact service personnel.
Fault 25:Wiring Fail
The wiring is wrong.
Contact service personnel.
Fault 26:Bat Fuse Open
Battery fuse is broken.
Contact service personnel.
Fault 27:Charge Short
The battery is short circuited.
Contact service personnel.
The communication between UPS
Fault 32:Host Line Fail
The host line between UPS modules fails.
Contact service personnel.
The load share line between UPS
The firmware version between UPS
The internal communication in UPS
Fault 42:Over load
Heavy overload causes UPS fault.
Reduce some load.
Battery polarity is connected reversely or
Fault 44:Model Fault
UPS model is not able to identify.
Contact service personnel.
Fault 45:Mcu Comm Fail
As stated.
Contact service personnel.
Fault 46:CT Satiation
Load current sensor is abnormal.
Contact service personnel.
Make sure fans work well when UPS is
Charge the battery when the mains is
1. Check battery breaker status.
4. Contact service personnel if necessary
Warning 03:BatPhaseLoss
The voltage between positive and
Check the battery connection.
beyond the range.
Contact service personnel.
Fault 1B:Nega Power S
Fault 1C:Nega Power T
Fault 31:Para Comm Fail
Fault 33:OP Curr Unbal
Fault 34:Ver Incompat
is beyond the range.
is beyond the range.
modules is interrupted.
modules fails.
modules is incompatible.
Contact service personnel.
Contact service personnel.
Contact service personnel.
Contact service personnel.
Contact service personnel.
Fault 41:DSP Comm Fail
module is interrupted.
Fault 43:Charger Fail
charger voltage is abnormal.
Fault 47:Fan Fault The two fans are stuck or broken.
Warning 01:BatLow Battery voltage is low.
Warning 02:BatOpen Battery is not connected.
Contact service personnel.
Contact service personnel.
working.
normal.
2. Check if the battery connection is well
connected.
3. Check the setting of Nominal Battery
voltage.
36
Page 38
negative battery is different.
Warning 04:LineIpNLoss Neutral loss
Check if the Neutral connection is well
Check if the Mains phase sequence is
Check if the input wiring is correct or
Warning 07:LinePhaseFail
As stated.
Contact service personnel
Check the setting of Nominal Battery
Battery voltage is detected as low level.
in UPS is higher than
Check if the ambient temperature is over
Warning 0B:PFCCurUnbal
PFC current is unbalance.
Contact service personnel
Check if the fan is blocked or contact
Turn off UPS and replace a good one with
Warning 0E:IICEepromFail
EEPROM operation error
Contact service personnel.
Check if the Neutral connection is well
Check if the Bypass phase sequence is
Check the wiring or contact service
Warning 14:BpsPhaseFail
As stated.
Contact service personnel
In line mode, the connected devices are
g more power than the UPS
Reduce some load and check output
The connected devices are demanding
more power than the UPS can supply.
UPS will transfer to bypass mode from
some load and check output
Check if the connector is loose when EPO
Check if external maintenance bypass
Each module gets different line voltage
Each module gets different bypass
Warning 1B:InvCurUnbal
As stated.
Contact service personnel.
and contact service personnel.
Warning 05:LinePhaseError As stated.
Warning 06:LineVoltError As stated.
Warning 08:OverCharge Battery voltage is too high.
Warning 09:ChgFail
However, the charge is able to work.
Warning 0A:OverTemp
The temperature
75°C. At this time, the UPS is still running.
Warning 0C:FanError Fan error.
Warning 0D:LineFuseOpen Fuse is broken.
correct and contact service personnel.
contact service personnel
voltage and contact service personnel.
Contact service personnel.
specification.
Or contact service personnel.
service personnel.
the broken one. If UPS fails again after you
do this, contact the service personnel.
Warning 11:BypassIpNLoss Neutral loss.
Warning 12:BpsPhaseError Bypass phase error.
Warning 13:BpsVoltError Bypass voltage error.
Warning 15:OverLoad
demandin
can supply.
Warning 16:OverLoadLock
line mode.
Warning 17:EpoActive Check the EPO connector.
Warning 18:MaintainOpen The UPS is in maintenance mode.
and contact service personnel.
correct and contact service personnel.
personnel
Load-Capacity in specification.
Reduce
Load-Capacity in specification.
acts abnormally.
signal port is not connected to 2-pin EPO
port on the optional controller module
when it acts abnormally.
Warning 19:LineDiff
when they are in parallel.
Warning 1A:BypassDiff
voltage when they are in parallel.
Contact service personnel.
Contact service personnel.
37
Page 39
Warning 1C:BpsUnstable
UPS switches between bypass mode and
standby mode five times in 30 minutes
Check if redundancy setting is correct or
Check if the battery has been used over its
Warning! Dry Contact Input
Warning! Dry Contact Input
Warning! Control Module
Warning! Control Module
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
Contact service personnel.
due to abnormal utility.
Warning 1D:RedundancyFail As stated.
Warning! Battery Age Alert Battery life is expired.
Alarm 1
Alarm 2
SPS 1 Fault
SPS 2 Fault
As stated. Remove the node
As stated. Remove the node
As stated. Contact service personnel.
As stated. Contact service personnel.
not. Then, contact service personnel.
service age. Or contact service personnel.
5. Storage and Maintenance
5-1. Storage
Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in
accordance with the following table:
For the battery pack, please charge it at least 7 hours before storage.
5-2. Maintenance
⚠ The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified
maintenance personnel.
⚠ Even after the unit is disconnected from the mains, components inside the UPS system are still
connected to the Battery packs which are potentially dangerous.
⚠ Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no
current is present and no hazardous voltage exists in the terminals of high capability capacitor such as
BUS-capacitors.
⚠ Only persons are adequately familiar with batteries and with the required precautionary measures may
replace batteries and supervise operations. Unauthorized persons must be kept well away from the
batteries.
⚠ Verify that no voltage between the battery terminals and the ground is present before maintenance or
repair. In this product, the battery circuit is not isolated from the input voltage. Hazardous voltages may
occur between the battery terminals and the ground.
⚠ Batteries may cause electric shock and have a high short-circuit current. Please remove all wristwatches,
rings and other metal personal objects before maintenance or repair, and only use tools with insulated
grips and handles for maintaining or repairing.
⚠ When replace the batteries, install the same number and same type of batteries.
⚠ Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The
batteries must be rightly deposed according to local regulation.
⚠ Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be
toxic.
⚠ Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
⚠ Do not disassemble the UPS system.