PowerWalker VFI 160K CPG 3/3 BX, VFI 200K CPG 3/3 BX, VFI 120K CPG 3/3 BX, VFI 100K CPG 3/3 BX User Manual

Page 1
PowerWalker
VFI 100-200K CPG 3/3
Manual
Uninterruptible Power Supply System
Version: 1.1
Page 2
Please comply with all warnings and operating
instructions in this manual. This equipment
should only be installed, serviced, and
maintained by qualified personnel. Do not
operate this unit before reading through all
safety information and operating instructions
carefully.
Disclaimer
We assumes no responsibility or liab ility for loss or da mages, whether d irec t , indirect, consequential or incidental, which might arise out of the use of such information. The use of any such information wi ll be e nti rel y a t the us e r’s ri s k. Informa ti on i n thi s m anua l is subje ct to change without notice. W e ma ke no c ommi tment to update or keep current the infor mati on i n this manual. If you fi nd i nfor mati on i n this manual that i s i ncorr ect, mi sl e a ding, o r i ncom ple te, we would appr eciat e y o u r c om m en t s an d suggestions.
Page 3
Table of Contents
1. SAFETY AND EMC INSTRUCTIONS ................................................................................................. 1
1-1. TRANSPORTATION AND STORAGE...........................................................................................................1
1-2. PREPARATION .................................................................................................................................1
1-3. INSTALLATION .................................................................................................................................1
1-4. CONNECTION WARNINGS ....................................................................................................................2
1-5. OPERATION ....................................................................................................................................3
1-6. STANDARDS ....................................................................................................................................3
2. INSTALLATION AND OPERATION .................................................................................................. 4
2-1. UNPACKING AND INSPECTION ...............................................................................................................4
2-2. OPEN FRONT PANEL VIEW ..................................................................................................................6
2-3. REAR PANEL VIEW ............................................................................................................................8
2-4. WIRING TERMINAL VIEW ....................................................................................................................8
2-5. SINGLE UPS INSTALLATION .................................................................................................................9
2-6. UPS INSTALLATION FOR PARALLEL SYSTEM ............................................................................................ 11
2-7. SOFTWARE INSTALLATION ................................................................................................................. 15
3. CONTROL PANEL AND LCD OPERATION ...................................................................................... 16
3-1. INTRODUCTION ............................................................................................................................. 16
3-2. SCREEN DESCRIPTION ..................................................................................................................... 17
3-3. ALARM LIST.................................................................................................................................. 35
3-4 HISTORY RECORD ........................................................................................................................... 36
4. INTERF AC E AND COMMUNICATION ............................................................................................ 38
4-1. X1- TEMPERATURE DETECTION PORT FOR EXTERNAL BATTERY PACK .............................................................. 38
4-2. X2 - REMOTE EPO INPUT PORT ......................................................................................................... 39
4-3. OTHER COMMUNICATION INTERFACE .................................................................................................... 39
5. OPERATION PRINCIPLES ............................................................................................................. 40
5-1. BLOCK DIAGRAM OF UPS .................................................................................................................. 40
5-2. OPERATION MODE .......................................................................................................................... 41
6. UPS OPERATION .......................................................................................................................... 47
6-1. AC STARTUP ................................................................................................................................. 47
6-2. COLD START STARTUP ..................................................................................................................... 48
6-3. MAINTENANCE BYPASS OPERATION ...................................................................................................... 50
6-4. TURN OFF OPERATION ..................................................................................................................... 53
7. TROUBLE SHOOTING ................................................................................................................... 56
8. STORAG E AND MAIN TENANCE ..................................................................................................... 59
Page 4
1
8-1.
STORAGE ..................................................................................................................................... 59
8-2. MAINTENANCE .............................................................................................................................. 59
9. SPECIFICATIONS ......................................................................................................................... 60
Page 5
1. Safety and EMC instructions
All safety instructions in this document must be read, understood and followed.
1-1. Transportation and Sto rage
Please transport the UPS system only in the original package to protect against shock and
impact.
The UPS must be stored in the room where the temperature is well regulated. Ambient
temperature must not exceed 40°C
1-2. Preparation
Condensation may form if t he UPS system is moved immediately from cold to warm e nvir onme nt.
The UPS system must be absolutely dry before being installed. Please allow at least two hours
for the UPS system to acclimate the environment. Do not install the UPS system near water or in moist environments. Do not install the UPS system where it would be exposed to direct sunlight or near by heat
source.
Do not block ventilation holes on the UPS housing .
1-3. Installation
Do not conn e ct appliances or devices which w ou l d over load th e U PS ( e .g. big mot or-type
equipment)) to the UPS output terminal. Place cables in such a way that no one can step on or trip over them. Do not block air vents on the housing of UP S. En sure proper unit spacing of ventilation. UPS came equipped with grounding terminal, in the final installation phase, connect grounding/
earthing wire to the external UPS battery cabinets or appropriate grounding terminals. Th e UPS can be inst a l l ed on l y by qua l ified m aintenance personnel. An appropriate disconnection device such as short-circuit backup protection should be
incorporated during installation. An integral emergency shutoff switch which prevents additional load from the UP S in any mo d e
of operation should be implemented duri ng the installation. Secure the grounding/earthing wire before connecting to any live wire terminal. Installation and wiring must be performed in accor dance with the local electrical l aws and
regulations.
The unit must be inst a l l e d on level ground suitable for compu ter or electronic equipment.
The UPS cabinet is heavy. If unloading instructions are not closely followed, cabinet may cause
serious injury.
Page 6
2
Do not tilt the cabinets more tha n 10 degree. Th e disco nnection device should be installed on the input current break line and neutral
conductors - four poles for three phases.
1-4. Connection Warnings
• This UPS should be connect e d with TN grounding/earthing system .
• The po we r supply for this uni t must be three-phase rated in accordance with the equipment nameplate. It also must be suitabl y grounded.
• Use of this equipment in medical instrument of any life-sustaining equipment where failure of this equipment can reasonably be expected to cause the failure of the life-sustaining equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable mixture with air, oxygen or nitrous oxide.
• Connect grounding terminal of power stage to a grounding ele ctrode conductor.
• In accordance with safety standard EN-IEC 62040-1, installation has to be provided with aBackfeed Protection》 system, for example a contactor , w hich will prevent the appearance of voltage or dangerous energy in the input mains during a mains fault (see figure 24 and conforms to the wiring diagram of «Backfeed Protect i on» depe nding on the phase input).
There can be no derivation in the line that goes from the «Backfeed Protection» to the UPS, as
the standard safety would be compromised.
• Warning labels should be placed on all primary power switches installed in places away from the unit to alert maintenance personnel of the presence of a UPS in the circuit. The label will bear the following or an equivalent text:
The isolation devi ce mu st be rated to carry the UPS input current.
Before working on this circuit
- Isolate Uninterruptible Power Supply (UPS)
- Then check for Hazardous Voltage between all terminals in cludi ng the protected earth
Risk of Voltage Backfeed
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
Page 7
3
1-5. Operation
Do not disconnect the grounding/earthing conductor cable on the UPS or the building wiring
terminals under any circumstance.
In order t o full y di scon nect t he UP S syste m, first p ress t he “O FF” b utto n and then d isco nnect the
Mains/live wires. Ensure that no liquid or other foreign objects can enter into the UPS system. Th e UPS can be operated by any indiv i duals with no previous exper i ence .
1-6. Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission...............................:IEC/EN 62040 -2
Category C3
Radiated Emission..................................: IEC/EN 62040-2
Category C3
*EMS
ESD................................ .........................:IEC/EN 61000-4-2
Level 3
RS........................................................ ...:IEC/EN 61000-4-3
Level 3
EFT.................................... ..................... :IEC/EN 610 0 0 -4-4
Level 4
SURGE........................... ........................ :IEC/EN 61000-4-5
Level 4
CS........................................................... :IEC/EN 61000-4-6
Level 3
Power-frequency Magnetic field.............. :IE C/EN 61000-4-8
Level 4
Warning:
This is a product for commercial and industrial application in the
second environment-installation restrictions or add
itional measures may be
needed to prevent disturbances.
Page 8
4
2. Installation and Operation
There are two d ifferent types of online UPS: single input and dual input models. Please refer to the following table.
Model Type Model Type
100KVA
Single input
100KVA DUAL
Dual input
120KVA 120KVA DUAL
160KVA
160KVA DUAL
200KVA
200KVA DUAL
2-1. Unpacking and Inspection
1. Use a forklift to move the product to installed area. Refer to Figure 2-1. Please make sure the
bearing capacit y of for k l i ft is su fficient.
2. Please follow the unpacking order in Figure 2-2 to remove carto n (
and ) and foams ( ).
3. Remove two fixing plates (
, and )
located on the two sides of the unit. Loosen leveling feet (
) in figure by rotating them in
counterclockwise. Then, move the cabin et from
the pallet.
4. To fi x the cabi net in position, simpl y rotate leveling feet clockwise.
Page 9
5
Unpack the packa ge and check th e pa ck a ge contents. The shipping pack a ge contains:
User manual
Monitoring software CD
RS-232 cable
USB cable
NOTE: Before installation, please inspect the unit. Be sure that there is no physical damage to the unit. Do not tur n on the unit and notify the carrie r and de al e r immed i a te ly i f there is a n y d am a g e or missing parts or accessories. Please keep the original packages for future use. It is recomm ende d to keep each equipment and battery set in their original packaging because they have been designed to provide maximum protection during transportation and storage.
Page 10
6
2-2. Open Front Panel View
Each UPS comes equipped with a front door key. After opening the front door, you will see communication area and several power stages/modules inside. An d from each power stage/module, you can easily identify their ID as shown belo w:
Table 2-1 Power Stage/Module ID
Install Parallel Board of UPS 1
Power Rating
100K 120K 160K 200K
stage ID
Install Parallel Board of UPS 2 (For Parallel)
Power Rating
100K 120K 160K 200K
stage ID
Page 11
7
Interface and Communication
This UPS comes equipped with various communication devices. Please refer to chapter 4 Interface and Communication for furt her deta ils.
Power Stage/Module
Each power stage/module includes a pow er factor correction rectifier, a battery charger, an inverter and control circuit.
No.
Item
Description
Fan
Air enters the power stage/module through the front grills and exhausted through rear of the module. Please do not block the ventilation vent p o rt.
DIP Switches
There are three DIP switches for power stage/module address setting. In the same cabinet, each power stage/ module ID MUST be exclusive. Please refer to
Table 2-1 Power Stage/Module ID
Battery Start Button
When AC input is not existing, use this button to start battery power for UPS.
FAULT LED
ON
The power stage/module is in fault cond i ti o n.
ON/OFF 0.5 sec
The power stage/module IDs in conflict.
RUN LED
ON
The power stage/module normally works as a slave unit.
ON/OFF 0.5 sec
The pow er stage/module normally works as a master unit.
ON/OFF 0.15 sec
The CAN BUS communication doesn’t work.
1. Dry contact port X 1
2. Dry contact port X2
3. SNMP slot (SNMP card
optional)
4. Extended communication slot(Extra Com m. card
optional)
5. RS-232 port
6. USB port
Page 12
8
2-3. Rear Panel View
There are several breakers located on the rear panel of the UPS.
100KVA/120KVA 160KVA/200KVA
1. Input breaker Q1
2. Input breaker Q2 (only available for Dual Input Models)
3. Output and maintena nce bypass switch
4. Maintenance bypass breaker (Q4)
5. Output break er Q3
2-4. Wiring Te rmin al Vie w
100KVA/120KVA 160KVA/200KVA
Page 13
9
No.
Item
Function
Description
Output Block
Connects to the critical loads
Includes R, S, T and Neutral terminals.
Bypass Input Block (Q2,
only available for dual
input model)
Connects to bypass AC source
Includes R, S, T and Neutral terminals.
Main Input Block
Connects to mai n AC source
Includes R, S, T and Neutral terminals.
For UPS Grounding
For UPS grounding
Includes one grounding terminal.
Battery Input Block
Connects to an external
battery cabinet
Includes:
Positive (+), Ne gative (-) and Neutral
(N) ter minals.
2-5. Single UPS Installation
Installation and wiring must conform in accordance with the loca l elect ric laws/regulations and execute the following instructions by professional personnel.
1) Make sure the mains wire and breakers in th e building provide adequate power for the r ated capacity of UPS to avoid the hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the inp ut po wer so urce fo r the UPS, a s it s rated c urren t is le ss t han the UPS’s maximum input current. Otherwise the receptacle may be shorted and destroyed.
2) Switch off the mains switch in the building before installation.
3) Turn off all the connected devices before connecting to the UPS.
Page 14
10
4) Prepare wires based on the following table: Table 2-2 Power Cable
Model
Power cable (mm2 and AWG)
Input(Ph)
Output(Ph)
Neutral
Battery
Ground
100KVA 70 mm2
(2/0AWG)
70mm
2
(2/0AWG)
70mm
2
(2/0AWG)
150 mm
2
(300 MCM)
70 mm
2
(2/0AWG)
120KVA 95 mm
2
(3/0AWG)
95 mm
2
(3/0AWG)
95 mm
2
(3/0AWG)
240 mm
2
(500 MCM)
95 mm
2
(3/0AWG)
160KVA 150 mm
2
(300 MCM)
150 mm
2
(300 MCM)
150 mm
2
(300 MCM)
120mm
2
x 2
(4/0AWG x 2)
150 mm
2
(300 MCM)
200KVA 185 mm
2
(400 MCM)
185 mm
2
(400 MCM)
185 mm
2
(400 MCM)
185mm2x 2
(400 MCM x 2)
185 mm
2
(400 MCM)
WARNING:
Before connecting any wires, make sure the AC input and battery power is compl etely shut off. Make sure that the breakers, input1 breaker (Q1), input2 breaker (Q2 for dual input model), output
breaker (Q3 for 160K/200K models), maintenance breaker (Q4 for 160K/200K models), and battery breaker are all in the “OFF position.
Make sure the maintenance bypass switch is in “UPS” position (only for 100K/120K models).
5) Remove the terminal block cover on the rear panel of UPS. Then, connect the input1, input2 (only available for dual input model), output and battery wires according to the function indicated on terminal block. (Connect the grounding/earthing wire first when making wire connection. Disconnect the grounding/earthing wire last when making wire di sconnection!)
NOTE 1: Make sure that the wires are connected securely with the terminals. NOTE 2: Please install the output breaker between the output terminal and the load. This breaker must
have leakage current protective function.
6) Put the terminal block cover back to the rear panel of the UPS.
Warning:
● Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring connection.
Warning:
● Make sure a DC breaker or other protection device between UPS and external battery pack is installed.
Switch off the battery breaker before installation.
NOTE: Set the battery pack breaker to “OFF” position and then install the battery pack.
● Pay special attention to the rated battery voltage marked on the label. If you want to change the numbers of the battery pack, please make sure you modify the setti ng accordingly. The c onnecti o n with wrong battery voltage may cause permanent damage to the UPS.
● Make sure the protective grounding/earthing wiring is correct. The current spec, color, position, connection an d conductance reliability of the wires needed be checked carefully.
Page 15
11
● Make sure that the utili ty input & output wi ring is correct . The current spec, co lor, posi tion, conne ction and conductance r eliability of the wires needed be checked carefully. Make sure th e L/N is correct , not reverse or short-circuited.
2-6. UPS Installation for P aral le l Sy st e m
The section introduces how to install and set up the multiple UPSs to run parallel UPS system.
Warning:
The input harmonic current distortion will be between 3% and 4.5% in parallel UPS operation. You need one parallel kit for every two UPS systems.
2-6-1. Input and Output Wiring
1. When install the parallel system, the lengt h of input wires (R, S, T , N) in the one of the UPS parallel syste m must be e qual to an ot her UPS input wi re s. Lik ewise, the length of output wires (R, S, T , N) must also be in equal length. Otherwise, it will cause the unbalance current on output lo ad.
2. Refer to section “2-5. Single UPS Installation” about the input and output wiring and battery wiring methods in User Manual.
Dual input wiring in parallel system
Page 16
12
Single input wiring in parallel system
2-6-2. Parallel Board Setting 2-6-2-1. Install Parallel Board of UPS 1
1. Please set SW2 on the parallel board of the UPS 1 to the right side as shown in below figure.
Page 17
13
SW2 position on UPS 1
2-6-2-2. Install Parallel Board of UPS2
1. Please set SW2 on the parallel board of the UPS 2 to the left side as shown in below figure.
SW2 position on UPS 2
Page 18
14
2-6-3. Parallel Function Setting
1. For the input and output wiring, please be sure to follow the instruction in section 2-6-1.
2. For the parallel board setting, please be sure to follow the instruction in section 2-6-2.
Once the two steps above have been completed correctly, and then set parallel function and battery configuration. Proceed with the following steps:
1. Do not connect Parallel Cable until informed.
2. Place the input breakers (Q1) of two UPSs to the “ON” position. But keep the output breakers (Q3) of two UPSs in the “OFF” position.
3. Turn on the battery breaker.
4. Turn on the external AC source breaker to apply AC input so urc e to both UPS.
5. Wai t for the completion of power-cycles. Proceed to set UPS 1.
6. Set up the parallel func tion through the LCD panel on UPS 1. Enter the “PARALLEL” menu in “SETUP” page. (Refer to User Manual 3-2-5-5. Setup-Parallel Screen)
7. Enable “UPS Parallel” function of UPS 1. (Ignore the warning of “Parallel UPS Cable Loosen”)
8. Choose the battery configuration as “independent” or “common” battery, depending on your preference.
9. Select the “Save Setting” icon in “General” screen of “SETUP” page to save your settings.
10. Proceed to set up UPS 2.
11. Setup the parallel function through the LCD panel on UPS 2. Enter the “PARALLEL” menu in “SETUP” page. (Ref er to User Manual 3-2-5-5. Setup-Parallel Screen)
12. Enable “UPS Parallel” function of UPS 2. (Ignore the warning of “Parallel UPS Cable Loosen”)
13. Choos e the bat tery configuration as “in de pendent” or “common” batter y, depending on your preference.
14. Select the “Save Setting” icon in “General” screen of “SETUP” page to save your settings.
15. Turn off the external AC source breaker and wait for comple te sh utdo wn of both UPS.
16. Turn off battery breakers.
2-6-4. Parallel Cable Connection
There are two connectors at the end of each parallel cable. One is a 16-pin connector and the other is a 2-pin connector. Insert the 16-pin connector into the CN7 port of UPS 1 and 2-pin connector into the CN10 socket of UPS 2 and vice versa. Pleas e refer to bel ow f i gur es for details. For the UPS with two parallel boards, use any one of two boards.
UPS 1 Parallel Board
Page 19
15
UPS 2 Parallel Board
Warning: The parallel cable of each UPS must to be connected correctly. Incorrect connection will result in abnormal operations.
2-6-5. Parallel System Turn On Procedure
1 Please be sure that the sections 2-6-1 to 2-6-4 are correctly followed. 2 Please confirm the input breaker and output breakers of each UPS have been turned “ON”. 3 Turn on the battery breaker. 4 Turn on the external AC source breaker to apply AC input so ur c e to both UPS. 5 Watch for any abnormal event message on the LCD display. (Refer to User Manual 3-2-7. Event Screen) 6 Switch on the U P S b y p r e s si ng the power button at the f ront pane l o f the U PS or through control page
on the LCD panel. (Refer to User Manual 3-2-3. Control Screen)
2-7. Software Installation
For optimal computer system protection, install UPS monitoring software to configure UPS shutdown operations.
Page 20
16
3. Control Panel and LCD Operation
3-1. Introduction
This control panel and display screen are located at the fro nt panel of the UPS. This interface monitori ng all measured parameters, UPS status, battery status and alarms. The control inter face is divided into four sections: (1) LCD display, (2 ) L ED indications, ( 3 ) P o wer Button, (4) Audible Alarm, a s s ho wn in Figure 3-1.
Figure 3-1 Control Panel
(1) LCD displ a y: Graphic display and all measur e d parameters. (2) LED indica tions. Refer to Table 3-1. (3) Power Button. Refer to Table 3-2. (4) Audible Alarm. Refer to Table 3-3.
Table 3-1: LED Indications
LED
Color
Status
Definition
LINE Green
On
Input so ur c e is n orm a l .
Flashing
Input source is abnor m a l .
Off
No input source
BYPASS Yellow
On
Load on Bypass.
Flashing
Input source is abnor m a l .
Off
Bypass not oper ating.
LOAD Green
On
There is power output for the load.
Off
There is no power output for the load.
INV Green
On
Load on inverters.
Off
Inverters not operating .
BATTERY Red
On
Load on Battery.
Flashing
Low battery
Off
Battery converter is normal and battery is charging.
FAULT/ ALARM
Red
On
UPS fault.
Flashing
UPS alarm.
Off
Normal.
Table 3-2: Power Button
Control Key
Description
Power On/Off
Turn on UPS or Turn off UPS. (hold 2-Sec)
Page 21
17
Table 3-3: Audible Alarm
UPS condition
Description
Power on/off
Buzzer sounds 2 seconds.
Battery mode
Buzzer sounds every 2 seconds.
Low battery
Buzzer sounds every 0.5 seconds.
UPS alarm
Buzzer sounds every 1 second.
UPS fault
Buzze r continuously sounds.
3-2. Screen Description
3-2-1. Initial Screen
Upon powering on, the UPS will execute POST (Power-On Self-Test). The initial screen will remain approximately 5 secon ds as shown below.
Figure 3-2 Initial Screen
3-2-2. Main Screen
After initialization, the main screen will display as shown in Figure 3-3. Ma in Screen is divided into six sections.
Figure 3-3 Main Screen
(1) UPS operation mode: It shows UPS current operation mode and status. (2) UPS flow chart: It shows current flow chart and measurement data.
Page 22
18
(3) Main menu: Touch each icon to enter submenu. Refer to Figure 3-4 for menu tree.
Figure 3-4 Menu Tree (4) UPS power rating: It show UPS power rating. (5) D ate and time: It shows current date and time. (6) UPS status: The meanings of each icon are listed as below.
Icon
UPS status
UPS operates in Standby mode
or Shut d own Mode.
UPS operates in Line mode or
Converter Mode.
UPS operates in Bypass mode
or ECO Mode.
UPS operates in Battery mode
or Battery Test Mode.
UPS operates in Fault mode.
3-2-3. Control Screen
Touch icon to enter into the submenu as shown in Figure 3-5 and Figure 3-6.
Figure 3-5 Control Menu Tree
Page 23
19
Figure 3-6 Control Screen Page
Touch any option directly. Then, confirmation screen will pop up. Touch icon to confirm
command or touch
icon to cancel co mmand as shown below.
Figure 3-7 Confirmation Screen
3-2-4. Measurement Screen
Touch
icon to enter into the sub-menu. You may choose input, output, bypass, load or battery to monitor each detailed status. Please refer to Figure 3-8 and 3-9 for detailed descriptions. All detailed measurement items are listed in Table 3-4.
Figure 3-8 Measurement Menu
Page 24
20
Figure 3-9 System Measurement Screens
Table 3-4: Measurement Items
Submenu
Item
Explanation
Input
L-N Voltage (V)
Input phase voltage ( L1, L2, L3). Units 0.1V.
Frequency (Hz)
Input frequency (L1, L2, L3). Units 0.1Hz.
Output
L-N Voltage (V) Output phase voltage (L1, L2, L3). Units 0.1V.
L-N Current (A)
Output phase current (L1, L2, L3). Units 0.1A.
Frequency (Hz) Output frequency (L 1 , L2, L3). Units 0.1Hz.
Power Factor
Output power factor (L1, L2, L3).
Bypass
L-N Voltage (V) Bypass phase voltage (L1, L2, L3). Units 0.1V.
Frequency (Hz)
Bypass frequency (L1, L2, L3). Units 0.1Hz.
Power Factor Bypass power factor (L1, L2, L3).
Load
Sout (KVA)
Apparent power. Uni ts 0 .1 KVA.
Pout (KW) Active power. Units 0.1KW.
Load Level (%)
The percentage of connected load. Units 1%.
Battery
Positive Voltage (V)
Battery positive voltage. Units 0 .1 V .
Negative Voltage (V)
Battery negative voltage. Units 0.1V.
Positive Current (A) Battery positive current. Units 0.1A.
Negative Current (A)
Battery negative current. Units 0.1A.
Remain Time (Sec) Battery remaining runtime. Units 1s ec.
Page 25
21
Capacity (%) The percentage of the battery capacity. Units 1%.
Test Result
Battery test result
Chargi ng Status Battery charging status Temperature 01() Temperatur e of extern a l battery pack. Units 0.1℃.
Temperature 02()
Temperature of external battery pack through extra communication ca rd T1. Units 0.1℃.
Temperature 03()
Temperature of external battery pack through extra communicati on ca rd T2. Units 0.1℃.
Temperature 04()
Temperature of external battery pack through extra communication ca rd T3. Units 0.1℃.
Temperature 05()
Temperature of external battery pack through extra communication ca rd T4. Units 0.1℃.
3-2-5. Setup Screen
Touch the
to enter into the Setup submenu. It requires a password to access the GENERAL, SYSTEM, BATTERY and PRE-ALARM sub-menus as shown in Figure 3-10 and 3-11. The def ault password is “0000”.
Figure 3-10 Setup Menu
Touch the grey column and you will be prompt with a number keyboard. Please enter 4-digit password and
press
to enter SETUP sub-menu. If incorrect password is entered, you may retry.
Page 26
22
Figure 3-11 Enter Password Screen
There are two levels of password protection, user password and administrator password. The default password for user is “0000”. It coul d be changed by users. The administrator password is owned by trained service personnel. Different level of password can access to differnet settings. The setting can be changed in various operation modes. Please refer to Table 3-5 for details.
Table 3-5: All setting items in Setup menu
UPS operation
Mode
Setting item
Standby
Mode
Bypass
Mode
Line
Mode
Battery
Mode
Battery
Test
Mode
Fault
Mode
Converter
Mode
ECO
Mode
Authorization
User
Admini-
strator
General
Model Name
Y Y Y Y Y Y Y Y Y Language
Y Y Y Y Y Y Y Y Y
Y
TIME
Y Y Y Y Y Y Y Y
Y
Change
Password
Y Y Y Y Y Y Y Y Y Y
Baud Rate
Y Y Y Y Y Y Y Y Y
Y
Audible Alarm
Y Y Y Y Y Y Y Y Y
Y
Factory Reset
Y
Y
EEPROM Reset
Y
Y
EPO Function
Y Y Save Setting
Y Y Y
Y
Startup Screen
Y Y Y Y Y Y Y Y
Y
System
Output Voltage
Y Y
Y
Bypass Voltage
Range
Y Y Y Y Y Y Y Y Y
Bypass
Frequency
Range
Y Y Y
Converter
Mode
Y Y
ECO Mode
Y Y Y Y
Y
Bypass Mode
Y Y
Y
Auto-Restart
Y Y Y Y Y Y Y Y
Y
Cold Start
Y Y Y Y Y Y Y Y
Y
Battery Mode
Delay Time
Y Y Y Y Y Y Y
System
Shutdown
Time
Y Y Y Y Y Y Y Y Y
System
Restore Time
Y Y Y Y Y Y Y Y Y
Charger Test
Y Y Y Y Y
Y
Page 27
23
Battery
Nominal
Battery Voltage
Y Y Y
Battery
Capacity in Ah
Y Y Y Y Y Y Y
Maximum
Charging
Current
Y Y Y
Battery
Low/Shutdown
Setting
Y Y Y Y Y Y Y
Periodic
Battery T e st
Y Y Y Y Y Y Y Y Y
Battery T e st
Interval
Y Y Y Y Y Y Y Y Y
Stop by Time
Y Y Y Y Y Y Y
Y
Stop by Battery
Voltage
Y Y Y Y Y Y Y Y
Stop by Battery
Capacity
Y Y Y Y Y Y Y Y
Battery Age
Alert
Y Y Y Y Y Y Y Y Y
Temperature
Compensation
Y Y Y Y Y Y Y Y Y
Charging
Voltage
Y Y Y
Auto-Restart
Battery Voltage
Y Y Y Y Y Y Y Y Y
Pre-Alarm
Line Voltage
Range
Y Y Y Y Y Y Y Y Y
Line Frequency
Range
Y Y Y Y Y Y Y Y Y
Load
Y Y Y Y Y Y Y Y
Y
Parallel
UPS Parallel Y Y Y
Independent
Battery
Y Y Y
“Y” indicates that available options in each given mode.
Setting Procedure
Step 1: Choose between GENERAL, SYSTEM, BATT ERY and PRE-ALARM. Step 2: Each item wi ll s how c ur rent val ue . Simply click current value and it will list all alternatives in the end.
Step 3: Choose
to confirm the change or choose icon to cance l any modifications.
Figure 3-12 Setting Procedure
Page 28
24
3-2-5-1. Setup-General Screen
The Setup-General screen and setting options are shown in Figure 3-13 and Table 3-6. General Setting can be set in any operating mode.
Figure 3-13 Setup-General Screen
Table 3-6: Setup-General Setting List
Setting Item
Sub Item
Explanation
Model Name
Set UPS Name (xxxxxxxxxx). The max. length is 10 characters .
Language --
Provides 3 optional LCD languages:
English (Default) Traditional Chinese
Simplified Chinese
TIME
Adjust Time
Set current date and time.
(yyyy / mm / dd hour : min : sec)
MUST be set after UPS installation
System Insta ll ed Da te
Set system installed date
(yyyy / mm / dd) 2015/1/1 (Default)
MUST be set after UPS installation
System Last Maintain Date
Set system latest maintenance date
(yyyy / mm / dd)
MUST be set after UPS installation
Battery Instal le d Date
Set battery installed date
(yyyy / mm / dd)
MUST be set after UPS installation
Battery Last Maintain Date
Set battery latest maintenance date
(yyyy / mm / dd)
MUST be set after UPS installation
Baud Rate --
Set COM Port0 Baud Rate
2400 (Default) 4800 9600
Set COM Port1 Baud Rate
2400 (Default) 4800
9600
Audible Alarm --
Set Audible Alarm
Disable
Enable (Default)
Page 29
25
Factory Reset --
Restore to factory default setting Refer to Table 3-7
EEPROM Reset
--
Restore EEPROM to default setting Refer to Table 3-7
EPO Function --
Set EPO active sta t us
Normal Close Active
Normal Open Active (Default)
Password --
Set New Password. 0000 (Default)
Save Setting --
Save all settings to EEPROM.
Use this feature to save the setting(s) you have done.
Startup Screen
Set up initial screen. (xxxxxxxxxxxx). The max. length is 12 characters.
Table 3-7: EEPROM Reset Category List
Setting Item
Factory Reset
EEPROM Reset
General
Model Name
Language Y Y
Adjust Time
System Insta ll ed Da te
Y
System Last Maintain Date
Y
Battery Instal le d Date
Y
Battery Last Maintain Date
Y
Change Password
Y
Baud Rate Y
Audible Alarm
Y
Y
Factory Reset
--
--
EEPROM Reset
--
--
EPO Function
Y
Save Setting
--
--
Startup Sc re en
System
Output Voltage
Y
Bypass Voltage Range
Y
Y
Bypass Frequen cy Ran ge
Y
Y
Converter Mode
Y
Y
ECO Mode Y Y
Bypass Mode
Y
Y
Auto-Restart Y Y
Cold Start Y
Battery Mode Delay Time
Y
Y
System Shutdown Time
Y
Y
System Restore Time
Y
Y
Charger Test
--
--
Battery
Nominal Battery Voltage
Y
Y
Battery Capacity in Ah
Y
Y
Maximum Charging Current
Y
Y
Battery Low/Shutdown Setting
Y
Y
Periodic Batte ry Test
Y
Y
Battery Test Interval
Y
Y
Stop by Time
Y
Y
Stop by Battery Voltage
Y
Y
Stop by Battery Capacity
Y
Y
Battery Age Alert
Y
Y
Temperature Compensation
Y
Y
Charging Voltage
Y
Y
Auto-Restart Battery Voltage
Y
Y
Pre-Alarm
Y
Page 30
26
3-2-5-2. Setup-System Screen
The Setup-System Scr een and setting options are show n in F igur e 3-14 and Table 3-8. System Setting can only be access when UPS is operated in certain mode. Please refer to Table 3-5 for the details. If an option is not available under specifi c mode, a warn ing screen will appear such as in Figure 3-15.
Figure 3-14 Setup-System Screen
Figure 3-15 Warning Screen
Table 3-8: Setup-System Setting List
Setting Item
Sub Item
Explanation
Output Voltage
--
Set output voltage
220Vac (Default) 230Vac 240Vac
MUST be reviewed after UPS installation
BYPASS SETTING
Bypass Voltage Range
Set bypass voltage range:
Upper limit
+10% +15% (Default) +20%
Lower limit
-10% -20% (Default)
-30%
Page 31
27
Bypass Frequen cy Ran ge
Set bypass Frequen cy range:
Upper/ Lower limit
+/- 1Hz +/- 2Hz
+/- 4Hz (Default)
Converter Mode
--
Set converter mode
Disable (Default)
Enable
ECO Mode --
Set ECO mode
Disable (Default)
Enable
Bypass Mode --
Set bypass mode
Disable (Default) Enable
MUST be reviewed after UPS installation.
If you need the Bypass power when UPS is OFF, please enable it.
Auto-Restart --
Set auto-restart
DisableEnable (Default)
After “Enable” is set, once UPS shutdown occurs du e to low
battery an d t hen utili ty re sto re s, t he U PS will re tur n to l ine m ode .
Cold Start --
Set cold start
DisableEnable (Default)
After “Enable” is set, the UPS can be turned on without connecting to utility by pressing Battery Start Button. Refer to
cold start operat ion for the details. (Refer to Section 6-2. Cold
Startup.)
Battery Mode Delay Time
--
Set system shutdown delay time in battery mode (0~9990sec).
0: Disable (Default)Not 0: En able
When this feature is enabled, UPS will shut off output after UPS
operates in Battery mode for certain seconds.
Shutdown/ Restore
System Shutdown Time
Set system shutdown time (0.2~99min)
0.2 min (Default) This dela y tim e wil l sta rt co unti ng whe n the C ONT RO L-Shutdown
Restore command is executed.
System Restore Time
Set system restore time (0~9999min)
1 min (Default) This delay time will s tart cou nting af ter s hutdown tim e is elap sed
when the CONTROL-Shutdown Restore command is executed.
Charger Test --
Set charger test
Disable (Default)
Enable
3-2-5-3. Setup-Battery Screen
The Setup-Battery Screen and Setting options are show n in F igur e 3-16 and Table 3-9. Ba t t e r y Setting can only be set when UPS is operated in STANDBY mode.
Page 32
28
Figure 3-16 Setup-Battery Screen
Table 3-9: Setup-Battery Setting List
Setting Item
Sub Item
Explanation
Nominal Battery Voltage
--
Set battery nominal voltag e
16x12V (Default) 18x12V 20x12V
MUST be set after UPS installation
Battery Capacity in Ah
--
Set battery capacit y. (up to 999)
9Ah (Default)
MUST be set after UPS installation or Battery capacity is
changed.
Maximum Charging Current
--
Set battery maximum charging current (1~24A 100KVA/1~32A
120KVA/1~40A 160KVA/1~48A 200KVA) 2A (Default)
MUST be set after UPS installation or Battery capacity is
changed.
Battery Low/ Shutdo wn Se tti ng
Low Voltage
Set battery low voltage (10.5~11.5V)x(battery Number) 11V x Battery Number (Default)
Low Capacity
Set battery low capacity (20~50%) 20% (Default)
Shutd own Voltage
Set battery voltage point for system shutdown in battery mode
(10.0~11V) x (battery Number)
10V x Battery Number (Default)
Battery Tes t
Periodic Batte ry Test
Set periodic battery test disable or enable
Disable (Default)
Enable
Battery Test Interval
Set battery test interval (7~99 Days) 30 Days (Def ault )
Stop by Time
Set testing time for battery test (10~1000sec) 10 sec (Default)
Stop by Battery Voltage
Set stop battery voltage in battery test (11~12V) x (battery
Number)
11V x Battery Number (Default)
Stop by Battery Capacity
Set battery capacity to stop battery-testing. (20~50%) 20% (Default)
Battery Age Alert
Battery Age Alert (Months)
Set battery age for replacem ent. (Disable,12~60Mont hs)
Disable (Default) If this feature is enabled and the battery has been installed over
this period, the r e is a warnin g “Battery Age Alert” to indicate it.
Page 33
29
Temperature Compensation
--
Set battery temperature compensation. (0~-5 (mV/C/cl)) 0(mV/C/cl) (Default)
Charging Voltage --
Set battery charging voltage. (2.30~2.35V)
2.35V (Default) Set battery float voltage. (2.23~2.35V)
2.29V (Default)
Auto-Restart Battery Voltage
--
Set auto-restart battery voltage. (0 or 12.0V~13.0V) 0V (Default)
3-2-5-4. Pre-Alarm Screen
The Set up-Pre-Alarm Screen and Setting options are sho wn i n Fi g ure 3-17 and Table 3-10. Pre-Alarm Setting can be access in any operatio n mode.
Figure 3-17 Setup-Pre-Alarm Screen
Table 3-10: Setup-Pre-Alarm Setting List
Setting Item
Sub Item
Explanation
Line Voltage Range
--
Set line voltage range:
Upper limit
+5% +10% +15% +20% (Default)
Lower limit
-5% -10% -15%
-20% (Default)
Line Frequency Range
--
Set line frequency range:
Upper / Lower limit
+/- 1Hz +/- 2Hz +/- 3Hz
+/- 4Hz (Default)
Load --
Set UPS overload percentage (40~100%)
100% (Default) Set UPS load unbalance percentage (20~100%)
100% (Default)
Page 34
30
3-2-5-5. Setup-Parallel Screen
Simply t ouch on the “PARALLEL” tab to show parallel function page as shown belo w .
.
Figure 3-18 Setup-Parallel Screen
Refer to Table 3-11 for Setup-Parallel Setting List. Table 3-11: Setup-Parallel Setting List
Setting Item
Sub Item
Explanation
UPS Parallel --
Set UPS parallel
Disable (Default)
Enable
Independent Battery
--
Set Independent Battery
Disable (Default)
Enable
3-2-6. Information Screen
Touch
to enter the sub-menu. In this Information screen, you can check the UPS configuration s.
There are three sub-menus, Identification, Syste m and Batte r y.
Figure 3-19 Information Menu
3-2-6-1. INFORMATION - Identification Screen
When Identification tab is touched, the Model Name, Serial No. and Firmware Version will be displayed as shown in Figure 3-20.
Page 35
31
Figure 3-20 Identification Screen Page
3-2-6-2. INFORMATION - System Screen
When Sys te m sub m enu tab is touched, i nf orm ation such as the system power, nominal voltage, nominal frequency … etc. will be displayed as shown in Figure 3-21 and Figure 3-22. To uch UP and DO WN a r row s t o switch between different pages.
Figure 3-21 INFORMATION System Screen Page 1
Page 36
32
Figure 3-22 INFORMATION System Screen Page 2
3-2-6-3. INFORMATION - Battery Screen
When Battery submenu is selected, the inf ormation such as battery nominal voltage, ca paci ty, charging current … etc. will be displayed as shown in Figure 3-23..
Figure 3-23 INFORMATION Battery Screen Page
3-2-7. Event Screen
When an event occurs, you will see
flashing in the main screen as shown in Figure 3-24. You also
can touch
to check the latest event, history events and reset all events. Refer to Figure 3-25 for
menu tree.
Page 37
33
Figure 3-24 Alarm Warning Screen
Figure 3-25 Events Menu
3-2-7-1. Current Events
When an event occurs, it will display power stage/module ID* and alarm code in Current Events screen. It can save up to 50 events. Only 10 events can be listed per page. Therefore, if it exceeds more than 10, you
have to touch
to read other event as shown in Figure 3-26..
*NOTE: Please refer to section 2 -2 Front Door Open View to identify power stage/module ID.
Figure 3-26 Current Events Screen
Page 38
34
3-2-7-2. History Events
The detailed event information is saved in history events. It can save up to 500 events. When warning occurs, it will display alarm code, alarm time and power stage/module ID*. When fault event occurs, it will display alarm description, alarm time and power stag e/module ID* . (Refer to Table 3-12 Alarm List) I n o rder to record more his torical i nformatio n abou t the UPS system, the imp orta nt cha ng es i n set ting (refe r to Table 3-13 Warning List For Changing Important Settings), UPS operation mode changes (refe r t o Table 3-14 UPS Mode Changes) and c ontrol ac t ion execution (refer to Table 3-15 Control Executio n) will be sa ved in History Events. Refer to Figure 3-27 for the details. *NOTE: Please refer to section 2-2 Front Door Open View to identify power stage/module ID.
Figure 3-27 History Events Screen
3-2-7-3. Reset All Events
It’s necessary to enter administrator password before accessing Reset All Events screen as shown in Figure 3-28.
Figure 3-28 Reset All Events Screen
After entering a correct password, it will prompt for c onfirmed . Then, touch
to reset all events or
touch
to cancel.
Page 39
35
Figure 3-29 Reset All Events Confirmation Screen
3-3. Alarm List
In Table 3-12, it provides the complet e l ist of UPS alarm messages. Table 3-12: Alarm List
Messages in the LCD
Explanation
Fault! Bus Over Voltage
DC bus voltage is too high
Fault! Bus Under Voltage
DC bus voltage is too low
Fault! Bus Voltage Unbalance
DC bus voltage is not balanced
Fa ult! Bus Shor t
DC bus is short
Fault! Bus Soft Start Time Out
The rectifiers can’t start due to low DC bus voltage within specified duration
Fault! Inverter Soft Start Time Out
Inverter bus voltage cannot reach desired voltage within specified duration
Fault! Inverter Voltage Over
Inverter Voltage is over peak value.
Fault! Inverter Voltage High
Inverter Voltage is too high
Fault! Inverter Voltage Low
Inverter Voltage is too low
Fault! R Inverter Voltage Short
R phase inverter output is short-circuited.
Fault ! S Inve rter Voltage Short
S phase inverter outp ut i s short-circuited.
Fault! T Inverter Voltage Short
T phase inverter output is short-circuited.
Fault! RS Inverter Voltage Short
R-S inverter output is short-circuited.
Fault! ST Inverter Voltage Short
S-T inverter output is s ho rt-circuited.
Fault! TR Inverter Voltage Short
T-R inverter output is short-circuited.
Fault! Inverter R Negative Power
R phase inverter output Negative Power over range
Fault! Inverter S Negative Power
S phase inverter output Negative Power over range
Fault! Inverter T Negative Power
T phase inverter output Negative Power over range
Faul t! Over Load Fault
Heavy overload causes UPS fau lt.
Faul t! Battery Fault
Batteries reversed
Fault! Over Temperature
Make sure adequate space is allowed for air ventilation and the fan is working
Faul t! CAN Fa ul t
CAN communication fault
Faul t! TRIG0 Fault
Synchronized trigger s i gnal fault
Fault! Relay F aul t
Inverter relay fault
Fault! Line SCR Fail
Line SCR short circuit fault
Fault! EEPROM Fault
EEPROM operation error
Fault! Parallel Cable Loosen Fault
As stated.
Fault! DSP MCU Stop Communicate
As stated.
Faul t! Bypa ss Temperature Fault
As stated
Faul t! Bypass SCR Fault
As stated.
Page 40
36
Line Fail
Utility lost or abnormal
Line Restore
Utility recovered to normal
Warning! EPO Active
Check the EPO connect or
Warning! Over Load Fail
The load devices are demanding more power than the UPS can supply. Line mode will transfer to Bypass mode.
Warning! Communicate CAN Fail
CAN communication error
Warning ! Over Loa d
In Line mode, the load devi ce s ar e demanding more power than the U P S ca n sup p l y.
Warning! Battery Open
Battery not connected
Warning! Battery voltage High
Battery voltage is too high
Warning! Turn On Abnormal
As stated.
Warning! Charge Fail
As stated.
Warning! EEPROM Fail
EEPROM operation error
War ning! Fan Lock
As stated.
Warning! Line Phase Error
As stated.
Warning! Bypass Phase Error
As stated.
Warning! N Loss
Neutral loss
Warning! Internal Initial Fail
As stated.
Warning! Comm Syn Signal Fail
Communicate synchronization signal fail
Warning! Comm. TRIG0 Fail
Communicate trigger signal fault
Warning! Power Stage loss
Power stage is not detected.
Warning! Parallel Sys Config. Wrong
Parallel system configuration error
War ning! Mai n te nance Bypass
Enter maintenance bypass status
Warning! Battery Age Alert
Battery life expiration
Warning! Parallel UPS Cable Loosen
As stated.
Warning! Parallel UPS Config. Wrong
Parallel UPS configuration error
Warning! Battery Voltage Low
Battery voltage is too low.
Warning! ID Conflict
Power stage/module ID in conflict
Pre-Alarm! Line Voltage Fail
Line voltage over ra nge
Pre-Alarm! Line Voltage Normal
Line voltage recovered to normal
Pre-Alarm! Line Frequency Unstable
Line frequency over range
Pre-Alarm! Line Frequency Normal
Line frequency recovered to normal
Pre-Alarm! Over Load
Output Load over range
Pre-Alarm! Load Normal
Output Load recovered to normal
Pre-Alarm! Load Unbalance
Output Load unbalance
3-4 History Record
Table 3-13: Warning List For Changing Important Settings
Item
No.
Description
Item
No.
Description
1
Setup! Model Name
2
Setup! Turn On Password
3
Setup! Language
4
Setup! Change Turn On Password
5
Setup! Ad j ust Time
6
Setup! Nominal Power Display
7
Setup! System Installed Date
8
Setup! Output Voltage
9
Setup! System Last Maintain Date
10
Setup! Bypass Voltage Range
11
Setup! Battery Installed Date
12
Setup! Bypass Frequency Range
13
Setup! Battery Last Maintain Date
14
Setup! Converter Mode
15
Setup! Change Password
16
Setup! ECO Mode
17
Setup! Baud Rate
18
Setup! Bypass Mo de
19
Setup! Audible Alarm
20
Setup! Auto-Restart
21
Se tu p! Factory Reset
22
Setup! Co ld Start
23
Setup! EEP R OM Reset
24
Setup! Battery Mode Delay Time
25
Setup! EP O F unc tion
26
Setup! Shutdown Rest or e Ti me
27
Setup! Save Setting
28
Setup! Redundancy
29
Setup! Power Rating Setting
30
Setup! Charger Test
31
Setup! Nominal Battery Voltage
32
Setup! Battery Capacity in Ah
Page 41
37
33
Setup! Maximum Charging Current
34
Setup! Battery Low Voltage
35
Setup! Battery Low Capacity
36
Setup! Battery Shutdown Voltage
37
Setup! Periodic Battery Test
38
Setup! St op By Time
39
Setup! BATTERY Age Alert
40
Setup! Temperat ure Compensation
41
Setup! Charging Voltage
42
Setup! PRE-ALARM
43
Setup! UPS Parallel
44
Setup! Independent Battery
45
Setup! Auto-Restart Battery Voltage
Table 3-14: UPS Mode Changes
Item
No.
Description
Item
No.
Description
1
UPS Mode! Power On Mode
2
UPS Mode! Standby Mode
3
UPS Mode! Bypass Mo de
4
UPS Mode! Line Mode
5
UPS Mode! Battery Mode
6
UPS Mode! Battery Test Mode
7
UPS Mode! Fault Mode
8
UPS Mode! Converter Mode
9
UPS Mode! ECO Mode
10
UPS Mode! Shutdown Mode
11
UPS Mode! Un-Connection
Table 3-15: Control Execution
Item
No.
Description
Item
No.
Description
1
Control! System Turn On
2
Control! System Turn Off
3
Control! Manual Battery Test
4
Control! Cancel Battery Test
5
Control! Turn To Bypa ss
6
Control! Shutdow n Res tore
7
Control! Cancel Shutdown
8
Control! Charger Turn On
9
Control! Charger Turn Off
Page 42
38
4. Interface and Communication
As shown in Figure 4-1, there are Battery Temperature sensor port (X1), Emergency Power Off Port (X2), communication port (RS232/USB), SNMP Card slot and extra Comm. card slot on the front panel.
Figure 4-1 Dry Contact Ports and Communication Ports
Dry Contact No.
Function
X1
Battery Temperature Detection Port
X2
Remote EPO input port
4-1. X1- Temperature Detection Port for External Batt ery Pack
The UPS is equipped with battery temperature detection function. UPS can receive battery temperature signal through the temperature detection board. Communication between the UPS and battery temperature detection board is via I 2C c om municatio n p rotocol. X1 is the battery temperature detection port. The port is shown in Figure 4-2 and described in Table 4-1.
Figure 4-2 Battery Temperature Detection Port
Table 4-1 D escript ion of Battery Temperature Detection Port
Name
Position
Description
SCL
X1.1
I²C comm u ni c a ti o n SC L Si g na l
SDA
X1.2
I²C comm u ni c a ti o n SDA Si gnal
+3.0V
X1.3
3V
Power GND
X1.4
GND
Page 43
39
4-2. X2 - Remote EPO Inp ut Port
The UPS is equipped with Emergency Power off (EPO) Function that can be o perat e d by a remote contact assigned by the users. Users can set the logic (N.C or N.O) of this EPO Function through LCD panel.
X2 is the remote EPO input port. This port is shown in Figure 4-3 and described in Table 4-2.
Figure 4-3 Remote EPO Input Port
Table 4-2 Description of Remote EPO Port
EPO Logic Setting
Position
Description
N.C
X2.1 & X2.2
EPO activated when Opened X2.1 & X2.2
N.O
X2.1 & X2.2
EPO activated when Shorted X2.1 & X2.2
If EPO Logic settin g is Norma l Close d ( N.C) , EPO is triggered when pins 1 and pin 2 of X1 are opened. Otherwise, EPO Logic setting is Normal Opened (N.O). EPO is t riggered when pin 1 and pin 2 of X2 are closed.
Note:
1. EPO action shuts down the rectifiers, inverters and static transfer switch. But it does not internally disconnect the input powe r supply.
2. The default settin g of the EPO funct i on logic is Normal Opened (N.O).
4-3. Other Communication Interface
4-3-1. Extra Comm. Slot
There is an optional slot to allow Extra Comm. Card. This option can enhance the communication capability of th e UPS. It provides an additional SNMP slot, dry contact I/P & O/P signals and temperature sensor ports.
4-3-2. Local Communication Ports – RS232 & USB
This UPS is equipped wit h one RS-232 port and one USB port.
Note: The RS232 and USB ports CANNOT work simultaneously .
4-3-3. SNMP Slot
The SNMP card or AS400 card can be inserted into this slot to work with the UPS.
Page 44
40
5. Operation Principles
5-1. Block diagram of UPS
Figure 5-1 Wiring diagram for dual inputs
Figure 5-2 Wiring diagram for single input
Page 45
41
5-2. Operation Mode
This UPS is a three-phase, four-wir e on-line, double-conversion and reverse-transfer UPS that permits operation in the following modes:
Standby Mode Line Mode Battery Mode Bypass Mode ECO Mode Shutdown Mode Maintenance Bypass Mode (manual bypass)
5-2-1. Standby Mode
Upon connecting to utility input power, the UPS is in St andby mode unless UPS is turned on (if BYPASS enable setting is Di sabled), and charger fun ction will be active when the batt ery is connected. The load is not powered under this mode.
Standby Mode Diagr am
5-2-2. Line Mode
In Line Mode, the recti fier delivers power from the mains and supplies DC power to the inverter and the charger charge s the bat tery. The inve rter fil ters t he DC p ower and convert s it int o pure and stabl e AC p ower
Page 46
42
to the load.
Line Mode Diagram
5-2-3. Battery Mode
The UPS a u tomatically tr an sfe r s t o Battery m od e if the Utility f ail s. There is no inte rr uptio n to the load up o n failure. In battery mode, the rectifier delivers power from the battery and supplies DC power to the inverter. The inverter filters the DC power and converts it into pure and stable AC power to the load.
Page 47
43
Battery Mode Diagram
5-2-4. Bypass Mode
Upon co nnecti ng to utili ty inp ut po wer, the UP S is i n Byp ass mo de be fore UP S is t urned o n (if BYPA SS ena ble setting is Enabled), and charger function wil l be a ctive when bat tery is connected.
After UPS has been turned on, if the UPS encounters abnormal situations (over-temperature, overload …, etc.), the static transfer switch will perform as a transference of the load from the inverter to the bypass source with no interr up tion. If the transference i s caused b y a reco v e r a b l e re ason, the U P S wi l l t urn back t o line mode when abnormal situation has been solved.
Bypass Mode Diagram
Page 48
44
5-2-5. ECO Mode
The ECO Mode can be enabled through the LCD control panel. In ECO mode, the load is diverted to bypass when the bypass voltage and frequency are within the acceptable ranges. If the bypass is out of range, the UPS will tr an sfer the power source o f l oad from b yp ass to inverter. In order to shorten the transfer time , t he rectifier and inverter are working when the UPS is in ECO mode.
ECO Mode Diagram
5-2-6. Shutdown Mode
When the UPS is in the off state and the utility power source is absent, the UPS will enter into shutdown mode. Or when the UPS has discharged the battery to the cut-off level, the UPS will also enter into shutdown model. When the UPS enters this mode, it is going to shut off the control power of UPS. The rectifier, charger and inverter will be all shutdown.
Page 49
45
Shutdown Mode Diagram
5-2-7. Maintenance bypass Mode
A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS becomes unavailable e.g. du ring a maintenance procedure. Before entering the maintenance bypass mode, make sure the bypass power source is normal.
Page 50
46
Maintenance By pass Mode Diagram
Page 51
47
6. UPS Operation
Do not start the UPS until the installation is completed.
Make sure the wiring is connected correctly and the power cables are fixed firmly. Make sure the power stage/module ID have b e en configure d correctly. Refer to section 2-2
Power Stage/Module for details.
Make sure all the breakers are switch OFF.
6-1. AC Startup
Use the following procedures when tur nin g on the UPS from a fully powered-down state. Step 1: Refer to “2-4. Wiring Terminal View” to connect the power cables and the battery required for the
UPS system.
Step 2: Switch ON the battery breaker. Step 3: Switch ON the external power switch to power the UPS. Then, LCD panel is displayed as shown
below.
Step 4: Switch ON the input breaker (Q1). The UPS will enter into Standby Mode, if the setting of Bypass mode is disabled.
Or the UPS will enter into Bypass Mode, i f th e sett i ng of Bypass mode is enabled
Page 52
48
Step 5: Make sure that there is no warning or fau lt event. If ye s, please refer t o C hapter 7 Troubleshooting to resolve it .
Step 6: Press POWER button for two seconds to enter into Line Mode as shown below .
After POST ( Power-On Self -Test), the UPS will enter i nto the Line mode.
Step 7: Switch ON the output br eaker (Q3 ). AC startup procedure is now complete.
6-2. Cold Start Startup
Step 1: Switch ON the battery Breaker. Step 2: Press the “Bat tery Sta rt” b utton on a ny one of power stages/modules to start up the control po wer.
Page 53
49
Step 3: After pressing the “Battery Start” button, UPS will enter into Standby mode. Refer to the diagram below for LCD display .
Step 4: Before UPS enters into shutdown mode, please press “POWER” button for 2 seconds immediately as shown in the diagram below.
Step 5: Then, UPS will enter Battery Mode as shown in the diagram below.
Step 6: Switch ON the output breaker (Q3). Cold start startup procedure is complete.
Page 54
50
6-3. Maintenan ce Bypass Operation
If any fault occurs on any one of power sta ges/modules, please follow below steps to transfer to maintenance bypass for maintenance and UPS protection as below.
6-3-1. Transfer to maintenance bypass
Step 1:
Remove the mechanical lock plate of ma intenance bypass.
100KVA/120KVA 160KVA/200KVA
Step 2
Make sure the UPS operates in Bypass mode as shown below.
Step 3
Switch ON the maintenance by pa ss breaker as shown below.
100KVA/120KVA 160KVA/200KVA
Page 55
51
Step 4
Single input model:
Switch OFF t he Input1 B re aker (Q1 ) a s shown below.
Dual input model :
Switch OF F the Inp ut1 B reak er (Q1 ) and Input2 Breaker (Q2) as shown below.
Single input mo de l:
Switch OFF t he Input1 B re aker (Q1 ) a s shown below.
Dual input model :
Switch OFF t he Input1 B re aker (Q1 ), I nput2 Breaker (Q2) and Out put Break er (Q3) a s shown below.
Step 5
It is possible to change the power stage/module now.
6-3-2. Transfer to UPS Protection
Step 1
Make sure the maintenance is complete. All power stages/modules have been installed
well.
Step 2
Single input mo de l:
Switch ON the Input1 Breaker (Q1) as shown below.
Single input mo de l:
Switch ON the Input1 Breaker (Q1) as shown below.
Page 56
52
Dual input model :
Switch ON the Input1 Breaker (Q1) and Input2 Breaker (Q2) as shown below.
100KVA/120KVA
Dual input model :
Switch ON the Input1 Breaker (Q1 ), Input2 Breaker (Q2) and Output Breake r (Q3) as sho wn below
Step 3
Please enter LCD SETUP MENU and choose “SYSTEM” to ensure that the “Bypass
mode” is enabled. If the “Bypass mode” is disabled, you have to set it “enabled”. T hen, exit the SETUP menu and check if the UPS operates in bypass mode.
Step 4 Turn off maintenance bypass breaker as shown below.
100KVA/120KVA 160KVA/200KVA
Step 5 Lock back the mechanical lock plate as shown below.
100KVA/120KVA 160KVA/200KVA
Page 57
53
6-4. Turn off Operation
6-4-1. Turn Off Operation in Bypass Mode/ Standby Mode
When the UPS is neither turned on or off, the UPS operates in the Standby Mode or Bypass Mode, depending on the “Bypa s s Mo d e” Setting .
The LCD diagrams are shown below.
Bypass Mode Setting is Disabled
Bypass Mode Setting is Enabled
Step 1: Switch O FF the Q1 Breaker. The LCD diagrams are shown below.
Bypass Mode Setting is Disabled
UPS enters Shutdown Mode.
It is normal the Un-Connection is shown when power stages have shut off their control power.
Bypass Mode Setting is Enabled
UPS stay in Bypass mode and No AC input is indicated.
Step 2: Switch OFF the external power switch to disconnect the AC power to the UPS. Wait until the LCD is
OFF.
Page 58
54
Step 3: Switch OFF the battery breaker if the UPS will disconnect from the AC power for a long time.
6-4-2. Turn Off Operation in Line Mode
The LCD diagrams are shown below when the UPS operates in the Line Mode.
Step 1: Press “POWER” button for 2 seconds to turn off the UPS. Or use the Menu-Control-System Turn Off to turn off the UPS.
After turning off, the UPS will tranfer to Standby Mode or Bypass Mode, depending on the “Bypass Mode” Setting.
6-4-3. Turn Off Operation in Battery Mode
The LCD dia g ram is s ho w n be l ow when the UPS operates in the Battery Mode.
Step 1: Press “POWER” button for 2 seconds to turn off the UPS. Or use the Menu-Control-System Turn
Off to turn off the UPS.
Page 59
55
After turning off, the UPS will tranfer to Standby Mode.
Page 60
56
7. Trouble Shooting
Most of the Fault and Warning need to be released by authorized service personnel. Few of them can be solved by users themselves.
LCD Message
Explanation
Solution
Fault! Bus Over Voltage
DC bus voltage is too high
Contact service personnel.
Fault! Bus Under Voltage
DC bus voltage is too low
Contact service personnel.
Fault! Bus Voltage
Unbalance
DC bus voltage is not balanced Contact service personnel.
Fault! Bus Short
DC bus is sh ort
Contact service personnel.
Fault! Bus Soft Start Time Out
The rectifiers could not start due to low DC bus voltage within specified duration.
Turn off UPS and then restart the
UPS. If it fails again, contact service personnel.
Fault! Inverter Soft Start Time Out
Inverter voltage cannot reach desired voltage in specified duration.
Turn off UPS and then restart the
UPS. If it fails again, contact service personnel.
Fault! Inverter Voltage Over
Inverter Voltage is over peak value.
Contact service personnel.
Fault! Inverter Voltage High
Inverter Voltage is too high
Contact service personnel.
Fault! Inverter Voltage Low
Inverter Voltage is too Low
Contact service personnel.
Fault! R Inverter Voltage
Short
R phase inverter output is shorted Contact service personnel.
Fault! S Inverter Voltage
Short
S phase inverter output is shorted Contact service personnel.
Fault! T Inverter Voltage
Short
T phase inverter output is shorted Contact service personnel.
Fault! RS Inverter Voltage
Short
R-S inverter output is shorted Contact service personnel.
Fault! ST Inverter Voltage
Short
S-T inverter output is shorted Contact service personnel.
Fault! TR Inverter Voltage
Short
T-R inverter output is shorted Contact service personnel.
Fault! Inverter R Negati ve
Power
R phase inverter output Negative Power
over range
Contact service personnel.
Fault! Inverter S Negative
Power
S phase inverter Output Negative Power
over range
Contact service personnel.
Fault! Inverter T Negative
Power
T phase inverter Output Negative Power
over range
Contact service personnel.
Fault! Over Load Fault
Heavy over load causes UPS fault.
Reduce some load.
Fault! Battery Fault Battery connection is reverse.
Check the polarity of battery
connection and contact service personnel.
Fault! Over T em peratu re
Make sure adequate space is allowed for air vents and the f an is working
Check if the ambient temperature is
over specification. Or contact service personnel.
Fault! CAN Fault
CAN communication fault
Contact service personnel.
Fault! TRIG0 Fau lt
Synchronized trigger signal fault
Contact service personnel.
Fault! Relay Fault
Inverter relay fault
Contact service personnel.
Fault! Line SCR Fail
Line SCR short circuit fault
Contact service personnel.
Page 61
57
Fault! EEPROM Fault
EEPROM operation error
Contact service personnel.
Fault! Parallel Cable Loosen
Fault
As stated.
Check if the para llel cabl e is loose
and contact service personnel.
Fault! DSP MCU Stop
Communicate
As stated.
Contact service personnel.
Fault! Bypass T emper ature Fault
As stated
Check if the ambient temperature is
over specification. Or contact service personnel.
Fault! Bypass SCR Fault
As stated.
Contact service personnel.
Warning! EPO Active Check the EPO connector
Check if the connector is loose
when EPO acts abnormally.
Warning! Over Load Fail
The load devices are demanding more
power than the UPS can supply. Line mode will transfer to Bypass mode.
Reduce some load and check output Load-Capacity and specification
Warning! Communicate CAN
Fail
CAN communication error Contact service personnel.
Warning! Over Load
In Line mode, the load devices are
demanding more power than the UPS can supply.
Reduce some load and check output Load-Capacity and specification
Warning! Battery Open Battery is not connected.
1. Check battery breaker.
2. Check if the battery connection is well connected.
3. Check the setting of Nominal Battery voltage.
4. Contact service personnel if
necessary.
Warning! Battery voltage High
Battery voltage is too High
Check the setting of Nominal
Battery voltage and contact service personnel.
Warning! Turn On Abnormal As stated.
Check if the input voltage or
frequency is out of range.
Warning! Charge Fail
As stated.
Contact service personnel.
Warning! EEPROM Fail
EEPROM operation error
Contact service personnel.
Warning! Fan Lock As stated.
Check if the fan is blocked or
contact service personnel.
Warning! Line Phase Error As stated.
Check if the Mains phase sequence
is correct and contact service personnel.
Warning! Bypass Phase Error
As stated.
Check if the Bypass phase sequence
is correct and contact service personnel.
Warning! N Loss Neutral loss
Check if the Neutral connection is
well and contact service personnel.
Warning! Internal Initial Fail
As stated.
Contact service personnel.
Warning! Comm. Syn. Signal
Fail
Communicate Synchronization Signal
Fail
Contact service personnel.
Warning! Comm. TRIG0 Fail
Communicate Trigger si gnal fault
Contact service personnel.
Warning! Power Stage Lo ss As stated.
Check if the number of power
stage/module installed in the system is correct.
Warning! Parallel Sys
Parallel S ystem Configure error
Contact service personnel.
Page 62
58
Config. Wrong
Warning! Maintenance
Bypass
Enter maintenance
Check if the connector is loose
when it acts abnormally.
Warning! Battery Age Alert Battery Life expiration
Check if the battery has been used
over its service age. Or contact service personnel.
Warning! Parallel UPS Cable
Loosen
As stated.
Check if the Paral lel UPS Cable is
loose and contact service personnel.
Warning! Parallel UPS Config. Wrong
Parallel UPS Configure error
Check the Parallel UPS Setting is
correct and contact service personnel.
Warning! Parallel Firmware Error
Power Stage parallel firmware error
The firmware version does not
support UPS Parallel feature. Contact service personnel.
Warning! ID Conflict Power Stage ID conflict.
There are two Power
Stages/Modules with the same ID numbers. Change the repeated ID to release it. Or contact service personnel.
Page 63
59
8. Storage and Maintenance
8-1. Storage
Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following ta bl e:
Storage Temperature Recharge Frequency Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
8-2. Maintenance
The UPS system ope r a tes with hazardous voltages. Repairs may be carried out only by qualif i e d
maintenance personnel.
Before performaning any kind of service and/or maintenance, disconnect th e batteries and verify
that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
Only qualified maintenance personnel may replace batt eries and supervise operations.
Unauthorized persons must be kept well away from the batteries.
Verify that no voltage between the battery termi nal s a nd the gro u nd i s p re sen t be fore m ai nte na nce
or repair. In this product, the battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery term ina ls and the gr ounding/earthing.
Batteries may cause electric shock and have a high short-circuit current. Please remove all
wristwatches, rings and other conductive objects before maintenance or repair, and only use
tools with insu lated grips and handles for maint a ining or r epa i r ing. When replacing the batteries, install the same number and same type of batteries. Do not attem pt to dispose of batteries by burning the m . Th i s could cause battery explosion. The
batteries must be deposed of a ccording to local environmental regulations.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may
be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
Do not disassemble the UPS system.
Page 64
60
9. Specifications
MODEL
100KL
120KL
160KL
200KL
CAPACITY
100KVA / 90KW
120KVA / 108KW
160KVA / 144KW
200KVA / 180KW
INPUT
Voltage Range
Nominal Volta ge 380V/400V/415V (220V/230V/240V)
Voltage Range (Full Load)
305V ~ 478 V 10 0% lo ad ; (176V ~ 276V)
Voltage Range (De-rating)
208V ~ 304V 70% Load Max(120V ~ 175V*)
Voltage Comeback
Low Loss Voltage +10V , High Loss V oltage -10V
Nominal Frequency
50Hz/60Hz(Auto-selectable)
Frequency Range
40Hz ~ 70Hz
Phase
3 Phase with Neutral(Three Phase, Neutral + Ground)
Synchronized Range
+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz) User Programmable
Power Factor
0.99 at 100% Load
THDi (100% lo ad)
< 3%@Full Load(@Linear L oad)
* De-rating
Mains Input (Bypass)
Voltage Range
Nominal Volta ge 380V/400V/415V
Voltage Range
Upper lim it: + 10 , +1 5 or + 20, defau lt: +1 5%
Lower li mit: -10, -20, -30 default:-20%
Nominal Frequency 50Hz/60Hz(Auto-selectable)
Frequency Range
+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz)
Phase
3 Phase with Neutral(Three Phase, Neutral + Ground)
Synchronized Range
+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz) User Programmable
OUTPUT
Phase
3 Phase with Neu tra l(Three Phase, Neutral + Ground)
Output voltage
380/400/415VAC (Ph-Ph)
220/230/240VAC (Ph-N)
AC Voltage Regulation
< 1% Typical (balanced load) < 2% Typ ical (unb al anc ed lo ad )
Frequency Range (Synchronized Range)
40Hz ~ 70Hz
Frequency Range (Ba tt. Mode )
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mode
1 hour for 105 ~110%, 10 mins for 111~125%, 1 min for 126~150%, 200ms for
>150%
Battery mode
1 hour for 105 ~110%, 10 mins for 111~125%, 1 min for 126~150%, 200ms for
>150%
Current Crest Ratio
3:1 max
Harmonic Distortion
100% line ar load: < 2% 10 0% n onlinear load: < 4%
Transfer Time
Line Battery
0 ms
Inverter Bypass
Synchronous transfer: <= 0ms Asynchronous transfer: < 1 cycle
Inverter ECO
<20 ms
EFFICIENCY
AC mode
94%, Line mode @ 100% R Load
93.5%, Line mode @ 50% R Load
ECO Mode
98%, ECO Mode @ 100% R Load
97%, ECO Mode @ 50% R Load
Battery Mode
93 %, Batte ry mo d e @ 1 00% R L oad
92.5%, Battery mode @ 50% R Load
Page 65
61
MODEL
100KL
120KL
160KL
200KL
BATTERY
Type
Depending on applications
Numbers
32 36 40 (adjustable)
Maximum charging current*
24A**
32A**
40A**
48A**
Floating Voltage
2.29V/cell
Boost Cha rg in g
2.35V/cell
Charger Voltage Regulation
< 1%
Ripple Volta ge
< 1%
Ripple Current (% C10)
< 5
PHYSICAL
Dimension D X W X H mm
945 x 567 x 1015 995 x 567 x 1455
Single input Model
Net Weight(kg)
194 229 301 335
Dual Input Model
Net Weight(kg)
197 232 309 343
ENVIRONMENT
Operation Temperature
0 ~ 40°C
Operation Humidity
<95 % and non-condensing
Operation Altitude***
<1000m**
Acoustic Noise Level
Less than 70dB @ 1 Meter
Less than 73dB @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
Option al SN M P
Power management from SNMP manager and web browser
*NOTE 1:AC Input >200Vac **NOTE 2:Scale=1A ***If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be de-rated 1% per 100m. Product specifications are subject to change without further notice.
Loading...