Power-Sonic PSX12-3.5 User Manual

PSX Series Designed for UPS Applications
(VRLA 6yr Design Life at 20°C)
Dimensions (mm)
134 2
66 2
60 2
-
+
Standard terminal (mm)
F1
67 2
4.75
PSX12-3.5 12V 3.5AH
3.2
6.35
0.8
Physical Specification
Nominal Voltage Nominal Capacity
Length
Width
Dimension
Container Height
Total Height (with terminal)
Weight
Standard Terminal
Constant Current Discharge Characteristics Unit: Amperes (25ºC, 77ºF)
12V
3.5 AH
+
134
2 mm
-
+
67
2 mm
-
+
60
2 mm
-
+
66
2 mm
-
Approx 1.35kg
F1
F.V(V/cell) 15min 1H 3H
1.85 4.91 2.03 0.81
1.80 5.34 2.14 0.87
1.75 5.85 2.24 0.89
1.70 6.24 2.31 0.92
1.67 6.63 2.39 0.95
1.60 6.96 2.47 0.98
Discharge Characteristics (25ºC, 77ºF)
Power
Rating
Capacity
Affected by
Temperature
3hr Rate(1.67V/cell)
1hr Rate(1.67V/cell)
15min Rate(1.67V/cell)
40°C (104°F)
25°C (77°F)
0°C (32°F)
11.04 Watts
27.12 Watts
70.98 Watts
103%
100%
86%
ge
r a h
C e
oltag
Standby
tant V s
on C
Recommended Charge Current less than 0.87A Voltage 13.5V ~
13.8V at 25°C (77°F)
Internal Resistance mΩ
Approx 45.0 mΩ
Constant Power Discharge Characteristics Unit: W atts / Cell (25ºC, 77ºF)
F.V(V/cell) 15min 1H 3H
1.85 9.19 3.91 1.59
1.80 9.89 4.10 1.71
1.75 10.67 4.28 1.73
1.70 11.25 4.40 1.78
1.67 11.83 4.52 1.84
1.60 12.22 4.65 1.89
3 Buckingham Square, Wickford, Essex, SS11 8YQ Tel: +44 (0)1268 560686 Fax: +44 (0)1268 560902
In the event of further technical development we reserve the right to alter our design, specification and price without notice. E&O.E
Power-Sonic Europe Limited
sales@power-sonic.co.uk
www.power-sonic.co.uk
Rev3 - 02/13