![](/html/da/da79/da79255ecfae229bc76660299b2d8e4167bbfde95801f6942e4e7cebdfc23fc2/bg1.png)
12 Volt 82 AH @ 20-hr. rate
PHR-12300
Physical Dimensions: in (mm)
324 W/Cell @ 15-min. rate
Features
• Superb high-rate discharge characteristics that ensure reliable
performance in UPS applications for up to 10 years. UL recognized
• Flame retardant ABS case and cover to UL 94 V-O for superior
performance
• VRLA Absorbent Glass Mat (AGM) Technology guarantees safe
operation without maintenance and “non-restricted article” status for
transportation. Approved for transport by air. D.O.T., I.A.T.A. and
F.A.A. certified.
• Precision plate pasting for higher consistency with 100% load
testing to ensure uniform capacity
• Patented dual-paste process for enhanced active material bonding,
and computer guided volumetric electrolyte control for precision
filling
• Lead-calcium alloy grids and the use of high purity lead account for
superior shelf-life characteristics
Performance Specifications
Nominal Voltage ............................................... 12 volts (6 cells)
Nominal Power (15 min.) .....................................324 W/Cell
H
HT
Rated Capacity
20-hr. (4.10A to 10.80 volts) ...................................... 82.0 AH
10-hr. (8.00A to 10.50 volts) ...................................... 80.0 AH
8-hr. (9.66A to 10.50 volts) ...................................... 77.3 AH
Approximate Weight .................................. 52.5 lbs. (23.8 kg)
016
3
W
M6
Internal Resistance (approx.) ............................. 4.5 milliohms
Max Discharge Current (5 Sec.) ....................... 1230 amperes
Charging Voltage @ 77°F (20° C)
Standby Use ............. 2.275 ± 0.025 V/Cell, (-3.3mV/°C/Cell)
Cycle Use .......................... 2.45±0.05 V/Cell, (-5 mV /°C/Cell)
Maximum Charging Current ........................................ 24.6 A
L: 10.20 (259) W: 6.61 (168) H: 8.19 (208) HT: 8.31 (211)
Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions.
Constant Current Discharge (Amperes) at 25ºC Constant Power Discharge (Watts/Cell) at 25ºC (Blue)
PHR-12300 5 min 10 min 15 min 20 min 30 min 45 min 1h 2h 3h 4h 5h 6h 8h 10h 20h
1.85V 187.0 144.2 126.0 110.2 85.0 63.6 51.2 29.1 20.7 16.2 13.5 11.6 9.19 7.70 4.02
1.80V 214.5 158.9 138.1 118.8 89.5 65.9 52.9 30.0 21.4 16.7 13.9 12.0 9.46 7.86 4.10
1.75V 244.0 178.4 150.2 126.0 93.3 68.0 54.3 30.9 21.9 17.1 14.2 12.3 9.66 8.00 4.17
1.70V 268.6 193.4 160.1 134.1 98.1 70.9 55.9 31.4 22.4 17.6 14.6 12.5 9.82 8.14 4.24
1.67V 297.2 210.6 171.2 140.2 102.3 73.0 57.5 32.0 22.8 17.8 14.8 12.6 9.99 8.28 4.31
1.60V 326.7 227.3 180.7 147.6 106.3 75.7 58.8 32.6 23.1 18.2 15.1 12.9 10.2 8.43 4.36
1.85V 363.7 282.0 247.8 217.9 168.9 127.0 102.5 58.4 41.9 32.9 27.4 23.7 18.8 15.8 8.30
1.80V 413.0 307.7 269.0 232.7 176.4 130.6 105.2 59.9 42.9 33.7 28.1 24.3 19.3 16.1 8.42
1.75V 465.0 342.2 290.0 244.5 182.2 133.6 107.2 61.3 43.7 34.3 28.6 24.7 19.6 16.3 8.53
1.70V 506.0 366.8 305.4 257.5 189.6 137.9 109.5 61.9 44.4 34.9 29.1 25.0 19.8 16.5 8.61
1.67V 555.3 396.5 324.6 267.6 196.7 141.4 112.0 62.7 44.9 35.3 29.4 25.2 20.0 16.7 8.72
1.60V 603.6 423.4 339.1 279.0 202.3 145.1 113.5 63.3 45.1 35.7 29.7 25.5 20.2 16.8 8.73
Case....... ........................... Flame Retardant ABS Plastic (UL 94 V-O)
To ensure safe and efcient operation always refer to the latest edition of our Technical Manual, as published on our website.
All data subject to change without notice.