Datasheet TIS Datasheet (Powersolve)

www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel :01635 521858 Fax: 01635 523771 Email: sales@powersolve.co.uk
Industrial Power Supplies
TIS Series with Function Modules
= Additional Functions for System Applications in
Process Automation, Machine Tools, etc.
= Basic Model Power Supplies can be extended with one
of the following integrated Function Modules:
RED: for True N+1 Redundancy Operation SIG: AC-Power Fail, DC-OK Signal plus Remote On/Off UDS: DC-UPS with automatic Battery Management
Models
Description *Order code Output power Output voltage Output current
max. nominal max. Models with RED Module TIS 150-148 RED 150 Watt 48 VDC 3 A
Models with TIS 300-124 UDS 300 Watt 24 VDC 12 A UDS Module TIS 600-124 UDS 600 Watt 24 VDC 24 A Battery Pack TIS 24-32 AP 24 VDC 3.2 Ah
* includes power supply, relative function module and terminal plugs
TIS 150-124 RED 150 Watt 24 VDC 6 A
TIS 300-124 RED 300 Watt 24 VDC 12 A TIS 300-148 RED 300 Watt 48 VDC 6 A TIS 600-124 RED 600 Watt 24 VDC 24 A TIS 600-148 RED 600 Watt 48 VDC 12 A
TIS 300-124 SIG 300 Watt 24 VDC 12 A TIS 300-148 SIG 300 Watt 48 VDC 6 A TIS 600-124 SIG 600 Watt 24 VDC 24 A TIS 600-148 SIG 600 Watt 48 VDC 12 A
TIS 24-70
AP
24 VDC
7
Ah
RED Module
With this module it is possible to parallel up to 5 power supplies with active current sharing for true N+1 operation. De-coupling diodes (OR-ring diodes) and also alarm output to signal a unit failure are included in this option.
SIG Module
This module provides 3 functions: AC-Power fail signal and DC-OK signal, both with isolated relay contacts. In addition a remote On/Off input is available to control the power supply.
UDS Module
With this module, a professional battery management system to charge and monitor an external battery is added to the basic power supply battery is switched automatically and without any interruption to the DC-output.Power fail and low battery alarm signals are available. During normal operation battery status is checked periodically and the external battery is fully protected under any operation condition.
. In case of a power failure the
Battery Pack
The battery pack contains high quality maintenance free lead-acid batteries with 3.2 Ah resp. 7.0 Ah capacity fixed together with a resetable fuse in a mounting frame. Together with models 124 UDS the battery pack provides a complete and reliable DC-UPS system.Backup time depends on load current and battery capacity.
For further information and specifications please refer to Industrial Power Supplies TIS Series 50–600 Watt. Dimensions same as basic models.
TIS 300-124 UDS or
,
TIS 600-