Powersolve CAC User Manual

www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel:01635 521858 Fax: 01635 523771 Email: sales@powersolve.co.uk
50-22 kWatts
UPS/INVERTERS
C (AC-DC) Series
Specification
CE Marked LVD & EMC
1-4 Outputs
5-400 Volts Output
Parallel Redundant Operation
Fully Wired Customised Racks
Power Factor Correction Modules
Input
DC Input Voltage • See Table AC Input Voltage • See Table Input Frequency • 47-440 Hz No-Load Input Current • 3% of full load current typical Inrush Current • AC/DC limited by thermistor
DC/DC depends on impedance of supply line, see List of Options for Option ‘I’
Earth Leakage • <3.5 mA at 230 VAC, to EN60950
Output
DC Output Voltages • See Table, for voltages above 250 VDC
contact Sales Office
Switch-On Time • 100 ms typical C300-C4700,
500 ms typical C5600-C5800
Hold-Up Time • AC/DC increases with input voltage
15 ms typical at 230 VAC DC/DC depends on input voltage
(typical 2 ms at 12 VDC) Line Regulation • 0.1% (±10% change Vin) Load Regulation • 0.2% (10-90% load) Transient Response • 6% maximum deviation 2ms
C300-C4700, 10ms C5600-C 5800
recovery time to within 1% for load
change 20-100- 20% of full load Ripple & Noise • ≤1% +30 mV pk-pk
(0.5% typical lin. regulator auxiliary) Overvoltage Protection • Standard on single output models &
main output on multi output units Overload Protection • Current limited at 105-110% of full load Temperature Coefficient • 0.02%/°C typical Remote Sensing • Standard for main output
General
Efficiency at Full Load • 60-95%, depending on model Isolation • EN60950 Class 1 Switching Frequency • Approx. 33 KHz MTBF • AC/DC & DC/DC approx 130,000 hrs
at +25 °C
Connector • H 15 DIN 41612 or studs for higher
current outputs C300-C4700, studs only for C5600-C5800
Environmental
Operating Temperature • -20 °C to +75 °C, derate from +55 °C
at 2.5%/°C (Optional -40 °C to +75 °C) Storage Temperature • -40 °C to +85 °C Relative Humidity • 5-95%, non-condensing
EMC & Safety
RFI-Interference • VDE 0878, EN 55022, Level A Construction (Safety) • EN60950 Class 1 Creepage Distance • VDE 0110, 4 mm Air Distance • VDE 0110, 3 mm High-Energy • ENV 50142, Level 3
Pulses/Surges Spike/Bursts • IEC 1000-4-4, Level 3
1
www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel:01635 521858 Fax: 01635 523771 Email: sales@powersolve.co.uk
UPS/INVERTERS
C300 Models, 150 Watt (3U x 14TE x 160 mm, 1 kg)
10-16 Output 18-36 36-75 45-90 80-160 160-320 93-138 Output
Current 185-264 Current
C 300 15.0 A C 320 C 330 C 340 C 350 C 370 C 390 20.0 A 4.5 5.5 C 301 10.0 A C 321 C 331 C 341 C 351 C 371 C 391 15.0 A 8.0 10.0 C 302 8.0 A C 322 C 332 C 342 C 352 C 372 C 392 12.0 A 11.0 13.0 C 303 6.5 A C 323 C 333 C 343 C 353 C 373 C 393 10.0 A 14.0 16.0 C 304 4.0 A C 324 C 334 C 344 C 354 C 374 C 394 6.0 A 23.0 26.0 C 305 3.5 A C 325 C 335 C 345 C 355 C 375 C 395 5.0 A 26.0 30.0 C 309 2.0 A C 329 C 339 C 349 C 359 C 379 C 399 3.0 A 45.0 55.0 C 306 1.6 A C 326 C 336 C 346 C 356 C 376 C 396 2.3 A 58.0 68.0 C 307 0.8 A C 327 C 337 C 347 C 357 C 377 C 397 1.2 A 100.0 130.0 C 308 0.4 A C 328 C 338 C 348 C 358 C 378 C 398 0.6 A 200.0 250.0
Note: 12 TE available upon request - contact Sales Office.
C500 Models, 250 Watt (3U x 21(24)TE x 160 mm, 2.1 kg)
10-16 Output 18-36 Output 36-75 45-90 80-160 160-320 93-138 Output
Current Current 185-264 Current
C 500 25.0 A C 520 30.0 A C 530 C 540 C 550 C 570 C 590 35.0 A 4.5 5.5 C 501 17.0 A C 521 20.0 A C 531 C 541 C 551 C 571 C 591 25.0 A 8.0 10.0 C 502 14.0 A C 522 16.0 A C 532 C 542 C 552 C 572 C 592 20.0 A 11.0 13.0 C 503 11.0 A C 523 13.0 A C 533 C 543 C 553 C 573 C 593 16.0 A 14.0 16.0 C 504 7.0 A C 524 8.0 A C 534 C 544 C 554 C 574 C 594 10.0 A 23.0 26.0 C 505 6.0 A C 525 7.0 A C 535 C 545 C 555 C 575 C 595 8.5 A 26.0 30.0 C 509 3.5 A C 529 4.0 A C 539 C 549 C 559 C 579 C 599 4.5 A 45.0 55.0 C 506 3.0 A C 526 3.5 A C 536 C 546 C 556 C 576 C 596 3.7 A 58.0 68.0 C 507 1.5 A C 527 1.8 A C 537 C 547 C 557 C 577 C 597 2.0 A 100.0 130.0 C 508 0.8 A C 528 0.9 A C 538 C 548 C 558 C 578 C 598 1.0 A 200.0 250.0
INPUT VDC Input VAC OUTPUT VDC
Min Max
INPUT VDC Input VAC OUTPUT VDC
Min Max
C600 Models, 500 Watt (3U x 14 TE x 160 mm, 3.5 kg)
10-16 Output 18-36 Output 36-75 45-90 80-160 160-320 93-138 Output
Current Current 185-264 Current
C 600 50.0 A C 620 70.0 A C 630 C 640 C 650 C 670 C 690 80.0 A 4.5 5.5 C 601 30.0 A C 621 45.0 A C 631 C 641 C 651 C 671 C 691 50.0 A 8.0 10.0 C 602 25.0 A C 622 35.0 A C 632 C 642 C 652 C 672 C 692 40.0 A 11.0 13.0 C 603 20.0 A C 623 28.0 A C 633 C 643 C 653 C 673 C 693 32.0 A 14.0 16.0 C 604 12.0 A C 624 18.0 A C 634 C 644 C 654 C 674 C 694 20.0 A 23.0 26.0 C 605 10.0 A C 625 15.0 A C 635 C 645 C 655 C 675 C 695 17.0 A 26.0 30.0 C 609 6.0 A C 629 8.0 A C 639 C 649 C 659 C 679 C 699 9.0 A 45.0 55.0 C 606 5.0 A C 626 7.0 A C 636 C 646 C 656 C 676 C 696 7.5 A 58.0 68.0 C 607 2.5 A C 627 3.5 A C 637 C 647 C 657 C 677 C 697 4.0 A 100.0 130.0 C 608 1.2 A C 628 1.8 A C 638 C 648 C 658 C 678 C 698 2.0 A 200.0 250.0
INPUT VDC Input VAC OUTPUT VDC
Min Max
C1300 Models, 400 Watt (3U x 14TE x 160 mm, 3.5 kg)
10-16 Output 18-36 Output 36-75 45-90 80-160 160-320 93-138 Output
Current Current 185-264 Current
C 1300 35.0 A C 1320 45.00 A C 1330 C 1340 C 1350 C 1370 C 1390 50.0 A 4.5 5.5 C 1301 24.0 A C 1321 30.00 A C 1331 C 1341 C 1351 C 1371 C 1391 35.0 A 8.0 10.0 C 1302 20.0 A C 1322 25.00 A C 1332 C 1342 C 1352 C 1372 C 1392 30.0 A 11.0 13.0 C 1303 16.0 A C 1323 21.00 A C 1333 C 1343 C 1353 C 1373 C 1393 25.0 A 14.0 16.0 C 1304 10.0 A C 1324 13.00 A C 1334 C 1344 C 1354 C 1374 C 1394 15.0 A 23.0 26.0 C 1305 8.5 A C 1325 11.00 A C 1335 C 1345 C 1355 C 1375 C 1395 13.0 A 26.0 30.0 C 1309 5.0 A C 1329 6.00 A C 1339 C 1349 C 1359 C 1379 C 1399 7.3 A 45.0 55.0 C 1306 4.0 A C 1326 5.00 A C 1336 C 1346 C 1356 C 1376 C 1396 6.0 A 58.0 68.0 C 1307 2.0 A C 1327 2.50 A C 1337 C 1347 C 1357 C 1377 C 1397 3.0 A 100.0 130.0 C 1308 1.0 A C 1328 1.25 A C 1338 C 1348 C 1358 C 1378 C 1398 1.5 A 200.0 250.0
INPUT VDC Input VAC OUTPUT VDC
Min Max
www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel:01635 521858 Fax: 01635 523771 Email: sales@powersolve.co.uk
UPS/INVERTERS
C1500 Models, 600 Watt (6U x 21(24)TE x 160 mm)
10-16 Output 18-36 Output 36-75 45-90 80-160 160-320 93-138 Output
Current Current 185-264 Current
C 1500 40.0 A C 1520 60.0 A C 1530 C 1540 C 1550 C 1570 C 1590 80.0 A 4.5 5.5 C 1501 25.0 A C 1521 38.0 A C 1531 C 1541 C 1551 C 1571 C 1591 50.0 A 8.0 10.0 C 1502 24.0 A C 1522 33.0 A C 1532 C 1542 C 1552 C 1572 C 1592 42.0 A 11.0 13.0 C 1503 20.0 A C 1523 25.0 A C 1533 C 1543 C 1553 C 1573 C 1593 34.0 A 14.0 16.0 C 1504 15.0 A C 1524 18.0 A C 1334 C 1544 C 1554 C 1574 C 1594 23.0 A 23.0 26.0 C 1505 13.0 A C 1525 15.0 A C 1535 C 1545 C 1555 C 1575 C 1595 20.0 A 26.0 30.0 C 1509 7.0 A C 1529 8.0 A C 1539 C 1549 C 1559 C 1579 C 1599 11.0 A 45.0 55.0 C 1506 5.5 A C 1526 6.5 A C 1536 C 1546 C 1556 C 1576 C 1596 9.0 A 58.0 68.0 C 1507 3.0 A C 1527 3.3 A C 1537 C 1547 C 1557 C 1577 C 1597 4.5 A 100.0 130.0 C 1508 1.4 A C 1528 1.6 A C 1538 C 1548 C 1558 C 1578 C 1598 2.4 A 200.0 250.0
C3500 Models, 800 Watt (6U x 21(24)TE x 220 mm, 5 kg)
18-36 Output 36-75 45-90 80-160 160-320 320-380
Current 185-264 Current
C 3520 80.0 A C 3530 C 3540 C 3550 C 3570 C 3580 Z C 3590 100.0 A C 3521 55.0 A C 3531 C 3541 C 3551 C 3571 C 3581 Z C 3591 65.0 A 8.0 10.0 C 3522 50.0 A C 3532 C 3542 C 3552 C 3572 C 3582 Z C 3592 56.0 A 11.0 13.0 C 3523 40.0 A C 3533 C 3543 C 3553 C 3573 C 3583 Z C 3593 45.0 A 14.0 16.0 C 3524 27.0 A C 3534 C 3544 C 3554 C 3574 C 3584 Z C 3594 30.0 A 23.0 26.0 C 3525 23.0 A C 3535 C 3545 C 3555 C 3575 C 3585 Z C 3595 27.0 A 26.0 30.0 C 3529 12.0 A C 3539 C 3549 C 3559 C 3579 C 3589 Z C 3599 14.0 A 45.0 55.0 C 3526 10.0 A C 3536 C 3546 C 3556 C 3576 C 3586 Z C 3596 12.0 A 58.0 68.0 C 3527 5.3 A C 3537 C 3547 C 3557 C 3577 C 3587 Z C 3597 6.5 A 100.0 130.0 C 3528 2.8 A C 3538 C 3548 C 3558 C 3578 C 3588 Z C 3598 3.5 A 200.0 250.0
INPUT VDC Input VAC OUTPUT VDC
Min Max
INPUT VDC Input VAC OUTPUT VDC
(1)
93-138 Output
(2)
Min Max
4.5 5.5
C3700 Models, 1250 Watt (6U x 21(24)TE x 220 mm, 6.5 kg)
18-36 Output 36-75 45-90 80-160 160-320 320-380
C 3720 120 A C 3721 80 A C 3731 C 3741 C 3751 C 3771 C 3781 Z C 3791 100 A 8.0 10.0 C 3722 70 A C 3732 C 3742 C 3752 C 3772 C 3782 Z C 3792 85 A 11.0 13.0 C 3723 56 A C 3733 C 3743 C 3753 C 3773 C 3783 Z C 3793 70 A 14.0 16.0 C 3724 40 A C 3734 C 3744 C 3754 C 3774 C 3784 Z C 3794 50 A 23.0 26.0 C 3725 35 A C 3735 C 3745 C 3755 C 3775 C 3785 Z C 3795 42 A 26.0 30.0 C 3729 19 A C 3739 C 3749 C 3759 C 3779 C 3789 Z C 3799 23 A 45.0 55.0 C 3726 15 A C 3736 C 3746 C 3756 C 3776 C 3786 Z C 3796 18 A 58.0 68.0 C 3727 8 A C 3737 C 3747 C 3757 C 3777 C 3787 Z C 3797 10 A 100.0 130.0 C 3728 4 A C 3738 C 3748 C 3758 C 3778 C 3788 Z C 3798 5 A 200.0 250.0
Current 185-264 Current
(2)
C 3730 C 3740 C 3750 C 3770 C 3780 Z C 3790 150 A
INPUT VDC Input VAC OUTPUT VDC
(1)
93-138 Output
(2)
Min Max
4.5 5.5
C3600 Models, 1700 Watt (6U x 42TE x 220 mm)
18-36 Output 36-75 45-90 80-160 160-320 320-380
C 3620 180.0 A C 3621 120.0 A C 3631 C 3641 C 3651 C 3671 C 3681 Z C 3691 130 A 8.0 10.0 C 3622 100.0 A C 3632 C 3642 C 3652 C 3672 C 3682 Z C 3692 115 A 11.0 13.0 C 3623 80.0 A C 3633 C 3643 C 3653 C 3673 C 3683 Z C 3693 90 A 14.0 16.0 C 3624 55.0 A C 3634 C 3644 C 3654 C 3674 C 3684 Z C 3694 65 A 23.0 26.0 C 3625 48.0 A C 3635 C 3645 C 3655 C 3675 C 3685 Z C 3695 55 A 26.0 30.0 C 3629 26.0 A C 3639 C 3649 C 3659 C 3679 C 3689 Z C 3699 30 A 45.0 55.0 C 3626 21.0 A C 3636 C 3646 C 3656 C 3676 C 3686 Z C 3696 25 A 58.0 68.0 C 3627 11.0 A C 3637 C 3647 C 3657 C 3677 C 3687 Z C 3697 14 A 100.0 130.0 C 3628 5.5 A C 3638 C 3648 C 3658 C 3678 C 3688 Z C 3698 7 A 200.0 250.0
Notes:
1. Models supplied by external PFC module.
2. External fan recommended.
Current 185-264 Current
(2)
C 3630 C 3640 C 3650 C 3670 C 3680 Z C 3690 150 A
INPUT VDC Input VAC OUTPUT VDC
3. Three phase input versions available - contact Sales Office.
(1)
93-138 Output
(2)
Min Max
4.5 5.5
www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel:01635 521858 Fax: 01635 523771 Email: sales@powersolve.co.uk
UPS/INVERTERS
C4700 Models, 2500 Watt (6U x 28TE x 300 mm, 8 kg)
10-16 Output 20-32 Output 40-64 50-80 Output 80-160 160-320 320-380
INPUT VDC Input VAC Output VDC
Current Current Current 185-264 Current
C 4700 100.0 A
(2)
C 4720 160 A C 4701 60.0 A C 4721 110 A C 4702 55.0 A C 4722 95 A C 4703 50.0 A C 4723 80 A C 4733 C 4743 100 A
(2)
C 4730 C 4740 180 A
(2)
C 4731 C 4741 140 A
(2)
C 4732 C 4742 120 A
(2)
C 4750 C 4770 C 4780 Z C 4790 180 A
(2)
C 4751 C 4771 C 4781 Z C 4791 150 A
(2)
C 4752 C 4772 C 4782 Z C 4792 130 A
(2)
C 4753 C 4773 C 4783 Z C 4793 110 A C 4704 32.0 A C 4724 60 A C 4734 C 4744 70 A C 4754 C 4774 C 4784 Z C 4794 80 A 23.0 26.0 C 4705 28.0 A C 4725 50 A C 4735 C 4745 65 A C 4755 C 4775 C 4785 Z C 4795 70 A 26.0 30.0 C 4709 16.0 A C 4729 30 A C 4739 C 4749 40 A C 4759 C 4779 C 4789 Z C 4799 40 A 45.0 55.0 C 4706 13.0 A C 4726 25 A C 4736 C 4746 28 A C 4756 C 4776 C 4786 Z C 4796 30 A 58.0 68.0 C 4707 7.0 A C 4727 12 A C 4737 C 4747 18 A C 4757 C 4777 C 4787 Z C 4797 20 A 100.0 130.0 C 4708 3.5 A C 4728 6 A C 4738 C 4748 10 A C 4758 C 4778 C 4788 Z C 4798 10 A 200.0 250.0
Notes:
1. Models supplied by external PFC module.
2. External fan recommended.
3. Three phase input versions available - contact Sales Office.
C4800 Models, 5000 Watt (6U x 56TE x 300 mm, 18 kg)
20-32 Output 40-64 50-80 Output 80-160 160-320 320-380
INPUT VDC Input VAC Output VDC
C 4822 190 A C 4823 160 A C 4824 120 A C 4825 100 A C 4829 60 A C 4826 50 A C 4827 24 A C 4828 12 A
(3)(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
C 4832 C 4833
(4)
(4)
C 4842 C 4843
(4)
(4)
240 A 200 A
(3)(4)
(4)
C 4852 C 4853
(4)
(4)
C 4872 C 4873
(4)
(4)
C 4834 C 4844 150 A C 4854 C 4874 C 4884 Z C 4894 160 A 23.0 26.0 C 4835 C 4845 130 A C 4855 C 4875 C 4885 Z C 4895 140 A 26.0 30.0 C 4839 C 4849 80 A C 4859 C 4879 C 4889 Z C 4899 80 A 45.0 55.0 C 4836 C 4846 56 A C 4856 C 4876 C 4886 Z C 4896 60 A 58.0 68.0 C 4837 C 4847 36 A C 4857 C 4877 C 4887 Z C 4897 40 A 100.0 130.0 C 4838 C 4848 20 A C 4858 C 4878 C 4888 Z C 4898 20 A 200.0 250.0
Current Current 185-264 Current
Notes:
1. Models supplied by external PFC module.
2. Three phase input versions available - contact Sales Office.
3. With temperature controlled fans.
4. Wall mount only (plug-in units on request) 360(450)x280(320)x310mm (HxWxD).
(1)
C 4882 Z C 4883 Z
C5640 Models, 6000 Watt (6/9U x 19” x 360/460 mm, up to 65 kg)
40-64 50-80 Output 80-160 160-320 3 x 200 3 x 480 Output Min Max
C 5630 C 5640 360 A C 5650 C 5670 C 5660 V C 5690 V 400 A 4.56 5.5 C 5631 C 5641 280 A C 5651 C 5671 C 5661 V C 5691 V 400 A 8.00 10.0 C 5632 C 5642 240 A C 5652 C 5672 C 5662 V C 5692 V 400 A 11.0 13.0 C 5633 C 5643 200 A C 5653 C 5673 C 5663 V C 5693 V 375 A 14.0 16.0 C 5634 C 5644 150 A C 5654 C 5674 C 5664 V C 5694 V 230 A 23.0 26.0 C 5635 C 5645 130 A C 5655 C 5675 C 5665 V C 5695 V 200 A 26.0 30.0 C 5639 C 5649 80 A C 5659 C 5679 C 5669 V C 5699 V 110 A 45.0 55.0 C 5630 C 5646 56 A C 5656 C 5676 C 5666 V C 5696 V 88 A 58.0 68.0 C 5630 C 5647 36 A C 5657 C 5677 C 5667 V C 5697 V 46 A 100.0 130.0 C 5630 C 5648 20 A C 5658 C 5678 C 5668 V C 5698 V 24 A 200.0 250.0
INPUT VDC Input VAC Output VDC
Current 160-230 400-530 Current
C5700 Models, 8000 Watt (6/9U x 19” x 360/460 mm, up to 65 kg)
40-64 50-80 Output 80-160 160-320 320-640 450-800 3 x 200 3 x 480 Output Min Max
Current 160-230 400-530 Current
C 5730 C 5740 400 A 4.5 5.5 C 5731 C 5741 400 A 8.0 10.0 C 5732 C 5742 360 A 11.0 13.0 C 5733 C 5743 300 A C 5753 C 5773 C 5773 G C 5773 K C 5763 V C 5793 V 400 A 14.0 16.0 C 5734 C 5744 225 A C 5754 C 5774 C 5774 G C 5774 K C 5764 V C 5794 V 310 A 23.0 26.0 C 5735 C 5745 195 A C 5755 C 5775 C 5775 G C 5775 K C 5765 V C 5795 V 270 A 26.0 30.0 C 5739 C 5749 120 A C 5759 C 5779 C 5779 G C 5779 K C 5769 V C 5799 V 145 A 45.0 55.0 C 5736 C 5746 84 A C 5756 C 5776 C 5776 G C 5776 K C 5766 V C 5796 V 120 A 58.0 68.0 C 5737 C 5747 54 A C 5757 C 5777 C 5777 G C 5777 K C 5767 V C 5797 V 62 A 100.0 130.0 C 5738 C 5748 30 A C 5758 C 5778 C 5778 G C 5778 K C 5768 V C 5798 V 32 A 200.0 250.0
Notes:
1. C5640 & C5700 single phase input version available - contact Sales Office.
INPUT VDC Input VAC Output VDC
(1)
93-138 Output Min Max
(2)
(2)
(2)
11.0 13.0
(2)
14.0 16.0
93-138 Output Min Max
(4)
(4)
C 4892 C 4893
(4)
(4)
260 A 220 A
(3)
(3)
11.0 13.0
14.0 16.0
4.5 5.5
8.0 10.0
www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel:01635 521858 Fax: 01635 523771 Email: sales@powersolve.co.uk
UPS/INVERTERS
C5800 Models, 12000 Watt (6/9U x 19” x 360/460 mm, up to 65 kg)
80-160 160-320 320-640 450-800 Output 3 x 200 3 x 480 Min Max
C 5854 C 5874 C 5874 G C 5874 K 400 A C 5864 V C 5894 V 23 26 C 5855 C 5875 C 5874 G C 5875 K 400 A C 5865 V C 5895 V 26 30 C 5859 C 5879 C 5874 G C 5879 K 220 A C 5869 V C 5899 V 45 55 C 5856 C 5876 C 5874 G C 5876 K 180 A C 5866 V C 5896 V 58 68 C 5857 C 5877 C 5874 G C 5877 K 92 A C 5867 V C 5897 V 100 130 C 5858 C 5878 C 5874 G C 5878 K 48 A C 5868 V C 5898 V 200 250
Notes:
1. Single phase input versions available - contact Sales Office.
Wall Mounting Options
Input VDC Input VAC Output VDC
Current 160-230 400-530
Angles
Option Series Width Height Depth
W1
W1a
W1b 1500 140 mm 360 mm 260 mm
W1c 4700 140 mm 360 mm 340 mm
300 500
1300 1500 3500
3700
1200
1300
3500
3700
140 mm 220 mm 180 mm
(1)
(1)
140 mm 300 mm 260 mm
(1)
(1)
Plates
Option Series Width Height Depth
W2
W3 3600 220 mm 360 mm -
W4
600
220 mm 220 mm -
2600
3800
280 mm 360 mm -
4800
Plates
Option Series Width Height Depth
W5a 500 mm 400 mm ­W5b 5000 500 mm 600 mm ­W5c 500 mm 800 mm -
Notes:
1. No space available for conductor underneath module.
2. The size of the module plate depends on model size and output power, and on any additional equipment to be included - contact Technical Sales.
www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel:01635 521858 Fax: 01635 523771 Email: sales@powersolve.co.uk
UPS/INVERTERS
Options
Options
C5600
C500
C300
Designation
Tropical protection T• • • • • • • • • • • • • Extended temp. range C• • • • • • • • • • • • • Increased mech. strength MS •••••••••••••
Mech
Wall mounting W• • • • • • • • • • • • • Inrush current limiting Series diode SD Anti-parallel diode AD
Input
Autoranging AU Decoupling diode DD Active current sharing CS Inhibit (to be specified) H
Output
Externally programmable E Power fail P• • • • • • • • • • • • • DC-OK one output D• • • • • • • • • • • • • Signals with relay R
Signals
Notes:
1. Standard for mains input modelto Series C3700.
Option is available in combination with other options.
(1)
I
************* ************* * ********* * ************
**** *************
********
* ** * * * *
**
Option T (Tropical protection):
The unit is given additional protection by a heavy coat of varnish on the printed circuit board(s) and components.
Option C (Extended temperature range):
Units are designed & tested for operation at an ambient temperature down to -40 ºC.
Option MS (Increased mechanical strength):
Screws are fastened by Locktite and heavy components are fastened by ties or glue to following specification. Vibration: 2 – 2000 Hz at 2 G, Shock: 10 G for 11 ms to DIN 40046 part 7.
Option W (Wall mounting):
Module is screwed to a mounting plate for installation within a cabinet).
Option I (Inrush current limiting):
A thermistor is connected in series with the input lines which changes its resistance from high to low when it gets hot. It does not reduce the current surge if the input power is interrupted for a short period of time not allowing the thermistor to cool down. Electronic inrush current limiting device is available upon request.
Option SD (Series diode):
A series diode is connected on the input of the module to protect the unit from reverse input polarity connection.
Option AD (Parallel diode):
A diode is provided in parallel to the input. Should the input to the module be reverse-connected, the input fuse (either internal or external fuse) will blow, protecting the unit.
Option DD (Decoupling diode):
For redundant operation the outputs of two or more units are paralleled behind de-coupling diodes so that an internal fault of one module does not affect the operation of the others. These diodes cause power losses. For high currents the de-coupling diode may have to be installed externally.
Option SD, AD & DD:
May need to be fitted externally - contact sales office.
Option CS (Active current sharing):
C600
C1300
C1500
•••••••••
••••••••
Option is available with certain restrictions - contact Sales Office.
*
Option AU (Auto-ranging):
In standard dual AC input units (115/230 VAC) the range is selected by connecting the input line to different pins on the connector. With auto­ranging the unit senses the input voltage and automatically provides the correct connection.
Option H (Inhibit):
Operation of the unit is inhibited if a voltage signal (5 V/10 mA) is applied in reference to the negative line of the (main) output. Alternatively, a connector pin connected to the negative input line also shuts off the converter (to be specified). This can also be used in conjunction with a thermal trip which shuts unit down.
Option E (Programmable by ext. signal):
An ext. signal applied with reference to the negative output line programs the output voltage.
Option P (Power fail):
A signal (logic or relay) is given if the input voltage drops below the specified limit. In AC input units we sense the rectified input voltage so that a power fail alarm can be avoided if at light load mains power returns before the input capacitors are substantially discharged.
Option D (DC-OK, one output):
A signal (logic or relay) is given if the voltage of the main output is below the specified limit. In multi-output systems the main output is monitored.
Option M (DC-OK, all outputs):
In multi-output systems a signal is provided if the voltage of any output is below the specified limit.
Option AC (AC-OK)
A logic signal is given if the output voltage of an inverter is below the specified limit.
Option R (Relay):
Options P, D and M are available in conjunction with option R. A relay is provided for indication instead of a logic signal with a N.O., N.C. or changeover contact (to be specified).
Option ‘Y’ (Sys-reset):
This logic signal is a combination of power fail and DC-OK as specified for VME systems.
C3500
C3600
C3700
C4700
•••••
C4800
* **
By means of an additional control circuit active current sharing is provided via an interconnecting wire between 2 or more units.
C5700
C5800
www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel:01635 521858 Fax: 01635 523771 Email: sales@powersolve.co.uk
UPS/INVERTERS
C640 Models, 22 kW PSU
Specification
High Power Density
45-800 Volts Output
19” Rack Mounting
Parallel Redundant Operation
Temperature Controlled Fans
Input
Input Voltage • 320-800 VDC or 400/480 VAC Input Frequency • 47-440 Hz
Output
Output Voltage • Up to 800 VDC Output Current • Up to 360 A Output Power • Up to 22 kW Line Regulation • 0.1%(±10%) Load Regulation • 0.2%(10-90%) Ripple & Noise • 0.5% rms Overload Protection • Current limited to 105%-110% of full load Overvoltage Protecton • OVP switches off module with automatic
return to operation
Remote Sense • Up to 3 V per wire
General
Efficiency • 90% typical Input/Output • Input to Output 3500 VDC
Isolation Voltage Input to Earth 3500 VDC
Output to Earth 3500 VDC Output to Earth <60-700 VDC <60-250 V - 2100 VDC
>250 V - 3500 V DC Connector • Terminals/copper bars Dimensions • 8U x 19” x 600mm (355 x 483 x 600 mm) Weight • 90 kg
Environmental
Operating Temperature • -10 °C to +50 °C Storage Temperature • -40 °C to +85 °C
EMC & Safety
Emissions • EN55022, Class A EFT/Burst • EN61000-4-4 Level 3 Surges EN61000-4-5 Level 3 Safety • EN60950, Class 1
320-640 VDC 450-800 VDC 3 x 400 VAC 3 x 480 VAC Output Minimum Maximum
C 6479 G C 6479 K C 6489 V C 6499 V 360 A 45 55 C 6476 G C 6476 K C 6486 V C 6496 V 320 A 58 68 C 6477 G C 6477 K C 6487 V C 6497 V 170 A 100 130 C 6477 GJ C 6477 KJ C 6487 VJ C 6497 VJ 110 A 190 200 C 6478 G C 6478 K C 6488 V C 6498 V 88 A 200 250 C 6478 GJ C 6478 KJ C 6488 VJ C 6498 VJ 55 A 380 400 C 6477 GH C 6477 KH C 6487 VH C 6497 VH 36 A 570 600 C 6478 GH C 6478 KH C 6488 VH C 6498 VH 27 A 760 800
Notes:
1. For input voltage <400 VDC output power available reduces by 20%.
Input VDC Input VAC Output VDC
(320-460) (400-530) Current
Options
• Inrush current limiting
• Input polarity protection for DC input
• Output decoupling diode for redundant/parallel operation (depending on output current)
• Active current sharing for parallel operation
• Remote ON/OFF (inhibit)
• Monitoring of input and output voltage
• Output programmable via analogue signal
• RS232 or IEEE488 interface
• Automatic/manual selection of charging voltage
• Digital V- and A- meter
• Tropical protection
www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel:01635 521858 Fax: 01635 523771 Email: sales@powersolve.co.uk
UPS/INVERTERS
C Series Versatility
With over 3000 standard modules and many more modified and custom-built units available, the C Series of AC-DC and DC-DC Converters can be used in a wide variety of applications and environments.
Standard Modules
Standard modules are supplied in either Euro-Cassette or 19” rack mount formats depending on power rating.
Sub-Racks
Fully wired sub-racks can be configured as 3U, 6U or 9U allowing any mix of units - including ‘hot swap redundant systems complete with alarms, monitoring and controls.
Wall Plates
For customers looking to install units in their own cabinets the C Series can be supplied to a wall plate (W option). Units come fitted to a vertical mounting plate complete with screw terminals.
Customer Specific
In addition to the ‘W’ option, units can be configured into complete stand-alone systems. The picture opposite shows a switchmode battery charger specifically designed for installation into a lighthouse. It has been mounted in a stainless steel cabinet to withstand a salt water environment.