Powers SH1434 User Manual

HydroGuard
®
XP SH1434 & LFSH1434 Triple,
Quad & Six Valve Hi/Lo Supply Fixture
Technical Instructions
Description n
Powers' HydroGuard® XP Series SH1434 & LFSH1434 Triple, Quad and Six Valve Hi/Lo's are fully assembled, factory tested systems, designed to provide safe water throughout commercial and institutional facilities. Each consists of MM434 or LFMM434 and SH1434 or LFSH1434 Master Tempering Valves which utilize par­affin-based actuation technology to sense and adjust outlet temperature. Each system includes a PRV, ball valves, pressure/temperature gauges and Powers' triple-duty check stops and are supported by heavy-duty welded struts. Optional equipment includes cabinets and/or Powers' AquaSentry® 2 high-temperature alarm system. (Not available with LFSH1434 Series).
Operation n
The Triple, Quad and Six Valves Hi/Lo feature one low capacity valve that works in parallel with multiple high capacity valves. During low demand, the low capacity valve handles the load requirements. As the load demand increases, the pres­sure reducing valve, which is set at a certain pressure differential, will open and allow flow through the high capacity valves to assist the low capacity valve in meeting the increased load requirements.
IS-P-SF-SH1434-TV_QV_6V
Specifications n
Maximum Operating Pressure ............................. 125psi (861 kPa)
Maximum Hot Water Temperature ...................... 200°F (93°C)
Minimum Hot Water Supply Temp* .................... 5°F (3°C) Above Set Point
Hot Water Inlet Temperature Range ................... 120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range ................. 40 - 80°F (4 - 27°C)
Minimum Flow** ...................................................... 0.5 gpm (1.89 lpm)
Temp. Adjustment Range *** ............................... 90 - 160°F (32 - 71°C)
Listing/Compliance (Valve Only)............................ ASSE 1017, CSA B125
*With Equal Pressure **Minimum flow when Hi/Lo valve is installed at or near hot water source recirculating tempered water with a properly sized continuously operating recirculating pump. ***Note: Low limit cannot be less than the cold water temperature. For best operation, hot water should be at least 5°F (3°C) above desired set point.
Table 1 Capacity n
Flow Capacity at 50-50 Mixed Ratio
Pressure Drop Across Valve
Model
SH1434TV and
LFSH1434TV
SH1434QV and
LFSH1434QV
SH1434-6V and
LFSH1434-6V
Min. Flow
to ASSE 1017
1 gpm
4 lpm 526 lpm 742 lpm 1049 lpm 1287 lpm 1575 lpm 1817 lpm
1 gpm
4 lpm 704 lpm 996 lpm 1412 lpm 1726 lpm 2116 lpm 2442 lpm
1 gpm
4 lpm 1067 lpm 1514 lpm 2139 lpm 2620 lpm 3206 lpm 3702 lpm
C
V
62.0
83.3
126.3
5psi 10psi 20psi 30psi 45psi 60psi
(34 kPa) (69 kPa) (138 kPa) (207 kPa) (310 kPa) (414 kPa)
139 gpm 196 gpm 277 gpm 340 gpm 416 gpm 480 gpm
186 gpm 263 gpm 373 gpm 456 gpm 559 gpm 645 gpm
282 gpm 400 gpm 565 gpm 692 gpm 847 gpm 978 gpm
WARNING: TO ENSURE THE ACCURATE AND RELIABLE
!
OPERATION OF THIS PRODUCT, IT IS ESSENTIAL TO:
• Properly size each valve based on the indi­vidual application.
• Properly design the recirculation system to
minimize pressure and temperature variations.
• Conduct an annual maintenance program to
ensure proper operation of all critical com­ponents.
THIS VALVE MUST BE USED IN CONJUNCTION WITH TEMPERATURE ACTUATED POINT-OF-USE DEVICES THAT COMPLY WITH ASSE 1016, 1069, OR 1070. FAILURE TO COMPLY WITH PROPER INSTALLATION INSTRUCTIONS COULD CONTRIBUTE TO VALVE FAILURE, RESULTING IN IN JURY OR DEATH.
Prior to Installation
SH1434
#1 - MM434
#2 - MM434
Screw
1. Flush all piping thoroughly before installing.
2. Make sure all ball valve handles are in "OFF" position.
3. In order to make any temperature adjustment to the valves, you must open end-of-line fixtures to ensure you have ade­quate flow across the valve.
4. Use a thermometer at the showerhead or install an in-line thermometer at the point-of-use.
SH1434TV & LFSH1434TV
1. Close the ball valve at the outlet of the SH1434 or LFSH1434 and MM434 or LFMM434 valve #2.
2. Open the ball valve at the outlet of the MM434 or LFMM434 valve #1.
3. Open enough fixtures to meet the minimum flow requirement of the MM434 or LFMM434 valve #1 as per table 2.
4. Set MM434 or LFMM434 valve #1 temperature (refer to IS-P­MM430 if required).
5. Close ball valve at the outlet of the MM434 or LFMM434 valve #1 and open the ball valve at the outlet of the MM434 or LFMM434 valve #2. Repeat steps 3 and 4.
6. Loosen the locknut at the top of the PRV. This must be all the way out or you will be limiting range of the adjustment.
7. Adjust the PRV so the outlet pressure gauge (top) reads 15psi less than the supply pressure gauge (bottom). Turning the adjustment screw counterclockwise will increase the differ­ential across the PRV (allowing the PRV to open later).
8. Close the ball valve at the discharge of the MM434 or LFMM434 valve #2.
9. Open the ball valve on the outlet of the SH1434 or LFSH1434 valve.
10. Open enough fixtures to meet the minimum flow requirement
of SH1434 or LFSH1434 as per table 2.
11. Set SH1434 or LFSH1434 temperature (refer to IS-P- SH1430
if required).
12. Open all the ball valves at the outlets.
13. Verify outlet temperature remains at the set point.
14. For any problem, refer to Troubleshooting section of the
document or contact Powers' Technical Support Department at 1.800.669.5430 or info@powerscontrols.com.
Set Up Procedure nInstallation Instructions n
You must follow these procedures in order to properly adjust your Hi/Lo System. You need flow greater than the minimum shown in the capacity table across the valve in order to set a maximum temperature.
SH1434 or LFSH1434
#1 - MM434 or
LFMM434
#2 - MM434 or
LFMM434
Table 2
Model
MM434 and LFMM434 7 gpm (26 lpm)
SH1434 and LFSH1434 1 gpm (4 lpm)
Min. Flow to ASSE 1017
SH1434QV or LFSH1434QV
1. Close the ball valve at the outlet of the SH1434 or LFSH1434 and MM434 or LFMM434 valve #2 & #3.
2. Open the ball valve at the outlet of the MM434 valve #1.
3. Open enough fixtures to meet the minimum flow requirement of the MM434 or LFMM434 valve #1 as per table 2.
4. Set MM434 or LFMM434 valve #1 temperature (refer to IS-P­MM430 if required).
5. Close ball valve at the outlet of the MM434 or LFMM434 valve #1 and open the ball valve at the outlet of the MM434 or LFMM434 valve #2. Repeat steps 3 and 4.
6. Close ball valve at the outlet of the MM434 or LFMM434 valve #2 and open the ball valve at the outlet of the MM434 or LFMM434 valve #3. Repeat steps 3 and 4.
7. Loosen the locknut at the top of the PRV. This must be all the way out or you will be limiting range of the adjustment.
2
Loading...
+ 2 hidden pages