![](/html/85/85f3/85f38a9779e1dfa2b6e3b73002ee994c2f1c75d512c2f959808e0527cefa373c/bg1.png)
LiFe Premium Installaon and Operaon Manual - REV04 1
+61 3 8797 5557 | info@powerplus-energy.com.au | 4, 21 Power Road Bayswater Vic 3153 | powerplus-energy.com.au
![](/html/85/85f3/85f38a9779e1dfa2b6e3b73002ee994c2f1c75d512c2f959808e0527cefa373c/bg2.png)
LiFe Premium Installaon and Operaon Manual - REV04 2
Contents
Introduction 3
Safety 4
Transportation 4
Basic Safety 5
Handling 5
Damaged Battery 5
Fire 6
Qualified installation person (Installer) 6
Product Information 7
Weight and Dimensions 7
Specifications 8
Charging and discharging 9
Location and Environment 10
Installation 11
Battery Installation 11
Power Cabinet
12
Wall Mount
13
Battery Connections 14
Main DC Connections
14
Case Earthings
15
Alarm Contacts
15
Operation 18
Troubleshooting 18
Maintenance 19
Upgrading Battery Capacity 19
End of Life 20
Warranty 20
![](/html/85/85f3/85f38a9779e1dfa2b6e3b73002ee994c2f1c75d512c2f959808e0527cefa373c/bg3.png)
LiFe Premium Installaon and Operaon Manual - REV04 3
INTRODUCTION
The LiFe Premium Series Lithium Ferro Phosphate (LFP) battery by
PowerPlus Energy was designed and manufactured in Australia for the
worlds harshest conditions to be a simple, flexible and reliable energy
storage solution. As a result the LiFe Premium Series batteries can be
easily installed with most Inverter and charger combinations, UPS,
Rectifiers, DC or AC coupled charging devices, on-grid and off-grid in
single, Dual or three phase applications. There is almost no limitations in
applications and suitable devices that can charge or discharge the Life
Premium Series battery. Currently the LiFe Premium Series battery is
available in 24v and 48v models with the future release of a 120v version.
![](/html/85/85f3/85f38a9779e1dfa2b6e3b73002ee994c2f1c75d512c2f959808e0527cefa373c/bg4.png)
LiFe Premium Installaon and Operaon Manual - REV04 4
SAFETY
Installers and users are responsible for familiarising themselves with this manual.
The LiFe Premium Series batteries use a high grade Cylindrical Lithium Ferro Phosphate (LFP)
cells which are robust and reliable in higher ambient temperatures, have a long service life and
with no heavy metals are fully recyclable.
Each LiFe Premium Series battery has an internal Battery Management System (BMS) that
provides protection against Over and Under Voltage, Over Current, Over Temperature and Short
Circuit as well extended service life through managing cell string balancing.
Each battery has a 2 pole non polarised circuit breaker, status indicator light, volt free alarm
contact and high quality Amphenol SurLok DC connections for safe and easy installation.
Installation should be by qualified and experienced installers who can specify the correct cables
and DC bus arrangement, external circuit protection, polarity checking and suitability of the design
for the installation.
Transportation
Lithium Ferro Phosphate Batteries are classed as Dangerous Goods (DG) Class 9 UN3480.
They are safe for road transport. The batteries are shipped in a partially discharged state with
terminal protection and the circuit breaker off.
![](/html/85/85f3/85f38a9779e1dfa2b6e3b73002ee994c2f1c75d512c2f959808e0527cefa373c/bg5.png)
LiFe Premium Installaon and Operaon Manual - REV04 5
Basic Safety
The Following precautions should be observed:
• Battery should not be exposed to temperatures above or below the ambient temperature
rating specified in the rear of this manual.
• Battery should not be installed in direct sunlight.
• Battery should not be exposed to strong impacts.
• Battery should not be crushed or punctured.
• Battery connectors should not touch conductive surfaces unless intended to do so.
• Battery should not be disassembled unless qualified to do so.
• Battery should not be touched if wet.
• Battery should be kept dry at all times.
• Battery should be kept away from animals and children.
• Battery pack should not be exposed to pressure or have objects stood on top of them.
• Battery pack is intended to be a 2 person lift when installing.
Handling
• Use Battery only as directed.
• The battery is non user serviceable and should not be opened for repair.
• Do not use the battery if it appears damaged or broken.
• Handle battery with care when installing or transporting.
• Do not use chemicals to clean the battery.
![](/html/85/85f3/85f38a9779e1dfa2b6e3b73002ee994c2f1c75d512c2f959808e0527cefa373c/bg6.png)
LiFe Premium Installaon and Operaon Manual - REV04 6
Damaged battery
A damaged battery should not be used and should be returned to the PowerPlus Energy or
disposed of via a recycling facility. Leaking electrolyte can cause skin irruption and chemical burns
so contact should be avoided.
Eye Contact: Rinse gently with running water. Seek medical attention if irritation develops.
Skin Contact: Rinse gently with running water. Seek medical attention if irritation develops.
Ingestion: If Ingested do not induce vomiting and contact you local poisons information centre
or doctor.
Inhalation: Evacuate area and seek professional medical attention immediately, however an
inhalation hazard is not expected due to product form and nature of use
Fire
Should the battery pack catch on fire a dry agent fire extinguisher should be readily available and
used. DO NOT use water. Evacuate the area and call emergency services. Toxic gas may be
produced if the battery catches fire.
Note: Refer MSDS document for more details which is available from PowerPlus Energy’s web
page or upon request.
Qualified installation person (Installer)
This manual and task sets within regarding installation should be carried our by a suitable qualified
and skilled person. The installer needs to be a person with adequate skills, qualifications and
experience. They should:
• Have a thorough understanding of operations, design and installation principles of On and Off
Grid Electrical system.
• Have a thorough understanding of all dangers associated with installing and using electrical
devices as well as all risks.
• Hold all local, state and country base qualifications to carry out such work.
• Adhere to all safety and installations requirements within this manual.
![](/html/85/85f3/85f38a9779e1dfa2b6e3b73002ee994c2f1c75d512c2f959808e0527cefa373c/bg7.png)
LiFe Premium Installaon and Operaon Manual - REV04 7
PRODUCT INFORMATION
The Technical information presented here within outlines the physical and electrical
characteristics of the battery and what environment they should be installed in.
Weight and Dimensions
LiFe2433P LiFe4833P LiFe12033P
Depth 620mm 620mm 620mm
Width 430mm 430mm 430mm
Height 88mm 88mm 88mm
Weight 41kg 41kg 41kg