MODEL PVI-8.0-TL-OUTD PVI-10.0-TL-OUTD PVI-12.5-TL-OUTD
INPUT PARAMETERS
Nominal DC Power [kW] 8,25 10,3 12,8
Max. Recommended DC Power [kW] 11 11,4 14,3
Operating Input Voltage Range [V] 0,7xVstart - 850
Full Power MPPT input voltage range (symmetrical load) [V] 270-750 300-750 360-750
Full Power MPPT input voltage range (asymmetrical load) [V]
380-750 (@ 6,8kW) / 195-750 (@ 3,5kW)
380-750 (@ 6,8kW) / 195-750 (@ 3,5kW) 445-750 (@ 8kW) / 270-750 (@ 4,8kW)
Absolute Max. Input Voltage [V] 900
Activation voltage “Vstart” [V] 360 nominal (adjustable within the range 250Vdc-500Vdc, independently/each input)
No of independent MPPT trackers 2
Max. Input Power, each MPPT [kW ] 5,5 6,8 8
No. of DC Inputs
6 (3 each MPPT, optionally fused) in PVI-8.0/10.0/12.5-TL-OUTD
and in PVI-8.0/10.0/12.5-TL-OUTD-FS version,
4 (2 each MPPT) in PVI-8.0/10.0/12.5-TL-OUTD-S version
Max. DC Current, each MPPT [A] 17 18
Absolute Max. input short circuit current (ISC) [A] 22
DC Connection
2 x Weidmüller / Multicontact Ø 4mm (6 male - positive input + 6 female - negative input) in
PVI-8.0/10.0/12.5-TL-OUTD and in PVI-8.0/10.0/12.5-TL-OUTD-FS version (Mating cable connector included),
8 x Weidmüller / Multicontact Ø 4mm (4 male - positive input + 4 female - negative input) in
PVI-8.0/10.0/12.5-TL-OUTD-S version (Mating cable connector included)
Conductor cross section: 4-6mm2 (AWG12-10)
Cable Ø w/insulator: 5,5-9mm (Multicontact), 5,5-7,5mm (Weidmüller)
Max. inverter Backfeed Current to the array [A] Negligible
INPUT PROTECTION
Reverse polarity protection Yes
Fuse rating, each input (-FS sux versions only) [A] 12 (1000V ) 12 (1000V) 12 (1000V)
Thermally Protected DC side varistor 4 ( 2 for each MPPT )
PV array Insulation Control according to local standard
DC Switch (-S/-FS sux versions only) Integrated (Rating : 1000Vdc / 25A)
OUTPUT PARAMETERS
Nominal AC Power [up to 50°C, kW] 8 10 12,5
Max. AC Power [kW] 8,9 (*) 11 (**) 13,8 (***)
AC Grid Connection Three phase (5W or 4W+PE)
Nominal AC Voltage [V] 400
AC Voltage Range [V] 320-480 (may vary to comply with regulations in each country)
Nominal AC Frequency [Hz] 50
AC Frequency Range [Hz] 47-53 (may vary to comply with regulations in each country)
Max. AC Line Current [A] 13 ( 15 short circuit ) 16,6 ( 19 short circuit ) 20 ( 22 short circuit )
Maximum output fault current (a.c. A, peak and duration or RMS)
<25 A rms (100ms)
AC Connection
Screw terminal block
Conductor cross section: Solid 0,5-16mmq / Stranded: 0,5-10mmq / AWG20-6
Cable Gland: M40 - Cable Ø: 19-28mm
Line Power Factor >0,995
Inrush Current (a.c. A, peak and duration) Negligible
AC Current Distortion [THD%] <2% at rated power with sine wave voltage
OUTPUT PROTECTION
AC side varistors 3, star connected to common point, plus gas arrester to ground
Ground fault protection (AC + DC leakage current) according to local standard
ENVIRONMENTAL PARAMETERS
Cooling Natural cooling
Ambient Temp. Range [°C]
-25 / +60 (out. power der. above 55 °C) -25 / +60 (out. power der. above 55 °C) -25 / +60 (out. power der. above 50 °C)
Opertaing Altitude [m] 2000
Acoustical Noise [dBA] < 50 @ 1mt
Environmental IP Rating IP65
Relative Humidity 0-100% condensing
Environmental pollution classication for external enviroment 3
MECHANICAL
Dimensions [H x W x D] 645 x 645 x 211
Overall Dimensions (with anges) [H x W x D] 716 x 645 x 224
Weight [kg] 38
Protective Class I
Overvoltage Category in accordance with IEC 62109-1 II (DC Input); III (AC Output)
(*) Limited to 8000W for Germany. (**) Limited to 10000W for Benelux and Germany. (***) Limited to 12500W for Germany.